Official Exhibit - NYS000009-00-BD01 - Harlow, James H., Electric Power Transformer Engineering, 2nd Edition, CRC Press (2007), Excerpted: Pp. v-vi, 2-1 - 2-2 (2007 Harlow)
ML12334A507
Person / Time
Site: Indian Point  
Issue date: 12/12/2011
From: Harlow J
CRC Press
To:
Atomic Safety and Licensing Board Panel
SECY RAS
References
RAS 21523, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01, NYS000009
Download: ML12334A507 (6)


Text

United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:

Entergy Nuclear Operations, Inc.

(Indian Point Nuclear Generating Units 2 and 3)

ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:

Identified:

Admitted:

Withdrawn:

Rejected:

Stricken:

Other:

NYS000009-00-BD01 10/15/2012 10/15/2012 NYS000009 Submitted: December 12, 2011 EXCERPT Electric Power Engineering Handbook Second E(lItlOn HfCTRIC POWfH TRANSfORMfR fNGINHRING Second Edition Edited by James H. Harlow

~CRCPress V

Tayl'or&FrandsGroup Boca _

I..oodon New VOlt Ole ~

I. on irnpdnl of !he Tll.ylor k l'nDcill Group. IIIl intonna bwmcs.

OAGI0001239_00001

CRC Press Taylor & franci6 Group 6000 Broken Sound Parkway NW. Suite 300 Boca Raton. fL 33487-2742

© 2007 by Taylor & francis Group. LLC CRC Press is an imprint of Taylor & Francis Group. an Informa business No claim to orLginal U.S. Government works Prj nted in Canada on acid-free paper 10987654321 International Standard Book Number-IO: 0-8493-9186-5 (Hardcover)

International Standard Book. Number-13: 978-0-8493-9186-6 (Hardcover)

This book contains information obtained from authentic and highly regarded sources. Reprinted material is quoted wilh permission, and sources are Indicated. A wide variety of references are listed. Reasonable efforts have been made to publish reliable data and information, but the author and the publisher cannot assume responsibility for the validity of all materials or for the consequences of their use.

No part ofthis book may be reprinted. reproduced, transmitted. or utilized in any form by any electronic. mechanical. or other means. now known or hereafter invented, including photocopying, microfilming, and recording, or in any informa*

tion storage or retrieval system, without wdtlen permission from the publishers.

For permission to photocopy or use material electronically from this work. please access www.copyright.com (http://

www.copyright.comf) or contact the Copyright Clearance Center. Inc. (CCCl 222 Rosewood Drivc. Danvers, MA 01923.

978-750-8400. CCC is a not-for-profit organization that provides licenses and registration for a variety of users. for orga-nizations that have been granted a photocopy liccnse by the CCC, a separate system of payment has been arranged.

Trademark Notice: Product or corporate names may be trademarks or registered trademarks. and are used only for idenliflcation and ex.planation withou.t inlent to infringe.

Librar), of Congress Cataloging-ln-PubHcatlon Data Power transformer engineering / editor. James H. Hadow. -- 2nd ed.

p.cm.

Includes bibliographical references and index.

ISBN-13: 978-0-8493-9186-6 (alk. paper)

ISBN-IO: 0-8493-9186-5 (alk. paper)

1. ElecLric transformers. I. Harlow, James H. ll. Tille.

TK255L£652007 62L3l'4--dc22 Visit the Taylor & francis Web site at ht tp:! fwww.taylorandfrancis.com and the CRC Press Web sIte at http://www. c~cpreS8_com 2007010459 OAGI0001239_00002

Table of COl1tel1ts Preface................................................................................................................................................... vii Editor...................................................................................................................................................... ix Contributors................................................................................................................................ _......... xi Theory and Principles...................................................................................................................... I-I Dennis l. Allan and Harold Moore 2 Power Transfonners............................ '........................................................................................... 2-1 H. lin Sim and Scott H. Digby 3 Distribution Transfonners.............................................................................................................. 3-1 Dudley L. Galloway and Dan Mulkey 4 Phase-Shifting Transformers.......................................................................................................... 4-1 Gustav Preininger 5 Rectifier Transfonners..................................................................................................................... 5-1 Sheldon P. Kennedy 6 Dry-lfpe Transformers................................................................................................................... 6-1 Paulette Payne Powell 7 Instrument Transform.ers................................................................................................................ 7-1 Randy Mullikin 8 Step-Voltage Regulators............. :..................................................................................................... 8-1 Craig A. Colopy 9 Constant-Voltage Transformers...................................................................................................... 9-1 Arindam Ma;tra, Anish Gaikwad, Arshad Mansoor, Douglas Don, and Ralph Ferraro 10 Reactors.......................................................................................................................................... 10-1 Richard F. Dudley, Michael Sharp, Antonio Castanheira, and Behdad B. Biglar II Insulating Media............................................................................................................................ 11-1 Leo j. Savio, Ted Haupert. and Dave Hanson 12 Electrical Bushings........................................................................................................................ 12-1 Loren B. Wagenaar v

