PSEG Internal Use Only MAINTENANCE SC.MD-ST.28D-0004(Q) - REV. 14 28 VOLT STATION BATTERIES 18 MONTH SERVICE TEST AND ASSOCIATED SURVEILLANCE TESTING USING BCT -2000 USE CATEGORY: II Biennial Review Performed: Yes No NA-'-
Packages and Affected Document Numbers incorporated into this revision: None The following OTSCs were incorporated into this revision: None REVISION
SUMMARY
Page _1 of_l The following changes were made to support Technical Specification Amendments 249 and 229:
(Order 80038362, Act. 0040)
Technical Specification reference was changed from 4.8.2.5.2.d to 4.8.2.5.2,f in section 1.0.
Specific Gravity value in steps 5.7.3,5.7.5,5.16.10,5.16.12, Attachment 4A, 4B, and 9, step 5.7.4.B was changed from 1.200 to 1.190.
Technical Specification minimum voltage value in Attachment 19, Step 5.6.1 was changed from ;;a: 28 VDC to ;::: 27 VDC.
Deleted comparing quarterly Specific Gravity readings with previously taken readings in Steps 5.7.4,5.7.5, Attachment 4A, 5.16.11 and 5.16.12. This is no longer a Tech. Spec.
requirement.
Deleted step 5.5.2.B.4 which required taking B-B readings. 28 VDC batteries only have A-A readings.
IMPLEMENTATION REQIDREMENTS Effective Date 3b.r/0t3 I
APPROVED:
Manager n Plant Mainte
UJ w
C) z <<
- r::
u o z <<
UJ
- l f---<<
f---
UJ z o UJ W
0:::
C)
Z LL 0:::
W >
0::: o LL W
---1 CO UJ Z o 0...
UJ W
0:::
0:::
W UJ
- l Section S C.MD-ST.28D-0004(Q) 28 VOLT STATION BATTERIES 18 MONTH SERVICE TEST AND ASSOCIATED SURVEILLANCE TESTING USING BeT-2000 TABLE OF ~ONTENTS 1.0 PURPOSE...... 0
- 4 2.0 PREREQUISITES......................................... 4 3.0 PRECAUTIONS AND LIMITATIONS............................ 6 4.0 EQUIPMENT/MATERIAL REQUIRED........................... 9 5.0 PROCEDURE.......................................... 10 5.1 Prerequisites, Precautions and Limitations Review................ 10 5.2 Battery Room Inspection............................... 10 5.3 Individual Battery Rack/Enclosure Inspection................... 11 5.4 Individual Battery Cell Inspection.......................... 12 5.5 Battery Cell Connection Inspection......................... 13 5.6 Individual Cell Quarterly Data Collection..................... 17 5.7 Data Reduction..................................... 20 5.8 BCT-2000 Series System Interconnections..................... 23 5.9 Programming of BCT-2000 Laptop Computer.................. 24 5.10 Connecting BCT-2000 to Battery Cell Terminal Posts............. 26 5.11 Connecting Continuous Load Unit to Battery................... 27 5.12 Battery Service Test Using BCT-2000....................... 29 5.13 Battery Cell Connection Retorque/Cleaning.................... 35 Salem Common Page 1 of 96 Rev. 14
Vi w
()
z <<
- r::
u o z <<
Vi
- J f--<<
f--
Vi z o Vi W
0:::
()
Z Lc..
0:::
W >
0:::
o Lc..
W
-l OJ if)
Z o 0...
if)
W 0:::
0:::
W if)
- J sC.MD-ST. 28D-0004(Q)
TABLE OF CONTENTS (CQgt'd).
Section 5.14 Post Battery Service Maintenance Restoration.................. 39 5.15 Battery Equalize Charge............................... 41 5.16 Post Service Test Operability Detennination................... 45 5.17 Post Service Test Polishing Charge......................... 51 5.18 Completion Summary................................. 55 6.0 RECORDS................................................ 56
7.0 REFERENCES
............................................. 56 Salem Common Page 2 of 96 Rev. 14
Ul w
C)
Z
<t I
U o
Z
<t Ul
- J f---
<t f--
Ul z o Ul W
cr::
C) z LL cr::
W >
cr::
o L.L.
W
--.J m
Ul z o 0...
Ul W
0::::
0::::
I-L!
Ul
- J A TIACHMENTS A B 0 1 2 3 4 5 6 7 8 9 Salem Common Se.MD~ST.28D-0004(Q)
Discormect Log..................................... 58 Preparation of Contact Surfaces For Anti-Corrosion Coating......... 60 Cell Level Correction Factors............................ 61 Pre Service Test Battery Data table......................... 62 Post Service Test Equalize Battery Data table.................. 63 Cell Resistance Data Table.............................. 64 BCT -2000 Interconnection Diagrams........................ 66 Defining BCT-2000 Series Screens......................... 67 BeT -2000 Programming for Service Test..................... 69 BCT-2ooo Sense Lead Connection Diagram................... 75 Typical Load Test Display.............................. 76 BCT -2000 Programming for Equalize Charge.................. 77 Battery Cormection Torque Requirements..................... 82 Electrolyte Temperature (OF) Data Sheet..................... 83 Equalize Voltage Determination........................... 84 Battery Voltage and Current Data Sheet...................... 85 Charge ICV Data Sheet................................ 86 Specific Gravity Data Sheet............................. 87 Float ICV Data Sheet..............,.................. 88 Data Sheet....................................... 89 Page 3 of 96 Rev. 14
(f) w
()
z <<
I ()
sC. MD-ST.28D-0004(Q) 1.0 PURPOS~
To provide instructions for perfonning 28 Volt Battery 18 Month Surveillance Tests using BeT -2000.
To fulfill requirements of Technical Specification Surveillance Requirements 4.8.2.5.2.f and 4.8.2.6.2. [C0265]
Satisfactory completion of Performance Discharge Test shall also satisfy requirements of Technical Specification Surveillance 4.8.2.5.2.f, if Performance Discharge Test is conducted during a shutdown when that test and Battery Service Test would both be required.
To demonstrate the capability of the 28 Volt Battery to supply all required Station Blackout and LOOP/LOCA loads.
Applies to the following component ID#s:
Unit 1 lA 28 Volt Battery - 1BTRY1ADE IE 28 Volt Battery - IBTRY1BDE Unit 2 2A 28 Volt Battery ~ 2BTRY2ADE 2B 28 Volt Battery - 2BTRY2BDE
- Battery Performance Test should be perfonned during shutdown.
~
2.0 PREREQUISITES (f)
- l I---<<
I---
(f) z o (f)
W 0:::
()
Z LL 0:::
W >
0:::
o LL W
.-J CD (f)
Z o CL (f)
W 0:::
0:::
w (f)
~-:)
2.1 The individual assigned to perform this procedure is qualified lAW NC.NA-AP.ZZ-0014(Q), Training, Qualification and Certification.
2.2 If equalize charge is to exceed> 30.3 VDC, VERIFY tagging is complete lAW NC.NA-AP.ZZ-0015(Q), Safety Tagging Program:
2.3 VERlFY M&TE calibration due dates are NOT exceeded. RECORD on Work Activity Sheet and Attachment 19, Section 2.0.
2.4 Prior to any battery work. VERIFY all other vital batteries of same voltage and unit are in service.
Salem Common Page 4 of 96 Rev. 14
(/)
w
(')
z <<
I U
o Z <<
(/)
- J I-<<
l-(/)
z o
(/)
w r::t::
(')
Z LL r::t::
W >
r::t::
o LL W
~
m
(/)
z o 0...
(/)
W 0:::
0:::
uJ
(/)
- J sC. MD-ST. 28D-0004(Q) 2.5 VERIFY battery has NOT had an Equalizing Charge completed within 7 days prior to start of work.
2.6 VERIFY Maintenance Supervisor has obtained Fire Impairment Permit for the following fire doors (as applicable) lAW NC.NA~AP.ZZ-0025(Q), Nuclear Department Operational Pire Protection Program:
2.6.1 Unit 1 lA 28 Volt Battery - 1BTRYIADE, Door #108-1 1B 28 Volt Battery - IBTRYIBDE, Door #109-1 2.6.2 Unit 2 2A 28 Volt Battery - 2BTRY2ADE, Door #108-2 2B 28 Volt Battery - 2BTRY2BDE, Door #106-2 2.7 NOTIFY CRICRS (Control Room/Control Room Supervisor) prior to performing this procedure.
2.8 VERIFY Reactor Operator (RO) prior to performing this procedure.
2.9 VERIFY Load Control Unit software program is correct for the Load Bank. Shunt installed as follows:
2.9.1 TURN ON Load Control Unit, when "LOAD TEST PROGRAM MENU" is displayed, PRESS F4 - Hardware Diagnostics.
2.9.2 From Hardware Diagnostics PRESS PI - Calibrate.
2.9.3 "HARDWARE DIAGNOSTICS!! asks for a password, PRESS ENTER.
2.9.4 VERIFY Load Control Unit Shunt Rate displayed matches Load Bank Shunt installed:
2.9.5 Salem Common 1000 amps / 100 millivolts ~ Load Bank Shunt 202936.
1200 amps / 100 millivolts - Load Bank Shunt 206826.
1200 amps / 100 millivolts - Load Bank Shunt 206827.
IF Program Shunt Rate is not matched with the Load Bank Shunt THEN INFORM Job Supervisor that the Load Control Unit and Load Bank Shunt must be a matched set.
Page 5 of 96 Rev. 14
(f) w (9
z <<
I ()
o z <<
(f)
- )
I--<<
I--
(f) z o (f)
W 00::
(9 Z
LL 00::
W >
00::
o LL W
.-J m
(f) z o CL V)
W 00::
00::
W (f)
- )
sC. MD-ST. 28D-0004(Q) 3.0 PRECAUTION~LANJ> LIMITATIONS 3.1 ENSURE all applicable generic precautions and limitations of SH.MD-AP.ZZ-0003(Q),
Maintenance Department Written Instruction Use Standard, are applied during performance of this procedure.
3.2 This procedure may be completed in whole or in part. Applicable steps within a section should be completed prior to starting next section. Maintenance Supervisor should determine which sections and steps are to be performed.
3.3 Performing any corrective maintenance prior to Service Test can void results. DO NOT tighten, clean or disrurb any connection or perform equalizing charge/adjust battery float voltage. All connections should be monitored for excessive heating during test. Any required connection cleaning and torquing should be performed after test is complete.
3.4 Only one 28 Volt Battery of same unit may be tested at a tittle. DO NOT perform maintenance or testing on remaining batteries of same unit during this surveillance.
3.5 ENSURE battery is isolated as follows when specified in Section 5.0 lAW NC.NA-AP.ZZ-OOI5(Q), Safety Tagging Program:
All loads on associated DC bus are tagged out.
Associated battery chargers are tagged out.
3.6 Gases produced by this battery are explosive. DO NOT smoke, use open flame, create an arc or spark in battery room.
3.7 Periodically VERIFY associated battery room exhaust fan or temporary ventilation system is in operation to remove hydrogen gas.
3.8 ENSURE at least two (2) fully charged 20 lb. CO2 fire extinguisher are immediately available.
3.9 ENSURE unobstructed exit from battery room.
3.10 Unnecessary materials should NOT be taken into battery room, REMOVE items such as pens or other metallic materials from shirt pockets to prevent them from accidentally falling on battery terminals.
3.11 Voltage will be present at battery cell terminals. USE caution when working to prevent contact between positive and negative terminals/bus bar or between terminals/bus bar and ground.
3.12 Tools used on or in immediate vicinity of battery should be insulated so any remaining exposed metal portion of tools CANNOT short circuit battery terminals/bus bar.
Salem Common Page 6 of 96 Rev. 14
if) w C) z <<
I U
o Z <<
if)
- =J f-<<
f-if) z o if)
W 0::
C)
Z lL..
0::
W >
0::
o lL..
W -'
OJ if)
Z o 0...
if)
W 0::
0::
W if)
- =J SC.MD-ST.28D-0004(Q) 3.13 Two insulated wrenches should be used in counter-torque to avoid excessive stress to cell tenninal posts.
3.14 Battery contains diluted sulfuric acid (electrolyte) and can cause severe burns.
PersoIUlel should wear full face mask, acid-resistant gloves and apron when handling electrolyte or taking electrolyte specific gravity and temperature measurements.
3.15 If electrolyte is spilled or comes in contact with skin or clothing, immediately WASH with water and NEUTRAUZE with solution of baking soda and water (1 lb/ gal). If electrolyte comes in contact with eyes, FLUSH with large amounts of clean water and SECURE medical treatment immediately.
3.16 Pennanent eye wash station(s) or temporary unit(s) should be available and in working condition in immediate work area.
3.17 Demineralized water/baking soda solution is only cleaner approved for cleaning battery jars. DO NOT use solvents for cleaning which may enter cell and cause damage by chemical reaction with element of lead acid cell, or craze thennoplastic cover or jar of ceU(s).
3.18 DO NOT use a wire brush, steel wool, or emery cloth to clean connectors. Lead plating damage will occur.
3.19 Use and disposal of chemicals during perfonnance of this procedure should be lAW NC.NA-AP. ZZ-0038(Q), Chemical Control Program.
3.20 Electrolyte should NOT be taken from one cell and transferred to another cell.
DO NOT remove or add electrolyte to change a cell's specific gravity except as directed by Supervisor.
3.21 Maximum temperature of any monitored cell should NOT exceed 120 0 P during testing.
If temperature difference between highest and lowest monitored cell is > 5 of, or any cell temperature approaches 120°F, NOTIFY Supervisor. STOP TEST if temperature exceeds 120oP.
3.22 Stops should be installed on thermometers prior to use to prevent dropping thennometers into cell while obtaining cell temperatures.
3.23 In all cases, it is necessary for user to DEPRESS BCT~2000 Laptop Display Unit ENTER key once any menu field has been inputted/changed. Failure to depress ENTER key will cause menu field to change back to its original selection.
3.24 As with any software program, it is suggested that your program be saved often in event of a power outage or glitch. At Main Menu, SELECT "F6" (Save Configuration) to save changes made in Setup Test Parameter screen. System will prompt user Configuration File Update, <YIN>. SELECT "yn for yes or "N" for no.
Salem Common Page 7 of 96 Rev. 14
Vl w
C..? z <<
- r::
u o z <<
Vl f-<<
f-Vl z o Vl w
ex::
C..?
Z LL ex::
W >
ex:: o LL W
.-I ill Vl Z o 0...
Vl W
ex::
ex::
w Vl sC.MD-ST. 28D-0004(Q) 3.25 PLACE a Job Infonnation Tag on 120 VAC extension cord to inform personnel that testing is in progress. Loss of 120 V AC computer power/load bank power will void Service Test.
3.26 Intertier connection will alarm when voltage drop is > 0.2 VDC.
3.27 Data Logging Acquisition Device (DLAD) will alarm with a two tone audible alann when a cell or overall battery voltage (OV) indicates a warning alarm and a solid tone when a Shutdown Alann occurs.
3.28 If temperature field is changed in Setup Test Parameters screen after Step Load field, load values must be reentered so program can adjust to load amperes lAW IEEE-450 automatically.
3.29 When pausing test for extended periods, battery cells will be allowed to recover and cause results to be affected/voided.
3.30 During testing/while energized, Laptop Display Unit should be placed on a flat and sturdy surface.
3.31 If a WARNING or SHUTDOWN voltage prompt occur during testing, READ prompt.
3.32 Continuous Load Unit (CLU) cooling fans are NOT required to perform battery load testing. however personnel can be burned if they come in contact with CLU screen surfaces.
3.33 ENSURE NO materials are placed on top of CLU screen areas during battery load testing. CLU will become hot during load testing.
3.34 During test, BCT-2000 laptop computer screen will blackout/go blank when keys are NOT depressed for 30 minutes. DEPRESS ENTER key for test screen to appear.
3.35 Cable colors, cable lengths and/or number of pins may vary depending on various upgrades of the test System. If there are discrepancies between the body of the procedure and the actual Alber System Hardware (colors, cable lengths and/or number of pins) work may continue as long as the cable connections are verified correct.
3.36 The Load Control Unit and Load Bank Shunt have been calibrated as a matched set and must be used together. Use of non-matching Load Control Unit and Load Bank Shunt will result in incorrect load amperage applied to Battery, invalidating test results. The Calibration facility calibrates and maintains records for Load Control Units and Load Bank Shunts.
Salem Common Page 8 of 96 Rev. 14
(()
w C) z <<
I U
o Z <<
(()
- l I-<<
I-(()
z o (7j W
0::::
C)
Z LL 0::::
W >
0::::
o LL W
---.l m
(()
z o CL
(()
W 0::::
0::::
W
(()
Digital Low Resistance Ohmmeter (DLRO)
Stopwatch 4.2 Additional Tools and Egui.Qment 4.3 Two 400 amp fast acting, current limiting DC rated fuses (to be used with battery test cables)
Fused battery test cables, 296 MCM, (total of four) with bus bar plates (total of four)
Ground cable for CLU chassis grounding 3 112 in. backup floppy disk (for data transfer and backup configuration)
Clean, lint-free cloths Demineralized water Bucket (one gallon or greater capacity for demineralized water/baking soda SOlution)
Baking soda Electrical extension cords and Hubble adapters Two fully charged 20 lb. CO2 fire extinguisher Temporary eye wash station, if required Pocket calculator Electrical extension cords and Hubble adapters Insulated wrenches See Work Activity Sheet Section M&TE/TOOLS/EQUIPMENT/LUBE for additional requirements.
Procedures SC.MD-CM.28D-0004(Q), Battery Tenninal Post Resistance Measurements Salem Common Page 9 of 96 Rev. 14
UI w
G Z <<
- r::
U o z <<
UI
- J f-<<
f-UI z o UI W
et:
G Z
l>-
et:
W >
et:
o l>-
W
-I CD UI Z o C-UI W
et:
et:
W UI
- J sC.MD-ST. 28D-0004(Q) 5.0 I'ROCEDURE 5.1 Prerequi§ites. Precautions and Limitations Review
- 5. L 1 VERIFY all prerequisites required to start job have been met.
5.1.2 VERIFY all precautions and limitations have been reviewed.
CAUTION Performing any corrective maintenance prior to Service Test can void results. DO NOT tighten or disturb any connections. Identified connections should be monitored for excessive heating during test. Any required connection maintenance should be performed after test is complete. 00 NOT add water to battery cells at this time.
5.2 Battery Room Inspection 5.2.1 RECORD ambient temperature of battery room on Attachment 19.
5.2.2 VERIFY battery room exhaust fan operating by observing air flow.
5.2.3 VERIFY battery room is free of any accumulated dust, dirt and any non-essential materials. CLEAN and REMOVE, as applicable.
CAUTION Explosive gases may be present in battery room. Prior to performing corrective maintenance on explosive proof lights, battery room exhaust fans should be operational.
