ML11104A047

From kanterella
Jump to navigation Jump to search
Request to Terminate Sampling of the Diffuser Pond Inlet for Oil and Grease Due to Intertie Transformer Failure on September 22, 2010
ML11104A047
Person / Time
Site: Sequoyah  Tennessee Valley Authority icon.png
Issue date: 04/11/2011
From: Skaggs M
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation, State of TN, Div of Water Pollution Control
References
Download: ML11104A047 (5)


Text

Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 April 11,2011 Chattanooga Environmental Field Office Division of Water Pollution Control State Office Building, Suite 550 540 McCallie Avenue Chattanooga, Tennessee 37402 TENNESSEE VALLEY AUTHORITY - SEQUOYAH NUCLEAR PLANT - REQUEST TO TERMINATE SAMPLING OF THE DIFFUSER POND INLET FOR OIL AND GREASE DUE TO INTERTIE TRANSFORMER FAILURE ON SEPTEMBER 22, 2010 On September 22, 2010 at approximately 2130 EDT, a fire occurred while placing a non-polychlorinated biphenyl (PCB) transformer in service following routine maintenance. As a result of the fire, approximately 13,000 gallons of insulating oil spilled from the transformer into the surrounding gravel switchyard. The switchyard has a clay layer which routes spills to the yard drainage system via a french drain. The yard drainage system drains to the Yard Drainage Pond which is the secondary containment for the switchyard. A permanent oil skimmer is located on the discharge of the Yard Drainage Pond prior to entry into the Diffuser Pond. TVA mobilized its Emergency Response Team and began recovering the spilled mineral oil utilizing multiple guzzler trucks and an oil / water separator. Also, four skirted booms were placed between the Yard Drainage Pond inlet and the permanent oil skimmer at the Yard Drainage Pond discharge. At no time has oil been released to the Diffuser Pond or to the Tennessee River from this spill.

On September 23, 2010, at the request of TDEC, Sequoyah began sampling for oil and grease twice per day at the north end of the Diffuser Pond where the Yard Drainage Pond enters. Twice a day sampling continued through October 12, 2010. On October 13, 2010, with concurrence from TDEC, sampling was reduced to once per day. Daily sampling of the Diffuser Pond inlet continued through December 7, 2010. On December 7, 2010, with concurrence from TDEC, sampling frequency was reduced to once per week. Currently, sampling for oil and grease continues at the Diffuser Pond Inlet on a weekly basis. As of today, all oil and grease analytical sample results have been below minimum detectable limits and it has also been visually verified on a daily basis that no oil sheen has been present on the Diffuser Pond. No oil has been released into Waters of U.S. from the intertie transformer failure on September 22, 2010.

Enclosed as Table 1 are the analytical results for all oil and grease samples collected since September 23, 2010.

Chattanooga Environmental Field Office Division of Water Pollution Control Page 2 April 11,2011 As a result of the cleanup from the spill, 37 dump truck loads of non-hazardous oily soil / gravel have been excavated and shipped to Rhea County Landfill as special waste and 105,000 gallons of oily waste water have been removed from the Yard Drainage Pond and shipped to Clean Harbors LLC. Multiple booms remain in place in the Yard Drainage Pond prior to the oil skimmer to further minimize the likelihood of oil entering the Diffuser Pond. A portable oil / water separator is currently staged at the inlet of the Yard Drainage Pond where the switchyard drains to collect any oil drainage. During heavy rain events a small amount of oil enters the Yard Drainage Pond, but does not pass the booms placed near the Yard Drainage Pond inlet prior to being collected by the oil / water separator.

Sequoyah requests that oil and grease monitoring at the north end of the Diffuser Pond be discontinued based upon the following: all oil and grease analytical sample results have been below minimum detectable limits, no oil has been observed on the Diffuser Pond during the six months of daily observation, and no oil has been released to the Diffuser Pond. Sequoyah is aware that any sheen observed on the Diffuser Pond would result in an immediate notification to the National Response Center in addition to notification to TDEC. Sequoyah plans to discontinue sampling of the Diffuser Pond inlet on May 13, 2011 unless otherwise directed by TDEC.

If you have any questions or need additional information, please contact Brad Love at (423) 843-6714 or Stephanie Howard at (423) 843-6700 of Sequoyah's Environmental staff.

I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.

