ML11234A262

From kanterella
Jump to navigation Jump to search
Lr - FW: Davis-Besse Conference Call
ML11234A262
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 06/24/2011
From:
Office of Nuclear Reactor Regulation
To:
References
Download: ML11234A262 (3)


Text

Davis-BesseNPEm Resource From: CuadradoDeJesus, Samuel Sent: Friday, June 24, 2011 12:36 PM To: dorts@firstenergycorp.com

Subject:

RE: FW: Davis-Besse Conference call Ill sending a schedule soon From: dorts@firstenergycorp.com [1]

Sent: Friday, June 24, 2011 11:35 AM To: CuadradoDeJesus, Samuel Cc: 'custerc@firstenergycorp.com'

Subject:

Re: FW: Davis-Besse Conference call Sam... Tuesday is ok for a conference call. Please let us know the time and call-in information.

Thank you, Steve Dort DBNPS License Renewal 419.321.7662 work 412.974.3369 cell From: "CuadradoDeJesus, Samuel" <Samuel.CuadradoDeJesus@nrc.gov>

To: "'custerc@firstenergycorp.com'" <custerc@firstenergycorp.com>, "dorts@firstenergycorp.com" <dorts@firstenergycorp.com>

Date: 06/24/2011 09:41 AM

Subject:

FW: Davis-Besse Conference call Cliff and Steve Below are the rest of our staff concerns on Structural RAI responses. Well like to have a conference call early next week, would next Tuesday be ok with you guys?

Regards From: Sheikh, Abdul Sent: Friday, June 24, 2011 9:17 AM To: CuadradoDeJesus, Samuel

Subject:

RE: Davis-Besse Conference call RAI B.2.22-1 Provide basis for selecting only three locations for NDT for such a large area One time NDT before PEO will not be sufficient to establish a trend before the PEO FENOC did not provide details on what and how it will inspect the annulus area. Need specific details RAI B.2.22-2 The RAI response specific actions and details. Need firm plans. Just stating that FENOC plans to access the inside surface of containment is not acceptable.

1

RAI B.2.22-3 How and when coating is inspected.

RAI B.2.22-4 The response not consistent with GALL recommendations. GALL report, Program XI.S1 states:

Stainless steel penetration sleeves, dissimilar metal welds, bellows, and steel components that are subject to cyclic loading but have no current licensing basis fatigue analysis are monitored for cracking.

However, LRA states that the program is consistent with GALL.

From: CuadradoDeJesus, Samuel Sent: Friday, June 24, 2011 8:22 AM To: Sheikh, Abdul

Subject:

Davis-Besse Conference call Good morning Abdul Can you please send me the summary of your concerns with DB RAI responses? Ill schedule the conference call for next Tuesday.

Thanks Samuel Cuadrado de Jesús Project Manager Projects Branch1 Division of License Renewal U.S. Nuclear Regulatory Commission Phone: 301-415-2946 Samuel.CuadradoDeJesus@nrc.gov


The information contained in this message is intended only for the personal and confidential use of the recipient(s) named above. If the reader of this message is not the intended recipient or an agent responsible for delivering it to the intended recipient, you are hereby notified that you have received this document in error and that any review, dissemination, distribution, or copying of this message is strictly prohibited. If you have received this communication in error, please notify us immediately, and delete the original message.

2

Hearing Identifier: Davis_BesseLicenseRenewal_Saf_NonPublic Email Number: 77 Mail Envelope Properties (Samuel.CuadradoDeJesus@nrc.gov20110624123600)

Subject:

RE: FW: Davis-Besse Conference call Sent Date: 6/24/2011 12:36:07 PM Received Date: 6/24/2011 12:36:00 PM From: CuadradoDeJesus, Samuel Created By: Samuel.CuadradoDeJesus@nrc.gov Recipients:

"dorts@firstenergycorp.com" <dorts@firstenergycorp.com>

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 3183 6/24/2011 12:36:00 PM Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date:

Recipients Received: