PSEG Internal Use Only PSEG NUCLEAR L.L.C.

Page 1 of 1 HOPE CREEK GENERATING STATION HC.OP-AR.ZZ-0019(Q) - Rev. 17 OVERHEAD ANNUNCIATOR WINDOW BOX E6 USE CATEGORY: II

  • Packages and Affected Document Numbers incorporated into this revision:

CP No.

CP Rev.

AD No.

Rev No.

None 9

  • The following OPEX were incorporated into this revision: None
  • The following OTSCs were incorporated into this revision: None REVISION

SUMMARY

  • 1SD-RR-4813 has been removed by DCP 80083637. Operator Action 3.b on Attachment A4 is changed to refer to 1SP-RI-4813 for indication. The indicator and recorder were both located on panel 10C604. This was evaluated by the DCP and is editorial. (70101800-0010)
  • Combines Actions for Channels 1, 2, and 3 on Attachment A4 which are identical.

IMPLEMENTATION REQUIREMENTS Effective Date 10/8/09 None

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 1 of 54 Rev. 17 OVERHEAD ANNUNCIATOR WINDOW BOX E6 TABLE OF ATTACHMENTS 1 2 3

4 5

CONTROL RM DRYWELL REFUEL FLR NEW FUEL RB EXH A-VENT RAD COOLER FANS EXH RAD CRITICALITY RADIATION ALARM/TRBL TROUBLE ALARM/TRBL RAD HI ALARM/TRBL Page 2 Page 7 Page 8 Page 15 Page 18 CONTROL DRYWELL RB B-AREA HVAC PURGE ISLN PRESSURE FAN MALF OVERRIDE HI/LO Page 29 Page 39 Page 40 CONT AREA DIESEL AREA RBVS & WING C-HVAC EXH HVAC PANEL AREA HVAC PNL 1EC485 1EC483 PNL 10C382 Page 41 Page 42 Page 43 CABLE TRAY DIESEL AREA FRVS D-AREA HVAC HVAC 1E PNL VENT FAN PNL 00C383 1EC486 MALFUNCTION Page 44 Page 45 Page 46 SVCE AREA RADWASTE &

CHEM LAB FRVS E-SUPPLY SAE HVAC EXH HVAC RECIRC FAN PNL 00C181 PNL 00C381 PNL 00C392 TROUBLE Page 47 Page 48 Page 49 Page 50 SOLID RADW RADWASTE TK AUX BOILER ASPH STOR F-SUPPLY/EXH FILTER HVAC BLDG HVAC BLDG HVAC PNL 00C380 PNL 00C385 PNL 00C591 PNL 00C580 Page 51 Page 52 Page 53 Page 54

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 2 of 54 Rev. 17 ATTACHMENT A1 CONTROL RM VENT RAD Window Location E6-A1 ALARM/TRBL OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. IF valid alarm condition exists, VERIFY auto start of CREF Trains in pressurization (OA) mode.
3. DETERMINE radiation level in Control Room AND REFER TO HC.OP-AB.HVAC-0002(Q), Control Room Environment.
4. DETERMINE IF OPERATE failure condition for 1SP-RI-4858C(D) is cause of alarm. (Panel 10C604)
5. NOTIFY Radiation Protection of alarm condition.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action 1SP-RI-4858C CH 1 AND/OR CH 2 HIGH LED ILLUMINATED OR OPER LED EXTINGUISHED.

CONTROL ROOM ISOL/CREF AUTO START ON HIGH RAD IF "A" SUPPLY FAN RUNNING 1SP-RI-4858D CH 1 AND/OR CH 2 HIGH LED ILLUMINATED OR OPER LED EXTINGUISHED.

CONTROL ROOM ISOL/CREF AUTO START ON HIGH RAD IF "B" SUPPLY FAN RUNNING

REFERENCES:

J-26-0, Sht. 2 M-26-1, Sht. 1 H-89-0, Sht. 10 J373(Q)-45(5)-7 E-6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 3 of 54 Rev. 17 ATTACHMENT A1 NOMENCLATURE CTRL RM VENT RMS CH C SETPOINT HIGH 2 X 10-5 uCi/cc DESCRIPTION Channel C Control Room Inlet Plenum high radiation ORIGIN RY-4858C AUTOMATIC ACTION:

Computer indication of radiation level at Air Inlet Plenum to Control Room.

At radiation levels equal to 2 X 10-5 uCi/cc (HI HI RAD) CREF automatically initiates AND normal Control Building Ventilation (CAE) isolates.

OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. IF valid alarm condition exists, VERIFY AUTO START CREF trains.
3. DETERMINE radiation level in Control Room AND REFER to HC.OP-AB.HVAC-0002(Q), Control Room Environment.
4. DETERMINE IF OPERATE failure condition for 1SP-RI-4858C is cause of alarm.

CAUSE CORRECTIVE ACTION

1.

High radiation level at Control Building Air Inlet Plenum.

1A.

CLOSE HV-9588AA, AB, BA AND BB by pressing ISOLATE PB.

1B.

ENSURE Control Room Exhaust Fans are off by dispatching operator to Local Panel EC485.

1C. ENSURE proper operation of CREF Trains.

1D. DETERMINE radiation level in Control Room AND REFER TO HC.OP-AB.HVAC-0002(Q).

1E.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

J-26-0, Sht. 2 M-26-1, Sht. 1 H-89-0, Sht. 10 J373(Q)-45(5)-7

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 4 of 54 Rev. 17 ATTACHMENT A1 ALARM POINT 1SP-RI-4858C CAUSE CORRECTIVE ACTION

2. Power Failure 2A.

ENSURE power supply energized from 120VAC Distribution Panel 1CJ481, Bkr. 19.

3. Detector Failure 3A.

REFER TO T/S 3.3.7.1 for Action Statement 3B.

NOTIFY SM/CRS of failure AND T/S Action Statement.

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 5 of 54 Rev. 17 ATTACHMENT A1 NOMENCLATURE CTRL RM VENT RMS CH D SETPOINT HIGH 2 X 10-5 uCi/cc DESCRIPTION Channel D Control Room Inlet Plenum high radiation ORIGIN RY-4858D AUTOMATIC ACTION:

Computer indication of radiation level at Air Inlet Plenum to Control Room.