Sincerely, MichaelSqya Nucearlan Site Vice President Sequoyah Nuclear Plant Enclosure cc (Enclosure):

U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

Table 1. Oil and Grease Results from Diffuser Pond Inlet Samples Sample Location Sample Date Sample Time Analysis Date Analysis Time Results (mg/L)

Diffuser Pond Inlet 9/23/10 1645 10/01/10 1305

< 5.3 Diffuser Pond Inlet 9/24/10 0410 10/01/10 1306

< 5.6 Diffuser Pond Inlet 9/24/10 1900 10/01/10 0905

< 5.6 Diffuser Pond Inlet 9/25/10 0800 10/01/10 0923

< 5.6 Diffuser Pond Inlet 9/25/10 2010 10/01/10 0906

< 5.6 Diffuser Pond Inlet 9/26/10 0800 10/01/10 1304

< 6.3 Diffuser Pond Inlet 9/26/10 2000 10/01/10 1304

< 5.3 Diffuser Pond Inlet 9/27/10 0800 10/01/10 1305

< 5.6 Diffuser Pond Inlet 9/27/10 2000 10/06/10 1537

<5.6 Diffuser Pond Inlet 9/28/10 0800 10/06/10 1538

< 5.6 Diffuser Pond Inlet 9/28/10 2000 10/06/10 1538

< 5.6 Diffuser Pond Inlet 9/29/10 0800 10/06/10 1538

< 5.6 Diffuser Pond Inlet 9/29/10 2000 10/06/10 1539

< 5.6 Diffuser Pond Inlet 9/30/10 0800 10/06/10 1539

< 5.9 Diffuser Pond Inlet 9/30/10 2000 10/06/10 1540

< 5.3 Diffuser Pond Inlet 10/01/10 0800 10/06/10 1542

< 5.6 Diffuser Pond Inlet 10/01/10 2000 10/08/10 1515

< 5.3 Diffuser Pond Inlet 10/02/10 0800 10/08/10 1516

< 5.3 Diffuser Pond Inlet 10/02/10 2000 10/08/10 1517

< 5.6 Diffuser Pond Inlet 10/03/10 0800 10/08/10 1517

< 5.3 Diffuser Pond Inlet 10/03/10 2000 10/08/10 1518

< 6.3 Diffuser Pond Inlet 10/04/10 0800 10/08/10 1519

< 5.6 Diffuser Pond Inlet 10/04/10 2000 10/08/10 1519

< 5.3 Diffuser Pond Inlet 10/05/10 1230 10/08/10 1520

< 5.3 Diffuser Pond Inlet 10/05/10 2000 10/16/10 1928

< 5.6 Diffuser Pond Inlet 10/06/10 0800 10/16/10 1928

< 5.6 Diffuser Pond Inlet 10/06/10 2000 10/16/10 1928

< 5.6 Diffuser Pond Inlet 10/07/10 0800 10/16/10 1929

< 5.3 Diffuser Pond Inlet 10/07/10 2100 10/16/10 1930

< 5.3 Diffuser Pond Inlet 10/08/10 0800 10/16/10 1931

< 5.9 Diffuser Pond Inlet 10/08/10 2000 10/16/10 1931

< 5.6 Diffuser Pond Inlet 10/09/10 0800 10/16/10 1932

< 5.6 Diffuser Pond Inlet 10/09/10 2000 10/16/10 1933

< 5.9 Diffuser Pond Inlet 10/10/10 0800 10/16/10 1933

< 5.3 Diffuser Pond Inlet 10/10/10 2100 10/16/10 1934

< 5.6 Diffuser Pond Inlet 10/11/10 0800 10/16/10 1935

< 5.6 Diffuser Pond Inlet 10/11/10 2000 10/16/10 1935

< 5.6 Diffuser Pond Inlet 10/12/10 0800 10/16/10 1935

< 5.6 Diffuser Pond Inlet 10/12/10 2000 10/16/10 1936

< 5.6 Diffuser Pond Inlet 10/13/10 0800 10/16/10 1936

< 5.3

Table 1. Oil and Grease Results from Diffuser Pond Inlet Samples Sample Location Sample Date Sample Time Analysis Date Analysis Time Results (mgIL)