5.2.4 VERIFY battery room lights are lit and associated explosion proof enclosures are installed and NOT cracked.
A.
REWORK/REPLACE as necessary.
B.
RECORD on Attachment 19, Section 4.0, Comments, any corrective maintenance performed.
5.2.5 RECORD battery room condition on Attachment 19.
Salem Common Page 10 of 96 Rev. 14
(f) w C) z <<
- r::
u o z <<
(f)
- )
f-<<
f-(f) z o (f) w 0:::
C)
Z LL 0:::
W >
W
---I m
(f) z o 0...
(f)
W 0:::
0:::
W (f)
- )
S C. MD-ST.28D-0004(Q) 5.3 Indiyidual Batter:y Rack/Enclosure Inspection NOTE DO NOT correct any deficiencies that could affect test results unless directed by Supervisor.
5.3.1 INSPECT applicable battery rack/enclosure for the following:
Loose or missing nuts, bolts Grounding connection Damage 5.3.2 If required, REWORK using approved materials. RECORD on Attachment 19, Section 4.0 Comments.
NOTE Two cell support rails located beneath each row of cells are constructed of unistrut topped with gray plastic cover. Wherever joint exists in gray plastic cover, spilled electrolyte may flow under cover and erode unistrut.
5.3.3 INSPECT underside of all battery cell unistrut rails in vicinity of any existing joints in their respective gray plastic covers and aU side support rails for the following: Erosion, Peeling of coating OR Any other signs of deterioration.
5.3.4 RECORD battery rack/enclosure condition on Attachment 19.
Salem Common Page 11 of 96 Rev. 14
(f) w C) z <<
I U
o Z <<
(f)
- l f-<<
f-(f) z o (f)
W 0:::
C)
Z LL 0:::
W >
0::: o LL W
-..J m
(f) z o 0...
(f)
W 0:::
0:::
W (f)
- l S C. MD-ST. 28D-0004(Q) 5.4 Individual Battery Cel1 Inspection 5.4.1 INSPECT individual battery cells for the following deficiencies. RECORD all deficient conditions with associated cell number on Attachment 19, Section 4.0, Comments.
Any cracked or leaking cell jars NOTE Procedure SC.MD-CM.28D-0004(Q), "28 Volt Battery Terminal Post Resistance Measurements" I is required if connection is suspect or needs to be disassembled.
DO NOT tighten, loosen or disturb cell-to-cell bus bar connections and cell bank jumper connections until instructed by Supervisor.
Corrosion (white color on negative connections, blue-green on positive connections) or electrolyte staining (dark brown color) on cell connectors, bus bars or tenninal post. CLEAN with plastic bristle brush.
REGREASE as necessary (Refer to Attachment 2)
MiSSing anti-corrosion coating on battery tenninal posts and bus bar/cable lug and plate contact surfaces. REGREASE as necessary. (Refer to )
Major post seal fractures. (NOT blistering or distortion)
NOTE First signs of minor copper contamination appear as pinkish-red color on upper plate support strap and top of negative plates.
Salem Common Major copper contamination on the cell's negative plates (light gray-white) and upper support strap Major sulfate crystals buildup (Christmas Tree Garland or mossing appearance)
Flaking of cell positive plates and upper support strap Major buildup (mountain shaped) of plate materials at bottom of cell jar (it should be in close proximity to lower plate edges to be considered deficiency)
Loose or missing caps on flame arresters or sample tubes Wetness at specific gravity tube gaskets. Correct condition by gasket replacement or by thorough cleaning, neutraliZing and air drying Plate separator material floating on electrolyte surface Page 12 of 96 Rev. 14
(/)
w C) z <<
I U
o Z <<
(/)
=:l f-<<
f-(/)
z o
(/)
W 0:::
C)
Z LL 0:::
W >
0::: o LL W
...J m
(/)
z o 0...
(/)
W 0:::
0:::
W
(/)
=:l T
sC.MD-ST. 28D-0004(Q) 5.5 Battery Cell COJlllection Inspection 5.5.1 Visually INSPECT all inter-cell, inter-rack, inter-tier and field cable connections for the following deficiencies: DOCUMENT all deficient conditions, including associated cell number(s), on Attachment 19, Section 4.0, Comments.
A.
Electrolyte staining (brown color) on cell connectors, bus bars, or tenninal post(s)
B.
Dirt on cell connectors, bus bars, or terminal posts.
C.
Little or NO anti-corrosion coating (NO-OX-ID) is on battery tenninal posts, bus bar/cable lug, and plate contact surfaces..
D.
Corrosion (white color on negative connections, blue-green on positive connections) on cell connectors, bus bars, or tenninal post(s).
RECORD on Attachment 19.
5.5.2 If any connection contains visible corrosion, PERFORM As Found resistance measurements of each battery connection as follows:
Salem Common Page 13 of 96 Rev. 14
(f) w C9 z <<
I o o z <<
(f)
- J f-<<
f-(f) z o (f) w ex::
C9 z LL ex::
W >
sC.MD-ST. 28D-0004(Q)
NOTE Alligator clip test leads or test probes may be used interchangeably with DLRO when taking terminal post resistance readings. Ensure letter lip" engraved on test probes face each other.
When measuring battery lead connection resistance, press test probes of DLRO between approximate top center or side of terminal post and cable lug.
When measuring post*to-post intercell resistance, press DLRO test probes between top center of post "A" on Cell No. X and top center of post "A" on Cell No. Y. (Rafer to sketch below)
When measuring cell bank jumper cable resistance plus terminal post resistance, press DLRO test probes between top center or side center of cell posts A-A at either end of cell bank jumper, DLRO displays measured resistance values in milli~ohms. Data sheets require units to be in micro-ohms. Ensure resistance readings recorded on data tables are in units of micro-ohms. To convert from milli to micro, move decimal to right 3 places.
TOP VIEW - 28V BATTERY l
A I
CELL NO. X
/~--
/. ____.~ ______ ~
__ ~J
~--------------~--~I
~--------------------~
l Salem Common I
)
I A
I CELL NO. Y
~-----------------~
~----~--------------~
~
____ L-______________
~
~------------------/
Page 14 of 96 Rev. 14
(f) w o z <<
- r::
u o z <<
(f)
- J f---<<
1-.
(f) z o (f)
W 0::::
o Z
0::::
w >
W
...J CD (f)
Z o 0....
(f)
W 0::::
0::::
W (f)
- J 5.5.2 (Cont'd) sC.MD-ST. 28D,"0004(Q)
A.
Using DLRO, MEASURE forward and wer~ connection resistance for the following: RECORD resistance values on Attachment 5, Connection Resistance Data Table.
Positive (+ )CONN and negative (-)CONN battery lead connections Each II A It to II A It post-to-post connection Cell bank jumper connection(s)
B.
CALCULATE average resistance for each connection as follows:
- 1.
For Cell No.1, ADD forward and reverse battery lead connection resistance values.
- 2.
DIVIDE sum by 2.
- 3.
RECORD Cell's av~rage connection resistance on AttachmentS, Connection Resistance Data Table, in AVE CONN column~.
NOTE Steps 5.5.3 and 5.5.4 are required if one or more cell(s) have been replaced in battery, N/A these steps when NO cell(s) have been replaced.
CAUTION Positive/Negative battery lead connection and cell bank jumper connection resistance should NOT be used in calculating Battery Connection Average Resistance.
5.5.3 5.5.4 Salem Common PERFORM As Found Battery Connection Average Resistance Calculation as follows:
A.
ADD each "A" to "A" post to post Cell Connection Average Resistance value.
B.
DIVIDE sum by number of cell connections (Le, when number of cells are jumpered). RECORD As Found Battery Connection Average Resistance on Attachment S.
For new cells, MULTIPLY As Found Battery Connection Average Resistance(s) recorded in Step 5.5.3.B by 1.1 (110%). RECORD A to A Battery Connection 110% Average Value on Attachment 19.
Page 15 of 96 Rev. 14
(()
w
~
Z
<{
I ()
0 z
<{
(()
- J I-
<{
I-(()
Z 0
(()
w no::
~
Z LL.
no::
w >
no::
0 LL W
.-J m
(()
z 0
(L
(()
w no::
no::
w
(()
- J sC.MD-ST.28D-0004(Q)
NOTE Step 5.5.5 satisfies Technical Specification Surveillance Requirements for cell-to-cell and terminal connections to be tight and S:O.01 ohms.
5.5.5 EVALUATE Cell Average Connection Resistance against acceptance criteria as follows: INITIAL in the SAT or UNSAT column, as applicable on, Connection Resistance Data Table.
For new cell(s), AVE CONN. resistance(s) is < Battery Connection 110% AVERAGE value recorded in Step 5.5.4 and have little or NO corrosion.
For existing cells, AVE CONN. resistance(s) is < 120% AVERAGE BASELINE value listed in Attachment 2, Table 4 and have little or NO corrosion.
5.5.6 NOTIFY OSieRS and Supervisor of failure to meet Technical Specification acceptance criteria.
5.5.7 RECORD completion of As Found connection resistance measurements on Attachment 19.
Salem Common Page 16 of 96 Rev. 14
Ul W
(9 z <<
I U
o Z <<
Ul f-<<
f-Ul z o Ul W
Do::
(9 z
u...
Do::
W >
Do::
o LL.
L.t..J
-.J m
Ul Z o 0....
Ul W
Do::
et::
W Ul sC. MD-ST. 28D-0004(Q)
NOlI; Data collection steps need NOT be performed in exact order as written, provided all required steps are performed and all data is obtained. For example, temperatures, specific gravities and ICVs may be obtained simultaneously.
5.6 Individual Cell Quarterly Data Collection NOTE With all 13 cells connected, battery float voltage span is 28.9-29.3 VDC (ICV span 2.23 to 2.25 VDC).
Minimum Technical Specification battery voltage is 27 VDC. NOTIFY Supervisor immediately if battery is found below this value.
MEASURE voltage at positive and negative battery terminals, NOT at battery charger or bus.
5.6.1 MEASURE As Found battery terminal voltage at battery.
RECORD As Found battery float voltage on Attachment 19.
Individual Cell Voltage (ICV) minimum Technical Specification Value is ~ 2.13.
5.6.2 MEASURE ICV's for all cells, and RECORD ICV's on Attachment 4A Data Table, in "ICV" column.
5.6.3 REMOVE each cell's flame arrester cap and sample tube dust cover.
Salem Common Page 17 of 96 Rev. 14
(f) w l')
z <<
- r::
u sC.MD-ST. 28D-0004(Q) 5.6.4 Cell Temperature Measurements:
Cell temperatures should be obtained using electronic temperature measurement device with acid resistant probe, if available; otherwise, non-mercury thermometer should be used.
CAUTION If glass non-mercury thermometer is used. "Stops" should be attached to prevent dropping thermometer into cell.
A.
INSERT acid resistant probe or non-mercury thermometer with "Stop" attached into flame arrester filler vent for Cell No.1.
B.
ALLOW temperature to stabilize.
C.
RECORD stabilized temperature on Attachment 4A Data Table, in "CELL TEMP" column (expected value 6soF-IOS°F).
D.
REPEAT Steps 5.6.4.A through 5.6.4.C for all cells listed in Attaclunent 4A, Data Table.
~
DO NOT add water to any cells at this time.
~
Immediately report failure of any celf to meet Technical Specification acceptance criteria
~
to Supervisor for evaluation and possible corrective action.
I-(f) z o (f)
W 0:::
l')
Z w...
0:::
W >
0:::
o w...
W
.--l OJ (f)
Z o CL (f)
W 0:::
0:::
W (f)
- =J 5.6.5 Electrolyte Level Determination:
Salem Common A.
MEASURE distance between bottom of high level mark and electrolyte level for all cells.
Page 18 of 96 Rev. 14
(f) w C) z <<
- r::
u o z <<
(f)
- J f-<<
f-(f) z o (f)
W 0:::
C)
Z lL..
0:::
W >
0::: o lL..
W
-I co (f) z o (L
(f)
W 0:::
0:::
W (f)
- J T
S C. MD-ST. 28D-0004(Q) 5.6.5 (Cont'd)
B.
NOTIFY OS and Supervisor immediately if level is above high level mark or below low level mark (> 8/32 in. above high level mark or s low level mark.
C.
RECORD number of 1/32 in. increments, electrolyte level is below high level mark on Attachment 4A Data Table, in ItCELL LEVEL" column.
If level is > high level mark, indicate the number of 1/32 in.
increments electrolyte level is above high level mark by including a positive (+) sign preceding number.
5.6.6 Specific Gravity Measurement:
A.
INSERT hydrometer into sample tube of each cell.
B.
WITHDRAW electrolyte sample into hydrometer.
C.
RETURN electrolyte sample into flame arrester filler vent.
D.
RE-INSERT hydrometer into sample tube.
E.
WITHDRAW second electrolyte sample into hydrometer.
F.
READ specific gravity of sample.
G.
RETURN electrolyte into battery sample tube.
H.
RECORD Measured Specific Gravity on Attachment 4A Data Table, in "MEAS. S.G." column.
5.6.7 REPLACE each cell's flame arrester cap & sample tube dust cover.
Salem Common Page 19 of 96 Rev. 14
V)
W o z
<C I
U o z
<C V)
- J I-
<C l-V) z o V)
W 0::::
o z LL 0::::
W >
0:::: o u_
l-Ll
-.J m
V) z o 0...
V)
L.tJ 0::::
0::::
W V)
- J SC.MD-ST.28D-0004(Q) 5.7 Data Reduction NOTE Immediately report failure of any cell to meet Technical Specification acceptance criteria to Supervisor for evaluation and possible corrective action.
5.7.1 T
5.7.2 5.7.3 Salem Common Temperature Compensation Calculation:
A.
CALCULATE average cell temperature by adding cell temperatures recorded on Attachment 4A Data Table and dividing by total number of cell temperature measurements.
B.
RECORD cell average temperature on Attachment 19.
C.
CALCULATE cell specific gravity temperature compensation as follows:
RECORD (+) 0.001 temperature correction valu,e for every 3°F the cell temperature is above 77°F, on Attachment 4A Data Table, in "TEMP CORR" column for each cell.
OR RECORD H 0.001 temperature correction value for every 3°F the cell temperature is below 77 0 F, on Attachment 4A Data Table, in the "TEMP CORR" column for each cell.
D.
CALCULATE temperature corrected S. G. by adding or subtracting TEMP CORRECTION to/from MEASURED S.G. for all cells.
E.
RECORD temperature corrected S.G. on Attachment 4A Data Table, in "TEMP CORR S.G," column.
Level Compensation Calculation for level corrections factors. (Refer to )
A.
Using recorded 1fCELL LEVEL", DETERMINE cell level correction factor. for each cell. (Refer to Attachment 3)
B.
RECORD level compensation on Attachment 4A Data Table, in "LEVEL CORR FACTH column.
Corrected Specific Gravity Calculation (Tech Spec minimum is 2: 1.190).
A.
CALCULATE corrected specific gravity for each cell by subtracting LEVEL CORRECTION FACTOR from TEMP CORRECTED S.O.
B.
RECORD corrected specific gravity on Attachment 4A Data Table, in "CSG" column.
Page 20 of 96 Rev. 14
if) w
~
Z
<C I o o
Z
<C Vi
- J I-
<C 1--
if) z o if)
IJ.J 0:::
~
Z L.L 0:::
W >
0:::
o LL LLJ
.-.J CD if)
Z o 0...
if) i.JJ 0:::
0:::
W if)
- J sC. MD-ST. 28D-0004(Q) 5.7.4 A verage Corrected Specific Gravity Calculation:
A.
CALCULATE average corrected specific gravity by adding ail corrected specific gravities and dividing by total number of cel1s (NOT counting jumpered cells, normally 60).
B.
RECORD average corrected specific gravity on Attachment 19.
NOTE Immediately report failure of any cell to meet Technical Specification acceptance criteria to Supervisor for evaluation and possible corrective action.
5.7.5 ENSURE the following Tech Spec Acceptance Criteria have been met for each cell listed in Attaclunent 4A. INITIAL on Attachment4A Data Table, in "TECH SPEC CRIT SAT" column of each cell when criteria listed below are met.
Salem Common Individual cell voltage in "ICV" column is ;;;:: 2.13 VDC while under float charge (2.13 or more in ICV column).
Page 21 of 96 Rev. 14
Ul w
C) z <<
I U
o z <<
Ul I-<<
I-Ul z o Ul 2J 0:::
C)
Z lL.
0:::
W >
0:::
o lL.
W
-l CD Ul Z o 0...
Ul W
0:::
0:::
w Ul sC.MD-ST. 28D-0004(Q) 5.7.5 (Cont'd)
NPtE The next Tech Spec acceptance criteria is satisfied when any ICV is ~ 2.13 VDC. The bases is as follows:
All original ICV's were < 2.40 VDC.
2.40 VDC - 0.27 VDC = 2.13 VDC.
However, NO cell may be allowed to be < 2.13 VDC (Tech Spec lower limit).
Therefore, as long as ICV's are ~ 2.13 VDC, Tech Spec for ICV's NOT decreasing by more than 0.27 VDC for original acceptance test is satisfied.
Individual Cell Voltage in "ICV" column bas NOT decreased more than 0.27 VDC'fromvalue observed during original acceptance test. This criteria is satisfied when ICV is ~ 2.13 VDC in "ICV" column based on note above.
Corrected specific gravity in "CORRECTED S.G. It column for each cell is ~ 1.190.
Electrolyte level between high and low levels marks.
5.7.6 ENSURE the following Non-Tech Spec Acceptance Criteria have been met for each cell listed in Attachment 4A.
A.
NO "recorded" cell temperature is more than 5°P from cell average temperature recorded in Step 5.7.1.B. RECORD on Attachment 19.
NOTE Cells with corrected specific gravity more than 0.010 below Average Corrected S.G.
may require and equalizing charge. Contact Supervisor to determine if an equalizing charge is required (procedure number SC.MD-CM.ZZ~0009(Q)).
B.
NO cell's corrected specific gravity is more than 0.010 below average corrected S.O. recorded in Step 5.7.4.B. RECORD on Attachment 19.
5.7.7 If results are questionable. NOTIFY Maintenance Supervisor.
Salem Common Page 22 of 96 Rev. 14
S C. MD-ST. 280-0004(Q) 5.7.8 If results are satisfactory, PROCEED with Service Test lAW Subsection 5.8.
5.8 BCT-2000 Series System Interconnections 5.8.1 SITUATE BCT-2000 Continuous Load Unit (CLU) to minimize localized heating of nearby equipment due to its power dissipation.
NOTE should be used when performing the following BCT-2000 system interconnections.
Technician should review functions of the BCT~2000 by trial programming without CLU connected to the battery. Attachment 7 defines the BCT-2000 laptop computer screens.
