Text
I
'N 05/12/2011 U.S. Nuclear Regulatory Commission Operations Center Event Report Part 21 (PAR)
Event#
46846 Rep Org: ASCO VALVE Notification Date / Time: 05/12/2011 16:14 (EDT)
Supplier: ASCO VALVE Event Date / Time: 05/12/2011 (EDT)
Last Modification: 05/12/2011 Region:
1 Docket #:
City:
AIKEN Agreement State:
Yes County:
License #:
State: SC NRC Notified by: ROBERT ARNONE Notifications: ANNE DEFRANCISCO R1DO HQ Ops Officer: DONG HWA PARK EUGENE GUTHRIE R2DO Emergency Class: NON EMERGENCY DAVE PASSEHL R3DO 10 CFR Section:
DAVID PROULX R4DO 21.21 UNSPECIFIED PARAGRAPH PART 21 GROUP U-RINGS FABRICATED WITH INCORRECT MATERIAL "The following was received via facsimile:
"This report relates to two NP8344E series four-way solenoid valves found to be leaking through the exhaust port in both the energized and de-energized states.
"Background - On January 21, 2011, ASCO Valve, Inc. (ASCO) was notified by AREVA that a four-way solenoid valve NP8344A75E AC, (serial number F623557002-002) from the Dresden Station was leaking from the exhaust port in both the energized and de-energized states. AREVA reported that Exelon Labs had performed a Fourier Transform Infrared Spectroscopy (FTIR) analysis which indicated the piston U-ring exhibited properties consistent with a Nitrile compound instead of Teflon coated Ethylene Propylene as required by the ASCO design drawing.
The valve itself was not returned to ASCO. At ASCO's request, Exelon returned the U-ring on January 27, 2011.
ASCO provided a letter to Dresden Station on February 3, 2011 (Reference A) maintaining the correct U-ring material was installed at the time of shipment and that no additional action was required.
"The second occurrence involved another four-way solenoid valve, NPK8344A072E DC, (serial number F337837-2), from PSEG Nuclear's Salem station, returned to ASCO on Service RMA 47113 on February 25, 2011. The valve was brought to ASCO where testing confirmed the valve was leaking through the exhaust ports in both the energized and de-energized states. The inspection of parts showed that the U-ring material had become brittle. If the U-ring becomes brittle, it may no longer perform its sealing function.
"ASCO Investigation Results - The above referenced valves were manufactured in 1992 (Dresden) and 1995 (Salem) respectively. It was determined that both valves used the same piston U-ring, part number 029043-024-S.
This U-ring is common to both the 3/8" and 1/2" NPT valve constructions, A review of ASCO's incoming and
""U:-
I
I
~
05/12/2011 U.S. Nuclear Regulatory Commission Operations Center Event Report Page Part 21 (PAR)
Event #
46846 dedication inspection records indicated that these U-rings were Teflon coated Ethylene Propylene. The piston U-rings from the Salem and Dresden valves, along with a piston U-ring from ASCO's current stock, were sent to a third party laboratory for a FTIR analysis. The U-rings from both the Salem and Dresden valves were determined by the laboratory to be Nitrile. The U-ring from current stock was determined to be Teflon coated Ethylene Propylene, as called for by the design drawings, "Impact on Performance - The use of a Nitrile piston U-ring could potentially reduce the valve life and result in leakage through the exhaust port.
"Initial Action - FTIR analysis confirmed that the piston U-ring in ASCO's current stock was Teflon coated Ethylene Propylene. ASCO records disclosed no prior cases of piston U-rings fabricated with incorrect material.
Discussions with the distributor of the U-rings disclosed no other cases of improper material.
"Corrective Action - The customers that were shipped potentially affected NP8344E valves are being notified of the potential deviation. All variations of NP8344A72E, NP8344A73E, NP8344A74E, NP8344A75E, NP8344850E, NP8344[52E, NP8344B62E, and NP8344B64E manufactured from 1992 through 1995 are recommended to be monitored for leakage. Due to the qualified service life and date of manufacture, it is believed a majority of these valves are no longer in service, Subsequent to 1995, ASCO has implemented a more rigorous lot and batch control to verify the material compound at incoming and dedication inspection. This action further enhanced traceability of resilient materials used in specific production lots.
May, 12.
2011 3'11PM ASCO VALVE AIKEN PLANT No, 5017 P. I ASAValve Manufacturing, Inc.
AIKEN, S.C.
FAX: 803-641-9290 FAX FROM:
DATE:
3oV Sl(ce%*/h/
rUiŽQ t~&~ Q~A~k NAA C~4y~j~ kcoo~
)A61 \\J,~2 ON KS ý 'ývc/
ýj kQ,
~&~tNJ ~XCAk Qýwý ý t ~~sit\\
(tYX~X'CQ& ~KSH-3Pre Oft j 7) Pýz ý @4tw Q0A\\ 2os-Y1-9.W<9 PGas INCL UDiNG CsnrP a~te.
$I. f5-.
IIy h no..4,
'.!t.mz..# 4.tp *g en of this fax, ple, se cell (808) 641-g3 0..7
. Fonn Aiken i4$.5 R 101I:1
May. 12. 2011 3:11PM ASCO VALVE AIKEN PLANT No.5017 P. 2 EMERSON.
Industrial Automatron ASCO Valve, Inc.
50 Hanover Road Florham Park, NJ 07932 USA T (973) 966 2000 F (973) 966 2628 www.asconumalics.com May 12, 2011 NRC Documents Control Desk U,S. Nuclear Regulatory Commission Washington, D.C. 20555-001
Subject:
NP8344 Valve U-Rings Ref A:
ASCO letter to Dresden Station dated 2/3/2011 Gentlemen:
This report relates to two NP8344E series four-way solenoid valves found to be leaking through the exhaust port in both the energized and de-energized states.