Diffuser Pond Inlet 10/14/10 0800 10/16/10 1927

< 5.6 Diffuser Pond Inlet 10/15/10 0800 10/29/10 1026

< 6.3 Diffuser Pond Inlet 10/16/10 0800 10/29/10 1027

< 5.9 Diffuser Pond Inlet 10/17/10 0800 10/29/10 1027

< 5.6 Diffuser Pond Inlet 10/18/10 0800 10/29/10 1028

< 5.6 Diffuser Pond Inlet 10/19/10 0900 10/29/10 1028

< 5.3 DiffuserPondInlet 10/20/10 0830 10/29/10 1028

< 5.3 Diffuser Pond Inlet 10/21/10 0800 10/29/10

___1029

< 5.6 Diffuser Pond Inlet 10/22/10 0800 10/29/10 1029

< 6.3 Diffuser Pond Inlet 10/23/10 0800 10/29/10 1029

< 5.6 Diffuser Pond Inlet 10/24/10 0800 10/29/10 1029

< 5.9 Diffuser Pond Inlet 10/25/10 0800 10/29/10 1030

< 5.3 Diffuser Pond Inlet 10/26/10 0800 10/30/10 1722

< 5.3 Diffuser Pond Inlet 10/27/10 0900 11/09/10 1152

< 5.6 Diffuser Pond Inlet 10/28/10 0800 11/09/10 1224

< 5.6 Diffuser Pond Inlet 10/29/10 0800 11/09/10 1231

< 6.7 Diffuser Pond Inlet 10/30/10 0800 11/09/10 1233

< 5.3 Diffuser Pond Inlet 10/31/10 0800 11/09/10 1233

< 5.3 Diffuser Pond Inlet 11/01/10 0850 11/09/10 1234

< 5.6 Diffuser Pond Inlet 11/02/10 0800 11/09/10 1235

< 5.6 Diffuser Pond Inlet 11/03/10 0930 11/09/10 1359

< 5.6 Diffuser Pond Inlet 11/04/10 0900 11/09/10 1400

< 5.3 Diffuser Pond Inlet 11/05/10 0800 11/09/10 1401

< 5.6 Diffuser Pond Inlet 11/06/10 0800 11/09/10 1242

< 5.6 Diffuser Pond Inlet 11/07/10 0800 11/09/10 1243

< 5.6 Diffuser Pond Inlet 11/08/10 0800 11/09/10 1243

< 5.6 Diffuser Pond Inlet 11/09/10 0800 11/11/10 1407

< 5.6 Diffuser Pond Inlet 11/10/10 0800 11/15/10 1627

< 5.9 Diffuser Pond Inlet 11/11/10 0800 11/16/10 1459

< 5.3 Diffuser Pond Inlet 11/12/10 0800 11/16/10 1459

< 6.3 Diffuser Pond Inlet 11/13/10 0800 11/20/10 1557

< 5.6 Diffuser Pond Inlet 11/14/10 0800 11/20/10 1554

< 5.9 Diffuser Pond Inlet 11/15/10 0800 11/20/10 1557

< 5.6 Diffuser Pond Inlet 11/16/10 0800 11/20/10 155

<6.3 Diffuser Pond Inlet 11/17/10 0800 11/20/10 1555

< 5.6 Diffuser Pond Inlet 11/18/10 0800 11/20/10 1555

< 5.6 Diffuser Pond Inlet 11/19/10 0800 11/30/10 1554

< 5.3 Diffuser Pond Inlet 11/20/10 0800 11/30/10 1554

< 5.3 Diffuser Pond Inlet 11/21/10 0800 11/30/10 1555

< 5.3 Diffuser Pond Inlet 11/22/10 0800 11/30/10 1626

< 5.6

Table 1. Oil and Grease Results from Diffuser Pond Inlet Samples Sample Location Sample Date Sample Time Analysis Date Analysis Time Results (mg/L)

Diffuser Pond Inlet 11/23/10 0800 11/30/10 1556

< 5.9 Diffuser Pond Inlet 11/24/10 0800 11/30/10 1627

< 5.6 Diffuser Pond Inlet 11/25/10 0810 12/07/10 2129

< 5.3 Diffuser Pond Inlet 11/26/10 0800 12/04/10 1748

< 5.6 Diffuser Pond Inlet 11/27/10 0800 12/04/10 1748

< 6.3 Diffuser Pond Inlet 11/28/10 0900 12/04/10 1748

< 5.3 Diffuser Pond Inlet 11/29/10 0700 12/04/10 1749

< 5.9 Diffuser Pond Inlet 11/30/10 0800 12/07/10 2129

< 5.6 Diffuser Pond Inlet 12/01/10 0800 12/07/10 2129

< 5.6 Diffuser Pond Inlet 12/02/10 0800 12/07/10 2131

< 5.9 Diffuser Pond Inlet 12/03/10 0800 12/07/10 2131

< 5.6 Diffuser Pond Inlet 12/04/10 0800 12/07/10 2132

< 5.6 Diffuser Pond Inlet 12/05/10 0800 12/07/10 2132

< 5.6 Diffuser Pond Inlet 12/06/10 0800 12/07/10 2133

< 5.6 Diffuser Pond Inlet 12/07/10 0800 12/08/10 1813

< 5.3 Diffuser Pond Inlet 12/11/10 1000 12/20/10 1505

< 5.6 Diffuser Pond Inlet 12/26/10 1200 1/17/11 1255

< 5.6 Diffuser Pond Inlet 1/01/11 1130 1/17/11 1546

< 5.6 Diffuser Pond Inlet 1/08/11 1120 1/17/11 1547

< 5.6 Diffuser Pond Inlet 1/16/11 1830 1/25/11 1945

< 5.9 Diffuser Pond Inlet 1/22/11 1215 1/25/11 1946

< 5.3 Diffuser Pond Inlet 1/29/11 1230 2/04/11 1803

< 5.3 Diffuser Pond Inlet 2/06/11 1800 3/04/11 1508

< 5.9 Diffuser Pond Inlet 2/12/11 1200 2/16/11 2005

< 5.6 Diffuser Pond Inlet 2/18/11 1000 3/02/11 1423

< 5.3 Diffuser Pond Inlet 2/26/11 1115 3/02/11 1423

< 5.6 Diffuser Pond Inlet 3/05/11 1115 3/20/11 1125

< 5.6 Diffuser Pond Inlet 3/13/11 1800 3/20/11 1125

< 5.6 Diffuser Pond Inlet 3/19/11 1030 3/23/11 1459

< 5.6