Part 21 Report - Commercial Grade Dedication Not Properly Applied to Butterfly Valves
ML12318A041
Person / Time
Site: Beaver Valley, Peach Bottom, Salem, Mcguire, Palisades, Palo Verde, Indian Point, Watts Bar, Hope Creek, Cooper, Brunswick, Surry, Clinton, San Onofre, Cook, McGuire  Constellation icon.png
Issue date: 11/08/2012
From: Engle C
Fisher Controls International
To:
Office of Nuclear Reactor Regulation
References
48492
Download: ML12318A041 (11)


Text

11/08/2012 Part 21 (PAR)

U.S. Nuclear Regulatory Commission Operations Center Event Report PaE4 e I Event#

48492 Rep Org: FISHER CONTROLS INTERNATIONAL, LLC Notification Date / Time: 11/08/2012 10:11 (EST)

Supplier: FISHER CONTROLS INTERNATIONAL, LLC Event Date / Time: 11/07/2012 (CST)

Last Modification: 11/08/2012 Region:

3 Docket #:

City:

MARSHALLTOWN Agreement State:

Yes County:

License #:

State:

IA NRC Notified by: CHAD ENGLE Notifications: GLENN DENTEL R1DO HQ Ops Officer: VINCE KLCO MARVIN SYKES R2DO Emergency Class: NON EMERGENCY CHRISTINE LIPA R3DO 10 CFR Section:

THOMAS FARNHOLTZ R4DO 21.21 (d)(3)(i)

DEFECTS AND NONCOMPLIANCE PART 21 GROUP EMAIL PART 21 REPORT-COMMERCIAL GRADE DEDICATION NOT PROPERLY APPLIED TO BUTTERFLY VALVES The following information was received by facsimile:

"While reviewing an order for a Type 9200 Butterfly Valve, it was discovered that some parts [shipped from Marshalltown, Iowa from 2009-present] had not been identified for Commercial Grade Dedication, These parts were considered Essential-to-Function and Were needed for the valve assembly to perform its safety-related function(s).

"[The vendor] then extended its review to all safety-related orders going back to 2009. This review confirmed that the failure to dedicate was not confined to Type 9200 butterfly valves. The beginning of 2009 was selected because [an audit follow-up was] performed in January, 2009. A key point of emphasis during the audit was commercial grade dedication, with a recommended outcome being the addition of guidance on commercial grade dedication with all new quotations. Therefore, the 2009 audit brought clarity and consistency in approach, that was not always applied correctly between January, 2009 thru October, 2012.

"It is [vendor's] opinion that while the affected equipment identified as safety-related was not properly dedicated, the failure to dedicate does not appear to pose an inherent safety risk based on currently available Information.

The reason being that much of the equipment affected by [the vendor's] error were items such as mounting kits, wherein [the vendor] failed to dedicate the hardware used to mount the instrument (i.e., the bracket and screws),

but did properly dedicate the instrument. Additionally, in forming this opinion, [the vendor] has taken into account that there are no known field issues with the affected equipment and all such possibly non-dedicated equipment passed the required standard testing."

U.S. nuclear plants affected include the following:

I 6I~

11/08/2012 U.S. Nuclear Regulatory Commission Operations Center Event Report Paze 2 Part 21 (PAR)

Event#

48492 D.C. Cook; Millstone; Surry; McGuire; San Onofre; Indian Point; Palisades; Clinton; Peach Bottom; Beaver Valley; Cooper; Palo Verde; Brunswick; Hope Creek/Salem and Watts Bar. It is noted that numerous foreign facilities are also affected.

If there are any technical question, contact the Fisher Quality Manager (George Baitinger) : Fax: (641) 754-2854 or Phone: (641) 754-2026.

Nov, 8. 2012 8:56AM No. 4791 P. I EMERSON.-

(FISHER]

Process Managerent Facsimile 301 South First Ave Marshalltown, IA 50158 T 641-754-2381 F 641-754-2684 NRC To: Vernon Hodge Fax: 301-816-5151 Sent on behalf of Dennis Swanson by Trish Crosser Executive Assistant From: For QA Director NA Date: 11/7/2012 Pages: 8 (Incl cover)

Attached is a copy of Emerson Process Management - Fisher Division's Nuclear FIN Notice (FIN 2011-03) to be distributed today to our Nuclear Customers via Certified Mail.