At radiation levels equal to 2 X 10-5 uCi/cc (HI HI RAD) CREF automatically initiates AND normal Control Building Ventilation (CAE) isolates.

OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. IF valid alarm condition exists, VERIFY AUTO START CREF Trains.
3. DETERMINE radiation level in Control Room AND REFER TO HC.OP-AB.HVAC-0002(Q), Control Room Environment.
4. DETERMINE IF OPERATE failure condition for 1SP-RI-4858D is cause of alarm.

CAUSE CORRECTIVE ACTION

1.

High radiation level at Control Building Air Inlet Plenum.

1A.

CLOSE HV-9588AA, AB, BA AND BB by pressing ISOLATE PB.

1B.

ENSURE Control Room Exhaust Fans are OFF by dispatching operator to Local Panel EC485.

1C.

ENSURE proper operation of CREF Trains.

1D.

DETERMINE radiation level in Control Room AND REFER TO HC.OP-AB.HVAC-0002(Q).

1E.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

J-26-0, Sht. 2 M-26-1, Sht. 1 H-89-0, Sht. 10 J373(Q)-45(5)-7

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 6 of 54 Rev. 17 ATTACHMENT A1 ALARM POINT 1SP-RI-4858D CAUSE CORRECTIVE ACTION

2. Power Failure 2A.

ENSURE power supply energized from 120VAC Distribution Panel 1DJ481, Bkr. 19.

3. Detector Failure 3A.

REFER TO TS 3.3.7.1 for Action Statement 3B.

NOTIFY SM/CRS of failure AND T/S Action Statement.

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 7 of 54 Rev. 17 ATTACHMENT A2 DRYWELL COOLER FANS Window Location E6-A2 TROUBLE OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. IF necessary, ENTER HC.OP-AB.CONT-0001(Q), Drywell Pressure.
3. DETERMINE the Drywell Cooler that initiated the trouble alarm by checking Control Room indication.
4. IF needed, START additional Drywell Coolers.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D3668 DRYWELL CLR FANS A TROUBLE Standby fan auto starts.

D4304 DRYWELL CLR FANS B TROUBLE Standby fan auto starts.

REFERENCES:

H-86-0, Sht. 1, 3

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 8 of 54 Rev. 17 ATTACHMENT A3 REFUEL FLR EXH RAD Window Location E6-A3 ALARM/TRBL OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DETERMINE IF OPERATE failure condition for 1SP-RI-4856A(B,C) is NOT cause of alarm, THEN PERFORM the following:
a. REFER TO HC.OP-AB.CONT-0005(Q), Irradiated Fuel Damage, AND HC.OP-AB.COOL-0004(Q), Fuel Pool Cooling.
b. SUSPEND all Refuel operations OR Dry Cask Storage (DCS) operations on refuel floor.
c.

ENSURE FRVS (Filtration, Recirculation, Ventilation System) has started.

d. ENSURE Reactor Building Ventilation is isolated.
e. REFER TO HC.OP-EO.ZZ-0103(Q), Reactor Building Control, for possible entry condition.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action 1SP-RI-4856A Refueling Floor Exhaust RMS CH A / CH 1 HIGH LED ILLUMINATED OR OPER LED EXTINGUISHED RR4856A records radiation level at ALERT FRVS Auto starts (2/3)

RBVS Auto isolates (2/3) 1SP-RI-4856B Refueling Floor Exhaust RMS CH B / CH 1 HIGH LED ILLUMINATED OR OPER LED EXTINGUISHED FRVS Auto starts (2/3)

RBVS Auto isolates (2/3) 1SP-RI-4856C Refueling Floor Exhaust RMS CH C / CH 1 HIGH LED ILLUMINATED OR OPER LED EXTINGUISHED FRVS Auto starts (2/3)

RBVS Auto isolates (2/3)

REFERENCES:

M-84-1 M-26-1, Sht. 1 J-26-0, Sht. 2 E-6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 9 of 54 Rev. 17 ATTACHMENT A3 NOMENCLATURE RFLG FLR EXH RMS CH A SETPOINT HIGH 2 X 10-3 uCi/cc DESCRIPTION Refuel Floor Ventilation Exhaust Radiation High Ch A ORIGIN RE-4856A AUTOMATIC ACTION:

AUTO START of FRVS (2/3 logic), RBVS AUTO isolation (2/3 logic)

OPERATOR ACTION:

1. NOTIFY Radiation Protection of the alarm condition.
2. EVACUATE personnel from the Refuel Floor.
3. ENSURE HC.OP-EO.ZZ-0103/4(Q) has been entered.
4. REFER TO HC.OP-AB.CONT-0004(Q), Radioactive Gaseous Release, AND HC.OP-AB.CONT-0005(Q), Irradiated Fuel Damage.
5. MONITOR radiation level on Refuel Floor (RI-4856A,B,C).
6. DETERMINE source of activity AND ISOLATE IF possible.

CAUSE CORRECTIVE ACTION

1.

High radiation in Refueling Floor Exhaust Plenum Ch A.

1A.

ENSURE all Reactor Building Supply AND Exhaust Isolation Dampers are closed.

1B.

ENSURE proper operation of FRVS.

1C.

ENSURE all Reactor Building Supply AND Exhaust Fans are off.

1D.

IF refueling OR DCS operations are ongoing on refuel floor REFER TO HC.OP-AB.CONT-0005(Q);

Irradiated Fuel Damage.

1E.

IF activity is due to Fuel Pool inventory loss REFER TO HC.OP-AB.COOL-0004(Q);

Fuel Pool Cooling.

Continued next page REFERENCES M-84-1, M-26-1, Sht. 1 J-26-0, Sht. 2 E6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 10 of 54 Rev. 17 ATTACHMENT A3 CAUSE CORRECTIVE ACTION

1.

High radiation in Refueling Floor Exhaust Plenum Ch A. (continued) 1F. IF FRVS did not start OR Secondary Containment fails to isolate THEN REFER TO T/S 3.6.5 1G.

