Why Do Hospital Generators Keep Failing? - ProPublica

Page 1 of 6 UBLICA Patient Safety Exploring Quality of Care in the U.S.

Why Do Hospital Generators Keep Failing?

Hospital workers evacuate a patient from NYU Langone Medical Center during Hurricane Sandy on Oct. 29, in New York City. (Michael Heiman/Getty Images) by Charles Ornstein ProPublica, Oct. 31, 2012,4:53 p.m.

It is a hospitals nightmare: The power goes out and backup generators dont kick in, leaving critically ill patients without the mechanical help they need to breathe.

It happened in New Orleans after Hurricane Katrina, when hospital staff were on their own when electricity and water cut out [1]. Some died.

It happened last year in San Diego, when generators at two hospitals failed

[2] during a blackout.

http ://www.propub1ica.org/article/whydohospitalsgeneratOrS-keeP-failiflg

11/14/2012 CLE000069 Submitted November 14, 2012

Why Do Hospital Generators Keep Failing? - ProPublica

Page 2 of 6 And it happened last year in Connecticut [s], when a hospital had to be evacuated during Hurricane Irene when its generator failed.

As Hurricane Sandy headed toward the East Coast, New York City Mayor Mike Bloomberg said Sunday, he was assured that hospitals were ready. "The teams from the City Health Department are at these facilities making sure that the emergency generators are working and that they have back-up fuel supplies," he said [.] at a news conference before the storm.

In spite of this confidence, the generators at some hospitals did not work as expected.

In the most high-profile case, New York University Langone Medical Center had to evacuate all 215 of its patients [] when its power went out and both of its backup systems didnt work. Staff had to hand pump oxygen to critically ill patients until patients could be taken by ambulance to another hospital.

In New Jersey, patients at Palisades Medical Center had to likewise be evacuated [6]

in recent days after two generators failed. A hospital spokesman said today that officials were working to bring the "plant up to speed" and could not immediately answer questions about the generators.

And this afternoon, Bellevue Hospital in New York City said it is evacuating hundreds of patients because of failing power and deteriorating conditions. "Its Katrina-esque in there," one nurse told ABC News [v].

Experts say such failures are troubling but not entirely surprising. Dr. Arthur Kellermann founded the emergency department at Emory University and headed it from 1999 to 2007. Now, hes Paul ONeill-Alcoa Chair in Policy Analysis at RAND Corporation think tank.

The other night, as the NYU evacuation was unfolding, he tweeted [8], "Hospital preparedness and well-functioning backup systems are a costly distraction from daily business, until they are needed. Like now."

In an email interview with ProPublica, Kellermann elaborated: "I have no doubt when the hospital assured the Mayor that their backup systems were ready, they believed they were. They were wrong. What I find most remarkable about this story is that [more than seven] years after Hurricane Katrina, major hospitals still have critical backup systems like generators in basements that are prone to flooding."

Bruce Altevogt, a senior program officer at the Institute of Medicine who has studied crisis standards of care [p], lauded NYU for safely evacuating patients. But he said the incident should prompt a new discussion about where hospitals place generators and how to ensure they work when theyre needed.

http ://www.propublica.org/article/why-do-hospitals-generators-keep-failing

11/14/2012

Why Do Hospital Generators Keep Failing? - ProPublica

Page 3 of 6 Newly constructed hospitals are supposed to place their generators and fuel in adjacent locations above flood level. But the location requirements do not apply to already-built hospitals.

"These older facilities, its just an economic issue," Altevogt: said. "They dont have the resources, or they havent devoted the resources to moving the equipment to locations that would be less prone to disasters or flooding in these cases."

An NYU spokeswoman told Modern Healthcare magazine Tuesday [io] that "part of the generator is on the roof and part in the basement, which she said took on 8 feet of water. The reason for the failure, she said, is being investigated."

New York hospitals have had experiences with generator failures before and have seen the consequences firsthand.

In 1987, a 22-minute power failure led to the death of a 40-day-old infant at New York Hospital. "The prematurely born infant, whom officials declined to identify, died after his electric respirator stopped and efforts to help him breathe with a manual air pump failed," the New York Times reported [11] at the time.

A decade before that Bellevue Hospital lost all power during the massive New York City blackout in 1977. The Times reported [12] at the time: Doctors and nurses squeezed bags of air with their hands to resuscitate patients when respirators stopped, and emergency generators were brought in."

During another New York City-wide blackout in 2003, an official report later said

[13], "Despite prior testing according to applicable State and accreditation standards,

[some] generators malfunctioned, experiencing, for example, problems with switches and overheating....In a few cases hospitals reported that fuel supplies for generators fell to dangerously low levels, in part because of transportation difficulties encountered by fuel delivery trucks."

Back at NYU, a hospital trustee, Gary Cohn, said that the board knew the facilities generators were outdated and at risk, according to Bloomberg Businessweek

[14].

"The infrastructure at NYU is somewhat old," Cohn said in a television interview. The backup generators "are not state-of-the-art and not in the most state-of-the-art location."

