Part 21 Report - Potential Minimum Wall Violation on Seismic Plate Valve Bodies
ML12061A268
Person / Time
Site: Watts Bar, Clinton  
Issue date: 02/28/2012
From: Fitzgerald B
Emerson Process Management, Fisher Controls International
To: Hodge V
Office of Nuclear Reactor Regulation
References
47706
Download: ML12061A268 (5)


Text

0212812012 2 U.S. Nuclear Regulatory Commission Operations Center Event Report Paze I Part 21 (PAR)

Event#

47706 Rep Org: FISHER CONTROLS INTERNATIONAL Notification Date / Time: 02/28/2012 15:21 (EST)

Supplier: FISHER CONTROLS INTERNATIONAL Event Date I Time: 02/24/2012 (CST)

Last Modification: 02/28/2012 Region:

3 Docket #:

City: MARSHALLTOWN Agreement State:

Yes County:

License #:

State: IA NRC Notified by: BILL FITZGERALD Notifications: ANN MARIE STONE R3DO HQ Ops Officer: CHARLES TEAL MARK FRANKE R2DO Emergency Class: NON EMERGENCY PART 21 GROUP EMAIL 10 CFR Section:

21.21 UNSPECIFIED PARAGRAPH PART 21 REPORT - POTENTIAL MINIMUM WALL VIOLATION ON SEISMIC PLATE VALVE BODIES "While reviewing Valve Body drawing 16B2201, it was discovered that an area in the packing bore has the possibility to not meet the minimum wall requirements of ASME B16.34 for a Class 150 valve at the minimum material condition due to a potential stack up of tolerances.

"Upon discovery of this possible failure to comply, an investigation was performed on all NPS 3-12 Type Al1 Class 150 Seismic Plate Valve Bodies and it was determined that this issue was isolated to the NPS 8 Type Al 1 Class 150 Seismic Plate Valve Body per drawing 16B2201.

"It is the opinion of Fisher that there is no inherent safety risk associated with this situation. Fisher will be working with the individual plants [Clinton Power Station and Watts Bar] in question to measure the actual dimensions of the bodies to determine if a problem exits and will take appropriate corrective action."

Fisher Information Notice: FIN 2012-01 L e--

,L451':ýf

Feb. 28. 2012 2:1OPM EMERSON.

No. 3709 P. 1/4

[FuSE,=RJ Facsimile 301 South First Avel Marshalltawn, IA 50158 T 641-754-2688 F 641-754-2645 To: Vernon Hodge - NRC Fax: 301-816-5151 From: Dennis Swanson Date: 212812012 Pages: 4 (min covet)

Attachment:

Fisher Information Notice: FIN 2012-01 For technical questions, please contact George Baltinger (641) 754-2026, or Dennis Swanson (641) 754-2381. Any other questions, give me a call.

Trish Crosser I Executive Assistant I Fisher Division Emerson Process Management 1 301 S. 1st Avenue I Marshalltown, Iowa 501568 I USA T +1641.754.2688 IF t1 641.754.2688 Trlsh.Crosser@Emerson.com

Feb.28. 2012 2:10PM No. 3709' P. 2/4 4

EMERSON.

Fisher Controls International LLC Process Management 301 South First Ave.

P.O. Box 190 Marshalltown, Iowa 50158-0100 USA T (641) 754-3011 F (641) 754-2830 Fisher Information Notice: FIN 2012-01 February 24, 2012

Subject:

NPS 8 Class 150 Type All Potential Minimum Wall Violation on Seismic Plate Valve Bodies From:

Bill Fitzgerald Vice President, Nuclear Business Unit Fisher Controls International LLC 301 South First Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Equipment Affected By This Information Notice:

NPS 8 Class 150 Type All Seismic Plate Valve Bodies Manufactured per Fisher Drawing Number 16B2201 for the following Order and Item Numbers shipped from Marshalltown, Iowa:

Order Number Item Number Serial Number Utility Plant Site 014-A107131941 0001 16747009 Exelon Clinton Power Station 014-A107209414 0005 16986262

-Exelon Clinton Power Station 014-Al07209414 0006 16986263 Exelon Clinton Power Station 014-T107276947 002A 19040424 Exelon Clinton Power Station 014-T107276947 002B 19040425 Exelon Clinton Power Station 025-D230254781 0003 12421 1I'VA Watts Bar Unit 2 (FISHER]

auUI U

Feb. 28.

2012 2:10PM No.3709 P. 3/4 Fisher Information Notice: FIN 2011-01

Purpose:

The purpose of this Fisher Information Notice ("FIN") is to alert customers that as of February 15, 2012 Fisher Controls International LLC ("Fisher") became aware of a possible failure to comply.

Pursuant to 10 CFR 21.21(b), Fisher is providing the required written notification of a failure to comply.

Receipt of this notice does not necessarily mean that the recipient has been shipped any of the subject equipment. Fisher records indicate that only the listed serial numbers are the affected units. It is expected that the recipients of this notice will review the information for applicability to their facilities, and if required, take the appropriate action as described in the section at the end of this notice.

Applicability:

This notice applies only to the equipment identified in the table above. The table lists Fisher Order and Item Numbers that were delivered to Exelon and WVA. No other items were affected.

Discussion:

While reviewing Valve Body drawing 1682201 (NPS 8 Type All I Class 150 Seismic Plate Valve Body), it was discovered that an area in the packing bore has the possibility to not meet the minimum wall requirements of ASME B16.34 for a Class 150 valve at the minimum material condition due to a potential stack up of tolerances.

Upon discovery of this possible failure to comply, an investigation was performed on all NPS 3-12 Type All Class 150 Seismic Plate Valve Bodies and it was determined that this issue was isolated to the NPS 8 Type All1 Class 150 Seismic Plate Valve Body per drawing 16B2201.

It is the opinion of Fisher that there is no inherent safety risk associated with this situation, Fisher will be working with the individual plants in question to measure the actual dimensions of the bodies to determine if a problem exists and will take appropriate corrective action.

Fisher will revise the drawing to ensure that this issue is corrected.

[Page 2 of 3

Feb. 28. 2012 2:11PM No.3709 P. 4/4 Fisher Information Notice: FIN 2011-01 Action Required:

No action is required at this time. The affected customers are being contacted to resolve any situation that exists.

10CFR21 Implications:

Fisher requests that the recipient of this notice review it and take appropriate action in accordance with 1CFR Part 21.

If there are any technical questions or concerns, please contact:

George Baitinger Manager, Quality Fisher Controls International LLC 301 South First Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Phone: (641) 754-2026 George. Baitinger@Emerson. com Page 3 of 3