5.8.2 LOCATE 10 ft. gray cable with two female 37 pin molded computer connectors and CONNECT one end to BCT-128 Data Logging Acquisition Device (DLAD) labeled COMPUTER PORT. TIGHTEN thumb screws so they are secure.
CAUTION
~
Computer should be deenergized, when connecting/disconnecting any connectors/plugs
~
to prevent blowing internal computer fuses.
I u o z <<
(f)
- =J I-<<
I-(f) z o (f) 5.8.3 CONNECT other end of 10 ft. gray cable to Laptop Display Unit (LOU) as follows:
A.
LINE connector up with 10 ft cable connector, PUSH flrmly into mating COImector.
B.
After connector is seated, TIGHTEN thumb screws.
w
~
NOTE
(')
z if LOU and OLAO are powered by same Circuit, system current will trip circuit breaker.
l.L
~
W >
Salem Common C.
CONNECT LOU and DLAD power cables to a separate 20 amp, 120 VAC power source.
Page 23 of 96 Rev. 14
UI W
(')
z <<
I u o z <<
UI
- )
I-<<
I-UI z o
(/)
w cr::
(')
z S C.MD-ST. 28D-0004(Q) 5.8.4 LOCATE and CONNECT 50 ft. gray Load Control cable with two Amphenol 37 pin connectors on each end between DLAD and CLU connector J2 (connector J29 if Hope Creek BCT-2000 is being used).
5.8.5 INTERCONNECT 110 to J13 on CLU lAW Attachment 6.
5.8.6 INSTALL insulated boots over unused bus bars located at rear of CLU.
5.8.7 Using ground lug at rear of CLU cart, GROUND CLU.
5.8.8 CONNECT 120 VAC power cable to CLU (11) and CONNECT to a separate 20 amp, 120 V AC power source.
5.9 Programming of BCT-2000 Laptop Computer 5.9.1 INSTALL one thermometer in each cell specified on Attachment 13 (total of two). RECORD on Attachment 13 (T=O).
5.9.2 CALCULATE average electrolyte cell temperature by adding all monitored cell temperatures (Step 5.9.1) and dividing by two. RECORD on Attachment 19.
5.9.3 In sequence, ENERGIZE the following BCT-2000 system devices:
Laptop Display Unit will automatically execute/initialize to the Load Test Program Menu.
CAUTION If load Test Program Menu does NOT indicate the correct time and date, notify maintenance supervisor to enter the correct time and date using DOS.
A.
Laptop Display Unit (LDU)
B.
Data Logging Acquisition Device (DLAD) c:
NOTE cr::
~
A clicking sound should be heard coming from the DLAD. This is the sound of the cr::
mechanical relays scanning the monitored channels.
o LL W
-.I m
(/)
z o 0...
(/)
W cr::
cr::
w
(/)
- )
5.9.4 DEPRESS FI, Setup Test Parameters screen, Salem Common Page 24 of 96 Rev. 14
V) w (9
z <<
I U
o Z <<
V)
- =>
I-<<
l-V) z o V)
W 0,:
(9 Z
lL.
Ct:
W >
0,:
o lL.
W
---.l m
V) z o CL V)
W 0,:
0,:
W V)
- =>
S C. MD-ST. 28D-0004(Q) 5.9.5 PROGRAM BCT-2000 for Battery Service Test of 28 Volt Battery under test lAW Attachment 8.
5.9.6 DEPRESS FI and VERIFY screen inputted data is lAW Attachment 8, as applicable.
5.9.7 DEPRESS ESC key to return to Load Test Program menu.
5.9.8 BACKUP Setup Test Parameter as follows:
A.
INSERT backup floppy disk into LDU.
B.
DEPRESS F5, Utilities.
C.
DEPRESS Fl, Backup Configuration.
D.
DEPRESS ENTER key to backup configuration.
E.
On LDU screen, VERIFY file was copied.
F.
DEPRESS ESC to return to Load Test Program Menu.
5.9.9 RECORD for completion of BCT-2000 programming on Attachment 19.
5.9.10 DEENERGIZE all BCT-2000 devices.
5.9.11 REMOVE backup floppy disk from LDU.
Salem Common Page 25 of 96 Rev. 14
(j")
w
(')
z <<
- r::
u o z <<
(j")
I-<<
I-(j")
z o (j")
W et::
(')
Z w...
00::
W >
00:: o w...
W
-.J OJ (j")
Z o D...
(j")
W 00::
00::
W (j")
sC. MD-ST. 28D-0004(Q) 5.10 Connecting BCT -2000 to Battery Cell Terminal Posts NOTE contains a detailed diagram for connection of sense leads used to obtain individual cells, intertier cables and overall battery voltage for a REVERSED polarity configuration (i.e. when the field cable lead is connected to the positive terminal of Cell
- 13),
5.10.1 CONNECT BCT-2000 system to 28 Volt Battery as follows:
Salem Common A.
LOCATE 25 ft. Sense Lead Extender gray cables with DB37 pin on one end and an Amphenol (round/black) 37 pin connector on other end.
B.
CONNECT cable end with DB37 to DLAD port labeled CELL 1-32.
C.
LOCA TE red individual cell wire bundle with small numbered clips on one end (0-32) and Amphenol 37 pin on other end. CONNECT black connector end into other end of Sense Lead Extender Cable.
D.
LOCATE Sense Lead Clip #0 from first set of red Individual Cell Wire Bundle and PLACE this clip on positive (negative) post of Cell #1.
E.
LOCATE Sense Clip #1 from set of red Individual Cell Wire Bundle and PLACE this clip on negative post of Cell #2. CONTINUE this sequence until Clips #2-#12 have been connected.
F.
On Cell #13, PLACE Clip #13 on positive post.
G.
LEAVE Sense Leads Clips #14-#32 disconnected.
H.
CONNECT Individual Cell Wire Bundle leads labeled OV+, OV-and IT-I to connector labeled SYSTEM on back of DLAD.
I.
LOCA TE Sense Lead Clip labeled OV + and CONNECT to positive post on Cell #13. (Refer to Attachment 9)
J.
LOCATE Sense Lead Clip labeled OV - and CONNECT to negative post on battery Cell # 1. (Refer to Attachment 9)
Page 26 of 96 Rev. 14
(j) w C) z
<C I
U o z
<C (j)
- J I-
<C I-(j) z o (j)
W 00::
C)
Z LL 00::
W >
00:: o LL W
-.J m
(j) z o 0...
VI W
00::
00::
W (j)
- J 5.11.1 (Coned) sC.MD-ST.28D-0004(Q)
K.
LOCATE and CONNECT leads labeled IT-1(+) and IT-1(+) as follows:
- 1.
PLACE leads IT -1 ( +) on positive post and IT-I (-) on negative post of intertier jumper between Cell #7 and Cell #8.
- 2.
LEAVE leads IT-2 through IT-8 discOImected.
5.11 Connecting Continuous Load Unit to Battery 5.11.1 CONNECT fused battery test cables from CLU to 28 Volt Battery as follows:
Refer to Attachment 6.
A.
NOTIFY Maintenance Supervisor for safety tagging of associated battery bus loads and battery chargers.
B.
ENSURE associated battery bus loads and battery chargers are isolated.
CAUTION Fused battery test cables should be completely uncoiled and should NOT lie upon one another to preclude the possibility of overheating.
Extreme care should be used while performing the following steps. The possibility of electrical shock exists.
Insulated matting should be placed on floor under/near Continuous Load Units and battery connections to insulate Technician from ground.
Temporary Insulation should be installed on fused cable lugs and battery cable lugs as specified.
To minimize connection heating effects and overheating cell terminal post, each test fuse should be mounted to a large bus bar plate so that adequate space is available to separately bolt each 296 MCM cable lug.
Salem Common C.
DISCONNECT, INSULATE, and TIE BACK positive and negative battery leads at battery. RECORD on Attachment 1.
Page 27 of 96 Rev. 14
(f) w C) z
<r:
I U
o Z
<r:
(f)
- J I-
<r:
I-(f) z o (f) w et::
C)
Z LL et::
W >
et:: o LL w
CO (f)
Z o 0...
(f)
W et::
et::
W (f)
- J 5.11.1 (Cont'd)
Salem Common S C. MD-ST. 28D-0004(Q)
D.
CONNECT two parallel 296 MCM load test cables from CLU to 28 Volt Battery as follows:
- 1.
PLACE insulating matting on floor under/near cable connection end of battery and CLU.
- 2.
At CLU, ENSURE test cables are disconnected.
- 3.
INSULATE CLU test cable lugs from each other and ground with temporary insulation boots.
- 4.
Using bus bar plates, CONNECT 400 amp test fuses to positive and negative battery terminals.
- 5.
At battery, CONNECT negative test cable to negative battery terminal.
- 6.
At CLU, REMOVE temporary insulation boot from end of negative test cable and CONNECT to negative connection of CLU (112).
- 7.
At battery, CONNECT positive test cable to positive fused battery terminal.
- 8.
At CLU, REMOVE temporary insulation boot from end of positive test cable and CONNECT to positive cOIUlection of CLU (J1I).
Page 28 of 96 Rev. 1.4
If) w o z
<{
I U
o z
<{
If)
- J I-
<{
I-If) z o If)
L.LJ 0:::
o Z
LL 0:::
W >
0:::
o LL l..tJ
.-J CD If)
Z o Cl..
If)
W 0:::
0:::
W If)
- J sC,MD-ST.28D-0004(Q) 5.12 Battery Service Test Using BCT-2000 5.12.1 ENSURE associated battery area exhaust fan is running or temporary ventilation system is in place and running.
CAUTION DO NOT energize the Continuous Load Unit (CLU) at this time.
5.12.2 In sequence, ENERGIZE the following BCT-2000 devices:
NOTE Laptop Display Unit (LOU) will automatically execute/initialize to the Load Test Program Menu screen.
A.
Laptop Display Unit (LDU)
N.OTE A clicking sound should be heard coming from the Data Logging Acquisition Device (DLAD). This is the sound of the mechanical relays scanning the monitored channels.
B.
Data Logging Acquisition Device (DLAD) 5.12.3 After BCT-2000 system has initialized to Load Test Program Menu screen, PLACE CLU power switch ON.
CAUTION CLU can safely operate with loss of all cooling fans, however personnel should NOT come in contact with CLU screen surfaces because they will get hot.
5.12.4 VERIFY CLU control panel cooling fans and resistor bank cooling fans are running.
5.12.5 DEPRESS F3, Test Reports.
5.12.6 DEPRESS F4, Select Log File.
Salem Common Page 29 of 96 Rev, 14
(j) w C) z <<
- r::
U o z <<
(j)
- l I-<<
I-(j) z o (j) w
~
C) z LL
~
W >
~
o LL W
---.J m
(j) z o 0...
(j)
W
~
~
W (j)
- l sC.MD-ST.28D-0004(Q) 5.12.7 Within Select Log File window. SELECT Test File ID that was entered in Set Test Parameters screen (Attachment 8) using Up/Down arrow keys (as required) and DEPRESS F2, Accept Choice.
5.12.8 DEPRESS, ESC key to return to Load Test Program menu.
5.12.9 SET BCT~2000 for REVERSED polarity configuration as follows:
A.
DEPRESS Fl. Setup Test Parameters screen.
B.
Using DOWN ARROW key, move cursor to Voltage Polarity Field.
C.
Using (+) key. SELECT REVERSED. DEPRESS ENTER.
D.
DEPRESS ESC key to return to Load Test Program menu.
NOTE The Function Key menu located at the bottom left of the Load Test Program Menu screen provides the following selections before the test begins:
ESC - Escape Back to Main Menu F1 - Start Test F5 - Toggle Setup F6 - View Intertier - Display Toggles Between Cells and Intertier Connections F7 - Print Now While the test is running the following selections are available:
F1 - Stop Test F2 - Pause/Resume Test F3 - Manual/Auto Control (allows for increase/decrease of load in manual using + and - keys)
F4 - Reset Audible Alarm F5 - Change Setup F6 - View Intertier - Display Toggles Between Cells and Intertier Connections Intertier may NOT be visible at Step 5.12.1 O.B, but test may continue.
The BCT-2000 system will control the Service Test, as programmed, requiring only monitoring by Technician performing the test.
The BCT-2000 will automatically terminate test after 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and 10 minutes and provide final printout.
5.12.10 DEPRESS F2, Run Load Test and VERlFY BCT-2000 system is connected correctly as follows:
Salem Common A.
VERIFY all 13 cell voltages are displayed on LDU screen.
B.
DEPRESS F6, View Intertier and VERIFY all three intertier sensor voltage bars are indicating on LDU screen.
C.
DEPRESS F6, View Cells, to return to cell voltage screen.
D.
VERIFY battery overall voltage (OV =) is displayed at top of LDU screen.
Page 30 of 96 Rev. 14
Ul w
C')
Z
<C
- c o
o z
<C Ul
- l f---
<C f---
Ul z o Ul W
et:
C')
Z u-et:
W >
et:
o u-W
---1 OJ Ul Z o 0...
Ul W
et:
et:
W Ul
- l SC.MD-ST.28D-0004(Q)
NOTE On the far right side of the Load Test Display screen, a column labeled ALARM is displayed. This column will display cell and/or intertier that goes out of the programmed Low Cell Voltage or High Intertier Voltage Alarm. In addition the cell (vertical voltage bar) that is failing changes color state on the screen and is listed in the ALARM column.
Refer to Attachment 8, Section 8 (Test Setup Block) for other test alarm conditions.
Depressing F4 key will silence alarms.
Stopwatch will be used to record discharge time in event power is lost to computer/load bank during battery discharge.
CAUTION Any battery connections which were NOT acceptable in battery Terminal Post Resistance Test should be monitored for excessive heating during performance of Battery Service Test. Connection cleaning and torquing will be performed after Battery Service Test is complete.
II ANY of the following conditions occurs, Battery Service Test SHOULD BE STOPPED by depressing F2 (pause) to investigate problem:
Any cell voltage rapidly decreasing below 1.75 VDC (i.e. cell voltage may reverse).
Battery overall voltage (OV) is < 22.8 VDC.
Any monitored cell temperature exceeds 120°F.
Cell terminallcable connection temperature is much hotter than other oell terminal/connection temperatures.
Terminal post grease is melting/smoking.
Any other abnormal condition.
5.12.11 To start Service Test, simultaneously DEPRESS P1 and START stopwatch.
RECORD start time on Attachment 19.
5.12.12 On LDU Program Window (Test Started), OBSERVE the following:
Step: 001 Time: Clock Counting Down Load: Indicate Programmed Load Amps for Step 001 Total Run Time: Clock Counting Up Salem Common Page 31 of 96 Rev. 14
Ul W
C) z <<
I U
o Z <<
Ul
- J I-<<
I-Ul z o Ul W
et::
C)
Z lL.
et::
W >
et::
o lL.
W
--l CO Ul Z o 0...
Ul W
et::
et::
W Ul
- J S C,MD-ST.28D-0004(Q)
NOTE Steps 5.12.13 through 5.12.15 performance will overlap each other and be performed in parallel throughout the duration of the discharge test.
If a minimum voltage value IS NOT met in Step 5.12.13, this should be brought to immediate attention of Supervisor and OSieRS. The test may continue as long as battery minimum voltage is ~22.8 VDC.
T Battery lA IB 2A 2B 5.12.13 At end of each loaded programmed step, VERIFY battery terminal voltage (OV) value indicated on top of Load Test Display screen) is ~ minimum voltage values shown on Table 1 below. RECORD battery tenninal voltage at end of each Step on Attachment 19.
TABLE 1 Minimum Voltage Values for Progranuned Steps Step 001 Step 002 Step 003 Step 004 Step 005 Step 006
($)
($)
($)
($)
24.9 24.9 24.9 24.6 24.0 23.9 24.8 24.7 24.7 24.5 24.6 24.6 25.0 25.0 25.0 24.6 24.0 24.0 24.8 24.7 24.6 24.4 24.5 24.5 Salem Common Page 32 of 96 Rev, 14
(/)
w (9
z
<{
- r::
u o z
<{
(/)
- )
I-
<{
l-(/)
z o
(/)
W 0:::
(9 Z
LL 0:::
W >
0::: o LL w
~
CO
(/)
Z o Cl..
(/)
l.J.J 0:::
0:::
W
(/)
- )
sC. MD-ST. 28D-0004(Q)
CAUTION Load amps displayed on LOU should NOT be less than programmed current at each step If less than programmed current, test should be terminated. If > 2 amps above programmed current, load amps displayed on LOU should be recorded in Comments Section and Supervisor should be notified.
5.12.14 At end of each programmed step. VERIFY BCT-2000 LDU "Test Started block" changes to next step (e.g., "001" to "002", etc.) and Load Amps indicates programmed current lAW Attachment 8, Table 3.
5.12.15 MONITOR cell temperatures at 15 minute intervals lAW Attachment 13, to ensure overheating does NOT occur. If temperature exceeds 120°F, STOP test by depressing F2. RECORD cell temperatures and times on 3.
NOTE When test is finished, a message in Program Window I located at bottom right of Load Test Display screen, will show TEST ENDED.
T 5.12.16 VERIFY BCT-2000 stopped Battery Service Test after 250 minutes (240 minutes loaded and 10 minutes unloaded) by verifying LDU program window indicates Test Ended and Total Run Time is 04:10:00. RECORD time test ends on Attachment 19.
5.12.17 RECORD battery terminal voltage when test ended (OV value indicated on top of Load Test Display screen) on Attachment 19.
5.12.18 DEENERGIZE CLU by placing power switch OFF.
5.12.19 DEPRESS ESC key to return to Load Test Program Menu screen.
5.12.20 COPY Report File from LDU to backup floppy disk as follows:
A.
DEPRESS F5. Utilities, to go to Load Test Program Utilities screen.
B.
DEPRESS F2, Transfer File, to go to Transfer File screen.
C.
INSERT backup floppy disk into LDU.
D.
DEPRESS ENTER key to transfer file from LDU to floppy disk.
E.
DEPRESS enter again.
F.
On LDU screen, VERIFY file was copied.
G.
DEPRESS ESC key to return to Load Test Program Menu screen.
Salem Common Page 33 of 96 Rev. 14
(/)
w C) z <<
I U
o Z <<
(/)
- l f--<<
f--
(/)
z o
(/)
W Ct:
C)
Z LL Ct:
W >
Ct: o LL W
-I CD
(/)
Z o CL
(/)
W Ct:
Ct:
W
(/)
- l sC.MD-ST. 28D-0004(Q) 5.12.21 DEENERGIZE all BCT-2000 System devices.
CAUTION Extreme care should be used while performing the following step. The possibility of electrical shock exists.
Insulated matting should be placed on floor under/near Continuous Load Unit and battery connections to insulate Technician from ground.
Temporary insulation boots should be installed on fused test cable lugs and battery cable lugs as specified.
5.12.22 DISCONNECT Continuous Load Unit (CLU) from battery as follows:
Salem Common A.
PLACE insulating matting on floor under/near cable cOIUlection end of battery and master CLU.