A hospital spokeswoman defended its systems to the Huffington Post.

"Our generators are fully compliant with all state and federal regulations and, using good prudence, we test them all the time as we have to do anyway," Lisa Greiner said

[15].

http ://www.propublica.org!article/why-do-hospitals-generators-keep-failing

11/14/2012

Why Do Hospital Generators Keep Failing? - ProPublica

Page 4 of 6 Emails to NYU staff by ProPublica were not returned prior to publication.

Another expert in disaster planning, Dr. Dan Hanfling, said in an email that the failure of the back-up power at NYU Langone "is certainly unexpected."

Hospitals, he said, are required by the Joint Commission, a hospital accreditor, to have back-up power capabilities. They are required to "load test" those systems a few times each year. (Update 10/31: The Joint Commission says it requires tests 12 times a year for 30 minutes and once every three years for four hours.)

"Evidently, the catastrophic failure must be explained by something else," wrote Hanfling, a special adviser for emergency preparedness and response for Inova Health System in Virginia.

In his email to Pro Publica, Kellermann wrote that the irony of the NYU generator failure is that New York Citys hospitals and health department "have taken preparedness more seriously than nearly everyone else in the country, particularly since 9/11/01." RAND tested a novel, no-notice disaster drill at a different city hospital a few months ago and it performed very well.

The situation at NYU should be a lesson for all.

"Preparedness is not simply a hoop to jump through to satisfy the Joint Commission, or to keep the Fire Marshall off your back," Kellermann wrote. "It is a fundamental duty to the community, state and country. Assuming nothing will ever happen, or counting on your staff to rise to the occasion is not a plan, and it is not preparedness."

Hanfling went a step further. "Lesson to learn: hospitals must be prepared to evacuate patients. This may be the new normal for hospital preparedness efforts," he wrote.

Why arent hospitals better prepared for emergency events? Leave a comment, or join the discussion on Twitter with #InvestigateThis

1. http://www.propublica.org/article/the-deadlY-ChOiCeS-atmemOriaI826
2. http://www.utsandiego.com/news/2O11/sep/O9/regiOfla1hOSPitaIS_fU11Y0Perat1011al_fridaY/
3. http://articles.courant.com/2011-08-29/health/hCjmhhUfliCafleevaCuatioflo83o 20 11o829_1_connecticut_hospitals-evacuation-geflerator
4. http://www.nyc.gov/htm1/om/htmI/2012b/Pr377-12StatiC.html
5. http //www.nytimes.com/2o12/10/3o/nyregiofl/patiefltSeVaCUatedfr0mflYU_la11gOfle_after_P0Wer_

failure.html

6. http://www.nj.com/hudson/index.ssf/2012/1O/paliSadeS_mediCal_Ceflter_fUlIY.html http ://www.propublica.org/artic1e/whydohospita1s-generators-keeP-failing

11/14/2012

Why Do Hospital Generators Keep Failing? - ProPublica

Page 5 of 6

7. http://abcnews.go.com/Health/yOrk_CitYS_belleVUe_hOSPital-set_evacuatesandY/st0IY?

id=17607625#.UJF2vMU0BPE

8. https://twitter.com/ArtKellermanflMD/StatUS/263106526439424000
9. http://www.iom.edu/Reports/2o12/CrisisSta1dardS_Of-Care_A_SYStems_Framew0rk_f0r-Catastr0Phic

-Disaster-Response.aspx

10. http://www.modernhealthcare.com/article/20121030/NEwS/310309959/failednYu4angone-generators-draw-fire
11. http://www.nytimes.com/1987/o6/07/nyregiofl/hOSpitaiSPUZZled-bY-POwerfa1Iure.html
12. http://www.nytimes.com/learning/general/onthisday/big/0713.html#a -Cle
13. http://www.nyc.gov/html/om/pdf/em_task_force_fillal_10_28_03.Pdf
14. http : //ww.businessweek.com/news/2o12-lo-30/new-york-hospital-evaCUateSPatiefltSaSSandY hits-power
15. http://www.huffingtonpost.com/2012/10/30/nyU-hOSpital-gefleratOr&humcafle sandy_n_2o46o41.html What to Read Next Female Foreign Correspondents Code of Silence, Finally Broken TSA Removes X-Ray Body Scanners From Major Airports The Outlook for "Obamacare" in Two Maps The Deadly Choices at Memorial Discussion: The Top Patient Safety Challenges Medical Providers Face Sponsored Links io Worst-Rated States for Retirement (AARP.org )

6 worst home fixes for the money (BankRate.com )

10 Sleazy Moves by Everyday Companies (TheStreet)

The Terrifying Line in Obamas Speech That Everyone Missed (Investors.com )

The 10 Worst Hotels and Motels in America (The Fiscal Times)

From Around the Web Content from Sponsors

[Whats this?]

by Taboola

_ w http ://www.propub1ica.org/artic1e/whydohospitalsgefleratOr5keePJailiflg

11/14/2012