Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 February 25, 2011 Chattanooga Environmental Field Office Division of Water Pollution Control State Office Building, Suite 550 540 McCallie Avenue Chattanooga, Tennessee 37402 TENNESSEE VALLEY AUTHORITY - SEQUOYAH NUCLEAR PLANT - TENNESSEE STORM WATER MULTI-SECTOR GENERAL PERMIT FOR INDUSTRIAL ACTIVITIES PERMIT NO.
TNRO50015 SECTOR 0 EXCEEDANCE OF THE BENCHMARK MONITORING REQUIREMENT.
Please find enclosed the thirty day notification and the lab analysis for the exceedance of the benchmark monitoring requirement for total recoverable iron for Storm Water Outfall Numbers 1, 2, and 9.
Description of Event Tennessee Storm Water Multi-Sector General Permit for Industrial Activities Sector 0 requires annual monitoring of total recoverable iron. Sequoyah Nuclear Plant sampled for total recoverable iron on January 15, 2011 and January 16, 2011. The storm water analytical monitoring results were received on February 4, 2011. The analytical monitoring results for Storm Water Outfalls Nos. 1, 2, and 9 exceeded the benchmark monitoring requirement for total recoverable iron as stated in Table 0-2, Benchmark Monitoring Requirements for Steam Electric Power Generating Facilities. The storm water event was triggered by accumulated snowfall and
.associated snow melt runoff. The analytical results can be seen tabulated below in Table 1.
Table 1. Storm Water Annual Iron Exceedance Values Benchmark Storm Water Sample Date Sample Analysis Analytical Monitoring Outfall Number Received Date Results (mg/L)
Requirement (mg/L) 1 1/15/2011 2/04/2011 16.0 5
2 1/16/2011 2/04/2011 9.0 5
9 1/15/2011 2/04/2011 5.7 5
The Tennessee Storm Water Multi-Sector General Permit for Industrial Activities requires informing the division's local Environmental Field Office (EFO) within 30 days from the time storm water monitoring results were received describing the likely cause of the exceedance.
Likely Cause of the Exceedance The likely cause of the exceedance of the benchmark monitoring requirement for total recoverable iron is elevated background iron concentration in the soil around the storm water outfalls (based on historical sampling) and the need for more effective best management practices (BMPs). Sequoyah is examining the use of more effective filtration methods at these outfalls.
If you have any questions or need additional information please contact Brad Love at (423) 843-6714 or Stephanie Howard at (423) 843-6700 of Sequoyah's Environmental staff.
Sincerely, Michael D. Skaggs Site Vice President Sequoyah Nuclear Plant Enclosures cc (Enclosures):
U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555
- ESC LA,B S-C.I*E.NCES Brad Love TVA-Sequoyah Nuclear Plant P.O.Box 2000 Soddy-Daisy, TN 37384 12065 Lebanon Rd.
Mt. Juliet, TN 37122 (615) 758-5858 1-800-767-5859 Fax (615) 758-5859 Tax I.D. 62-0814289 Est. 1970 REPORT OF ANALYSIS February 04,2011 Date Received Description Sample ID Collected By Collection Date Parameter Iron 02/03/11 09:15 Annual Storm Water NPDES Samples SW 1 Chris Randolph 01/15/11 15:15 Result Det. Limit Units
- 16.
0.10 mg/l ESC Sample # :
L500219-01 Site ID Project #
Method 200.7 Prep PID Analyzed AID 02/03/11 1504 528 02/04/11 1346 ALT BDL -
Below Detection Limit Det. Limit -
Practical Quantitation Limit(PQL)
Laboratory Certification Numbers:
AIHA -
- 09227, AL -
- 40660, CA -
1-2327, CT-PH-0197, FL -
- E87487, GA -
- 923, IN -
C-TN-01 KY
- 90010, NC -
ENV375,DW21704, ND -
R-140, SC -
- 84004, TN -
- 2006, VA -
- 00109, WV -
233 AZ -0612, MN -
047-999-395, NY -
- 11742, NJ -
- TNO02, WI -
998093910 Notes:
The reported analytical results relate only to the sample submitted This report shall not be reproduced, except in full, without the written approval from ESC.
Reported: 02/04/11 15:41 Printed: 02/04/11 15:46 Page 2 of 9
7-
- ESC L'A'8 5'C-IM'-N-C-E'S Brad Love TVA-Sequoyah Nuclear Plant
?.O.Box 2000 Soddy-Daisy, TN 37384 12065 Lebanon Rd.
Mt.
- Juliet, TN 37122 (615) 758-585B 1-800-767-5859 Fax (615) 758-5859 Tax I.D. 62-0814289 Est. 1970 REPORT OF ANALYSIS February 23,2011 Date Received Description Sample ID Collected By Collection Date Parameter Iron 02/03/11 09:15 Annual Storm Water NPDES Samples SW 2 Chris Randolph 01/16/11 12:22 Result Det. Limit Units 9.0 0.10 mg/l ESC Sample # :
L500219-02 Site ID Project #
Method Prep PID Analyzed AID 200.7 02/03/11 1504 528 02/04/11 1348 ALT BDL -
Below Detection Limit Det. Limit -
Practical Quantitation Limit(PQL)
Laboratory Certification Numbers:
AIHA -
- 09227, AL -
- 40660, CA -
1-2327, CT-PH-0197, FL -
- E87487, GA -
- 923, IN -
C-TN-01 KY -
- 90010, NC -
ENV375,DW21704, ND -
R-140, SC -
- 84004, TN -
- 2006, VA -
- 00109, WV -
233 AZ -0612, MN -
047-999-395, NY -
- 11742, NJ -
- TNO02, WI -
998093910 Notes:
The reported analytical results relate only to the sample submitted This report shall not be reproduced, except in full, without the written approval from ESC.
Reported: 02/04/11 15:41 Revised: 02/23/11 08:29 Page 3 of 9
- OESC LA-8 S.C.I-E-NCýES Brad Love TVA-Sequoyah Nuclear Plant P.O.Box 2000 Soddy-Daisy, TN 37384 12065 Lebanon Rd.
Mt. Juliet, TN 37122 (615) 758-5858 1-800-767-5859 Fax (615) 758-5859 Tax I.D. 62-0814289 Est. 1970 REPORT OF ANALYSIS February 04,2011 Date Received Description Sample ID Collected By Collection Date Parameter Iron 02/03/11 09:15 Annual Storm Water NPDES Samples SSw 9
Chris Randolph 01/15/11 12:02 Result Det. Limit Units 5.7 0.10 mg/l ESC Sample # :
L500219-07 Site ID Project #
Method 200.7 Prep PID Analyzed AID 02/03/11 1504 528 02/04/11 1411 ALT BDL - Below Detection Limit Det.
Limit -
Practical Quantitation Limit(PQL)
Laboratory Certification Numbers:
AIHA -
- 09227, AL -
- 40660, CA -
1-2327, CT-PH-0197, FL -
- E87487, GA -
- 923, IN -
C-TN-01 KY -
- 90010, NC -
ENV375,DW21704, ND -
R-140, SC -
- 84004, TN -
- 2006, VA -
- 00109, WV -
233 AZ -0612, MN -
047-999-395, NY -
- 11742, NJ -
- TNO02, WI -
998093910 Notes:
The reported analytical results relate only to the sample submitted This report shall not be reproduced, except in full, without the written approval from ESC.
Reported: 02/04/11 15:41 Printed: 02/04/11 15:46 Page 8 of 9