B.
At CLU, DISCONNECT positive test cable from positive connection and place temporary insulation over lug.
C.
At battery t DISCONNECT positive test cable from positive fused battery tenninal.
D.
At CLU, DISCONNECT negative test cable from negative connection and place temporary insulation over lug.
E.
At battery t DISCONNECT negative test cable from negative fused battery terminal.
F.
DISCONNECT fuses from positive and negative battery terminals.
G.
DISCONNECT cable installed in Step 5.8.4.
Page 34 of 96 Rev. 14
(J) w C) z <<
- r:
()
o z <<
(J)
=:>
f-<<
f-(J) z o (J)
W 0:::
C) z LL 0:::
W >
0::: o LL W
.-J m
(J)
Z o Q
(J)
W 0:::
0:::
W (J)
=:>
sC.MD-ST. 28D-0004(Q) 5.13 Battery Cell COIUlection Retourge/Cleaning If any cell connections were unsatisfactory during battery cell connection inspection (Subsection 5.5)/ applicable Steps of Subsection 5.13 should be performed prior to connecting battery field leads.
Retorquing is defined as loosening connection (breaking connection) and then torquing it to value listed. Retorque values are listed in vendors manual as "Subsequent Retorque Values" (used for maintenance checks).
"Initial Torque Values" are used whenever associated connection is new or disassembled and reassembled.
5.13.1 RETORQUE all tenninal post cOIUlections which have resistance(s) 2:120%
A VERAGE BASELINE value. < MAXIMUM ALLOW ABLE value, and little or NO terminal post/coIUlection corrosion to 130 (125-135) in*lbs. RECORD Retorqued Connection No. 's on Attachment 19.
NOTE The following step is used to determine if retorque of cell(s) has been successful prior to performing As Left Intercell Resistance Measurements checks of all cells.
5.13.2 Using DLRO, MEASURE contact resistance of retorqued connection(s) lAW Step 5.5.2, and COMPARE values to Acceptance Criteria listed in Attachment 5, Table 1.
5.13.3 Supervisor Notification - CorrecJiY.e Action Determination Salem Common A.
If all retorqued resistance(s) are < 120% of associated AVERAGE BASELINE values and little or NO terminal post/connection corrosion exists, GO TO Subsection 5.14. RECORD on Attachment 19.
B.
If resistance(s) are still ~ 120% AVERAGE BASELINE value, GO TO Step 5.13.4. RECORD on Attachment 19.
Page 35 of 96 Rev. 14
(!)
LLJ
(:)
Z <<
I U
o Z <<
(!)
- J f-<<
f-(!)
z o
(!)
w n::
(:)
z li-n::
W >
n::
o LL.
LLI
_J m
(!)
z o 0...
(!)
W n::
n::
LLJ
(!)
- =:J sC. MD-ST. 28D-0004(Q)
CAUTION Voltage will be present at battery cell terminals. Use caution when working to prevent contact between positive and negative terminal posts or between terminal posts and ground.
5.13.4 LOOSEN and carefully REMOVE unsatisfactory terminal post hardware, applicable intercell bus bar(s), cable luges) and terminal plate(s). RECORD on Attachment 1, Disconnect Log connections disconnected.
CAUTION DO NOT use solvents, cleaning compounds, oils, waxes or polishes to clean battery containers or to remove NO-OX-ID grease from cell posts/connectors. A foreign liquid/material can enter cell and cause damage. Solvents can also craze thermoplastic cover or jar.
5.13.5 WIPE grease and dirt from terminal post(s), bus bares), and hardware.
5.13.6 INSPECT cell terminal posts for exposed copper or damage.
5.13.7 PERFORM Intercell Connection Inspection/Rework as follows:
A.
INSPECT bus bares) and hardware for damage and exposed copper.
B.
REPLACE, as required, with approved parts.
C.
DOCUMENT all replaced parts on Attachment 19, Section 4.0 Comments.
5.13.8 Using 1 lb. of baking soda per gallon of demineralized water, PREPARE a neutralizing solution in a plastic bucket or suitable container.
CAUTION DO NOT let solution enter battery cell.
5.13.9 APPLY solution to cell terminal post(s), cell jar, terminal plates, bus bar(s),
and hardware with a lint~free cloth. NEUTRALIZE until fIzzing action ceases.
Salem Common Page 36 of 96 Rev. 14
(f) w
(')
Z
<t I
U o z
<t (f)
- )
I-
<t I-(f) z o (f)
W 0:::
(')
Z LL 0:::
W >
0::: o LL W
---.J m
(f) z o 0....
(f)
W 0:::
0:::
W (f)
- )
sC.MD-ST. 28D-0004(Q) 5.13.10 Using a lint-free cloth dampened with demineralized water, REMOVE residue from area and parts. ALLOW to air dry.
5.13.11 Using a plastic bristle brush, CLEAN contact surfaces of applicable cell terminal posts, bus bars(s), cable lugs and terminal plates until a clean and bright surface is obtained.
Preferred method for applying corrosion resistant grease is by heating NO-OX-ID A to cream-like consistency. However, NO-OX-ID A SPECIAL compound (NO heat required) may be used at discretion of Maintenance Supervisor and System Manager.
[PR 990423148]
CAUTION Grease has a minimum flash point of 450°F. DO NOT use heaters with open flames.
Exercise extreme care when heating grease.
5.13.12 If Using NO-OX-ID A, PREPARE corrosion resistant grease as follows:
Salem Common A.
SET temperature of electric hot plate between 160°F and 185°F.
B.
HEAT corrosion resistant grease to a cream-like consistency (an infrared lamp may be used in lieu of a hot plate).
C.
APPLY a light coat of melted grease to ends of bus bar(s) by dipping them into melted grease coating approximately 2 inches in from each end.
D.
Using a paint brush, APPLY melted grease to both sides of middle holes and contact surfaces on four and six hole connectors.
E.
REMOVE any residue grease by wiping all terminal post surfaces with a clean lint-free cloth or paper towel.
F.
APPLY a thin film of grease to all post surfaces.
G.
WIPE all grease from cell jar cover(s).
Page 37 of 96 Rev. 14
IJ) w C) z <<
- r::
u o z <<
IJ)
- J f-<<
f-IJ) z o IJ)
W 0:::
C) z ll-0:::
w >
0:::
o ll-W
-I CD IJ)
Z o 0..-
IJ)
W 0:::
0:::
W IJ)
- J sC.MD-ST.28D-0004(Q) 5.13.13 If Using NO-OX-ID A SPECIAL, PERFORM the following:
A.
Using a brush, APPLY light coat of grease, to ends of bus bar(s).
B.
APPLY grease, to both sides of middle holes and contact surfaces on four and six hole connectors.
C.
REMOVE any residue grease by wiping all terminal post surfaces with a clean lint-free cloth or paper towel.
D.
APPLY a thin film of grease to all post surfaces.
E.
WIPE all grease from cell jar cover(s).
5.13.14 REASSEMBLE intercell bus bar(s) lAW manufacturer's required configuration.
NOTE Provide counter*torque during final nut and bolt assembly tightening by using two insulated wrenches.
5.13.15 TORQUE bolt assembly to 165 (160-170) in-lbs.
NOTE The following step is used to determine if rework of cell(s) has been successful prior to performing As Left Intercell Resistance Measurements check of all cells.
5.13.16 Using a DLRO, MEASURE contact resistance of all cleaned connection(s) lAW Step 5.5.2 and COMPARE values to Acceptance Criteria listed in, Table 1.
5.13.17 Supervisor Notification - Couective Action D~termination Salem Common A.
If any cleaned resistance(s) are still ~ 120% AVERAGE BASELINE value and < MAXIMUM ALLOWABLE value or ~ 120 % AVERAGE BASELINE value, GO TO Subsection 5.14. RECORD on 9.
B.
If any resistance(s) are still ~ MAXIMUM ALLOW ABLE value or new ceU(s) is/are ~ 120% AVERAGE BASELINE value, NOTIFY Maintenance Supervisor/System Manger for resolution. RECORD on 9.
Page 38 of 96 Rev. 14
(/)
w C) z
<{
I U
o Z
<{
(/)
- =)
I-
<{
l-(/)
z o
(/)
W 0::::
C)
Z LL 0::::
W >
0::::
o LL W
-l m
(/)
z o 0...
(/)
W 0::::
0::::
LtJ
(/)
- =)
5.14 SC.MD-ST.28D-0004(Q)
Post Service Test Battery Restoration 5.14.1 RECONNECT positive and negative output cables to batteIY, and TORQUE bolt assemblies to 160 to 170 in-lbs.
5.14.2 Using a DLRO, MEASURE forward and reverse resistance of battery positive and negative output cable connections. DLRO probes should be placed between approximate top center or side of terminal post and cable lug.
RECORD on Attachment 19.
NOTE At discretion of Maintenance Supervisor, individual cell voltages may be taken using BCT-20CO or a DVOM, during battery equalize charge. If using BCT-2000, LDU cables should remain connected. If NOT using BCT-2000, cables may be disconnected.
5.14.3 If BCT-2000 will NOT be used to obtain data during battery equalizing PERFORM the following:
A.
DISCONNECT cell and intertier sensing clips and REMOVE BCT -2000 test equipment from battery area.
B.
NOTIFY Maintenance Supervisor to release safety tags for 28 Volt battery Charger ONLY.
C.
REQUEST Operations to energize applicable battery charger, GO TO Subsection 5.15.
5.14.4 If BCT-2000 will be used to obtain data during batter equalizing charge, PERFORM the following:
CAUTION DO NOT energize battery charger until BeT ~2000 LOU and DLAD are energized/programmed first.
Minimize time the battery is in a discharged state.
5.14.5 NOTIFY Maintenance Supervisor to release safety tags for 28 Volt Battery Charger ONLY.
Salem Common Page 39 of 96 Rev. 14
sC.MD-ST.28D-0004(Q) 5.14.6 In sequence, ENERGIZE the following BCT-2000 devices:
A.
Laptop Display Unit (LOU)
B.
Data Logging Acquisition Device (DLAD) 5.14.7 DEPRESS FI, Setup Test Parameter screen.
5.14.8 PROGRAM BCT -2000 for 28 volt battery equalize charge lAW 1.
5.14.9 Using PERFORM the following:
A.
DEPRESS F2, Run Load Test.
B.
VERIFY all 13 cell voltages and overall battery voltage is displayed on LDU screen.
C.
DEPRESS FI to start equalize charge cell voltage recordings.
NOTE Charger may go into current limit state when energized. When charger current decreases to approximately 100 amps, charger should be switched to equalize voltage U) mode and charger voltage should be adjusted accordingly.
w (9
z <<
- c D.
REQUEST Nuclear Operations to energize applicable battery charger.
()
o z <<
U)
- J f-<<
f-U) z o U)
W 00::
(9 Z
l.L.
00::
W >
00::
o l.L.
W
..-J OJ U)
Z o CL U)
W 00::
00::
W U)
- J Salem Common Page 40 of 96 Rev. 14
Ul W o z <<
- r::
u o z <<
Ul f--<<
f--
Ul z o Ul W
IX o
Z lL-IX W >
IX o
l.L.
W
---l m
Ul Z o ll.
Ul W
IX IX W
Ul sC.MD-ST.28D-0004(Q) 5.15 Battery Equalize Charge 5.15,1 VERIFY applicable battery room exhaust fan is operating and exhaust air flow is observed.
CAUTION Battery loads can be damaged with higher voltage used during an equalized charge.
Associated bus loads SHOULD BE isolated for equipment protection lAW Step 2.2.
5.15.2 ENSURE battery is energized from its applicable charger.
5.15.3 CONNECT DVOM to monitor battery charger output voltage.
5.15.4 Using second DVOM, or BCT-2000 MEASURE the following voltages.
A.
As Found Battery Terminal Voltage. RECORD on Attachment 19.
B.
As Found Individual Cell Voltages (ICVs), Time, Date, and Initials.
RECORD on Attachment 16, Data Sheet.
5.15.5 DETERMINE equalize voltage by using one of the applicable methods outlined in Attachment 14.
RECORD Battery Equalize Voltage on Attachment 19.
5.15.6 PLACE applicable charger on equalize operation by placing selector switch or timer to EQUALIZE position, or by rotating timer to desired setting to maintain charger on equalize.
CAUTION It is NOT expected cell temperature will rise significantly during equalize charge.
However, cell temperatures should be monitored, especially in beginning when charging current is greatest, to ensure maximum temperature limits are NOT exceeded.
5.15.7 MONITOR Individual Cell Temperatures by installing a temperature measuring device (with "cell stop" attached) into associated cell's flame arrester.
MONITOR approximately six cells equally spaced (as indicated by # sign on 7, Data Sheet).
5.15. 8 VERIFY/ADJUST Battery Charger Voltage or TURN equalize potentiometer (EQ) clockwise to Equalize Voltage detennined in Step 5.15.5.
Salem Common Page 41 of 96 Rev. 14
(/)
llJ (9
Z <<
- r
()
o z <<
(/)
=:J f-<<
f-(/)
z o
(/)
W 0:::
C')
Z 0:::
W >
0:::
o LL.
W
.-.J CO
(/)
Z o (L
Vl LJJ 0:::
0:::
W
(/)
=:J sC.MD-ST.28D-0004(Q) 5.15.9 MEASURE Individual Cell Voltages. RECORD ICVs, Time, Date and Initials on Attachment 16, Data Sheet.
NOTE During equalize charge, cell connections should be monitored to ensure t::!Q hot spots exist (especially in beginning when charging current is highest).
Cell temperatures should be monitored to ensure NO cell exceeds 120 0 F I and the difference between any 2 cell temperatures DOES NOT exceed 5°F.
5.15.10 If any of the following occur, STOP equalize charge and NOTIFY Supervisor:
Any cell temperature exceeds 120°F.
The difference of any 2 cell temperatures exceeds Sop.
Cell connections become hot to touch or smoke is observed.
NOTE Battery terminal voltage and charging current should be monitored and recorded hourly.
The most accurate indicator of return to full charge is a stabilized charging/float current.
5.15.n RECORD hourly battery terminal voltage and charging current readings on Attachment 15, Data Sheet.
5.15.12 After battery has been on equalize charge for 8-12 hours. MEASURE rcvs.
RECORD ICV's Time, Date & Initials on Attachment 16, Data Sheet.
5.15.13 CALCULATE ICV Average by adding all ICVs and dividing by total number of cells (cells jumpered will NOT be counted toward lltotal numberll of cells).
RECORD ICV Average Voltage on Attachment 16, at end of Data Sheet.
Salem Common Page 42 of 96 Rev, 14
UJ W
sC. MD-ST. 28D-0004(Q)
NOTE Equalize charge should NOT continue for more than 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> without monitoring.
5.15.14 COMPARE ICV Average to recorded ICV's and PERFORM the following:
If ANY lev is >0.05 VDC below ICV Average, CONTINUE equalize charge lAW Step 5.15.12 for a number of 8-12 hour periods as detennined by Maintenance Supervisor, then GO TO Step 5.15.15.
If NO ICV measurement is >0.05 VDC below Average ICV, GO TO Step 5.15.17.
5.15.15 For ceU(s) >0.05 VDC below ICV Average, TAKE 3 consecutive ICV measurements, 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> apart. RECORD each hourly ICV on Attachment 16, Data Sheet, along with Time, Date and Initials.
5.15.16 COMPARE the three consecutive ICV measurements for each cell.
If all three ICV measurements are ::;;0.05 VDC of each other, GO TO Step 5.15.17.
If any ICV measurement(s) is >0.05 VDC of each other, CONTINUE equalize charge and GO TO Step 5.15.15.
NOTE
~
Battery can be considered charged when charger current is at zero or when charger
~
current has stabilized I where stabilized is defined as 3 consecutive readings 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> apart o
within 10% of each other. At this point, loads may be reapplied to the bus, as long as
~
bus voltage is equal to or less than maximum allowable voltage specified on
<{ 4. The remainder of procedure will be continued to ensure a "polishing UJ charge" is applied to the battery.
- J I-
<{
t;:;
5.15.17 REVIEW Attachment 16 fOf stabilized charging current.
z Q
UJ W
Do::
(')
z LL Do::
W >
Do::
o LL W
~
CD UJ Z o Cl-UJ W
Do::
Do::
W UJ
- J Salem Common A.
If the last three hourly readings are zero or stabilized (refer to NOTE above), CONTINUE the hourly readings and GO TO Step 5.1S,17.C.
B.
If charging current is NOT zero or stabilized, CONTINUE equalize charge and REPEAT Step 5.15.17.
C.
PLACE applicable battery charger on float charge.
Page 43 of 96 Rev. 14
Ul W
C) z
<r:
I U
o Z
<r:
Ul
- J I-
<r:
I-Ul z o Ul W
00::
C)
Z lL.
00::
W >
00:: o lL.
W
-..J OJ Ul Z o 0...
Ul W
00::
00::
W Ul
- J S C. MD-ST. 28D-0004(Q) 5.15.18 After battery has been on equalize charge DEPRESS F1, Stop Test.
5.15.19 DEPRESS ESC key to return to Load Test Program Menu screen.
5.15.20 COpy Report File from LDU to backup floppy disk as follows:
A.
DEPRESS F5, Utilities, to go to Load Test Program Utilities screen.
B.
DEPRESS F2, Transfer File, to go to Transfer File screen.
C.
INSERT backup floppy disk into LDU.
D.
DEPRESS ENTER key to transfer file from LDU to floppy disk.
E.
DEPRESS enter again.
F.
On LDU screen, VERIFY file was copied.
G.
DEPRESS ESC key to return to Load Test Program Menu screen.
5.15.21 DEENERGIZE all BCT-2000 System devices.
5.15.22 DISCONNECT cell and intertier sensing clips and REMOVE BCT-2000 Test Equipment from battery area. RECORD on Attachment 19.
5.15.23 If battery charger output and battery terminal voltage are equal to or less than maximum allowable voltage specified on Attaclunent 14, NOTIFY OSieRS that any battery loads tagged out in Step 2.2 may be returned to service.
Salem Common Page 44 of 96 Rev. 14
(j) w
(')
z <<
- r:
()
o z <<
(j)
- J f---<<
f---
(j) z o (j) w a:
(')
z lL.
a:
w a:
o lL.
W
-J CD (j)
Z o CL (j) w a:
a:
LLi (j)
- J SC.MD-ST.28D-0OO4(Q) 5.16 Post Service Test Operability DetenninatiQij NOTE Battery may be declared "OPERABLE" following satisfactory completion of Subsection 5.16.
Data collection steps need NOT be performed in exact order as written, provided all required steps are performed and all data is obtained. For example, temperatures, specific gravities and leVs may be obtained simultaneously.
T 5.16.1 MEASURE As Found battery tenninal voltage at battery.
RECORD As Found battery float voltage on Attachment 19.