REQUEST SM/CRS to initiate corrective action.

2. Power Failure 2A.

ENSURE power supply energized from 120VAC Distribution Panel 1AJ481, Bkr. 20.

3. Detector Failure 3A.

REFER TO T/S 3.3.2 for Action Statement 3B.

NOTIFY SM/CRS of failure AND T/S Action Statement.

REFERENCES:

M-84-1 M-26-1, Sht. 1 J-26-0, Sht. 2 E6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 11 of 54 Rev. 17 ATTACHMENT A3 NOMENCLATURE RFLG FLR EXH RMS CH B SETPOINT HIGH 2 X 10-3 uCi/cc DESCRIPTION Refuel Floor Ventilation Exhaust radiation high Ch B ORIGIN RE-4856B AUTOMATIC ACTION:

Auto Start of FRVS (2/3 logic) RBVS AUTO isolation (2/3 logic)

OPERATOR ACTION:

1. NOTIFY Radiation Protection of the alarm condition.
2. EVACUATE personnel from the Refuel Floor.
3. ENSURE HC.OP-EO.ZZ-0103/4(Q) has been entered.
4. REFER TO HC.OP-AB.CONT-0004(Q), Radioactive Gaseous Release, AND HC.OP-AB.CONT-0005(Q), Irradiated Fuel Damage.
5. MONITOR radiation level on Refuel Floor (RI-4856A,B,C).
6. DETERMINE source of activity AND ISOLATE IF possible.

CAUSE CORRECTIVE ACTION

1.

High radiation in Refueling Floor Exhaust Plenum Ch B.

1A.

ENSURE all Reactor Building Supply AND Exhaust Isolation Dampers are closed.

1B.

ENSURE proper operation of FRVS.

1C.

ENSURE all Reactor Building Supply AND Exhaust Fans are OFF.

1D.

IF refueling OR DCS operations are ongoing on refuel floor REFER TO HC.OP-AB.CONT-0005(Q);

Irradiated Fuel Damage.

1E.

IF activity is due to Fuel Pool inventory loss REFER TO HC.OP-AB.COOL-0004(Q);

Fuel Pool Cooling.

Continued next page

REFERENCES:

M-84-1, M-26-1, Sht. 1 J-26-0, Sht. 2 E6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 12 of 54 Rev. 17 ATTACHMENT A3 CAUSE CORRECTIVE ACTION

1.

High radiation in Refueling Floor Exhaust Plenum Ch B. (continued) 1F. IF FRVS did not start OR Secondary Containment fails to isolate THEN REFER TO T/S 3.6.5 1G.

REQUEST SM/CRS to initiate corrective action.

2. Power Failure
2.

ENSURE power supply energized from 120VAC Distribution Panel 1BJ481, Bkr. 20.

3. Detector Failure 3A.

REFER TO T/S 3.3.2 for Action Statement 3B.

NOTIFY SM/CRS of failure AND T/S Action Statement.

REFERENCES:

M-84-1, M-26-1, Sht. 1 J-26-0, Sht. 2 E6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 13 of 54 Rev. 17 ATTACHMENT A3 NOMENCLATURE RFLG FLR EXH RMS CH C SETPOINT HIGH 2 X 10-3 uCi/cc DESCRIPTION Refuel Floor Ventilation Exhaust radiation high Ch C ORIGIN RE-4856C AUTOMATIC ACTION:

AUTO START of FRVS (2/3 logic), RBVS AUTO isolation (2/3 logic)

OPERATOR ACTION:

1. NOTIFY Radiation Protection of the alarm condition.
2. EVACUATE personnel from the Refuel Floor.
3. ENSURE HC.OP-EO.ZZ-0103/4(Q) has been entered.
4. REFER TO HC.OP-AB.CONT-0004(Q), Radioactive Gaseous Release, AND HC.OP-AB.CONT-0005(Q), Irradiated Fuel Damage.
5. MONITOR radiation level on Refuel Floor (RI-4856A,B,C).
6. DETERMINE source of activity AND ISOLATE IF possible.

CAUSE CORRECTIVE ACTION

1.

High radiation in Refueling Floor Exhaust Plenum Ch C.

1A.

ENSURE all Reactor Building Supply AND Exhaust Isolation Dampers are closed.

1B.

ENSURE proper operation of FRVS.

1C.

ENSURE all Reactor Building Supply AND Exhaust Fans are OFF.

1D.

IF refueling OR DCS operations are ongoing on refuel floor REFER TO HC.OP-AB.CONT-0005(Q);

Irradiated Fuel Damage.

1E.

IF activity is due to Fuel Pool inventory loss REFER TO HC.OP-AB.COOL-0004(Q);

Fuel Pool Cooling.

Continued next page

REFERENCES:

M-84-1, M-26-1, Sht. 1 J-26-0, Sht. 2, E6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 14 of 54 Rev. 17 ATTACHMENT A3 CAUSE CORRECTIVE ACTION

1.

High radiation in Refueling Floor Exhaust Plenum Ch C. (continued) 1F. IF FRVS did not start OR Secondary Containment fails to isolate THEN REFER TO T/S 3.6.5 1G.

REQUEST SM/CRS to initiate corrective action.

2. Power Failure 2A.

ENSURE power supply energized from 120VAC Distribution Panel 1CJ481, Bkr. 20.

3. Detector Failure 3A.

REFER TO T/S 3.3.2 for Action Statement 3B.

NOTIFY SM/CRS of failure AND T/S Action Statement.

REFERENCES:

M-84-1 M-26-1, Sht. 1 J-26-0, Sht. 2 E6796-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 15 of 54 Rev. 17 ATTACHMENT A4 NEW FUEL CRITICALITY Window Location E6-A4 RAD HI OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Radiation Protection of alarm condition.
3. IF OPERATE failure condition of instruments is NOT cause of alarm, THEN PERFORM the following:
a. SUSPEND all Refueling operations OR DCS operations are ongoing on refuel floor.
b. IF alarm is high radiation (HIGH LED lit on 1SP-RI-4813, any channel)

AND the radiation level is increasing, THEN EVACUATE the Refuel Floor via the PA System.

c.

