Letter to W. Berg Amendment No. 71 to Possession Only License No. DPR-45 - Dairyland Power Cooperative, La Crosse Boiling Water Reactor (TAC No. J00359) (LAC-14071, LAC-14117)
ML110950072
Person / Time
Site: La Crosse File:Dairyland Power Cooperative icon.png
(DPR-045)
Issue date: 04/06/2011
From: John Hickman
NRC/FSME/DWMEP/DURLD/RDB
To: Berg W
Dairyland Power Cooperative
Hickman J, FSME/DWMEP,301-415-3017
References
LAC-14071, LAC-14117, TAC J00359
Download: ML110950072 (5)


Text

April 6, 2011 Mr. W. L. Berg President and Chief Executive Officer Dairyland Power Cooperative 3200 East Avenue South P.O. Box 817 La Crosse, WI 54602-0817

SUBJECT:

AMENDMENT NO. 71 TO POSSESSION ONLY LICENSE NO. DPR DAIRYLAND POWER COOPERATIVE, LA CROSSE BOILING WATER REACTOR (TAC NO. J00359) (LAC-14071, LAC-14117)

Dear Mr. Berg:

The U.S. Nuclear Regulatory Commission issued Amendment No. 71 to Possession Only License No. DPR-45 for the La Crosse Boiling Water Reactor on January 25, 2011.

Subsequent to the issuance of the amendment a typographical error was identified on Technical Specification pages 2-1 and 4/5-2. Corrected pages are enclosed.

In accordance with 10 CFR 2.390 of the NRCs Rules of Practice for Domestic Licensing Proceedings and Issuance of Orders, a copy of this letter will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records component of NRCs ADAMS. ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html.

Sincerely,

/RA/

John B. Hickman, Project Manager Reactor Decommissioning Branch Decommissioning and Uranium Recovery Licensing Directorate Division of Waste Management and Environmental Protection Office of Federal and State Materials and Environmental Management Programs Docket No.: 50-409 License No.: DPR-45

Enclosure:

TS Page 2-1 and 4/5-2 cc: La Crosse Boiling Water Reactor Service List

Mr. W. L. Berg President and Chief Executive Officer Dairyland Power Cooperative 3200 East Avenue South P.O. Box 817 La Crosse, WI 54602-0817

SUBJECT:

AMENDMENT NO. 71 TO POSSESSION ONLY LICENSE NO. DPR DAIRYLAND POWER COOPERATIVE, LA CROSSE BOILING WATER REACTOR (TAC NO. J00359) (LAC-14071, LAC-14117)

Dear Mr. Berg:

The U.S. Nuclear Regulatory Commission issued Amendment No. 71 to Possession Only License No. DPR-45 for the La Crosse Boiling Water Reactor on January 25, 2011.

Subsequent to the issuance of the amendment a typographical error was identified on Technical Specification pages 2-1 and 4/5-2. Corrected pages are enclosed.

In accordance with 10 CFR 2.390 of the NRCs Rules of Practice for Domestic Licensing Proceedings and Issuance of Orders, a copy of this letter will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records component of NRCs ADAMS. ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html.

Sincerely, John B. Hickman, Project Manager Reactor Decommissioning Branch Decommissioning and Uranium Recovery Licensing Directorate Division of Waste Management and Environmental Protection Office of Federal and State Materials and Environmental Management Programs Docket No.: 50-409 License No.: DPR-45

Enclosure:

TS Page 2-1 and 4/5-2 cc: La Crosse Boiling Water Reactor Service List DISTRIBUTION:

PLee/RIII JTapp/RIII CLipa/RIII ML11095072 OFC DWMEP:PM DWMEP:LA DWMEP:BC DWMEP:PM NAME JHickman CHolston BWatson JHickman DATE 4 /6/11 4 /6/11 4 /6/11 4 /6/11 OFFICIAL RECORD COPY

2.