Any questions or concern, do not hesitate to give me a call.

Trish Crosser I Executive As is&an[ I Fisher Division Emerson Process Management 1 301 S. 1st Avenue I Marshalltown, Iowa 50158 I USA T +1 641,754,2688 I F +1 641.754.2688 Tiish,Crosser@Eirerson,corn

Nov, 8. 2012 8:56AM No. 4791 P. 2 7

EMERSON,.

Fisher Controls InLernational LLC Ploces!; Millnmnllce~n t

301 South First Ave.

P.O. Box 190 Marshalltown. Iowa 80158-0190 USA T (041) 754-3011 F (641) 754-2854 Fisher Information Notice: FIN 2012-03 November 6, 2012

Subject:

Commercial Grade Dedication of Essential-to-FunctIon Equipment From:

Chad Engle Director, Nuclear Business Unit Fisher Controls International LLC 301 South First Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Equipment Potentially Affected By This Information -Notice:

Commercial Grade Dedication of Essential-to-Function equipment within certain Fisher valve assemblies, shipped from Marshalltown, Iowa from 2009-present.

A list of possibly affected serial numbers can be found in Table 1 below.

Purpose:

The purpose of this Fisher Information Notice ("FIN") is to alert potentially affected customers that, as of October 25, 2012, Fisher Controls International LLC ("Fisher")

became aware of a possible failure to comply, Fisher is providing this written notice per the requirements of 10 CFR 21.21(b).

Receipt of this FIN does not necessarily mean that the recipient has received subject

.equipment. It is expected that the recipients of this notice will review this information for applicability to their equiment and facilities, and if required, take the appropriate action as described in the 'Action Required' section at the end of this FIN.

Applicability:

This FIN applies to the equipment identified in Table 1, which lists serial, order and Item FISHER]

Page 1 of 4

Nov. 8, 2012 8:56AM No. 4791 P. 3 Fisher Information Notice: FIN 2012-03 numbers that were delivered to possibly affected customers. Only equipment from Fisher's Marshalltown site may be affected.

Discussion:

While reviewing an order for a Type 9200 Butterfly Valve, it was discovered that some parts had not been identified for Commercial Grade Dedication. These parts were considered Essential-to-Function and were needed for the valve assembly to perform its safety-related function(s).

Upon discovery of this possible failure to comply, an investigation was performed on all safety-related Type 9200 butterfly valves that were contractually required to be dedicated and had been shipped.

Fisher then extended its review to all safety-related orders going back to 2009, This review confirmed that the failure to dedicate was not confined to Type 9200 butterfly valves, The beginning of 2009 was selected because NUPIC had performed an audit in September 2008 and returned for a follow-up review in January 2009. A key point of emphasis during the audit was commercial grade dedication with a recommended outcome being the addition of' guidance on commercial grade dedication with all new quotations. Therefore, the 2009 audit brought clarity and consistency in approach, that was unfortunately not always applied correctly between January 2009 thru October 2012.

It is Fisher's opinion that while the affected equipment we identified as safety-related was not properly dedicated, the failure to dedicate does not appear to pose an inherent safety risk based on currently available information. The reason being that much of the equipment affected by Fisher's error were Items such as mounting kits, wherein Fisher failed to dedicate the hardware used to mount the instrument (i.e., the bracket and screws), but did properly dedicate the Instrument. Additionally, in forming this opinion, Fisher has taken into account that there are no known field issues with the affected equipment and all such possibly non-dedicated equipment passed the required standard testing.

The following Corrective Actions have been completed or are in process:

@ An internal Corrective Action (CAR# 1570), classified as a Significant Condition Adverse to Quality, has been issued to the Director, Nuclear Business Unit regarding entry of safety related orders, in accordance with Fisher's Quality Program.

  • All shipped safety-related orders requiring dedication activities (going back to 2009) have been reviewed, as described above.

[FISHER]

Page 2 of 4

Nov, 8, 2012 8:57AM No, 4791 P. 4 Fisher Information Notice: FIN 2012-03

  • This notice was drafted and sent to NRC and all nuclear utilities (including non-US utilities). Additionally, Fisher is contacting each, individual potentially affected utility. This action is expected to be completed by November 16, 2012.