DETERMINE whether rad level was caused by radioactive equipment in the vicinity of the detector(s) (e.g. Dryer, Separator, etc.).

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action R9612 NEW FUEL CRITICALITY OR SPENT FUEL AREA CH A HIGH RAD/OPERATE FAILURE Alarm will sound on Refuel floor R9613 NEW FUEL CRITICALITY OR SPENT FUEL AREA CH B HIGH RAD/OPERATE FAILURE Alarm will sound on Refuel floor R9707 NEW FUEL CRITICAILITY//Spent Fuel Storage Pool// HIGH RAD/OPERATE FAILURE Alarm will sound on Refuel floor

REFERENCES:

M-26-1, Sht. 2 Dwg. J-26-0, Sht. 3 E-6796-0 J-R 1000-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 16 of 54 Rev. 17 ATTACHMENT A4 NOMENCLATURE DESCRIPTION SETPOINT ORIGIN NEW FUEL CRITICALITY//Spent Fuel Storage Pool Radiation High radiation in the vicinity of the Spent Fuel Storage Pool/OPERATE Failure HIGH 13.8 mr/hr 1SD-RE-6607 (Channel 1)

NEW FUEL CRITICALITY CH A Radiation High radiation in the vicinity of the New Fuel Storage Vault/OPERATE Failure HIGH 6.54 mr/hr 1SP-RE-4813A (Channel 2)

NEW FUEL CRITICALITY CH B Radiation High radiation in the vicinity of the New Fuel Storage Vault/OPERATE Failure HIGH 6.54 mr/hr 1SP-RE-4813B (Channel 3)

AUTOMATIC ACTION:

Evacuation alarm will sound on Refuel Floor.

OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Radiation Protection of alarm condition.
3. IF alarm is high radiation (HIGH LED lit on 1SP-RI-4813, any channel)

AND the radiation level is increasing, THEN EVACUATE the Refuel Floor via the PA System.

CAUSE CORRECTIVE ACTION

1. High radiation in the vicinity of the Spent Fuel Storage Pool (Ch 1)

New Fuel Storage Vault (Ch 1 or 2) 1A. IF moving radioactive equipment OR parts SECURE as soon as possible.

(HIGH LED lit) 1B.

IF refueling OR DCS operations are ongoing on refuel floor REFER TO HC.OP-AB.CONT-0005(Q);

Irradiated Fuel Damage.

1C. IF activity is due to Fuel Pool inventory loss REFER TO HC.OP-AB.COOL-0004(Q); Fuel Pool Cooling.

Continued next page

REFERENCES:

M-26-1, Sht. 2 J-26-0, Sht. 3 E-6796-0 J-R 1000-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 17 of 54 Rev. 17 ATTACHMENT A4 CAUSE CORRECTIVE ACTION

1.

High radiation in the vicinity of the Spent Fuel Storage Pool (Ch 1) 1D.

NOTIFY the SM/CRS to initiate corrective action.

New Fuel Storage Vault (Ch 1 or 2)

(HIGH LED lit)

(continued) 1E.

CONSIDER isolation of the Reactor Building Ventilation System AND starting FRVS.

1F.

PERFORM any actions required IAW HCGS Emergency Plan

2. Power Failure 2A.

CHECK power supply

3. Detector Failure 3A.

NOTIFY SM/CRS of failure

REFERENCES:

M-26-1, Sht. 2 Dwg. J-26-0, Sht. 3 E-6796-0 J-R 1000-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 18 of 54 Rev. 17 ATTACHMENT A5 RB EXH RADIATION Window Location E6-A5 ALARM/TRBL OPERATOR ACTION:

1.

NOTIFY SM/CRS of alarm condition.

2.

NOTIFY Radiation Protection of alarm condition.

3.

EVACUATE the Reactor Building.

4. IF alarm is high radiation (HIGH LED lit on 1SP-RI-4856A[B,C] Panel 10C604):
a. ENSURE FRVS (Filtration Recirculation, Ventilation System) is started.
b. ENSURE Reactor Building Ventilation is isolated.
5.

REFER TO HC.OP-AB.CONT-0004(Q), Radioactive Gaseous Release.

6.

REFER TO T/S 3.11.2.1, 3.11.2.2, 3.11.2.3 and 3.11.2.5. 3.

7. IF alarm is downscale (OPERATE LED extinguished on 1SP-RI4856A[B,C]

Panel 10C604) ENSURE power supply energized.

8.

REFER TO HC.OP-EO.ZZ-0103(Q), Reactor Building Control, for possible entry condition.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action 1SP-RI-4856A REACTOR BLDG EXHAUST RMS CH A / CH 2 HIGH LED lit or OPERATE LED extinguished Red pen (RR-4857A) on DRYWELL ATMOS POST ACCIDENT RAD MONITOR recorder records the rad level in Reactor Building Ventilation Exhaust (ALERT LED) FRVS AUTO STARTS (2/3) RBVS AUTO ISOLATES (2/3)

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht.

1E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 19 of 54 Rev. 17 ATTACHMENT A5 INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action 1SP-RI-4856B REACTOR BLDG EXHAUST RMS CH B / CH 2 HIGH LED lit OR downscale OPERATE LED extinguished)

FRVS AUTO STARTS (2/3)

RBVS AUTO ISOLATES (2/3) 1SP-RI-4856C REACTOR BLDG EXHAUST RMS CH C / CH 2 HIGH LED lit OR downscale OPERATE LED extinguished)

FRVS AUTO STARTS (2/3)

RBVS AUTO ISOLATES (2/3)

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 1 E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 20 of 54 Rev. 17 ATTACHMENT A5 ALARM POINT 1SP-RI-4856A SETPOINT HIGH 1.0E-3 uCi/cc NOMENCLATURE REACTOR BLDG EXHAUST SETPOINT Radiation DESCRIPTION ORIGIN 1SP-RE-4857A High radiation in Reactor Building Ventilation Exhaust Plenum (HIGH LED lit)

AUTOMATIC ACTION:

IF radiation level reaches 1.0 E-3 uCi/cc (HIGH LED lit on 1SP-RI-4856A[B,C]) the Reactor Building Ventilation System will isolate AND FRVS will auto start.

OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Radiation Protection of alarm condition.
3. EVACUATE the Reactor Building.
4. IF HIGH LED is lit on 1SP-RI-4856A(B,C) (at least two)

ENSURE Reactor Building Ventilation System has isolated AND FRVS has started.

5. REFER TO HC.OP-AB.CONT-0004(Q); Radioactive Gaseous Release.
6. DETERMINE source of activity AND ISOLATE.

CAUSE CORRECTIVE ACTION

1.

High airborne radiation from one or more Reactor Building rooms, compartments or 1A.

ENSURE proper operation of FRVS.

Drywell and Torus 1B.

ENSURE Reactor Building Ventilation System is isolated.

1C.

IF refueling OR DCS operations are ongoing on refuel floor REFER TO HC.OP-AB.CONT-0005(Q);

Irradiated Fuel Damage.

Continued next page

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 1 E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 21 of 54 Rev. 17 ATTACHMENT A5 ALARM POINT 1SP-RI-4856A CAUSE CORRECTIVE ACTION

1.

High airborne radiation from one or more Reactor Building rooms, compartments OR Drywell and Torus. (continued) 1D.

DETERMINE area(s) of high airborne radiation AND ISOLATE.

1E.

IF activity is due to Fuel Pool inventory loss REFER TO HC.OP-AB.COOL-0004(Q);

Fuel Pool Cooling.

1F.

REFER TO ODCM 3.11.2.1, 3.11.2.2, 3.11.2.3, & 3.11.2.5.

1G.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 1 E-6796-0 J-R 1000-0 J-26-0, Sht 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 22 of 54 Rev. 17 ATTACHMENT A5 NOMENCLATURE REACTOR BLDG EXHAUST Radiation SETPOINT N/A DESCRIPTION ORIGIN 1SP-RE-4857A Reactor Building Ventilation Exhaust Radiation Monitor downscale (OPERATE LED extinguished)

AUTOMATIC ACTION:

None OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Radiation Protection of alarm condition.
3. ENSURE power supply energized.

CAUSE CORRECTIVE ACTION

1. Power failure 1A.

ENSURE power supply energized from 120 VAC Distribution Panel 1AJ481 Bkr 1AJ481-20.

2. Detector failure 2A.

REFER TO T/S 3.3.2 for Action Statement.

2B.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 1 E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 23 of 54 Rev. 17 ATTACHMENT A5 ALARM POINT 1SP-RI-4856B SETPOINT HIGH 1.0E-3 uCi/cc NOMENCLATURE REACTOR BLDG EXHAUST Radiation DESCRIPTION ORIGIN 1SP-RE-4857B High radiation in Reactor Building Ventilation Exhaust Plenum (HIGH LED lit)

AUTOMATIC ACTION:

IF radiation level reaches 1.0 E-3 uCi/cc (HIGH LED lit on 1SP-RE-4856A[B,C]) the Reactor Building Ventilation System will isolate AND FRVS will auto start.

OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Radiation Protection of alarm condition.
3. EVACUATE personnel from the Reactor Building.
4. IF HIGH LED is lit on 1SP-RE-4856A(B,C) (at least two)

ENSURE Reactor Building Ventilation System has isolated AND FRVS has started.

5. REFER TO HC.OP-AB.CONT-0004(Q); Radioactive Gaseous Release.
6. DETERMINE source of activity AND ISOLATE.

CAUSE CORRECTIVE ACTION

1.

High airborne radiation from one or more Reactor Building rooms, compartments OR Drywell and Torus 1A.

ENSURE proper operation of FRVS.

1B.

ENSURE Reactor Building Ventilation System is isolated.

1C.

IF refueling OR DCS operations are ongoing on refuel floor REFER TO HC.OP-AB.CONT-0005(Q);

Irradiated Fuel Damage.

Continued next page

REFERENCES:

M-76-1, M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 1 E-6796-0 J-R 1000-0, J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 24 of 54 Rev. 17 ATTACHMENT A5 ALARM POINT 1SP-RI-4856B CAUSE CORRECTIVE ACTION

1.

High airborne radiation from one or more Reactor Building rooms, compartments OR Drywell and Torus (continued) 1D.

DETERMINE area(s) of high, airborne radiation AND ISOLATE.

1E.

IF activity is due to Fuel Pool inventory loss REFER TO HC.OP-AB.COOL-0004(Q);

Fuel Pool Cooling.

1F.

REFER TO ODCM 3.11.2.1, 3.11.2.2, 3.11.2.3, & 3.11.2.5.

1G.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht.

1, E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 25 of 54 Rev. 17 ATTACHMENT A5 NOMENCLATURE REACTOR BLDG EXHAUST Radiation SETPOINT N/A DESCRIPTION ORIGIN 1SP-RE-4857B Reactor Building Ventilation Exhaust Radiation Monitor downscale (OPERATE LED extinguished)

AUTOMATIC ACTION:

None OPERATOR ACTION:

1. ENSURE power supply energized.
2. NOTIFY SM/CRS of alarm condition.
3. NOTIFY Radiation Protection of alarm condition.

CAUSE CORRECTIVE ACTION

1. Power failure 1A.

ENSURE power supply energized from 120 VAC Distribution Panel 1BJ481 Bkr 1BJ481-20.

2. Detector failure 2A.

REFER TO T/S 3.3.2 for Action Statement.

2B.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 1 E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 26 of 54 Rev. 17 ATTACHMENT A5 ALARM POINT 1SP-RI-4856C SETPOINT HIGH 1.0E-3 uCi/cc NOMENCLATURE REACTOR BLDG EXHAUST Radiation DESCRIPTION ORIGIN 1SP-RE-4857C High radiation in Reactor Building Ventilation Exhaust Plenum (HIGH LED lit)

AUTOMATIC ACTION:

IF radiation level reaches 1.0E-3 uCi/cc (HIGH LED lit on 1SP-RE-4856A[B,C]) the Reactor Building Ventilation System will isolate AND FRVS will auto start.

OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Radiation Protection of alarm condition.
3. EVACUATE personnel from the Reactor Building.
4. IF HIGH LED is lit on 1SP-RE-4856A(B,C) (at least two)

ENSURE Reactor Building Ventilation System has isolated AND FRVS has started.

5. REFER TO HC.OP-AB.CONT-0004(Q); Radioactive Gaseous Release.
6. DETERMINE source of activity AND ISOLATE.

CAUSE CORRECTIVE ACTION

1.

High airborne radiation from one or more Reactor Building rooms, compartments OR Drywell and Torus 1A.

ENSURE proper operation of FRVS.

1B.

ENSURE Reactor Building Ventilation System is isolated.

1C.

IF refueling OR DCS operations are ongoing on refuel floor REFER TO HC.OP-AB.CONT-0005(Q);

Irradiated Fuel Damage.

Continued next page

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 2 E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 27 of 54 Rev. 17 ATTACHMENT A5 ALARM POINT 1SP-RI4856C CAUSE CORRECTIVE ACTION

1.

High airborne radiation from one or more Reactor Building rooms, compartments OR Drywell and Torus (Continued) 1D.

DETERMINE area(s) of high, airborne radiation AND ISOLATE.

1E.

IF activity is due to Fuel Pool inventory loss REFER TO HC.OP-AB.COOL-0004(Q),

Fuel Pool Cooling.

1F.

REFER TO ODCM 3.11.2.1, 3.11.2.2, 3.11.2.3, & 3.11.2.5.

1G.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 2 E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 28 of 54 Rev. 17 ATTACHMENT A5 ALARM POINT 1SP-RI-4856C NOMENCLATURE REACTOR BLDG EXHAUST Radiation SETPOINT N/A DESCRIPTION Reactor Building Ventilation Exhaust Radiation ORIGIN 1SP-RE-4857C Monitor downscale (OPERATE LED extinguished)

AUTOMATIC ACTION:

None OPERATOR ACTION:

1. ENSURE power supply energized.
2. NOTIFY SM/CRS of alarm condition.
3. NOTIFY Radiation Protection of alarm condition.

CAUSE CORRECTIVE ACTION

1. Power failure 1A.

ENSURE power supply energized from 120VAC Distribution Panel 1CJ481 Bkr 19.

2. Detector failure 2A.

REFER TO T/S 3.3.2 for Action Statement.

2B.

REQUEST SM/CRS initiate corrective action.

REFERENCES:

M-76-1 M-83-1 M-84-1 M-26-1, Sht. 1 E-0012-1, Sht. 2 E-6796-0 J-R 1000-0 J-26-0, Sht. 2 J-102-0, Sht. 1 through 9

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 29 of 54 Rev. 17 ATTACHMENT B1 CONTROL AREA HVAC Window Location E6-B1 FAN MALF OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DETERMINE source of malfunction alarm.
3. REFER TO T/S 3.7.2.
4. REFER TO HC.OP-AB.HVAC-0001(Q), HVAC.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action CRS Low flow Results in trip of the associated malfunction High D/P Control Room Ventilation System.

A(B)V403 Loss of bus power Loss of control power Fan auto start Fan trip Low Supply air temp High Supply air temp Low Inlet pressure CREF Low flow Results in possible trip of the malfunction High D/P associated Control Room A(B)V400 Loss of bus power Ventilation System.

Loss of control power Fan auto start Fan trip

REFERENCES:

H-89-0, Sht. 1 J-105-0, Sht. 8

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 30 of 54 Rev. 17 ATTACHMENT B1 INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action CERS Low flow Results in trip of the associated malfunction Loss of bus power fan and Control Room Chiller.

A(B)V407 Loss of control power Low Supply air temp High Supply air temp Fan trip Fan auto start Chill water pump trip CRRA Low flow Results in possible trip of the malfunction Loss of bus power associated Control Room A(B)V415 Loss of control power Ventilation System.

Fan trip Fan auto start

REFERENCES:

H-89-0, Sht. 1 J-105-0, Sht. 8 E-6790-0, Sht. 1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 31 of 54 Rev. 17 ATTACHMENT B1 NOMENCLATURE Control Area HVAC Fan Malfunction SETPOINT Multiple DESCRIPTION CRS (Control Room Supply Fans)

ORIGIN Various malfunction A(B)VH403 AUTOMATIC ACTION:

None OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DETERMINE which fan A(B)VH403 has malfunctioned AND the parameter involved.
3. REFER TO HC.OP-AB.HVAC-0001(Q), HVAC.
4. IF there are any adverse affects on the Control Room instrumentation, IMPLEMENT HC.OP-AB.HVAC-0002(Q); Control Room Environment.

CAUSE CORRECTIVE ACTION

1. Low flow 1A.

OBSERVE Control Room indication for flow (alarm setpoint < 18,500 scfm).

(trip setpoint at 16,420 scfm) 1B.

DETERMINE IF proper valve lineup exists for malfunctioning fan.

2. High D/P 2A.

OBSERVE Control Room indication for D/P (alarm setpoint 1.8 inches water gauge).

Continued next page

REFERENCES:

H-89-0, Sht. 1 J-105-0, Sht. 8 E-6790-0, Rev. 7

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 32 of 54 Rev. 17 ATTACHMENT B1 CAUSE CORRECTIVE ACTION

3.

Loss of bus/control power 3A.

DISPATCH an EO to check A(B)V403 Brkr 52-471062 (52-481072).

4.

Fan auto start 4A.

Fans auto start on a LOCA OR LOP.

5. Fan trip 5A.

DETERMINE IF fan has tripped AND INITIATE corrective action.

6.

Supply air High or Low Temp.

6A.

OBSERVE Control Room indication for (1GKTSHL-9589A(B))

proper Chill Water flow (supply air temp setpoint High 76°F - Low 52°F)

7.

Low inlet pressure PDSL-9587A(B)

(15 second T.D.)