Background - On January 21, 2011, ASCO Valve, Inc. (ASCO) was notified by AREVA that a four-way solenoid valve NP8344A75E AC, (serial number F623557002-002) from the Dresden Station was leaking from the exhaust port in both the energized and de-energized states. AREVA reported that Exelon Labs had performed a Fourier Transform Infrared Spectroscopy (FTIR) analysis which' indicated the piston U-ring exhibited properties consistent with a Nitrile compound instead of Teflon@ coated Ethylene Propylene as required by the ASCO design drawing, The valve itself was not returned to ASCO, At ASCO's request, Exelon returned the U-ring on January 27, 2011. ASCO provided a letter to Dresden Station on February 3, 2011 (Reference A) maintaining the correct U-ring material was installed at the time of shipment and that no additional action was required.
The second occurrence involved another four-way solenoid valve, NPK8344AO72E DC, (serial number F337837-2),
from PSEG Nuclear's Salem station, returned to ASCO on Service RMA 47113 on February 25, 2011. The valve was brought to ASCO where testing confirmed the valve was leaking through the exhaust ports in both the energized and de-energized states. The inspection of parts showed that the U-ring material had become brittle. If the U-rng becomes brittle, It may no longer perform its sealing function.
ASCO Investigation Results - The above referenced valves were manufactured in 1992 (Dresden) and 1995 (Salem) respectively. It was determined that both valves used the same piston U-ring, part number 029043-024-S. This U-ring is common to both the 318" and %" NPT valve constructions. A review of ASCO's incoming and dedication inspection records indicated that these U-rings were Teflon coated Ethylene Propylene. The piston U-rings from the Salem and Dresden valves, along with a piston U-ring from ASCO's current stock, were sent to a third party laboratory for a FTIR analysis. The U-rings from both the Salem and Dresden valves were determined by the laboratory to be Nitrite. The U-ring from current stock was determined to be Teflon coated Ethylene Propylene, as called for by the design drawings.
Impact on Performance - The use of a Nitrile piston U-ring could potentially reduce the valve life and result in leakage through the exhaust port.
Initial Action - rTIR analysis confirmed that the piston U-ring in ASCO's current stock was Teflon coated Ethylene Propylene. ASCO records disclosed no prior cases of piston U-rings fabricated with incorrect material. Discussions with the distributor of the U-rings disclosed no other cases of Improper material.
May,12, 2011 3:11PM ASCO VALVE AIKEN PLANT No. 50 17 P - 3 Corrective Action - The customers that were shipped potentially affected NP8344E valves are being notified of the potential deviation. All variations of NP8344A72E, NP8344A73E, NP8344A74E, NP8344A75E, NP8344BSOE, NP8344B52E, NP8344B62E, and NP8344B64E manufactured from 1992 through 1995 are recommended to be monitored for leakage. Due to the qualifled service life and date of manufacture, it is believed a majority of these valves are no longer in service. Subsequent to 1995, ASCO has implemented a more rigorous lot and batch control to verify the material compound at incoming and dedication inspection. This action further enhanced traceability of resilient materials used in specific production lots.
Please contact Bob Arnone at 803-641-9395 if you have any questions.
Very Truly Yours, Lars S-ac Vice-President Quality ASCO Valve, Inc.
ASU8 nUmaTRI.
May. 12.
2011 3:11PM ASCO VALVE AIKEN PLANT No, 5017 P. 4 EMERSON.
Ind.'ustril Au a Vol-no A8CO Val6ve, Ilog.
1501. Codluibla Highway Aiken, so 28801 USA T (803) 041-9200 F (803) 04t-929Q www.asconumal*ccorn Dresd'en Nuclear Power Plant Exehxdo'Ctbpot-itibri 6JODbN~ilh t~resde~fi;nad
- M@?iJýi4fL-q6s4Q
-Subject. Ahalysis f ASCO NP S344A75ULrrn Dorsd*e Nudlear Powe? Ilant.
'eft. Ar Rdi~bWrt=fro* E~eloh P6Wfer:*L~bs ated' 104/l,.ptbJpc~hun~ber PBIE-23Q45.
,Atfachrtenf*..
,.2-hlotot'o:f uti-rng with* ma~rIngss(rgd vfl.d plnk',dotslj b**n nuara*y2'..
hrIs Marsh o fAreva. provided a copy o'f ref A to.ASCO for review and camniten t., the:,,epart detaiI5Ben anaiysl-sO fan N.M3*44 valVe.lhat war'removed'horn service, Among the.firdlhgs'of'Th*=-iprdOr*. wasthe, b4servAlah'that 0o-lntheu-rihgs.(larger) wa's ident6fieda' b'eiig di4n of a blend of Biin'a-N arid Fla0e, la omers; Te vlve' Is supposed
.tbl :asse*mbled with Ethylene PaOp1ee S8verilrcorference;cails~wer.e Intlited between AS*C, Arevai Fxefon an*dbresdenhih order to revl.w (lte investigdal~o and
.dIscu ssexpla natlon *for:m are[aliI,
'S'ummaryof Investgalgon, ASCO rtvledwe the Incom.ing..and Oi&sstfbhy de dlaloin~iwCtion retordsforthe valveand.u-rl:n. The$,records
.,Oqqfrnuent t.h".
qinpeatjon ofil ela.1ers, and qltil dI.fiepionsb..n.ng chced,. Yhp !nkspectlon roqrds: conirn 'that t'he
ýmtMetlal tLsed.ln WadsýnblIng thevalves were confortMngh.Indicating that the material valldated In.1993 wat Ethylene Propylene wlih a Teilon coating. Copies of the inspection records were forwarded to Exeloir for, revfewandxreincuded as att chmen ts.
nuimanoict