" All pending orders are being reviewed and will be corrected prior to shipment.

" Mandatory enhariced training will be provided to all employees engaged in processing safety-related orders, to ensure that the equipment requiring Commercial Grade Dedication is properly identified and listed on the order.

" A thorough review of the order entry process, Including a mapping of the process, is being conducted, The future, process will Include additional controls and review points, which will be documented In the operating procedure.

" In the short-term pending the completion of the aforementioned corrective actions, the Nuclear Qualification Engineer, the engineer designated for determining which parts are Essentlal-to-Function, will be engaged during the quotation stage of an order to ensure that the proper Essential-to-Function equipment for Commercial Grade Dedication is identified based on the equipment's safety-related function,

" We continue to review all applicable customer purchase orders (from 2009 through the present) to determine whether a failure to comply actually occurred. In an abundance of caution, Fisher.has elected to notify all potentially affected customers via this FIN, understanding that it may eventually be determined that some of the notified customers did not receive affected, equipment.

Action Required:

Fisher will supply properly dedicated equipment, at Fisher's cost, for the affected valve assemblies that are in inventory or in service.

10 CFR Part 21 Implications:

Fisher requests recipients carefully review this notice and take appropriate action In accordance with 10 CFR Part 21.

If there are any technical questions or concerns, please contact; (FISHER]

Page 3 of 4

Nov. 8. 20 12 8 :57AM No, 4791 P. 5 Fisher Information Notic:e: FIN 2012-03 George Baitinger Manager, Quality Fisher Controls International LLC 301 South First Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Phone: (641) 754-202(3 Georoe.Baitinaera.iErnerson.com FISHEl]

Page 4 of 4

FIN 2012-03 Table I I

lAAE

~~AE n-[we Tno qv Ehrke and Co Ehrke and.Co Copes Vulcan Operation Cop~es Vulcan Oneration AE AE AE

  • 1 a and Co Copes Vulcan Operation 4

American Electdc Power Co Inc D.C. Cook Dominion Nuclear Connecticut Millstone Power Station

.t -~-------------------.$---------

19819071 Dor mion Nuclear Connecdcut Millstone Power Station 555-000 OP 555-000 OP 555-000 OP 1539576 k5757974 15787218 k5787218 15787218 15844536 5844535 15844536 I49819070 Dominion Nuclear Connecticut Millstone Power Station 19819060 Dominion Nuclear Connecticut Millstone Power Staion Z

20204886 Dominion Nuclear Connecticut Millstone Power Station 20204887 Dominion Nuclear Connectircut Mvton Power St--fon 71W/10 719110 7/9/1 0 7/22J i0 3/11/11 5/31/11 1/25/12 6/t3/11 1017/11 10/7/1l 20204888 Dominion Nuclear Connecticut Millstone Power Station I.

20204889 Dominion Nuclear Connecticut Millstone Power Station 45844536 20204890 Dominion Nuclear Connecticut Millstone Power Station 45844536 10/7/11 20204891 Dominion Nuclear Connecticut Millstone Power Station 45844536 10/7111 20204892 Dominion Nuclear Connecticut Millstone Power Station 458536 10/7111 20204893 Dominion Nuclear ConnecticUt Millstone Power Station 45844536 10/7)11 20268731 Dominion Nuclear Connecticut Millstone Power Station 45842360 4/25/2012 19930541 Dominion Virginia Power Su/

Power Station 45801851 3/161 1 20503240 Dominion Virginia Power o

Staton 45895D45 4/3/12 19659589 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 1/12 19659588 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 1216/11 19659587 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 1216111 19659585 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 9/27111 19659585 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 927111 19659584 Duke Energy Carolinas, LLC McGuire Nuclear Station 4D916 9/15/11 19659583 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 9/15111 19659582 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 9116/11 1-9659581 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 9115_11 19659580 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 8311 19659579 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 830/11 19659578 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 82211 19659577 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 7/29/11 19659576 Duke-Energy Carolinas, LLC McGuire Nuclear Station 140916 729111 19659575 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 7/26/11 Page I of 4