7A.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

H-89-0, Sht. 1 J-105-0, Sht. 8 E-6790-0, Rev. 7

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 33 of 54 Rev. 17 ATTACHMENT B1 NOMENCLATURE Control Area HVAC Fan Malfunction SETPOINT Multiple DESCRIPTION Control Room Emergency Filtration A(B)V400 trouble ORIGIN Various AUTOMATIC ACTION:

None OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DETERMINE which fan A(B)V400 has malfunctioned AND the parameter involved.
3. REFER TO HC.OP-AB.HVAC-0001(Q), HVAC.
4. IF there are any adverse affects on the Control Room instrumentation, IMPLEMENT HC.OP-AB.HVAC-0002(Q); Control Room Environment.

CAUSE CORRECTIVE ACTION

1. Low flow 1A.

OBSERVE Control Room indication to AND DETERMINE IF low flow light is illuminated (alarm setpoint < 4,000 scfm, trip setpoint 3,380 scfm).

1B.

DETERMINE IF proper valve lineup exists for malfunctioning fan.

Continued next page

REFERENCES:

J-105-0, Sht. 8 E-6790-0 H-89-0, Sht. 1 CD-181X FSAR 6.5.1.1.2

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 34 of 54 Rev. 17 ATTACHMENT B1 CAUSE CORRECTIVE ACTION

2. High D/P 2A.

OBSERVE Control Room indication for filter D/P (alarm setpoint 3.5 inches water gauge).

3.

Loss of bus/control power

[CD-181X]

3A.

DISPATCH an EO to check A(B)V400 Brkr 52-431035(52-441035).

4.

Auto start or trip of fan 4A.

A(B)V400 auto start on hi hi radiation/

Control Room Ventilation isolation/

LOCA/LOP.

IF a fan trips or auto starts REFER TO Technical Specifications 3/4.7.2. Manual operation is required to start the standby fan.

4B.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

J-105-0, Sht. 8 E-6790-0 H-89-0, Sht. 1 CD-181X FSAR 6.5.1.1.2

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 35 of 54 Rev. 17 ATTACHMENT B1 NOMENCLATURE Control Area HVAC Fan Malfunction SETPOINT Multiple DESCRIPTION ORIGIN Various CERS A(B)V407 malfunction (Control Room Equipment Room Supply Fans)

AUTOMATIC ACTION:

None OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DETERMINE which fan A(B)V407 has malfunctioned AND the parameter involved.
3. REFER TO HC.OP-AB.HVAC-0001(Q), HVAC.
4. IF there are any adverse affects on the Control Room instrumentation, IMPLEMENT HC.OP-AB.HVAC-0002(Q); Control Room Environment.

CAUSE CORRECTIVE ACTION

1. Low flow 1A.

OBSERVE Control Room indication AND DETERMINE IF low flow light is illuminated (alarm setpoint 49,640 scfm, trip setpoint 49,600 scfm).

1B.

DETERMINE IF proper valve lineup exists for malfunctioning fan.

Continued next page

REFERENCES:

H-89-0, Sht. 1 J-105-0, Sht. 8 E-6790-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 36 of 54 Rev. 17 ATTACHMENT B1 CAUSE CORRECTIVE ACTION

2.

Loss of bus/control power 2A.

DISPATCH an EO to check A(B)V407 Brkr 52-47013(52-48013).

3.

Supply air temp > or < SPT 3A.

OBSERVE Control Room indication AND DETERMINE IF hi/low supply air light is illuminated (alarm setpoint High 68°F - Low 54°F).

3B.

OBSERVE Chill Water System AND DETERMINE if a malfunction exists.

4. Fan trip 4A.

DETERMINE IF fan has tripped AND INITIATE corrective action.

5.

Fan auto start 5A.

Fans auto start on a LOCA OR LOP.

6.

Chill Water Pump trip 6A.

DISPATCH operator to determine cause of malfunction of Chill Water System/Pump.

6B.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

H-89-0, Sht. 1 J-105-0, Sht. 8 E-6790-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 37 of 54 Rev. 17 ATTACHMENT B1 NOMENCLATURE Control Area HVAC Fan Malfunction SETPOINT Multiple DESCRIPTION ORIGIN Various CRRA A(B)V415 malfunction (Control Room Return Air Fans)

AUTOMATIC ACTION:

None OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DETERMINE which fan malfunctioned A(B)V415 AND the parameter involved.
3. REFER TO HC.OP-AB.HVAC-0001(Q), HVAC.
4. IF there are any adverse affects on the Control Room instrumentation, IMPLEMENT HC.OP-AB.HVAC-0002(Q), Control Room Environment.

CAUSE CORRECTIVE ACTION

1. Low flow 1A.

OBSERVE Control Room indication AND DETERMINE IF low flow light is illuminated (alarm setpoint 18,500 - 20,350 scfm, trip at 10,125 scfm).

1B.

DETERMINE IF proper valve lineup exists for malfunctioning fan.

Continued next page

REFERENCES:

J-105-0, Sht. 8 H-89-0, Sht. 1 E-6790-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 38 of 54 Rev. 17 ATTACHMENT B1 CAUSE CORRECTIVE ACTION

2.

Loss of bus/control power 2A.

DISPATCH an EO to check A(B)V415 Brkr 52-431062(52-441062).

3. Fan trip 3A.

DETERMINE IF fan has tripped AND INITIATE corrective action.

4.

Fan auto start 4A.

Fans auto start on a LOCA OR LOP.

4B.

REQUEST SM/CRS to initiate corrective action.

REFERENCES:

J-105-0, Sht. 8 H-89-0, Sht. 1 E-6790-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 39 of 54 Rev. 17 ATTACHMENT B2 DRYWELL PURGE ISLN Window Location E6-B2 OVERRIDE OPERATOR ACTION:

1. DESELECT ISOLATION OVERRIDE Switch in Control Room.

This applies only IF the operator does not wish to override the Hi Hi radiation signal for the Reactor Building and/or Refuel Floor Ventilation Exhaust and/or Level 2 isolation signal(s).

2. NOTIFY SM/CRS of alarm condition.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action Amber isolation override light illuminated in control room N/A Overrides isolation signals on:

a. Hi Hi radiation in Reactor Bldg. Exhaust Plenum
b.

Hi Hi radiation in Refueling Floor Ventilation Exhaust Plenum

c.

