Interim Report Concerning Battery Cells with Potentially Reduced Discharge Capacity
ML12073A347
Person / Time
Site: North Anna  
Issue date: 03/13/2012
From: Ross W
EnerSys
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
47735
Download: ML12073A347 (3)


Text

0311312012 U.S. Nuclear Regulatory Commission Operations Center Event Report Pak~e I Part 21 (PAR)

Event#

47735 Rep Org: ENERSYS Notification Date I Time: 03/12/2012 15:33 (EDT)

Supplier: ENERSYS Event Date / Time: 03/12/2012 (EDT)

Last Modification: 03/13/2012 Region:

1 Docket #:

City:

READING Agreement State:

Yes County:

License #:

State:

PA NRC Notified by: WILLIAM ROSS Notifications: GEORGE HOPPER R2DO HQ Ops Officer: PETE SNYDER NRR PART 21 GROUP EMAIL Emergency Class: NON EMERGENCY 10 CFR Section:

INFORMATION ONLY INTERIM REPORT CONCERNING BATTERY CELLS WITH POTENTIALLY REDUCED DISCHARGE CAPACITY "This letter will serve as the interim report to the Commission as pursuant to 10CFR21.21 (a) (2). The notification is in regards to a 2GN-23 battery manufactured by EnerSys and installed as part of Station Battery 2-2 at the Dominion Virginia Power, North Anna Station. Battery verification testing performed at North Anna indicated that although the battery was able to meet North Anna's 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> discharge requirements, cell #59 appeared to show reduced capacity. As a result, Dominion returned cells #59 and #60 to EnerSys. The cells were received at the EnerSys Corporate Laboratory under Return for Analysis (RFA) ENS-1 1204.

"During our analysis, which consisted of float charging, discharge testing at the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rate and an internal inspection it was determined that the cell was unable to meet the defined technical requirements for discharge capacity. Following the determination a series of analytical tests were ordered to perform more in depth analyses of the internal components. Testing on the component samples is currently underway. At this time we have not yet been able to determine if a "defect" as defined in Part 21 exists and therefore this interim report has been prepared. It is expected that the current tests will be completed by May 11, 2012. However, it should be noted that further analysis including the return of additional cells may be required to determine the cause and the reportability under Part 21 reporting."

"Throughout the return and analysis processes EnerSys has been in contact with representatives of the North Anna Station. They have been made aware of the electrical test results and recently of the internal inspection results. They are also aware that there has been no cause determination at this time. Station personnel have also been notified that this interim report has been issued."

MAR/-12/2012/MON 03:33 PM FAX No, F. 001 EnerSys P.0, Box 14145 Reading, PA 19612-4145 800-638-3627 x 1974 Fax 610-208-1971 emai[: bil.ross(qenersys.com Foe oiwwnr

w. enorsys.com William R. Ross Manager, Americas Quality Assurance March 12, 2012 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-001 To Whom It May Concern, This letter will serve as the interim report to the Commission as pursuant to 1 OCFR21.21 (a) (2). The notification is in regards to a 2GN-23 battery manufactured by EnerSys and installed as part of Station Battery 2-2 at the Dominion Virginia Power, North Anna Station. Battery verification testing performed at North Anna indicated that although the battery was able to meet North Anna's 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> discharge requirements, cell #59 appeared to show reduced capacity. As a result, Dominion returned cells #59 and #60 to EnerSys.

The cells were received at the EnerSys Corporate Laboratory under Return for Analysis (RFA) ENS-1 1204.

During our analysis, which consisted of float charging, discharge testing at the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rate and an internal inspection it was determined that the cell was unable to meet the defined technical requirements for discharge capacity. Following the determination a series of analytical tests were ordered to perform more in depth analyses of the internal components. Testing -on the component samples is currently underway. At this time we have not yet been able to determine if a "defect" as defined in Part 21 exists and therefore this interim report has been prepared. It is expected that the current tests will be completed by May 11, 2012. However, it should be noted that further analysis including the return of additional cells may be required to determine the cause and the reportability under Part 21 reporting.

Throughout the return and analysis processes EnerSys has been in contact with representatives of the North Anna Station. They have been made aware of the electrical test results and recently of the internal inspection results. They are also aware that there has been no cause determination at this time. Station personnel have also been notified that this interim report has been issued.

Please contact me with requests for additional information, comments or questions.

MAR/42/2012/MON 03:34 PM FAX No, P. 002

Regards, (2

24 William RoAs Cc: W. Hunsberger (Dominion), J. Lewis, S. McHugh (Dominion), J. Reber, S. Vechy, S.

Weik, R, Zuidema, QA files