ML12020A058

From kanterella
Jump to navigation Jump to search
NRR E-mail Capture - Draft - Request for Additional Information - LaSalle County Station, Unit 1 - SLMCPR License Amendment
ML12020A058
Person / Time
Site: LaSalle  Constellation icon.png
Issue date: 01/10/2012
From: Nicholas Difrancesco
Division of Operating Reactor Licensing
To: Mathews M
Exelon Generation Co
References
Download: ML12020A058 (4)


Text

1 NRR-PMDAPEm Resource From:

DiFrancesco, Nicholas Sent:

Tuesday, January 10, 2012 5:01 PM To:

Mitchel.Mathews@exeloncorp.com Cc:

Zimmerman, Jacob; Huang, Tai; David.Gullott@exeloncorp.com; terrence.simpkin@exeloncorp.com; DiFrancesco, Nicholas

Subject:

DRAFT - Request for Additional Information - LaSalle County Station, Unit 1 - SLMCPR License Amendment Attachments:

LSCS Unit 1 SL MCPR RAIs.pdf Follow Up Flag:

Follow up Due By:

Monday, January 09, 2012 4:00 PM Flag Status:

Flagged Mr. Mathews, By letter to the Nuclear Regulatory Commission dated October 12, 2011, Exelon Generation Company, LLC, the licensee for LaSalle County Station, Unit 1, submitted a License Amendment Request regarding revisions to the safety limit minimum critical power ratios (SLMCPR).

The Reactor Systems Branch has reviewed the information provided and determined that additional information is needed to complete its review. The draft request for additional information is attached.

Please contact me after you have reviewed the questions to discuss the need for a clarification call on the RAI questions and the response date.

Sincerely, Nicholas DiFrancesco Project Manager - LaSalle U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Operating Reactor Licensing nicholas.difrancesco@nrc.gov l Tel: (301) 415-1115

Hearing Identifier:

NRR_PMDA Email Number:

238 Mail Envelope Properties (8DBF4F9959B56A41BFAD44DF618A435B0671322244)

Subject:

DRAFT - Request for Additional Information - LaSalle County Station, Unit 1 -

SLMCPR License Amendment Sent Date:

1/10/2012 5:01:06 PM Received Date:

1/10/2012 5:01:00 PM From:

DiFrancesco, Nicholas Created By:

Nicholas.DiFrancesco@nrc.gov Recipients:

"Zimmerman, Jacob" <Jacob.Zimmerman@nrc.gov>

Tracking Status: None "Huang, Tai" <Tai.Huang@nrc.gov>

Tracking Status: None "David.Gullott@exeloncorp.com" <David.Gullott@exeloncorp.com>

Tracking Status: None "terrence.simpkin@exeloncorp.com" <terrence.simpkin@exeloncorp.com>

Tracking Status: None "DiFrancesco, Nicholas" <Nicholas.DiFrancesco@nrc.gov>

Tracking Status: None "Mitchel.Mathews@exeloncorp.com" <Mitchel.Mathews@exeloncorp.com>

Tracking Status: None Post Office:

HQCLSTR01.nrc.gov Files Size Date & Time MESSAGE 972 1/10/2012 5:01:00 PM LSCS Unit 1 SL MCPR RAIs.pdf 261607 Options Priority:

Standard Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received:

ZZZ

DRAFT REQUEST FOR ADDITONAL INFORMATION LASALLE COUNTY STATION, UNIT 1 LICENSE AMENDMENT REQUEST REGARDING PROPOSED SAFETY LIMIT MINIMUM CRITICAL POWER RATION CHANGE DOCKET NO. 50-373 By letter dated October 12, 2011 (Agencywide Documents Access and Management System Accession (ADAMS) Accession No. ML112860067), Exelon Generation Company LLC (Exelon, the licensee) submitted a license amendment request (LAR) proposing to modify technical specification (TS) Section 2.1, Safety Limits, for LaSalle County Station (LSCS), Unit 1. The requested change involved revised safety limit minimum critical power ratios (SLMCPRs) calculated as a result of the cycle-specific analysis performed by Global Nuclear Fuel (GNF) to support operation in the upcoming LSCS, Unit 1, Cycle 15. The U.S. Nuclear Regulatory Commission (NRC) staff has been reviewing the submittal and has determined that additional information is needed to complete its review.

1. In the LAR, Attachment 6, Tables RAI-06-1 and RAI-06-2, provide core map to show those bundles experienced 0.1 boiling transition criterion of limiting cases for single-loop operation (SLO) and two-loop operation (TLO). Please provide identification of bundle group and number of bundles in the Figure 1, Attachment 5, corresponding to their burnup status (once-burned, twice-burned, or fresh fuel) for Cycle 15.
2. Core design is an iterative process designed to develop an optimal configuration that meets operational requirements. In the LAR, Attachment 7, for the slides titled Pre-Estimation

- Linear Reactivity, please provide the most current updated parameters applicable to LSCS, Unit 1, Cycle 15. Also, provide the details of a plant-specific final core loading pattern as shown in Figure 1 including core design procedures, guidelines, criteria, and approved methodologies used for this Cycle 15 analysis with respect to a mixed core application.

3. GNF2 fuel deviates from traditional 10x10 design through the introduction of a partial length rod configuration, the use of higher linear power, and the use of mixing vanes. The NRC staff considers this a new fuel design with regards to the four restrictions identified in the safety evaluation of General Electric (GE) Licensing Topical Reports NEDC-32601P, NEDC-32694, and Amendment 25 to NEDE-24011-P-A. Given that LSCS, Unit 1, Cycle 15, uses a core loading pattern which includes GNF2 fuel, provide the following: (1) an evaluation of the four restrictions in NEDC-32601P, NEDC-32694 and Amendment 25 to NEDE-24011-P-A and the applicability to mixed core with ATRIUM 10 fuel; (2) a description that explains under what conditions the methodologies listed in Section 1.0 of Attachment 5 are sufficient and applied to the LSCS, Unit 1, Cycle15, application; and (3) a clarification for the statement no new GNF2 fuel designs are being introduced in LSCS, Unit 1, Cycle 15, in Section 2.5 of.
4. The LSCS, Unit 1, Cycle 15, is a mixed core with once and twice burned ATRIUM 10 fuel.

Please provide: (1) a detailed description of the methodologies used and procedures applied

DRAFT to the LSCS, Unit 1, Cycle 15, calculation for the proposed SLMCPR values based on Figure 3, ; and (2) justification that the methodologies related to ATRIUM 10 fuel may not be needed in this application because none is listed in Section 1.0, Attachment 5.

5. Please identify the breakdown of the 10x10 data shown in Attachment 5, Figure 5, by fuel type (i.e., GE14, GNF2), because Figure 5 only shows combined data points for the two fuel types. Also, provide: (1) details of the application of Figure 5 data to a mixed core with ATRIUM 10 fuel; and (2) justification that the estimation formula for SLMCPR value is still valid for LSCS, Unit 1, Cycle 15, application.
6. Please clarify that there is no effect of GNF2 bent spacer wing to LSCS, Unit 1, Cycle 15, operation. If there is an adverse impact, please provide an assessment of the impacts on operations and fuel thermal performance.
7. Please provide an updated version of power/flow map for Cycle 15 operation including stability Option III features of scram region and controlled entry region for backup stability protection based on the Boiling-Water Reactor Owners Group position stated in NEDO-31960A for SLO and TLO.