FIN 2012-03 Table '

19659574 Duke Energy Carolinas, LLC KoGuire Nuclear Station 140916 7120111 19659573 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 6/23/11 19659572 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 6/16/11 19659571 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 6/16/11 19659570 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 6115/11 19659569 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 6/16111 19659568 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 618il1 19659567 Duke Energy Carolinas, LLC McGuire Nuc[ear Station 140916 6/8/11 19659566 Duke Energy Carofinas, LLC McGuire Nuclear Station 140916 6/10111 19490135 Duke Energy Carolinas, LLC MoGuire Nuclear Station 132960 2123/11 I 199034--

uk~rry arins LC c~uire NuLea Stir-1296E

/3l 19490133 Duke Energy Carolinas, LLC McGu ire Nuclear Station 132960 1223111 19490132 Duke Energy Carolinas, LLC McGuire Nuclear Station 132960 1217110 19490131 D uke Energy Carolinas, LLC MaG uire Nuclear Station 132960 1215M10 19490130 Duke Energy Carolinas, LLC McGuire Nuclear Station 132960 11/5/10 19490129 Duke Energy Carolinas, LLC McGuire Nuclear Station 132960 11(5/10 19484999 Duke Energy Carolinas, LLC McGu*re Nuclear Station 132960 11(/t10 19675627 Duke Energy Carolinas, LLC MoGuire Nuclear Station 132960 4123/11 19675626 Duke Energy Carolinas, LLC McGuire Nuclear Station 132960 4112/11 19971997 Duke Energy Carolinas, LLC McGuire Nuclear Station 140916 1V23112 19911996 Duke Energy Carolinas, LLC McGuire Nuclear Statori 140916 1V23112 20304106 Duke Energy Carolinas, LLC McGuire Nuclear Station 00140916 REV 003 3/26/12 20304105 Duke Energy Carolinas, LLC McGuire Nuclear Station 00140916 REV 003 25/12 20304104 Duke Energy Carolinas, LLC McGuire Nuclear Station 00140916 REV 003 1/25/12 20304103 Duke Energy Carolinas, LLC McGuire Nuclear Station 00140916 REV 003 1/25/12 20304102 Duke Energy Carolinas, LLC McGuire Nuclear Station 00140916 REV 003 1/2-5/12 18277880 Edison Material Supply SONGS 4500023509 9/18109 20517717 Emerson Process Management-Asia 253-KF36080SR 4/25/12 20517718 Emerson Process Management-Asia 253-KF36080SR 4/25/12 20699192 Emerson Process Management-Asia 253-KF36184SR 819112 20699193 Emerson Process Management-Asia 253-KF36184SR 819112 19118224 Emerson Process Management-Belgium 4500299608 6/29109 19118223 Emerson Process Management-Belgium 4500299608 6/29J09 19118222 Emerson Process Managemernt-Belgium 4500299608 6/29109 19362540 Emerson Process Management-Be[gium 4500315767 3/31/10 Page 2 of 4

FIN 2012-03 Table I t-merson rrocess uManac Emerson Prooess Mana Entermy gLIu Indian Point Enerov Center Entergy Corp Palisades Entergy Corp Palisades Entergy Nuclear Generation Co Indian Point 2 Exelon Busness Services Co Clinton Nuclear Station Exelon Business Services Co Clinton Nuclear Station Exelon Business Services Co Clinton Nuclear Station Exelon Corp Peach Bottom Atomic Power Station 9

Exe!on Corp P-ea h B aot*m Atomic Power Staton 5767 447 REV. 001 REV- 001 REV- 001 47 15 15

'927

'927 36 REV 004 REV 004 36 3131J1 0 3/31110 9/28112 1008/10 10/7110 214111 3/25/09 9114110 9/14/10 8/26/11 8126111" 12123109 9/23/09 11/20/09 12123/09 ILtM+ i U4