NOTE Individual Cell Voltage (lCV) minimum Technical Specification Value is ~ 2.13.
5.16.2 MEASURE ICV's for all cells, and RECORD ICV's on Attachment 4B T
Data Table, in lIICV" column.
5.16.3 REMOVE each cell's flame arrester cap and sample tube dust cover.
5.16.4 Cell Temperature Measurements:
NOTE Cell temperatures should be obtained using electronic temperature measurement device with acid resistant probe, if available; otherwise, non~mercury thermometer should be used.
CAUTION tl glass non-mercury thermometer is used, "Stops" should be attached to prevent dropping thermometer into cell.
Salem Common A.
INSERT acid resistant probe or non-mercury thermometer with "Stop" attached into flame arrester filler vent for Cell No. 1.
B.
ALLOW temperature to stabilize.
C.
RECORD stabilized temperature on Attachment 4B Data Table, in "CELL TEMP" column (expected value 65°F-105°F).
D.
REPEAT Steps 5.16.4.A through S.16.4.C for aU cells listed in B, Data Table.
Page 45 of 96 Rev. 14
VI W
C) z
<r:
I ()
o z
<r:
VI
=:>
f-
<r:
f-VI z o VI W
fr::
C)
Z u...
fr::
W >
fr::
o u...
W
---.J ill VI Z o (l
VI W
fr::
fr::
W VI
=:>
SC.MD-ST.28D-0004(Q)
DO NOT add water to any cells at this time.
Immediately report failure of any cell to meet Technical Specification acceptance criteria to Supervisor for evaluation and possible corrective action.
Technical Specifications require level to be > low level mark and ~ 8/32 inch above high level mark.
5.16.5 Electrolyte Level Detennination:
A.
MEASURE distance between bottom of high level mark and electrolyte level for all cells.
B.
NOTIFY OS and Supervisor immediately if level is above high level mark or below low level mark (> 8/32 in. above high level mark or
~ low level mark).
C.
RECORD number of 1/32 in. increments, electrolyte level is below high level mark on Attachment 4B Data Table, in I1CELL LEVEL" column.
If level is > high level mark, indicate the number of 1132 in.
increments electrolyte level is above high level mark by including a positive (+) sign preceding number.
5.16.6 Specific Gravity Measurement:
A.
INSERT hydrometer into sample tube of each cell.
B.
WITHDRAW electrolyte sample into hydrometer.
C.
RETURN electrolyte sample into flame arrester filler vent.
D.
RE-INSERT hydrometer into sample tube.
E.
WITHDRAW second electrolyte sample into hydrometer.
F.
READ specific gravity of sample.
G.
RETURN electrolyte into battery sample tube.
H.
RECORD Measured Specific Gravity on Attachment 4B Data Table, in ItMEAS. S.G." column.
Salem Common Page 46 of 96 Rev. 14
(/)
W o z <<
I U
o Z <<
(/)
- J I-<<
l-(/)
z o
(/)
W 0::::
o Z
LL 0::::
W >
0::::
o LL W
--.J m
(/)
z o 0...
(/)
W 0::::
0::::
W
(/)
- J sC. MD-ST. 28D-0004(Q) 5.16.7 REPLACE each cell's flame arrester cap & sample tube dust cover.
5.16.8 Temperature Compensation Calculation:
A.
CALCULATE average cell temperature by adding cell temperatures recorded on Attachment 4B Data Table and dividing by total number of cell teDlperature rneasureDlents.
B.
RECORD cell average temperature on Attachment 19.
C.
CALCULATE cell specific gravity temperature compensation as follows:
RECORD (+) 0.001 temperature correction value for every 3°F the cell temperature is above 77°F, on Attachment 4B Data Table, in "TEMP CORR" column for each cell.
RECORD (-) 0.001 temperature correction value for every 3°F the cell temperature is below 77°F, on Attachment 4B Data Table, in the "TEMP CORR" column for each cell.
D.
CALCULATE temperature corrected S.G. by adding or subtracting TEMP CORRECTION to/from MEASURED S.G. for all cells.
E.
RECORD tempel'ature corrected S.G. on Attachment 4B Data Table, in "TEMP CORR S.G." column.
NOTE Level compensation is NOT required if:
recorded level is ~ high level mark, or battery charging current is < 2 amps while on float charge
- 5.16.9 Level Compensation Calculation for level corrections factors. (Refer to )
A.
Using recorded "CELL LEVEU. DETERMINE cell level correction factor, for each cell. (Refer to Attachment 3)
B.
RECORD level compensation on Attachment 4B Data Table, in "LEVEL CORR FACT" column.
Salem Common Page 47 of 96 Rev. 14
if)
LLJ C)
Z <<
I u 0 z <<
if)
- )
I-<<
I-if)
Z 0
(j) w cr::
C) z LL cr::
W >
cr::
0 LL W
---.J m
if) z 0
LL if) w cr::
cr::
w if)
- )
S C. MD-ST.28D-0004(Q) 5.16.10 Corrected Specific Gravity Calculation (Tech Spec minimum is ~ 1.190).
A.
CALCULATE corrected specific gravity for each cell by subtracting LEVEL CORRECTION FACTOR from TEMP CORRECTED S.O.
NOTE Individual battery cell corrected specific gravity nominal range should be 1.200-1.220 for fully charged cell. If any cell's corrected specific gravity is < 1.200 QB any cell's corrected specific gravity is > 1.230/ NOTIFY Supervisor and System Manager.
B.
RECORD corrected specific gravity on Attachment 4B Data Table, in "CSG" column.
5.16.11 Average Corrected Specific Gravity Calculation:
Salem Corrunon A.
CALCULATE average corrected specific gravity by adding all corrected specific gravities and dividing by total number of cells (NOT counting jumpered cells, normally 60).
B.
RECORD average corrected specific gravity on Attachment 19.
Page 48 of 96 Rev. 14
V) w o z <<
- r::
u o z <<
V)
I-<<
l-V) z o V)
W 0::
o z l..l-0::
W >
0::
o l..l-W
-l CD V)
Z o 0...
V)
W 0::
0::
W V)
SC,MD-ST.28D-0004(Q)
NOTE Immediately report failure of any cell to meet Technical Specification acceptance criteria to Supervisor for evaluation and possible corrective action.
5.16.12 ENSURE the following Tech Spec Acceptance Criteria have been met for each cell listed in Attachment 4B. INITIAL on Attachment 4B Data Table, in "TECH SPEC CRIT SAT" column of each cell when criteria listed below are met.
Individual cell voltage in "ICV" column is ;;:: 2.13 VDC while under float charge (2.13 or more in ICV column).
NOTE The next Tech Spec acceptance criteria is satisfied when any ICV is ;;:: 2.13 VDC. The bases is as follows:
All original ICV's were < 2.40 VDC.
2.40 VDC - 0.27 VDC = 2.13 VDC.
However, NO cell may be allowed to be < 2.13 VDC (Tech Spec lower limit).
Therefore, as long as ICV's are;;:: 2.13 VDC, Tech Spec for ICV's NOT decreasing by more than 0.27 VDC for original acceptance test is satisfied.
Individual Cell Voltage in IIICV" column has NOT decreased more than 0.27 VDC from value observed during original acceptance test. This criteria is satisfied when ICV is ;;:: 2.13 VDC in IIICV" column based on note above.
Corrected specific gravity in "CORRECTED S.O." column for each cell is ~ 1.190.
Electrolyte level between high and low levels marks.
Salem Common Page 49 of 96 Rev. 14
Vl w
G Z <<
- r::
u o z <<
Vl
- J f-<<
f-Vl z o Vl W
0:::
G Z
lL..
0:::
W >
0:::
o lL..
W
-1 co Vl Z o CL Vl W
0:::
0:::
W Vl
- J sC.MD-ST.28D~0004(Q) 5.16.13 ENSURE the following Non-Tech Spec Acceptance Criteria have been met for each cell listed in Attachment 4B.
A.
NO "recorded" cell temperature is >sop from cell average temperature recorded in Step 5.16.9.B. RECORD on Attachment 19.
NOTE Cells with corrected specific gravity >0.010 below average corrected S.G. should corrected by polishing charge (Subsection 5.17).
B.
NO cell's corrected specific gravity is >0.010 below average corrected S.O. recorded in Step 5.16.11.B. RECORD on Attachment 19.
5.16.14 REVIEW Attaclunent 4B for individual cells that have level> 16/32 in.
below high level mark.
5.16.15 ADD demineralized water to all cells whose electrolyte level is > 16/32 in.
below high level mark AND lITEMP CORRECTED S.G." listed in Step 5.16.8.E of Data Table 4B is 1.218 or greater. FILL cell between 10/32 &
12/32 in. below high level mark.
NOTE Electrolyte in all cells should be at approximately same level, and all cells should require watering at same time. Cell with levels considerably lower than majority of cells, may be indicative of leaks or internal problems, and should be investigated.
If, in judgement of Supervisor, electrolyte level will decrease to > 16/32 in. below high level mark prior to next quarterly inspection, demineralized water may be added to those cells with an electrolyte level between 13/32 and 16/32 in. below high level mark provided those cell's "TEMPERATURE CORRECTED" S.G. is 1.218 or greater.
5.16.16 At Supervisor~s discretion, ADD demineralized water to those cells whose electrolyte level is between 13/32 and 16/32 in. below high level mark AND "TEMP CORR S.G. II listed in column Step 5.16.8.E of Data Table 4B is 1.218 or greater. FILL cell between 10/32 & 12/32 in. below high level mark.
5.16.17 RECORD yes (Y) or no (N) on Attachment 48 Data Table, in "WTR ADD" column for individual cells.
Salem Common Page 50 of 96 Rev. 14
V) w
(')
z <<
I U
o Z <<
(j)
I-<<
l-V) z o V) w ex::
(')
z l.L.
ex::
W >
0::: o l.L.
W
-l m
V) z o (L
V) w ex::
ex::
w V)
SC.MD-ST.28D-0004(Q) 5.16.18 RECORD on Attachment 19 individual cell numbers for all cells from Steps 5.16.15 and 5.16.16 that were NOT filled due to "TEMPERATURE CORRECTED" S.G. being < 1.218 ANQ level ~ 16/32 in. below high level mark.
5.16.19 CONTACT Supervisor for resolution of cells recorded in Step 5.16.18.
5.16.20 If all Tech Spec acceptance criteria of Step 5.16.12 was satisfactory, NOTIFY Operations that battery may be declared operable.
5.17 Post Service Test Polishing Charge NOTE Equalize charge may be terminated any time during performance of Step 5.17.2 at the discretion of Supervisor/System Manager.
5.17.1 PLACE applicable battery charger on equalize.
5.17.2 OBTAIN daily temperature corrected specific gravity measurement for each cell as follows:
A.
REMOVE each cell's flame arrester and sample tube dust cover.
NOTE Cell temperatures should be obtained using electronic temperature measurement device with acid resistant probe, if available; otherwise, a non-mercury thermometer may be used.
CAUTION If a glass non-mercury thermometer is used, "Stops" must be attached to prevent dropping thermometer into cell.
B.
Salem Common OBTAIN cell temperature measurements as follows:
- 1.
INSERT acid resistant probe or non-mercury thermometer with a t1stop" attached into applicable cell's (as indicated on Attachment
- 17) flame arrester filler vent.
Page 51 of 96 Rev. 14
Ul w
C)
Z
<{
I U
o z
<{
Ul
=>
f-<<
f-Ul z o Ul W
0::
C)
Z Lt-0::
W >
0::
o Lt-W
.-J m
Ul Z o 0...
Ul W
0::
0::
W Ul
=>
sC,MD-ST. 28D-0004(Q) 5.17.2 (Cont'd)
The expected stabilized cell temperature is 65 0 F to 120 0 F.
Salem Common
- 2.
ALLOW temperature to stabilize. RECORD stabilized temperatures on Attachment 17, in CELL TEMP column.
C.
OBTAIN specific gravity measurements as follows:
D.
E.
- 1.
INSERT hydrometer into sample tube of cell.
- 2.
WITHDRA W electrolyte sample into hydrometer.
- 3.
RETURN electrolyte sample into flame arrester filler vent.
- 4.
REINSERT hydrometer into sample tube.
- 5.
WITHDRAW a second electrolyte sample into hydrometer.
- 6.
READ specific gravity of sample.
7, RETURN electrolyte sample into flame an-ester filler vent.
RECORD measured specific gravity on Attachment 17, in MEASURED SG column.
REPLACE each cell's flame arrester and sample tube dust cover.
PERFORM specific gravity temperature compensation/correction calculation as follows:
- 1.
ADD all cell temperatures recorded on Attachment 17.
- 2.
DIVIDE sum of cell temperatures by total number of cells measured. RECORD cell temperature average on 9.
Page 52 of 96 Rev. 14
lI) w C) z <<
I U
o Z <<
U)
- J I-<<
l-ll) z o lI)
W 0:::
C)
Z LL.
0::::
W >
0::::
o lL.
s C.MD-ST. 28D-0004(Q) 5.17.2.F (Cont'd)
- 3.
CALCULATE cell specific gravity temperature compensation as follows:
RECORD a (+) 0.001 temperature correction value for every 3°F, average cell temperature is above 77°F, on 7, in TEMP CORR FACTOR column for each cell.
RECORD a (-) 0.001 temperature correction value for every 3°F, average cell temperature is below 77°F, on 7, in TEMP CORR FACTOR column for each cell.
- 4.
CALCULATE temperature corrected specific gravity by adding OR subtracting temperature correction to/from measured specific gravity for all cells. RECORD temperature corrected specific gravity on Attachment 17, TEMP CORR SG column.
F.
REPEAT Steps 5.17.2.A through 5.17.2.EA daily (as determined by supervisor) until temperature corrected specific gravity for each cell is ~ 1.215 or as determined by Supervisor/System Manager.
G.
VERIFY temperature corrected specific gravity for each cell is :::: 1.215 or as determined by Supervisor or System Manager. RECORD on 9.
5.17.3 TERMINATE equalize charge by performing the following:
Salem Common A.
RECORD on Attachment 19 battery Nominal Float Voltage.
[28.9*29.3]
B.
PLACE charger selector switch or timer to FLO A T position, or by turning timer to zero (0) position.
Page 53 of 96 Rev. 14
(j) w
(')
z <<
I U
o Z <<
(j)
- J f-<<
f-(j) z o (j)
W (Y-(')
Z LL (Y-W >
(Y-O LL W
---.J CD (j)
Z o CL (j) lJJ cr::
cr::
w (j)
=J sC.MD-ST.28D-0004(Q) 5.17.3 (Cont'd)
,NOTE Float voltage span is the number of cells connected, multiplied by minimum and maximum Individual Cell Voltage ICV).
When one or more cells are jumpered, reduce battery float voltage to maintain maximum "volt/cell" value while maintaining minimum required battery voltage is 28 VDC.
CAUTION DO NOT set float voltage greater than 29.3 VDe.
C.
ADJUST Battery Charger Output Float Voltage Pot so Battery Terminal Voltage is within Nominal Float Voltage Range recorded in Step 5.17.3.A. RECORD on Attachment 19.
5.17.4 TAKE 3 consecutive ICV measurements of all cells, 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> apart. RECORD each hourly lev on Attachment 18, Data Sheet, along with Time, Date and Initials.
5.17.5 COMPARE the three consecutive ICV measurements for each cell.
If all three ICV measurements (of an individual cell) are SO.05 VDC of each other, GO TO Step 5.17.6.
If any ICV measurement(s) (of an individual cell) is >0.05 VDC of each other, CONTINUE Float Charge and REPEAT Step 7.5.8.
5.17.6 MEASURE As Left Battery Terminal Float Voltage. RECORD on 9.
5.17.7 VERIFY electrolyte level is between high and low level mark on each cell.
RECORD on Attachment 19.
5.17.8 NOTIFY OSICRS equalize charge is complete, and if loads were NOT returned to service in Step 5.15.17. C, they may be return to service at this time.
5.17.9 PERFORM SC.MD-ST.28D-0003(Q), Quarterly Inspection and Preventive Maintenance, in its entirety 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after battery has been restored to float charge.
Salem Common Page 54 of 96 Rev. 14
(.f) w (C)
Z
<{
- r:
o o z
<{
(.f)
~
f-
<{
1-(.f) z o Ul w
(Y.
(C)
Z LL (Y.
W >
ex::
o LL W
-.-J CD
(.f)
Z o Q
Ul w
ex::
ex::
w
(.f)
~
S C. MD-ST.28D-0004(Q) 5.18 Completion Summaty 5.18.1 NOTIFY OSieRS testing is complete.
5.18.2 NOTIFY RO testing is complete.
5.18.3 Independently VERIFY all calculations are correct. RECORD signature of verifier on Attachment 19, Section 4.0. [C0284]
5.18.4 FORWARD backup floppy disk to System Manager.
END OF PROCEDURE SECTION Salem Common Page 55 of 96 Rev. 14
(/)
w
(')
Z
<t I
U o
Z
<t
(/)
~
f-
<t f-(/)
z o
(/)
W 0:::
(')
Z l.L.
0:::
W >
0:::
o l.L.
sC. MD-ST. 28D-0004(Q) 6.0 RECORDS 6.1 Retain the entire procedure.
7.0 REFERENCES
7.1 UFSAR Sections 7.1.1 8.3.2, DC Power 7.2 Technical Specifications - Units 1 & 2 7.2.1 4.8.2.3.2.f, Surveillance Requirement 7.2.2 4..8.2.4.2, Surveillance Requirement 7.2.3 Technical Specification Amendments 249 and 229 7.3 Commitments 7.3.1 C0265 NSO#LER 311/89-015-00 7.3.2 C0284 NSO#LER 272/90-014-00 7.4 PSBPs 7.4.1 121834, C&D Installation and Operation Instructions for Stationary Batteries 7.4.2 316844, Alber Corp. - BCT-2000 Series Operations Manual 7.4.3 301960, C&D Stationary Battery Operating Instructions (LC-33) 7.5 Others 7.5.1 7.5.2 7.5.3 7.5.4 Salem Common IEEE-450~1987, Recommended Practice for Maintenance, Testing and Replacement of Large Lead Storage Batteries for Generating Stations and Substations C&D Battery-Installation and Operating Instructions12-800 Copyright 1986 and 1988 C&D Calculated Short Circuit Current Values, September 1983 C&D Battery Discharge Characteristics Curves - KCR(D842 Rev. 1),
LCR(D-841 Rev. 1) and C&D Data Sheets KCR(12-316) and LCR(12-334)
Page 56 of 96 Rev. 14
(J) w C)
Z
<C I
U o
Z
<C (J)
=:J f-
<C
}-
(J) z o (J)
W ct:
C)
Z l.L.
ct:
W >
ct:
o LL.
W
--I CO (J)
Z o 0....