OAGI0001239_00003

vi 13 load Tap Changers........................................................................................................................ 13-1 Dieter Dohnal 14 loading and Tbermal Performance............................................................................................. 14-01 Robert F. TiJ1man 15 Transformer Connections............................................................................................................. 1 s-t Dan D. Pereo 16 Transformer Testing...................................................................................................................... 16-1 Shirish P. Mehta and WIlliam R. Henning 17 load-Tap-Change Control and Transformer Paralleling............................................................ 17-1 James H. Harlow 18 Power Transformer Protection..................................................................................................... 18-1 Armando Guzman, Hector J. Aituve, and Gabriel Benmouyai 19 Causes and Effects of TnlDsformer Sound Levels....................................................................... 19-1 Jeewan L. Purj 20 Transient-Voltage Response.......................................................................................................... 10-1 Robert C. Degeneff 11 Transformer Installation and Maintenance................................................................................. 21-1 Awn C. Oswalt 22 Problem and Failure Investigation............................................................................................... 22-1 Wallace B. Binder and Harold Moore 23 On-Line Monitoring of Uquid-lDlmersed Transformers........................................................... 23-1 Andre Lux 24 United States Power Transformer Equipment Standards and Processes.................................. 24-1 Philip f. Hopkinson Index.. :.................................................................................................................................................... I-I OAGI0001239_00004

H. Jin Sim Wal!kesha Electric Systems Scott H. Digby City of Wilson, NC 2.1 Introduction Power Transformers 2.1 Introduction......................................................................... 2-1 2.2 Rating and Classifications................................................... 2-2 Rating* Insulation Classes' Cooling Classes 2.3 Short-Circuit Duty.............................................................. 2-5 2.4 Effidency, Losses, and Regulation..................................... 2-6 Efficiency* Losses* Economic Evaluation of Losses' Regulation 2.5 Construction........................................................................ 2-8 Core' Windings' Taps-Thrns Ra[io Adjustment 2.6 Accessory Equipment........................................................ 2-17 Accessories

  • Liquid* Preservation Systems 2.7 Inrush Current................................................................... 2-20 2.8 Transformers Connected Directly to Generators........... 2-20 2.9 Modern and Future Developments.................................. 2-22 High-Voltage Generator
  • High-Temperature Superconducling (H'fS) 'fransformer ANSI/IEEE defines a transformer as a static electrical "device, involving no continuously moving parts, used in electric power systems to transfer power between circuits through the use of electromagnetic induction. The term power transformer is used to refer to those transformers used between the generator and the distribution circuits, and these are usually rated at 500 kVA and above. Power systems typically consist of a large number of generation locations, distribution points, and interconnections within the system or \\'lith nearby systems, such as a neighboring utility. The complexity of the system leads to a variety of transmission and distribution voltages. Power transformers must be used at each of these points where there is a transition between voltage levels.

Power transformers are selected based on the application, with the emphasis toward custom design being more apparent the larger the unit. Power transformers are available for step-up operation, primarily used at the generator and referred to as generator step-up (GSU) transformers, and for step-down operation, mainly used to feed distribution circuits. Power transformers are available as Single-phase or three-phase apparatus.

The construction of a transformer depends upon the application. Transformers intended for indoor use are primarily of the dry type but can also be liquid immersed. For outdoor use, transformers are usually liquid immersed. This section focuses on the outdoor, liquid-immersed transformers, such as those shown in Figure 2.1.

2-1 OAGI0001239_00005

2*2 Electric Power Transformer Engineering. Second Edition FIGURE 2.1 20 MVA, 161:26.4 x 13.2 kV with LTC, three phase transformers.

2.2 Rating and Classifications 2.2.1 Rating In the U.s" transfouners are rated based on the power output they are capable of delivering continu-ously at a specified rated voltage and frequency under "usual" operating conditions without exceeding prescribed internal temperature limitations. "Insulation is known to deteriorate with increases in temperature, so the insulation chosen for use in transfouners is based on how long it can be expected to last by limiting the operating temperature. The temperature that insulation is allowed to reach under operating conditions essentially deteunines the output rating of the transformer, called the kVA rating.

Standardization has led to temperatures within a transformer being expressed in teuns of the rise above ambient temperature, since the ambient temperature can vary under operating or test conditions.

Transformers are designed to limit the temperature based on the desired load, including the average temperature rise of a winding, the hottest-spot temperature rise of a winding, and, in the case of liquid-filled units, the top liquid temperature rise. To obtain absolute temperatures from these values, simply add the ambient temperature. Standard temperature limits for liquid-immersed power transformers are listed in Table 2.1.

The nonnallife expectancy of a power transformer is generally assumed to be about 30 years of service when operated within its rating. However, under certain conditions, it may be overloaded and operated beyon<:l its rating, with mOderately predinable ~loss oflife." Situations that might involve operation beyond rating include emergency rerouting of load or through-faolts prior to dearing of the faolt condition.

Outside the U.S., the transformer rating may have a slightly different meaning. Based on some standards, the kVA rating can refer to the power that can be input to 11 transformer, the rated output being equal to the input minus the uansformer losses.

TABLE 2.1 Standard LiInits for Temperature Rises Above Ambient Avet"age winding temperature rise Hot spot temperature rise Top liquid temperalUfl: rise

'The base rating is frequently specified and tested as a 55"C rise.