(

1904D425 Exelon Nuclear

  • Clnton Nuclear Station Exelon Nuclear Clinton Nuclear Station 00z 190404241 Edon Nuclear Clinton Nuclear Station 19163174 Exelon Nuclear Clinton Nuclear Station 19029600 First Energy Corp Beaver Valley Nuclear Plant' 45296865 9/25/09 19029363 First Energy Corn Beaver Valley Nuclear Plant 45296865 9125/09 19294715 Lakeside Process Controls RCMT-265412-P9 2)25110 19294716 Lakeside Process Controls RCMT-265412-P9 2/2511 0 19294717 Lakeside Process Controls RCMT-265412-P9 22511 0 19294718 Lakeside Process Controls RCMT-265412-P9 2125110 19294719 Lakeside Process Controls RCMT-265412-P9 2125/10 19294720 Lakeside Process Controls RCMT-265412-PS 212511 0 20080090 Lakeside Process Controls RCMT-265412-P13-13142 6t17/11 20080091 Lakeside Process Controls RCMT-265412-P13-13142 6117111 20080092 Lakeside Process Controls RCMT-265412-P13-13142 6/17/11 20080093 Lakeside Process Controls RCMT-265412-P13-13142 6117111 20080094 Lakeside Process Controls RCMT-265412-P13-13142 6/17111 20080095 Lakeside Prooess Controls RCMT-265412-P13-13142 6117/11 19583178 Nebraska PublFic Power District Cooper Nuclear Station 4500098906 1112211 20637913 Nebraska Public Power District Cooper Nuclear Station 4500144836 8/15112 19445013 NEK KRSKO 41052406 1015/10 19443837 NEK KRSKO 41052406 9/30/10 19443835 NEK KRSKO 41052406 10/5/10 19443835 NEK KRSKO 41052406 9130/10 Page 3 of 4

FIN 2012-03 Table I I

j UAL 029556 PEAB Process AB D295551 PEAS Process AB 2,32378 Pinnacle West Capita] Corp 232379 Pinnacle West Capita] Corp UJul

-I.

Palo Verde Nuclear Generating Staton Palo Verde Nuclear Generatinc Station Pinnacle West Capita] Corp Palo Verde Nuclear Generating Station j Progress Energy.

Brunswick Plant PSEG Energy Holdings Inc Hope Creek/Salemn

=.rio 1205042271 1205D42281 PSEG Energy Holdings Inc Hope Creek/Salem PSEG Energy Holdincs Inc Hope Creek/Salem 2051 1 40 PSEG EI..r... ol'ings [n.......

Hope CreekdSalem 20511481 PSEG Energy Holdings Inc Hope CreekSalfern 20511482 PSEG Energy Holdings Inc Hope Creel/Salem r

20511483 PSEG Energ Holdings Inc Hope Creek/Safem 20795094 PSEG Nuclear LLC Hope Creek/Salemr 19829184 Public Service Electric and Gas Co Hope Creek/Salem 19829185 Public Service Electric and Gas Co Hope Creek/Salem --

19829186 Public Service Electric and Gas Co Hope CreeklSalem 19829187 Public Service Eectlic and Gas Co Hope Creek/Salem 19829188 Public Servioe Electric and Gas Co Hope CreekfSalem 19829189 Public Service Electric and Gas Co Hope Creek/Salemr 198291 90 Public Service Electric and Gas Co Hope Creek/Salem 19829191 Publfc Service Electjic and Gas Co Hope Creek/Salemr 19829192 Public Service Electric and Gas Co Hope Creek/Salem 19829193 Public Service Electric and Gas Co Hope Creek/Salem 19829194 Public Service Electric and Gas Co Hope Creek/Salem 19495584 Westinghouse Electric Company LLC Watts Bar Nuclear Plant Unit 2 19520007 Westinghouse Electric Company LLC Watts Bar Nuclear Plant Unit 2 19493497 Westinghouse Electric Company LLC Watts Bar Nuclear Plant Unit 2 19518726 Westinghouse Electric Company LLC Watts Bar Nuclear Plant Unit 2 19493496 Westingthouse Electric Company LLC Watis Bar Nuclear Plant Unit 2 59 39 59 at IurI I I 6/1/109 6/21/12 Y7/111 4/10112 t4/20112 3/10/11 3/10411 3/10/11 3/10/11 3/10111 3/10111 3110/11 3110/111 3110/111 3110/111 3/10/111 6/3/I 313/11 6/3/11 63/I 1 6/3/11

'C Page 4 of 4