(J)
W ct:
ct:
W (J)
=:J 7.5.5 Field Directive S-C-E200-EFD-0318, Rev. 0 7.5.6 C&D Batteries Letter dated October 3, 1989 from Graham Walker, Manager Applications Engineering to L. Miceli/R. Chranowski;
Subject:
Correcting Electrolyte Specific Gravity for Level 7.5.7 Design Calculation ES-4.003(Q), Rev. 1 7.5.8 Design Calculation ES~4.004(Q), Rev. 2 7.5.9 UFSAR Change Notice #94-04 7.5.10 UFSAR Change Notice 96-53 7.5.11 Engineering Memo, NE-96-0647, Subject; 125 & 28 VDC Envelope (LOOP/LOCA and SBO) Battery Load Profile 7.5.12 Salem BCG Section 7.2, Loss of DC Power Capabilities 7.5.13 PR 960504082 7.5.14 PR 970829096 7.5.15 PR#971201342 - TSSIP project enhancements 7.5.16 PR#971126143 - TSSIP project enhancements 7.6 Cross-References 7.6.1 SC.MD-CM.ZZ-0009(Q), Battery Equalizing Charge Procedure 7.6.2 NC.NA-AP.ZZ-OOll(Q), Document Management Program 7.6.3 NC.NA-AP.ZZ-0014(Q), Training, Qualification and Certification 7.6.4 NC.NA-AP.ZZ-0015(Q), Safety Tagging Program 7.6.5 NC.NA-AP.ZZ-0038(Q), Chemical Control Program Baking soda (bicarbonate sOdium) CICP# 900-0047 7.6.6 SH.MD-AP.ZZ-0003(Q), Maintenance Department Written Instruction Use Standard Salem Common Page 57 of 96 Rev. 14
(f) w
(:;J z <<
I U
o Z <<
(f)
- l I-<<
I-(f) z o (f)
W 0:::
(:;J Z
LL 0:::
W >
0:::
o LL W
~
CO (f)
Z o Q...
(f)
W 0:::
0:::
W (f)
- l TERMINAL CONNECTION
( +) BATTERY LEADS
(-) BA ITERY LEADS lA-2A 2A*3A 3A-4A 4A-5A 5A-6A 6A-7A
- 7-8 SA-9A 9A-IOA lOA-IIA 11A-12A 12A-13A Salem Common sC. MD-ST. 28D-0004(Q)
ATTACHMENT 1 DISCONNECT LOG DISCONNECTED CONNECTED CONCURRENT DISCONNECTED DUAL CONNECTED INDEPENDENT BY VERIFICATION BY BY VERIFICA nON BY Page 58 of 96 Rev. 14
Vl w
(9 z <<
- r::
o o z <<
Vl
- J f-<<
f-Vl z o Vl w
0:::
(9 Z
lL..
0:::
W >
L.cJ
-1 CD Vl Z o CL Vl LtJ 0:::
0:::
l.cJ (f)
- J
§ NO.
TERM.
BLOCK Salem Common TERMIN.... 1. I.OCATION FROM TERM.
TERM.
NO.
BLOCK.
sC.MD-ST. 28D-0004(Q)
ATTACHMENT 1 (Cont'd)
JUMPER LOG IMS1'ALI.ED REMOVED TO CONCURRENT DUAL INDEPENDENT INSTALLED VERIFICATION RllMOVED VERIFICATION TERM.
BY BY BY BY NO, Page 59 of 96 Rev. 14
Ul W
(')
z <<
I ()
o z <<
Ul
~
I-<<
I-Ul z o Ul W
Dc::
(')
Z LL Dc::
W >
Dc::
o LL sC.MD-ST.28D-0004(Q)
ATTACHMENT 2 PREPARATION OF CONTACT SURFACES FOR ANTI-CORROSION COATING NOTE All electrical surfaces should have clean, bright finish before NO-OX-IO Grease is applied.
A.
NO-OX-ID GREASE (C&D Part No. RG-26)
- 1.
INSPECT surfaces and REMOVE all grease, oil and discoloration with clean cloth and plastic bristle brush.
CAUTION If hot plate DOES NOT have thermostatic control, exercise extreme care to avoid overheating grease and causing a fire. DO NOT use heaters with open flames.
NO-OX*IO grease has minimum flash point of 450°F (232°C)
Salem Common
- 2.
HEAT NO-OX-ID grease to cream like consistency, using infrared lamp or thennostatically controlled hot plate.
- 3.
- 4.
SET temperature somewhere between 160°F (71 °C) to 185°F (85°C) to maintain this consistency.
Use 1 in. paint brush to apply NO-OX-ID grease. APPLY light coat of NO-OX-ID grease to each surface of intercell connectors that has been cleaned.
Page 60 of 96 Rev. 14
(/)
w
(')
z <<
- r::
u o z <<
(/)
- J f--<<
f--
(/)
z o
(/)
W 0:::
(')
Z lI-0:::
W >
0:::
o lI-W
-1 m
(/)
z o 0...
(/)
W 0:::
0:::
W
(/)
- J NO. OF 1/32 11 INCREMENTS 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 Salem Common SC.MD-ST.28D-0004(Q)
ATTACHMENT 3 CELL LEVEL CORRECTION FACTORS CORRECTION NO. OF 1132" CORRECTION FACTOR INCREMENTS FACTOR 0.001 17 0.011 0.001 18 0.012 0.002 19 0.012 0.003 20 0.013 0.003 21 0.014 0.004 22 0.014 0.005 23 0.015 0.005 24 0.016 0.006 25 0.016 0.007 26 0.017 0.007 27 0.018 0.008 28 0.018 0.009 29 0.019 0.009 30 0.020 O.OlD 31 0.020 O.OlD 32 0.021 Page 61 of 96 Rev. 14
USER RESPONSIBLE FOR VERIFYING REVISION, STATUS AND CHANGES sC.MD-ST. 28D-0004(Q)
ATIACHMENT 4A PRE SERVICE TEST BATTERY DATA TABLE STEP 5.6.2 5.6.4.C 5.6.5.C 5.6.6.H 5.1.1.C 5.1.l.E 5.1.2.B 5.1.3.B 5.7.5 CORRECfED SPECIFIC GRAVITY CALCULATION CELL ACCEP ICV (VDq CELL LEVEL NO.
SG (*) TC = TCSG (-) LC = CSG CRIT. SAT CELL NO.
OF 1132'S TEMP (oF)
LEVEL CaRR. S.G.
MEAS. S.G. TEMP CaRR.
TEMP CaRR.
INIT.
CaRR. S.G.
FACT.
1 2
3 4
5 6
7 8
9 10 11 12 13 Enter plus or minus sign in parenthesis from temperature compensation calculation performed in Step 5.7.1.C.
$ TECH SPEC ACCEPTANCE CRITERIA:
L
- 2.
- 3.
- 4.
ICV's ~ 2.13 VDC Present ICV's NOT < 0.27 VDC from original acceptance test (satisfied if_present lev is ~ 2.13 VDC).
Electroly!e revel between high & low marks.
Correctoo specific gravity.:::!: 1.190 Salem Common Page 62 of 96 N/A WTR.
ADD YIN I
Rev. 14
USER RESPONSiBLE FOR VERIFYING REVISION, STATUS AND CHANGES sC.MD-ST.28D-0004(Q}
ATTACHMENT4B POST EQUALIZE BA'ITERY DATA TABLE STEP 5.16.2 5.16.4.C 5.16.S.C 5.16.6.H 5.16.8.C 5.16.8.E 5.16.9.B 5.16.1O.B 5.16.12 CORRECTED SPECIFIC GRAVITY CALCULATION CELL ACCEP ICV (VDq CELL LEVEL NO.
SG (*) TC = TCSG (-) LC== CSG CRIT. SAT CELL NO.
TEMPeF)
OF 1/32'S LEVEL CORR. S.G.
MEAS. S.G. TEMPCORR.
TEMP CaRR.
INIT.
CaRR. S.G.
FACT.
S 1
2 3
4 5
6 7
8 9
10 11 12 13 Enter plus or minus sign in parenthesis from temperature compensation calculation performed in Step S.16.8.C.
$ TECH SPEC ACCEPTANCE CRITERIA:
- 1.
- 2.
- 3.
- 4.
ICV's > 2.13 VDC Present ICV's NOT < 0.27 VDC from original acceptance test (satisfied if.present ICV is ;a: 2.13 VDC).
Electrolyte revel between high & low marks.
Corrected specific gravity ;a: 1.190.
Salem Common Page 63 of 96 5.16.17 WTR.
ADDYJN i
I Rev. 14
(J) w C)
Z
<{
I U
o Z
<{
(J)
- J J-
<{
J-(J) z o (J)
W 0:::
C)
Z LL 0:::
W >
0:::
o LL W
.-J ill (J)
Z o D-(J)
W 0:::
0:::
W (J)
- J S C. MD-ST. 28D-0004(Q)
ATTACHMENT 5 CELL Resistance Data Table UNIT NO. ___ _
BATTERY NO. __
DATE ___ _
Step 5.S.2.A Step 5.S.2.B.3 Step 5.5.5 RESISTANCE (MICRO-OHMS)
ACCEPTANCE CRITERIA BETWEEN A-A AVE NOT CONN.
FWD REV CONN.
SAT SAT INITIAL
... (-)CONN lA-2A 2A-3A 3A-4A 4A*5A 5A-6A 6A*7A
- 7-8 8A~9A 9A-lOA lOA-IIA llA-12A 12A-13A III (+)CONN STEP S.5.3.B BATTERY CONNECTION AVERAGE RESISTANCE
~Ohms NOTE Enter cOlmection resistance of tenninal post and positive or negative field cable. These resistance NOT to be used in BATTERY CONNECTION AVERAGE RESISTANCE calculation.
Enter measurement of cell bank jumper plus connection resistance. These resistance NOT to be used in BATTERY CONNECTION AVERAGE RESISTANCE calculation.
Salem Common Page 64 of 96 Rev. 14
(f) w
(')
z <<
I ()
o z <<
(f)
- J f-<<
f-(f) z o U)
W 0:::
(')
Z LL 0:::
W >
0:::
o LL W
-l CD (f)
Z o 0...
(f)
W 0:::
0:::
W (f)
- J sC.MD-ST. 28D-0004(Q)
ATTACHMENT 5 (Continued)
Table 1 - Cell Resistance Acceptance Criteria 28V BATTERIES CONNECTION TYPE 120% AVE BASELINE MAXIMUM ALLOWABLE Square Four Post:
- $;31 lL0hms
~50 ",ohms (A~A)
Field Cable:
- =;;8 jkohms s20 jkoluns
( + )CONN, (-)CONN Jumper Cable + Connections:
s; 135 ",ohms s: 150 ",ohms NO. 7-8 Salem Common Page 65 of 96 Rev. 14
(f) w
(')
Z
<{
- r::
()
o z
<{
(f)
- =l f-
<{
f-(f) z o (f)
W 0:::
(')
Z lL.
0:::
W >
0:::
o lL.
W
-1 CO (f)
Z o 0...
(f)
W 0:::
0:::
W (f)
- =l sC. MD-ST, 28D-0004(Q)
ATTACHMENT 6 BCT-2000 SERIES INTERCONNECTION DIAGRAM (4)0 SENSE LEAD CABLE ASS'Y o
CONTROL UNIT J1U J17 JU CONTINUOUS Jl LOAD UNIT J12 (Sid. Allier Moo"l)
JIJ J15 ONLY CABLE EXTENDER PORT 1-32 WILL BE USED FOR 13 CELL BATTERY SENSE LEAD CABLE CONNECTIONS Salem Common Page 66 of 96 Rev. 14
i*
(J) l1.J C)
Z <<
I U
o Z <<
(J)
- J J-<<
J-(J) z o (J) l.LJ 0:::
C)
Z LL 0:::
l1J >
0::: o LL l.J..J
-I m
if)
Z o Cl..
(J)
W 0:::
0:::
LeJ (J)
- J sC. MD-ST. 28D-0004(Q)
ATTACHMENT 7 DEFINING BCT*2000 SERIES SCREENS Load Test Program Menu - The Main Menu Load Test Program Menut also known as Main Menu is where user begins all operations. This is point where user makes selection to use subsequent Menu Screens. Whenever a user finishes with a screen they will revert back to Load Test Program Menu (Main Menu). If user wants to exit to BCT-2000 program, hit F6 (Function Key) to exit to DOS and DOS SHELL program. To return from DOS to program, tum computer off, and then tum back on or select Exit from DOS SHELL and then depress ENTER. If you exited DOS SHELL to C: >, type in CD\\ALBERt depress ENTER, then type BCT -2000 and depress ENTER.
Each time a test is performed or system is used fOf data-logging, it is necessary to go through this screen. Set-Up Test Parameter screen allows user to input information on battery being tested for report purposes. In addition, this screen is where user will set all parameters such as Cell Alarms, Voltage Alarms, Number of Cells Tested, Intertier Connections and Test Program. THIS SCREEN GIVES SYSTEM ALL ITS INSTRUCTIONS ON HOW TO OPERATE TEST.
Run Load Test Display Screen F2 User will spend majority of test time in this screen. This screen provides all relative information pertaining to battery during testing in a real time mode. All individual cells are in a bar graph format enabling user to visually scan all individual cell voltages (ICVs) without having to interpolate columns of numbers. In addition to ICVs, Overall Volts, Current, KW and Capacity, Test Parameters, Cell Faults (alarms), Step Number(s) and Total Run Time are also displayed. This screen also allows user to toggle between rcvs screen and Intertier Voltage screen.
Load Test Report Screen F3 This screen is used when a report is required from a previously completed test. This screen gives option of listing Test Files, how report will be outputted and type of report wanted. This screen is the ONLY screen that will provide user with a final report or option of transferring test data file to a floppy disk for analysis using another commercial software package or for report printout using BCT-2000 software on a PC. Printout of completed test file will be performed by System Engineer or Maintenance Supervisor.
Salem Common Page 67 of 96 Rev. 14
(J")
w
(')
z <<
- r::
u o z <<
(J")
- J f-<<
f-(J")
z o (J")
W 0:::
(')
z 1..1...
0:::
LLI >
0::: o LL W
~
CD (J")
Z o lL (J")
W 0:::
0:::
W (J")
- J S C.MD-ST. 28D-0004(Q)
ATTACHMENT 7 (Cont'd)
Hardware Diagnostics Screen E4 Hardware Diagnostic Screen basically moves user to a second Sub-Menu labeled Hardware Diagnostic menu. This menu allows user to calibrate system (password protected), perform diagnostic on BCT-2000, 170 Control Board or to perform diagnostics on Load Control Board for use with Alber Optional Load Banks. This screen is primarily used when calibration of system is required or if a problem is encountered with unit. Diagnostic function is a tool to help user perfonn self checks on system. Use of this screen will void BCT-2000 calibration and test results. DO NOT USE THIS EUNCTION.
Utilities F5 This allows user to go to a sub-menu where configuration can be Backed-up to Transfer Files.
Follow procedure steps when asked to save files to a floppy disk.
Save Configuration F6 This allows for SAVING of all changed parameters, before exiting program. Failure to SAVE CONFIGURATION will result in loss of set-up screen parameters.
Exit to DQS F7 Load test program tenninates with F6 keystroke, causing all parameters to be lost unless otherwise saved before exiting. This then allows user to use Laptop Display unit for other programs. DO NOT USE THIS FUNCTION.
Entering c.orrect Time and Date At Load Test Program Menu screen, DEPRESS ESC to exit to DOS (when "EXIT PROGRAM? It appears select "Y"). At MS-DOS shell, tab to Main Command Prompt and DEPRESS ENTER.
At C:\\> TYPE "TIME" and DEPRESS ENTER. ENTER new time if applicable and DEPRESS ENTER.
At C:\\> TYPE "DATE" and DEPRESS ENTER. ENTER new date if applicable and DEPRESS ENTER.
At C:\\ > TYPE "CD\\ALBER" and DEPRESS ENTER.
At C:\\ALBER TYPE "BCT-2000" and DEPRESS ENTER to return to Load Test Program Menu.
DEPRESS Fl to Setup Test Parameters.
Salem Common Page 68 of 96 Rev. 14
(/)
w Cl z
<C I
U o z
<C
(/)
=>
f-
<C f-(/)
z o
(/)
W et::
C)
Z lL.
et::
W >
et:: o lL.
W
-l OJ
(/)
Z o 0....
(/)
W et::
et::
W
(/)
=>
r--l sC.MD-ST. 28D-0004(Q)
ATTACHMENT 8 BCT-2000 PROGRAMMING SERVICE TEST (TYPICAL)
BATTERV RI!CORD T... t Loo.t'on SALEM U1 Teat FII.
.,.... OEl10&3 a_ttelfY eD
" aTR"t")()()OOOOo T_rnp.....,*ur.-
077~"
"_U-rv Mflill.. Model C"'O KCA.:t1 Rated Th"l"l.
00'00:00 In.-tall.tlan !Oat.
O8/glI/lII:II
'reST SETUP r--- AI.nn 1..".1.
Pr1nt.I'TI.... I"' *.-vel, 00,00 I Cell.
ov Voltaa_ "'ol.rttyt NOJllMAL W.rnlnlill 11.,..10 c)V a:a.40V e..::' -C.'n.~ _"n ** ~
....... down 1.000 OV :t:t.80V Numb... ~:.u. TOo Sa."
TaM P...... ~....
st.p Time L.,.,.d Type r-Int_rT'.r C;::::onn_atlon_
001 00101100 017.
AMP.
IT, 007-00.
ITa 000-000 002 00 ** 0.00 0"7' ITa 000-000 ITe 000-000 tl1.00:00 01a3 IT:J 000-00.
IT?
000-000 0tI4 HH:MM,a. 0000 IT..
000-000 lTD 000-000 HELP WINDOW Typ. the name of til. to.to.... ".... re_ult *. Thlolo "Ie I *** t.r u ** cI to Iit-"_", ** t.... r.porhl~
[II ESC OJ I II p D-I I I I II P
..(J.. I I I I II + I -
I I 1 Ta M... ln M..,"U
.. rQg........ UP lP.. oa.,,*..... Dcn~¥N Qh.ng_ V_ly **
NOTE Setup Test Parameter screen is split into three main blocks as follows:
Center Block - Test Setup - This block is used to give BCT-2000 its complete instructions on in regards to service test.
Top Block - Battery Record - This block is used for information applicable to battery ID/test location. Much of this information is used for header of test report. Use as much detail, as required.
Bottom Block - Help Window - During all programming, bottom block acts as an on screen HELP WINDOW. This will provide instructions as to what system is requiring at that cursor location.
There are a few different ways to move around Setup Test Parameter screen. When moving to a specific block, TAB key can be used. When inside a block, UP and DOWN ARROW keys located on numeric keypad allow user to move to desired location inside that block.
Salem Common Page 69 of 96 Rev. 14
(J) w
(')
z <<
- r
()
o z <<
(J)
- J I-<<
I-(J) z o (J)
W 0::
(')
Z lL.
ct::
W >
ct::
o lL.
