Calvert Cliffs Nuclear Power Plant CENG a joint venture of Constellation

Energy, eDF CALVERT CLIFFS NUCLEAR POWER PLANT 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 October 6, 2011 Maryland Department of the Environment Water Supply Program 1800 Washington Boulevard, Suite 450 Baltimore, MD 21230 ATTENTION:

SUBJECT:

Mr. Saeid Kasraei Calvert Cliffs Nuclear Power Plant September 2011 Monthly Domestic Water and Disinfectant Residual Monitoring Reports

REFERENCES:

(a)

Code of Maryland Regulations, COMAR 26.04.01.26 (b)

Letter from N. Reilman (MDE) to Public Water Systems and Laboratories, Chlorine Residual Monitoring and Reporting for

2010, dated September 23, 2010 In accordance with References (a) and (b), enclosed are the Monthly Domestic Water and Disinfectant Residual Monitoring Reports for Calvert Cliffs Nuclear Power Plant.

Should you have questions regarding this matter, please contact me at (410) 495-5219 or Mr. Scott Strickland at (410) 495-2318.

Very truly yours, Douglas E. Lauver Director - Licensing DEL/CAN/bjd

Enclosures:

Monthly Operating Record (2 pages)

Domestic Water Log (2 pages)

Disinfectant Residual Monitoring Report Form (2 pages)

ENCLOSURES Monthly Operating Record (2 pages)

Domestic Water Log (2 pages)

Disinfectant Residual Monitoring Report Form (2 pages)

Calvert Cliffs Nuclear Power Plant, LLC October 6, 2011

Monthly Operating Record Calvert County Maryland, Calvert Cliffs Nuclear -

Owner Controlled Area PWSID#: 104-0055 Monthly 0 eratina Record for SeD-1 1 Date FAC TRC Cl2 Cl2Tank Signet APU Totalizer Vessel AAP Vessel Inlet Outlet Field Kit Level Totalizer Arsenic Comments I(ppm)

(ppm)

Stroke (gallons)

(gallons)

(gallons)

BP Pressure Pressure (ppb) 9/1/2011 10:00 CWH 0.40 0.41 20%

15 SEE LOG 9/2/2011 12:00 CWH 0.43 0.46 R

9/6/2011 9:30 JP 0.37 0.41 20%

14 51569 9847236 0

0 70 70 9/7/2011 8:00 CWH 0.52 0.60 SEE LOG 9/8/2011 CWH; SEE LOG 9/9/2011 12:00 CWH 0.51 0.57 SEE LOG 9/12/2011 16:00 CWH 0.35 0.39 9/13/2011 11:00 CWH 0.38 0.39 30%

13 72863 9872260 0

0 68 66 SEE LOG 9/14/2011 9:35 TB 0.37 0.39 9/15/2011 8:30 TB 0.32 0.35 9/16/2011 8:00 TB 0.34 0.36 30%

9 207109 10032539 0

0 68 66 9/19/2011 12:30 CWH 0.33 0.40 30%

15 291116 10141208 0

0 70 68 SEE LOG 9/20/2011 10:00 JP 0.35 0.41 9/21/2011 14:30 JP 0.33 0.34 9/22/2011 8:45 CWH 0.38 0.42 9/23/2011 9:45 TB 0.41 0.43 30%

12 443400 10329028 0

0 68 68 9/26/2011 15:00 JP 0.31 0.34 SEE LOG 9/27/2011 14:05 TB 0.35 0.37 9/28/2011 13:45 TB 0.32 0.34 30%

10 482007 10381666 0

0 70 68 9/29/2011 14:00 CWH 0.37 0.41 9/30/2011 13:15 CWH 0.34 0.37 30%

7 500355 10405845 0

0 70 68 HIGH 0.52 0.60 500355 10405845 F

LOW 0.31 0.34 51569 AVG 0.37 0.41 292631 TOTAL 500355 14138434 This report is submitted in accordance with Comar 26.04.01.26. 1 certify tha is report is truthful to the best of my knowledge and belief.

Scott G. Strickland 1 6944 1

IZcf I

/2,3 1 I z

OYZ Supt Drinking Water I License Number jExpiration Date ISirnature

Monthly Operating Record Calvert County Maryland, Calvert Cliffs Nuclear-Protected Area PWSID#: 104-0002 Monthly Oerating Record for Sep-1 1 FAC TRC C12 CL2lank Signet Totalizer APU Totalizer Vessel Inlet Outlet Field Kit Dath (ppm)

(ppm)

Stroke L elos (gallons)

(gallons)

Vessel AAP BAP Pressure Pressure (ppb)

Dae ie eh pm)

(pm trk (gallons) 9/1/2011 9:00 CWH 1.08 1.10 10%

9/2/2011 11:30 TB 0.67 0.69 9/6/2011 12:30 CWH 0.81 0.86 10%

9 0

912630 1

0 88 88 9/7/2011 11:05 TB 0.59 0.61 9/8/2011 10:30 TB 0.46 0.49 10%

9 0

915707 2

0 88 84 9/9/2011 9:00 CWH 0.52 0.53 9/12/2011 10:35 TB 0.38 0.41 10%

9 0

917119 1

0 88 85 9/13/2011 9:00 CWH 0.42 0.47 9/14/2011 11:35 TB 0.45 0.46 9/15/2011 9:50 TB 0.42 0.45 9/16/2011 9:30 TB 0.79 0.82 10%