DESIGN FEATURES

============================================================

2.1 SITE EXCLUSION AREA 2.1.1 The exclusion area shall be as described in the Off-Site Dose Calculation Manual.

2.2 FUEL STORAGE WHILE IN THE FUEL ELEMENT STORAGE WELL CRITICALITY 2.2.1 The spent fuel storage racks are designed with a nominal 7.0 inch center-to-center distance between fuel assemblies in each individual rack assembly, with a boron impregnated poison plate between adjacent storage locations to ensure Keff of < 0.95 when flooded with unborated water.

FUEL RESTRICTIONS 2.2.2 Fuel stored in the storage well is restricted to fuel with stainless steel cladding which has a U-235 loading of < 22.6 grams per axial centimeter of fuel assembly.

DRAINAGE 2.2.3 The Fuel Element Storage Well is designed and shall be maintained to prevent an inadvertent draining of the well below elevation of 679 feet MSL while spent fuel assemblies are in the Fuel Element Storage Well.

CAPACITY 2.2.4 The Fuel Element Storage Well was designed for a storage capacity of no more than 440 fuel assemblies. The maximum number of fuel assemblies stored in the Fuel Element Storage Well is limited to 333 spent fuel assemblies.

TS 2-1 Amendment No. 71

FUEL STORAGE AND HANDLING 4.1.2 FUEL ELEMENT STORAGE WELL AND CASK POOL LIMITING CONDITION FOR OPERATION

===========================================================

Note This LCO does not apply to the cask pool if the spent fuel storage canister lid is in place in the canister or if there are no spent fuel assemblies in the cask pool.

The Fuel Element Storage Well (FESW) and cask pool shall meet the following requirements.

a.

The Fuel Element Storage Well and cask pool water level shall be at least 11 feet, 61/2 inches above any spent fuel assembly stored in the spent fuel storage racks or in a spent fuel storage canister in the cask pool, and

b.

Water in the storage well and cask pool shall be maintained at a temperature

< 150°F.

APPLICABILITY:

While spent fuel assemblies are in the FESW or the cask pool.

ACTIONS

a.

With water level less than required by the LCO, take immediate action to restore water level and suspend all operations involving FUEL HANDLING.

b.

With water temperature in the storage well or cask pool above 150°F, take actions to reduce water temperature to < 150°F within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and suspend all operations involving FUEL HANDLING.

SURVEILLANCE REQUIREMENTS

===========================================================

Note SR 5.1.2.1 and 5.1.2.2 do not apply to the cask pool if the spent fuel storage canister lid is in place in the canister or if there are no spent fuel assemblies in the cask pool.

5.1.2.1 The Fuel Element Storage Well and cask pool water level and temperature shall be verified at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

5.1.2.2 The Fuel Element Storage Well and cask pool water level indication channel shall be calibrated (CHANNEL CALIBRATION) at least once per 18 months.

TS 4/5-2 Amendment. No. 71

La Crosse Boiling Water Reactor Service List Mr. Thomas Zaremba Wheeler, Van Sickle and Anderson Suite 801 25 West Main Street Madison, WI 53703-3398 Mr. George Kruck Chairman, Town of Genoa S5277 Mound Ridge Road Genoa, WI 54632 Mr. Jeffery Kitsembel Electric Division Wisconsin Public Service Commission P.O. Box 7854 Madison, WI 53707-7854 Mr. Paul Schmidt, Manager Radiation Protection Section Bureau of Environmental and Occupational Health Division of Public Health Wisconsin Department of Health Services P.O. Box 2659 Madison, WI 53701-2659 Mr. Michael A. Brasel, Plant Manager La Crosse Boiling Water Reactor Dairyland Power Cooperative S4601 State Highway 35 Genoa, WI 54632-8846 Mr. Jeff McRill, Technical Support Engineer La Crosse Boiling Water Reactor Dairyland Power Cooperative S4601 State Highway 35 Genoa, WI 54632-8846 Regional Administrator Region III U.S. Nuclear Regulatory Commission 2443 Warrenville Road Lisle, IL 60532-4352