W
---1 Q)
(J) z o CL (J)
W ct::
ct::
W (J)
- J sC.MD-ST. 28D-0004(Q)
ATTACHMENT 8 (Coned)
CAUTION In all cases it is necessary for user to hit ENTER key once any data has been inputted.
Failure to execute ENTER key will cause reading to change back to its original value.
A.
BATTERY RECORD BLOCK
- 1.
Test Location - TYPE [ SALEM STATION Ul ] OR [ SALEM STATION U2 ], as applicable for test location (maximum of 18 characters). DEPRESS ENTER key.
- 2.
Battery ID - TYPE [ applicable battery ID and work order number from Table 1 ] for 28 Volt Battery being tested (maximum of 18 characters). DEPRESS ENTER key.
TABLE 1 BATTERY IDs BATTERY IDs lA-28V 1 BTRYI AD EXXXXXXXXX 2A-28V 2BTRY2ADEXXXXXXXXX IBTRYIBDEXXXXXXXXX 2BTRY2BDEXXXXXXXXX
- 3.
Battery MFG. & Model - TYPE [C&D KCR-21 ] for Battery MFG. & Model (maximum of 18 charact:ers). DEPRESS ENTER key.
- 4.
Installation Date - TYPE [ applicable installation date from Table 2 ] date battery was installed (MM/DD/YY). DEPRESS ENTER key.
TABLE 2 UNIT 1 UNIT 2 Battery ID Installation Date Battery ID Installation Date IBTRYIADE 09/28/99 2BTRY2ADE 04/27/99 1BTRYIBDE 10/04/99 2BTRY2BDE 04/29/99 Salem Common Page 70 of 96 Rev. 14
(f) w Cl z <<
I o o z <<
(f)
J-<<
J-(f) z o (f)
W 00::
Cl Z
l.L.
00::
W >
00::
o l.L.
W
.--J CO (f)
Z o CL (f)
W 00::
00::
W (f) sC.
MD~ST. 28D-0004(Q)
ATTACHMENT 8 (Conttd)
- 5.
Test File - TYPE name of data file (maximum 8 characters, particular battery ID followed by present month and date test is run, e.g. lADE1093). Space and punctuation marks are NOT allowed in this field. DEPRESS ENTER key.
- 6.
Temperature - TYPE [ 77 ] for average electrolyte fahrenheit temperature.
Temperature correction is NOT required for a Profile/Multi-Step Service Test.
DEPRESS ENTER key.
- 7.
Fahrenheit or Celsius - Average electrolyte temperature should be indicated in fahrenheit. USE numerical keyboard's [+1-] key to change from celsius to fahrenheit, as required. DEPRESS ENTER key.
- 8.
Rated Time - Rated Time field (HH:MM:SS) asks for theoretical length of time test is being performed. This is important for On-Line Capacity calculation (visible in Load Test Display Window) that will be required during a single step capacity test (five year discharge test). It is NOT required for a profile/multi-step/Service Test. DEPRESS ENTER key.
B.
lEST SEIUP BLOCK NOTE Test Setup Block - Test Setup block includes sub-blocks that allow user to program Alarm Levels (Warning.. Cells, Shutdown - Cells, Overall Volts (OV) - Warning and Overall Volts (OV) - Shutdown), Test Program, Intertier Connections, Number of Cells, Voltage Polarity and Printer Time Interval.
Warning-Cells Field - If any cell voltage falls below 1.750 volts, during an actual test, a Warning-Cell alarm will signal user. Failing cell will be listed in ALARM column on Load Display Screen and bar graph on Load Display Screen will shade to a different contrast!
or from green to yellow. Run Load Test Display Screen F2 may be referred to as required.
Shutdown~Cells Field - If any cell voltage falls below 1.000 volts, during an actual test, BCT*2000 will automatically SHUTDOWN test.
OV-Warning Field - If battery overall voltage falls below 23.4 volts, during an actual test, a OV-WARNING alarm will signal user that battery system will be approaching shutdown shortly and OV field will be boxed.
OV-Shutdown Field - If battery overall voltage falls below 22.8 volts, during an actual test, BCT-2000 will automatically SHUTDOWN test.
Salem Common Page 71 of 96 Rev, 14
IJ) w C) z
<r:
- r::
u o z
<r:
IJ)
- =J I-
<r:
I-IJ) z o IJ)
W 0:::
C)
Z lI-0:::
W >
0:::
o lI-w ill IJ)
Z o 0...
IJ)
W 0:::
0:::
W IJ)
- =J sC.MD-ST. 28D-0004(Q)
ATTACHMENT 8 (Cont'd)
- 1.
Alarm Levels - Alarm Level block is broken into four separate fields. TYPE alarm level data as follows:
- a.
Warning - Cells - TYPE [ 1.750] in this field. DEPRESS ENTER key.
- b.
Shut-Down Cells - TYPE [ 1.000 ] in this field. DEPRESS ENTER key.
- c.
OV - Warning - TYPE [ 23.4 J in this field. DEPRESS ENTER key.
- d.
OV - Shutdown - TYPE [ 22.8 ] in this field. DEPRESS ENTER key.
NOTE Table 3 indicates test discharge rates (Step currents and times) to be inputted in "Test Program" block for applicable 28 VDC battery,
- 2.
Test Program - Test Program block is area user programs system for type of discharge to perform, length of discharge and load to be applied. Each Step is programmed individually with a maximum number of 99 Steps. PGUP/PGDN keys may be used to move step blocks. If cursor is NOT on Step 001, time field, USE PGUP/PGDN Arrow key to move to this field and PERFORM the following:
- a.
Step 001, Time Field - TYPE [ 00:01:00], DEPRESS ENTER key.
TABLE 3 LOAD FIELD AMPS Battery ID Step 001 Step 002 Step 003 Step 004 Step 005 step 006 Step 007 IBTRYIADE 151 137 134 128 105 107 0
IBTRYIBDE 166 173 156 121 83 82 0
2BTRY2ADE 161 130 127 125 106 106 0
2BTRY2BDE 169 176 167 126 83 84 0
Salem Common Page 72 of 96 Rev. 14
(()
w Cl z <<
I U
o Z <<
(()
- J I-<<
I-(()
z o
(()
W 0:::
Cl Z
u...
0:::
W >
0::: o u...
W
-1 CD
(()
Z o (L
(()
W 0:::
0:::
W
(()
- J Se.MD~ST. 28D-0004(Q)
ATTACHMENT 8 (Cont'd)
NOTE Load Field is location where amount of current is to be inputted for a test step.
- b.
Step 001, Load Field - TYPE [ applicable step current from Table 3 ]
DEPRESS ENTER key.
NOTE After Step 001 is completed, TYPE FIELD (KW/AMPSl is only field that CANNOT be changed.
- c.
Type Field - SELECT AMPS using (u) key to toggle field. DEPRESS ENTER key.
- d.
Step 002, Time Field - TYPE [ 00:29:00 ]. DEPRESS ENTER key.
- e.
Step 002, Load Field - TYPE [ applicable step current from Table 3 ].
DEPRESS ENTER key.
- f.
Step 003, Time Field - TYPE [ 00:30:00]. DEPRESS ENTER key.
- g.
- h.
- i.
- j.
- k.
- 1.
- m.
- n.
- o.
Salem Common Step 003, wad Field - TYPE [ applicable step current from Table 3 ].
DEPRESS ENTER key.
Step 004, Time Field - TYPE [ 01:00:00]. DEPRESS ENTER key.
Step 004, Load Field - TYPE [ applicable step current from Table 3 ].
DEPRESS ENTER key.
Step 005, Time Field - TYPE [ 01:59:00]. DEPRESS ENTER key.
Step 005, Load Field - TYPE [ applicable step current from Table 3 ].
DEPRESS ENTER key.
Step 006, Time Field - TYPE [00:01:00]. DEPRESS ENTER key.
Step 006, Load Field - TYPE [ applicable step current from Table 3 J.
DEPRESS ENTER key.
Step 007, Time Field - TYPE [ 00:10:00]. DEPRESS ENTER key.
Step 007, Load Field - TYPE [ applicable step current from Table 3 ].
DEPRESS ENTER key.
Page 73 of 96 Rev. 14
(f)
LLi C)
Z <<
I u o z <<
(/)
=:>
I-<<,-
(f) z o (f)
W 0::::
C)
Z LL 0::::
W >
0:::: o LL W
_1 m
(f)
Z o (L
(f)
W 0::::
0::::
W (f)
- =)
sC.MD-ST. 28D-0004(Q)
ATTACHMENT 8 (Cont'd)
- 3.
Printer Time Interval - This field allows user to input print interval (MM:SS) for connected on-line printer during test. Since BCT-2000 printer will NOT be used in field, TYPE [ 00:00]. DEPRESS ENTER key.
- 4.
Voltage Polarity - This field allows user to switch between NORMAL and REVERSED. NORMAL is used when field cable is connected to positive terminal of Cell #1. REVERSE is used when field cable is connected to positive terminal of Cell #13. Using (+) key, TOGGLE to REVERSED. DEPRESS ENTER key.
- 5.
Mode - SELECT Single String using numerical keyboard's (-) key. DEPRESS ENTER key.
- 6.
Number of Cells to Scan - TYPE [ 13]. DEPRESS ENTER key.
- 7.
Intertier Connections - This field allows user to input cells to which intertier cable jumpers are connected to. At IT-I field, USE numerical keyboard's +/- keys to change to select cells 007 - 008. DEPRESS ENTER key.
- 8.
DEPRESS ESC key to return to Load Test Program Menu.
- 9.
DEPRESS F6 and Y (yes) key to save configuration.
- 10.
RETURN to Step 5.9.6.
Salem Common Page 74 of 96 Rev. 14
USER RESPONSIBLE FOR VERIFYING REVISION, STATUS AND CHANGES ATTACHMENT 9 BCT-2000 SENSE LEAD CONNECTION DIAGRAM SENSE LEAD.JUNCTION POtNTS
'riM. s.1I'NI. "04 "......."..... 10 __ -"'7 i~-;;';'~
t~1"r.,!!:,:f5!~~~I~*=:.. :--::*~=*::;n
.......,ang; ftlt. Hl9h ** t He. S....... l_ad (lICK'
- ~~.. C
- :*':;;"'S :~b!'. -:.!. t':.~.::~t! :,.. a~
s.~.....,.t d-ft ""_ htt.ty...,nd_r t **
,~
(+) POS.-=:::;:::;====~
LOAO II s.n ** t...CdO~
SENSE LEAD CABLES To beT 2.00Q Control u~i~o 1(1iCtond.,. Cob'... Conn.. ct t-o Conn.c:;fo,.. lab_'.d CELLS t -32, CEl..l..S 33-6"..te-._i.o.
(-) NEG.
LOAD sC.MD-ST.28D-0004(Q)
V/IT SENSE LEAD CABLE To -8CT-2000 CBn1roi U *..tt Y10 Ext_noer Cabt.. Conn..ct to C'9-nn.ctor lctb.l.d SY5XEW.
£-cac:tc C.II *.- c.on... od OVERALL.
~B~i."t:t p~~~Ti~)c:!"~'f1:'*
.n-.. IMMh "Ctlnt.
t_.am. ~1I\\t.
SO"_. ~d ov-ONLY EXTENDER CABLE PORTS 1-32 WILL BE USED FOR 13 CELL BATTERY SENSE LEAD CABLE CONNECTIONS Salem Common Page 75 of 96 Rev. 14
S C. MD-ST. 28D-0004(Q)
ATTACHMENT 10 TYPICAL LOAD TEST DISPLAY 11 :55:59 LOAD TEST DISPLAY 8/24/93 CELLI # 13 = + 1.865 OV= 24.2 AMPS= 0147 KW= 35.6 CAPACITY=
+ 1.90 0..
ALARM
+ 1.840 I-l-
+ 1.780 J-
+ 1.900 )-
+ 1.840 1-
+ 1.780 1-IF51Toggie Setup lesci Stop Test IF61View Interior STEP: 002 TIME: 00:58:00 LOAD: 0147 A
TOTAL RUNTIME= 00:2:00 IF11 Pause Test IF11 Manual Control TEST STARTED Vl W
C) z
<t I
u FOR 28 VOLT BATTERY SERVICE TEST ONLY 13 BARS (CELLS) WILL BE SHOWN ON
~
RUN LOAD TEST SCREEN
<t Vl
- l f-
<t f-Vl z o
~
W 0:::
C)
Z LL 0:::
W >
0::: o LL W
....J co Vl z o 0..
Vl W
0:::
0:::
W Vl
- l Salem Common Page 76 of 96 Rev. 14
UI w
()
z <<
- r::
u o z <<
UI
- J I-<<
I-UI z o UI W
et::
()
Z lL.
et::
LLi >
et::
o lL.
W
_J en UI Z o (l.
UI w
0:::
et::
W UI
- J sC.MD-ST. 28D-0004(Q) 1 BCT-2000 PROGRAMMING EQUALIZE CHARGE NOTE Setup Test Parameter screen, illustrated in Attachment 3, is split into three main blocks as follows:
Top Block (Battery Record) ~ This block is used for information applicable to battery ID/test location. Much of this information is used for header of test report. Use as much detail, as required.
Center Block (Test Setup) - This block is used to give BCT-2000 its complete instructions in regards to Performance Discharge Test.
Bottom Block (Help Window) - During all programming, bottom block acts as an on screen HELP WINDOW. This will provide instructions as to what system is requiring at that cursor location.
There are a few different ways to move around Setup Test Parameter screen. When moving to a specific block, the TAB key can be used. When inside a block, UP and DOWN ARROW keys, located on the numeric keypad, allow user to move to desired location inside that block.
CAUTIQ",
In all cases it is necessary for user to hit ENTER key once any data has been inputted.
Failure to execute ENTER key will cause reading to change back to its original value.
A.
BATTERY RECORD BLOCK
- 1.
" 2.
Test Location - TYPE [SALEM STATION V1 ].oR [SALEM STATION V2], as applicable for test location (maximum of 18 characters). DEPRESS ENTER key.
Battery ID - TYPE [ applicable battery ID and work order number from Table 1 ] for 28 Volt Battery being tested (maximum of 18 characters). DEPRESS ENTER key.
Salem Common Page 77 of 96 Rev. 14
V) w C) z
<C I
U o
Z
<C V)
~
I-
<C l-V) z o V)
W cr::
C) z l.L cr::
W >
cr::
o l.L W
---1 CD V)
Z o (L
V)
W cr::
cr::
w V)
~
Se.MD-ST.28D-0004(Q) 1 (Cont'd)
TABLE 1 BATTERY IDs BATTERY IDs IA-28V 1 BTRYIADEXXXXXXXXX 2A-28V 2BTRY2ADEXXXXXXXXX IB-28V IBTRY1 BDEXXXXXXXXX 2B-28V 2BTRY2BDEXXXXXXXXX
- 3.
Battery MFG. & Model - TYPE [ C&D KCR-21 ] for Battery MFG. & Model (maximum of 18 characters). DEPRESS ENTER key.
- 4.
Installation Date - TYPE [ applicable installation date from Table 2 ] date battery was installed (MM/DD/YY). DEPRESS ENTER key.
TABLE 2 UNIT 1 UNIT 2 Battery ID Installation Date Battery ID Installation Date IBTRYIADE 09/28/99 2BTRY2ADE 04/27/99 IBTRYIBDE 10/04/99 2BTRY2BDE 04/29/99
- 5.
- 6.
- 7.
- 8.
Test File - TYPE name of data file (maximum 8 characters, particular battery ID followed by "EQUL" for equalize charge (e.g. 1ADEEQUL). Space and punctuation marks are NOT allowed in this field. DEPRESS ENTER key.
Temperature - TYPE [ 77 ] for average electrolyte fahrenheit temperature.
Temperature correction is NOT required for a Profile/Multi-Step Service Test.
DEPRESS ENTER key.
Fahrenheit or Celsius - Average electrolyte temperature should be indicated in fahrenheit. USE numerical keyboard's [+1-] key to change from celsius to fahrenheit, as required. DEPRESS ENTER key.
Rated Time - Time battery will be on equalize charged and LDU will record/display rcvs. TYPE [ 00;00;00 ] in this field. Field will default to HH:MM:SS when ENTER key is depressed. DEPRESS ENTER key.
Salem Common Page 78 of 96 Rev. 14
Ui w
C) z <<
- r::
u o z <<
Ui I-<<
I-Ui z o Ui W
0:::
C)
Z u...
0:::
W >
0:::
o LL W
...J m
Ui Z o Il.
Ui W
0:::
0:::
w Ui
- J sC. MD-ST. 28D-0004(Q) 1 (Cont'd)
B.
TEST SETUP BLOCK NOTE Test Setup Block - Test Setup block includes sub-blocks that allow user to program Alarm Levels (Warning - Cells, Shutdown - Cells, Overall Volts (OV) - Warning and Overall Volts (OV) - Shutdown), Test Program, Intertier Connections, Number of Cells, Voltage Polarity and Printer Time Interval.
Warning-Cells Field - If any cell voltage falls below 1.750 volts, during an actual test, a Warning-Cell alarm will signal user. Failing cell will be listed in ALARM column on Load Display Screen and bar graph on Load Display Screen will shade to a different contrastl or from green to yellow. Run Load Test Display Screen F2 may be referred to as required.
Shutdown-Cells Field - If any cell voltage falls below 1.000 volts, during an actual test, BCT-2000 will automatically SHUTDOWN test.
OV-Warning Field - If battery overall voltage falls below 23.4 VDC during an actual test, a OV-WARNING alarm will signal user that battery system will be approaching shutdown shortly and OV field will be boxed.
OV-Shutdown Field ~ If battery overall voltage falls below 22.8 volts, during an actual test, BCT-2000 will automatically SHUTDOWN test.
- 1.
Alarm Levels - Alann Level block is broken into four separate fields. TYPE alarm level data as follows:
- a.
- b.
- c.
- d.
Salem Common Warning - Cells - TYPE [ 1.750] in thls field. DEPRESS ENTER key.
Shut-Down Cells - TYPE [ 1.000 ] in this field. DEPRESS ENTER key.
OV - Warning - TYPE [23.4] in this field. DEPRESS ENTER key.
OV - Shutdown - TYPE [22.8 ] in this field. DEPRESS ENTER key.
Page 79 of 96 Rev. 14
VI l.w
~
Z <<
I u Se. MD-ST. 28D~0004(Q) 1 (Cont'd)
NOTE The following indicates EQUALIZE CHARGE step currents and times to be inputted in "Test Program" block for 28 VDC battery.
- 2.
Test Program - Test Program block is area user programs system for type of equalization to perform (length of equalize charging). Each Step is programmed individually with a maximum number of 99 Steps. PGUP!PGDN keys may be used to move step blocks. If cursor is NOT on Step 001, time field, USE PGUP/PGDN Arrow key to move to this field and PERFORM the following:
- a.