9 0

920221 1

0 88 86 9/19/2011 12:20 TB 0.43 0.45 9/20/2011 13:00 JP 0.45 0.49 10%

9 0

921669 1

0 90 90 9/21/2011 14:00 JP 0.40 0.43 9/22/2011 10:30 CWH 0.41 0.42 10%

9 0

922749 1

0 90 90 9/23/2011 7:45 TB 0.42 0.44 10%

0 9/26/2011 14:30 JP 0.33 0.34 10%

8 0

924589 1

0 90 90 9/27/2011 11:00 JP 0.35 0.38 SEE LOG 9/28/2011 8:45 JP 0.47 0.51 9/29/2011 12:30 TB 0.36 0.39 9/30/2011 13:25 TB 0.34 0.37 10%

7 0

927475 1

0 88 88 HIGH 1.08 1.10 0

927475 LOW 0.33 0.34 0

AVG 0.50 0.53 r

1 1

10 TOTAL

__0 4371909 This report is submitted in accordance with Comar 26.04.01.26. I certify that this report is truthful to the best of my knowledge and belief.

Scott G. Strickland I 6944 11-, -3.

1 e

Supt Drinking Water I License Number I Expiration Date ISigir'ature

Office Complex Domestic Water Log, 104-0055 Date/Time Initials Entry 9/1/2011 10:00:00 AM 9/7/2011 8:00:00 AM CWH Batched sodium hypochlorite to 15 gallons.

CWH Lost power to domestic water pumps and LMI pump 12:00.

Drinking water super intendent contacted MDE 9/8/2011 CWH Domestic water pumps still do not have power.No flow to grab sample. Only one flow reading this week. CR initiated.

9/9/2011 12:00:00 PM 9/13/2011 11:00:00 AM 9/19/2011 12:30:00 PM 9/26/2011 Sdflhetntendent CWH Domestic water restored. Temporary power to both chlorine and arsenic skids.

CWH Permanent Power restored to skid walkdowns complete.

Increased stroke to 30%

CWH Batched sodium hypochlorite to 15 gallons.

JP Called Faciltities, high flow in the OCA system is due to a cooling system valve stuck open. The valve has been repaired.

Lic.#

Exp Date Monday, October 03, 2011 Page I of I

PA Domestic Water Log, 104-0002 Date/Time 9/27/2011 11:00:00 AM Superintendet~t Initials Jp Lic.#

Entry Replaced LMI pump tubing and injector.

Exp. Date Monday, October 03, 2011 Page I of I

Mail to:

MARYLAND DEPARTMENT OF THE ENVIRONMENT WATER SUPPLY PROGRAM 1800 Washington Blvd. STE 450 Baltimore, Maryland 21230-1708 (410) 537-3729 (800) 633-6101 ext. 3729 http://www.mde.state.md.us DISINFECTANT RESIDUAL MONITORING REPORT FORM This report must be received quarterly by the 10th day of the month following the end of the quarter.

Results of invalidated samples are not to be included on this report form.

System Name: Calvert Cliffs Nuclear Power Plant-Owner Controlled Area PWSID: 104-0055 Reporting Period: Ending Year: 2011 Record for:

January 1 - December 31 Report Due January 10

[]

April 1 - March 31 Report Due April 10 El (Check 1 Period July 1 - June 30 Report Due July 10 Only)

October 1 - September 30 Report Due October 10 Z

Disinfectant (Check One)

Free Chlorine X

Combined Chlorine Chlorite Month/Year Average Residual Quarterly Average Annual Average Concentration (ppm)

(ppm)

(ppm)

July 2011 0.51 August 2011 0.46 0.46 September 2011 0.41 October 2010 0.47 November 2010 0.51 0.50 December 2010 0.52 0.55 January 2011 0.64 February 2011 0.88 0.65 March 2011 0.44 April 2011 0.54 May 2011 0.49 0.59 June 2011 0.74

Mail to:

MARYLAND DEPARTMENT OF THE ENVIRONMENT WATER SUPPLY PROGRAM 1800 Washington Blvd. STE 450 Baltimore, Maryland 21230-1708 (410) 537-3729 (800) 633-6101 ext. 3729 http://www.mde.state.md.us DISINFECTANT RESIDUAL MONITORING REPORT FORM This report must be received quarterly by the 10th day of the month following the end of the quarter.

Results of invalidated samples are not to be included on this report form.

System Name: Calvert Cliffs Nuclear Power Plant-Protected Area PWSID: 104-0002 Reporting Period: Ending Year: 2011 Record for:

(Check 1 Period Only)

January 1 - December 31 April I - March 31 July 1 - June 30 October 1 - September 30 Report Due January 10 Report Due April 10 Report Due July 1 Report Due October 10

[]0 Disinfectant (Check One)

Free Chlorine X

Combined Chlorine Chlorite Month/Year Average Residual Quarterly Average Annual Average Concentration (ppm)

(ppm)

_(ppm)

July 2011 0.63 August 2011 0.80 0.65 September 2011 0.53 October 2010 0.46 November 2010 0.44 0.44 December 2010 0.41 0.55 January 2011 0.50 February 2011 0.81 0.62 March 2011 0.55 April 2011 0.41 May 2011 0.49 0.49 June 2011 0.56