Step 001, Time Field - TYPE [ 23:00:00 ]. DEPRESS ENTER key.
NOTE Load Field is location where amount of current is to be inputted for a test step.
- b.
Step 001, Load Field - TYPE [ 0000] DEPRESS ENTER key.
- c.
Type Field - SELECT AMPS using (-) key to toggle field. DEPRESS ENTER key.
NOTE
~
After Step 001 is completed, TYPE FIELD (KW/AMPS) is only field that CANNOT be changed.
VI
- J f-<<
f-VI z o VI W
0:::
~
Z L.1-0:::
LLi >
0:::
o l.!-
llJ
-.J m
VI z o CL VI W
0:::
0:::
LLJ VI
- J
- d.
- e.
- f.
- g.
- h.
Salem Common Step 002, Time Field - TYPE [ 23:00:00]. DEPRESS ENTER key, Step 002, Load Field ~ TYPE [ 0000]. DEPRESS ENTER key.
Step 003, Time Field - TYPE [ 23:00:00 J. DEPRESS ENTER key.
Step 003, Load Field - TYPE [0000]. DEPRESS ENTER key.
DEPRESS ENTER key twice.
Page 80 of 96 Rev. 14
if) w
<.::> z
<t
- r:
()
o z
<t if)
- J f-<t f-if) z o
'£)
w cr::
<.::> z lL..
cr::
W >
cr::
o lL..
W
--I OJ if)
Z o 0..
if)
W cr::
cr::
w if)
- J sC. MD-ST.28D-0004(Q)
ATTACHMENT 11 (Cont'd)
- 3.
Printer Time Interval ~ This field allows user to input print interval (MM:SS) for connected on-line printer during test. Since BCT-2000 printer will NOT be used in field, TYPE [ 00:00]. DEPRESS ENTER key.
- 4.
Voltage Polarity - This field allows user to swit.ch between NORMAL and REVERSED. NORMAL is used when field cable is connected to positive terminal of Cell #1. REVERSE is used when field cable is cOImected to positive tenninal of Cell
- 13. Using (+) key, TOGGLE to REVERSED. DEPRESS ENTER key.
- 5.
Mode - SELECT Single String using numerical keyboard's (-) key. DEPRESS ENTER key.
- 6.
Number of Cells to Scan - TYPE [ 13]. DEPRESS ENTER key.
- 7.
Intertier Connections - This field allows user to input cells to which intertier cable jumpers are connected to. At IT.;1 field, USE numerical keyboard's +/- keys to change to select cells 007 - 008. DEPRESS ENTER key.
- 8.
DEPRESS ESC key to return to Load Test Program Menu.
- 9.
DEPRESS F6 and Y (yes) key to save configuration.
- 7.
RETURN to Step 5.8.4.
Salem Common Page 81 of 96 Rev. 14
Vl w
(')
z <<
- r::
o o z <<
Vl
- J r-<<
f-Vl z o Vl w
ex::
(')
z ll-n::
W >
n::
o lI-W
-I CD Vl Z o D....
Vl W
n::
n::
w Vl
- J S C. MD-ST. 28D-0004(Q)
ATTACHMENT 12 BATTERY CONNECTION TORQUE REQUIREMENTS BOLT ASSEMBLY SIZE INITIAL TORQUE SUBSEQUENT in-Ibs TORQUE in-lbs 114-20 stud w/cast lead brass 67 to 70 57 to 60 inserted lead nut 5/16-18 brass stud w/inserted 105 to 110 95 to 100 lead nuts 5/16-18 stainless steel bolt, 152 to 160 119 to 125 washers, nuts Salem Common Page 82 of 96 Rev. 14
(/)
w C) z <<
I U
o Z <<
(/)
- J f-<<
f-(/)
z o
(/)
W 0:::
C)
Z L!-
0:::
w 0:::
o L!-
W
--I m
(/)
z o 0...
(/)
W 0:::
0:::
W
(/)
- J sC.MD-ST. 28D-0004(Q)
ATTACHMENT 13 ELECTROLYTE TEMPERATURE CF) DATA SHEET NOTE The following table list cells which require temperature data to be taken during Service Test (thermometers to be installed rior to test).
CAUTION Monitor cells for excessive temperatures (~1200F) during Service Test.
TA.H"~: 1 INDIVIDUAL CELL TEMPERATURE DATA SHEET (STEPS 5.9.1 AND 5.12.15)
CELL NO 2
8 T:;:;:;O T+15 T+30 T+45 T+60 T+75 T+90 T+I05 T+120 T+135 T+150 T+165 T+180 T+195 T+210 T+225 T+240 Salem Common Page 83 of 96 Rev. 14
(f) w C..? z <<
I U
o Z <<
(f)
- l I-<<
I-(f) z o (f)
W cr::
C..?
Z LL cr::
W >
cr::
o LL W
-.-J m
W z o 0...
(f)
W cr::
cr::
w (f)
- l sC.MD-ST. 28D-0004(Q)
ATTACHMENT 14 EQUALIZE VOLTAGE DETERMINATION I.
Method 1 - NO Cells bypassed and ALL battery loads cleared and tagged. USE equalize voltage as close as possible to top of span (e.g., 30.9 VDC).
TABLE 1 BATTERY NUMBER OF BATTERY NOMINAL MAXIMUM (VDC)
CELLS EQUALIZE EQUALIZE EQUALIZE VOLTAGE VOLTAGE PER VOLTAGE PER (VDC)
CELL (VDC)
CELL (VDC) 28 Unit 1(2) 13 30.3 to 30.9 2.33 to 2.38 2.60 II.
Method 2 - NO cells bypassed and battery loads NOT cleared and tagged.
TABLE 2 BATTERY NUMBER OF MAXIMUM NOMINAL MAXIMUM (VDC)
CELLS BATTERY EQUALIZE EQUALIZE EQUALIZE VOLTAGE PER VOLTAGE PER VOLTAGE CELL (VDC)
CELL (VDC)
(VDC) 28 13 30.3 2.33 to 2.38 2.60 III.
Method 3 - With one or more cells bypassed, LOWER battery equalize voltage to 2.33 to 2.38 VDC per cell.
Salem Common Page 84 of 96 Rev. 14
(f) w o z <<
- r:
u o z <<
(f) f-<<
f-(f) z o (f)
W 0:::
o Z
LL 0:::
l-Li >
0:::
o LL LtJ
--l CO (f)
Z o (l-(t)
L.Ll 0:::
0:::
W (f)
S C. MD-ST. 28D-0004(Q)
ATTACHMENT 15 BATTERY VOLTAGE AND CURRENT DATA SHEET DATEI VOLTAGE CURRENT INfflALS DATEI VOLTAGE CURRENT INITIALS TIME (*)
(VDC)
(AMPS)
TIME (.)
(VDC)
(AMPS)
- - Battery terminal voltage and charging current should be logged every hour during charge.
Salem Common Page 85 of 96 Rev. 14
(/)
w c.::J z <<
I U
o Z <<
(/)
~
I-<<
l-(/)
STEP 5.15.4.B CELL TIME/
NO.
nATE 1
2 3
4 5
6
- 7 8
9 10 11 12 13 INT.
ICV AVERAGE STEP NO.
INITIALS ATTACHMENT 16 CHARGE ICV DATA SHEET 28V BATTERY S C. MD-ST. 28D-0004(Q)
INDIVIDUAL CELL VOLTAGE (VDC) 5.15.9 5.15.12 5.15.12*
5.15.12*
5.15.15 5.15.15 S.15.1S TIME/
TIME/
TIME/
TIME/
TIME/
TIME/
TIME/
_ DA:£E hA:£E nAT1?,
nATE
- hATR, DATE DATE 5.15.13 5.15.13*
5.15.13'"
z o
(/)
NOTES w
0:::
c.::J Z
LL 0:::
1.JJ >
0::: o l.L W
-.-J m
(/)
Z o CL
(/)
W 0:::
0:::
W
(/)
~
Use these columns if more than one 8 to 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> equalize period is used. Copy additional data sheets as required.
Install Thermometers with "Cell Stop" in this cell.
Salem Common Page 86 of 96 Rev. 14
(j) w C) z
<t:
I U
o z
<t:
(j)
I-
<t:
I-(j) z o (j)
W 0:::
C)
Z lL..
0:::
L.Ll >
0:::
o lL..
W
-1 m
(j) z o 0...
(j)
W 0:::
0:::
W (j)
ATTACHMENT 17 SPECIFIC GRAVITY DATA SHEET S C.MD-ST.28D-0004(Q)
Shaded blocks in CELL TEMP column DO NOT require a temperature reading STEP CELL NO.
1 2
3 4
5 6
7 8
9 10 11 12 13 Salem Common S.17.2.B.2 5.17.2.C.7 S.17.2.E.3 CELL TEMP MEASURED SG TEMP CORR (oF)
FACTOR 28V BATTERY Page 87 of 96 S.17.2.E.4 TEMPCORR SG Rev. 14
U) w
(')
z <<
I U
o Z <<
U)
~
f-<<
f-U) z o U)
W 00::
(')
Z l.L.
00::
W >
00::
o l.L.
W
-J m
U) z o
[L U)
W 00::
00::
W U)
~
CELL TIME!
NO.
DATE 1
2 3
4 5
6 7
8 9
10 11 12 13 INT.
Salem Common ATTACHMENT 18 FLOAT ICV DATA SHEET sC.MD-ST.28D-0004(Q)
INDIVIDUAL CELL VOLTAGE (VDC) (Step 5.17.4)
TIME!
TIME !
TIME/
TIME!
TIME!
TIME/
TIME/
DATE DATE DATE DATE DATE DATE DATE Page 88 of 96 Rev. 14
If) w C')
z <<
- r::
o o z <<
If)
- J f-<<
f-If) z o If) w rx C')
z Lt-rx w >
rx o
Lt-W
-l OJ If)
Z o
[L V) w rx rx w
If)
- J 1.0 JOB DATA:
ATTACHMENT 19 DATA SHEET sC. MD-ST. 28D-0004(Q)
Work Order No. ____________ _
Activity No. _______ _
Station Battery No. ________________________ _
2.0 TEST EQUIPMENT DATA DEVICE NAME DVOM DVOM BCT -2000 Series System DLRO Torque wrench Electronic Temperature Device Thermometer Thermometer Thermometer Thermometer Hydrometer 3.0 TEST DATA:
STEP DESCRIPTION Battery room 5.2.1 ambient temperature 5.2.5 Battery room condition Salem Common M&TE No.
DUE DATE DATA ACCEPTANCE COMPLETED CRITERIA BY; DATE None OF
/
Exhaust fan operable, room clean, lighting Sat Unsat operable I
Page 89 of 96 Rev. 14
IJi W
G Z <<
I U
o Z <<
IJi
- J f-<<
f-IJi z o IJi W
0:::
G Z
0:::
W >
0:::
o w
CD IJi Z o
[L IJi W
0:::
0:::
W IJi
- J 5.3.4 5.5.1.D STEP 5.5.4 5.5.7 5.6.1 5.7.LB 5.7.4.B 5.7.6.A 5.7.6.B 5.9.2 Salem Common S C.MD-ST. 28D-0004(Q)
ATTACHMENT 19 (Cont'd)
DESCRIPTION DATA ACCEPTANCE COMPLETED CRITERIA BY/DATE All bolts tight, no Battery rack unistrut damage, enclosure of no signs of Sat Unsat deterioration
/
No corrosion on Battery cell terminal posts, connections bus bars, cable lugs and plate Sat Unsat contact surfaces
/
As Found new cell 110%
J.l.ohms None resistance value
/
As Found IA W acceptance connection criteria specified resistance in Step 5.5.5 and measurements Sat unsat
/
Nominal Value Battery As Found 28.9-29.3 VDC float voltage Tech Spec min.
VDC
- 27 VDC I
Record cell Tech Spec Min.
average
> 65°P temperature OF
/
Record average
~ 1.190 corrected S. G.
I Verify Recorded All recorded cell cell temperatures temps:=;; 5°P within limit Sat Unsat average cell temp
/
No cell's Verify corrected corrected S. G. is S.G. is within more than 0.010 limits below average Sat Unsat corrected S. G.
I Calculate avg.
electrolyte Average __. OF AVG - > 65°F temperature
/
Page 90 of 96 Rev. 13
(f) w C) z <<
- r:
u o z <<
(f)
- l f-<<
f-(f) z o (f)
W 0::::
C)
Z u...
0::::
W >
0::::
o u...
W
-.J CD (f)
Z o 0...
(f)
W 0::::
0::::
W (f)
- l STEP 5.9.9 5.12.11 5.12.13 5.12.16 5.12.17 Salem Common S C.MD-ST. 28D-0004(Q)
ATTACHMENT 19 (Cont'd)
DESCRlPTION DATA ACCEPTANCE COMPLETED CRITERIA BY! DATE BCT-2000 Programmed programming Sat Unsat screen is IA W complete Attaclunent 8 I
Service Test start Time None time
/
Loaded Steps 001 VDC 002 VDC Per Design Calc.
Minimum battery (Reference 7.5.7 tenninal voltage 003 VDC and 7.5.8) for each Loaded Step 004 VDC
- voltage values shown on Table 1 005 VDC 006 VDC I
Programmed Service test end BCT -2000 runs 4 Time hours loaded and time 10 minutes unloaded
/
lA ~23.9 VDC Test Ended Battery #
IB ~24.6 VDC battery tenninal voltage VDC 2A ~24.0 VDC Sat Unsat 2B ;;?;24.5 VDC
~
/
Page 91 of 96 Rev. 13
IJ)
W o z <<
I U
o Z <<
IJ)
- l I-<<
I-IJ) z o IJ)
W D:::
o Z
lI-D:::
W >
D:::
o lI-W
.-J m
IJ) z o
!l.
IJ)
W 0-:::
D:::
W IJ)
- l STEP 5.13.1 5.13.3.A 5.13.3.B 5.13.17.A 5.13.17.B Salem Common sC. MD-ST. 28D-0004(Q)
ATTACHMENT 19 (Cont'd)
DESCRIPTION DATA ACCEPTANCE COMPLETED CRITERIA BY/DATE CELL# / CELU
/
Cell No. of all
_. I -
retorqued
/ -
None connections
/ -
/
/ -
1-If YES, Retorqued connections are resistance acceptable.
< 120% AVE RECORD As 1-BASELINE Left values per SN Yes No Subsection 5.14 1 -
As Left If YES, resistance connections I~
- 2:120% AVE should be cleaned SN BASELINE Yes No per Step 5.13.4 1-Cleaned connection resistance liYES, GO TO
~120% AVE BASELINE and Subsection 5.14 1-
< MAX SN ALLOWABLE Yes No 1
Cleaned If YES.
connection connections resistance NOTIFY
- 2: MAX Supervisor\\
1-ALLOWABLE System Manager SN Yes _No for resolution 1-Page 92 of 96 Rev. 13
if)
W o z <<
I o o z <<
if)
- l I-<<
I-if) z o if)
W et::
o Z
l.L.
Q::
W >
et:: o l.L.
W
1 OJ if)
Z o rl..
if)
W et::
et::
LLl if)
- l STEP 5.14.2 5.15.4.A 5.15.5 5.15.22 5.16.1 5.16.8.B 5.16.11.B 5.16.13.A S.16.13.B Salem Common S C. MD-ST. 28D-0004(Q)
ATTACHMENT 19 (Conttd)
DESCRIPTION DATA ACCEPTANCE COMPLETED CRITERIA BYI DATE Positive F
p.ohms
~easure forvvard and reverse R
p.oluns resistance of S; 20 poluns battery + and -
Negative output cable connections F
j.toluns R
J,Loluns I~
As Found battery VDC As Found tenninal voltage 1-Battery equalize VDC lAW voltage Attaclunent 1 I
Disconnect cell, Disconnected cell and intertier intertier sensing Sat Unsat sensing clips and clips and remove
~ removed BCT-2000 BCT-2000 I
Nominal Value Battery As Found 28.9-29.3 VDC float voltage Tech Spec min.
VDC
- =::28 VDC Record cell Tech Spec average of Min. >65°F temperature I
Verify
> 1.215 or as temperature Sat Unsat_
detennined by corrected specific Supervisor!
gravity System Manager 1-Verify recorded All recorded cell cell temperatures Sat Unsat temps S; of of within limits average cell temp
/
No cell's Verify corrected corrected S. G.is S.O. is within Sat Unsat
>0.010 below limits average corrected S.G.
1-Page 93 of 96 Rev. 13
Ul llJ G
Z <<
- r:
u o z <<
(I)
- J f-<<
f-Vi z o Ul W
~
G Z
~
W >
~
o LL W
-l co (f) z o D...
Ul W
~
~
w Ul
- ~
STEP 5.16.18 5.17.2.E.2 5.17.2.G 5.11.3.A 5.17.3.C 5.17.6 5.17.7 Salem Common sC.MD-ST.28D-0004(Q)
ATTACHMENT 19 (Cont'd)
DESCRIPTION DATA ACCEPTANCE COMPLETED CRITERIA BY/DATE Cell #
Cell #
Individual cells Level 2'! 16/32 in.
requiring System below high mark and temperature Manager's corrected S.G.
evaluation
< 1.218 I
Cell temperature OF 65 OF to 120°F average I
Verify
~ 1.215 or as temperature Sat Unsat detennined by corrected specific Supervisor!
gravity System Manager I
Record nominal float voltage VDC 28.9-29.3 VDC range
/
As Left battery VDC 28.9-29.3 VDC terminal voltage I
As Left battery tenninal float VDC 28.9-29.3 VDC voltage I
Verify electrolyte Sat Unsat Between high and level low mark I
Page 94 of 96 Rev. 13
(j) w
(')
Z
<C I
U o
Z
<C (j) f-
<C f-(j) z o (j)
W 0:::
(')
Z LL 0:::
W >
0:::
o LL W
--l CD (j)
Z o D-(j)
W 0:::
0:::
W (j)
Se.MD-ST.28D-0004(Q)
ATTACHMENT 19 (Cont.'d) 4.0 COMPLETION
SUMMARY
Calculations Independently Verified by (Step 5.18.3): [C0284]
Signature _~ _______ Date _____ _
Comments: ____________________________ _
Salem Common Page 95 of 96 Rev. 14
(j) w (9
z <<
- r::
u o z <<
(j)
- J f----<<
f----
(j) z o (j) w cr::
(9 z
w...
cr::
w cr:: o w...
W
......I m
(j)
Z o 0...
(j)
W cr::
cr::
w (j)
- J sC. MD~ST. 28D-0004(Q)
ATTACHMENT 19 (Cont'd)
Individuals Performing Work:
Print Name Signature Date This procedure has been reviewed for completion in accordance with SH.MD-AP.ZZ-0003(Q).
Maintenance Supervisor / Date Salem Common Page 96 of 96 Rev. 14