Rx Wtr Level 2

REFERENCES:

E-6787-0 H-83-0, Sht. 1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 40 of 54 Rev. 17 ATTACHMENT B5 RB PRESSURE Window Location E6-B5 HI/LO OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. IF Reactor Building pressure is low START the standby fan (AV206 or BV206).
3. REFER TO HC.OP-AB.CONT-0003(Q), Reactor Building.
4. DISPATCH operator to determine cause of condition AND take appropriate action.
5. IF sufficient negative pressure cannot be maintained in the Reactor Building REFER TO T/S 3.6.5.
6. REFER TO HC.OP-EO.ZZ-0103(Q), Reactor Building Control, for possible entry condition.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5405 BV206 RUNNING REAC BLDG PRESS HI/LO Alarm only D5406 AV206 RUNNING REAC BLDG PRESS HI/LO Alarm only

REFERENCES:

E-6787-0 H-84-0, Sht. 1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 41 of 54 Rev. 17 ATTACHMENT C1 CONT AREA HVAC EXH Window Location E6-C1 PNL 1EC485 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH operator to Remote Control Panel EC485 to determine cause of alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D3170 CONT AREA EXH HVAC EC485 TRBL BV402 auto start on low flow signal from AV402 AV402 auto start on low flow signal from BV402 A(B)V402 trip on a CREF initiation (approx. 20 sec. T.D.)

REFERENCES:

H-89-0, Sht. 1 E-6790-0 CD-181X FSAR 6.5.1.1.2

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 42 of 54 Rev. 17 ATTACHMENT C2 DIESEL AREA HVAC PANEL Window Location E6-C2 1EC483 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH an operator to local Panel 1EC483 to determine cause of alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5182 DSL AREA HVAC PNL EC483 Alarm only for all except smoke detection.

IF smoke is detected in the Wing Area Exhaust duct by Smoke Detectors XSH-9022, XSH-9029 OR XSH-9032 then fans1A(B)V414 AND 1A(B)V304 auto trip.

D5226 DSL AREA BTRY RM 5545 FLOW Alarm only D5227 DSL AREA BTRY RM 5541 FLOW Alarm only D5228 DSL AREA BTRY RM 5543 FLOW Alarm only D5229 DSL AREA BTRY RM 5539 FLOW Alarm only

REFERENCES:

E-6790-0 H-88-0, Sht. 1 H-89-0, Sht. 1 M-89-1 M-78-1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 43 of 54 Rev. 17 ATTACHMENT C5 RBVS & WING AREA HVAC Window Location E6-C5 PNL 10C382 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. REFER TO HC.OP-AB.CONT-0003(Q), Reactor Building.
3. DISPATCH an operator to the Remote Control Panel 10C382 to determine cause of alarm.
4. IF a low flow condition exists ENSURE standby fan(s) auto start to maintain a negative pressure in Secondary Containment.
5. REFER TO T/S 3.6.5.2.

NOTE The ORANGE DOT indicates the MCR annunciator will clear when the associated local panel annunciator is acknowledged. Thus with the MCR annunciator clear, the local panel may or may not be in alarm. If the local panel is not acknowledged, the MCR annunciator will be lit and will not re-alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D3960 RBVS EXH RTM PNL C382 Low flow condition on operating fan results in fan trip AND auto start of standby fan(s).

D3961 RBVS SUPPLY RTM PNL C382 Low flow condition on operating fan results in fan trip AND auto start of standby fan(s).

D3198 WING AREA SUPL HVAC 0C382 Alarm only

REFERENCES:

E-6787-0 CD-443A SER 060-81 H-83-0, Sht. 1 H-84-0, Sht. 1 H-89-0, Sht. 8; Sht. 13

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 44 of 54 Rev. 17 ATTACHMENT D1 CABLE TRAY AREA HVAC Window Location E6-D1 PNL 00C383 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH a Radwaste Operator to the Remote Control Panel 00C383 to determine cause of alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D2385 UNT CLRS/HTRS RCP-0C383 TRBL WITH room temperature > 90°F AND fan in auto, fan auto starts.

REFERENCES:

H-92-0, Sht. 1 E-6790-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 45 of 54 Rev. 17 ATTACHMENT D2 DIESEL AREA HVAC 1E PNL Window Location E6-D2 1EC486 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH an operator to Panel 1EC486 to determine cause of alarm.

NOTE For battery room low flow alarms resulting from planned maintenance, an entry into HC.OP-AB.HVAC-0001 is not required. In this situation guidance in HC.OP-GP.ZZ-0010(Q) should be followed.

3. REFER TO HC.OP-AB.HVAC-0001(Q), HVAC.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5742 DIESEL 1E PANEL RM HVAC EC486 Alarm only D5234 DSL AREA BTRY RM 5614 FLOW Alarm only D5235 DSL AREA BTRY RM 5609 FLOW Alarm only D5236 DSL AREA BTRY RM 5626 FLOW Alarm only D5237 DSL AREA BTRY RM 5627 FLOW Alarm only

REFERENCES:

E-6790-0 H-88-0, Sht. 1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 46 of 54 Rev. 17 ATTACHMENT D5 FRVS VENT FAN Window Location E6-D5 MALFUNCTION OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Radiation Protection of fan auto start.
3. REFER TO HC.OP-AB.CONT-0003(Q), Reactor Building.
4. DETERMINE IF an auto start has occurred on the standby fan.
5. REFER TO Technical Specification 3/4.6.5.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5407 FRVS VENT FAN BV206 TROUBLE Standby fan auto starts on low flow WITH an initiation signal (level 2, hi hi rad in Reactor Bldg OR Refuel Floor; LOCA and LOP)

D5408 FRVS VENT FAN AV206 TROUBLE Standby fan auto starts on low flow WITH an initiation signal (level 2, hi hi rad in Reactor Bldg OR Refuel Floor; LOCA and LOP)

REFERENCES:

H-84-0, Sht. 1 E-6787-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 47 of 54 Rev. 17 ATTACHMENT E1 SVCE AREA SUPPLY Window Location E6-E1 PNL 00C181 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH operator to Remote Control Panel 00C181 to determine cause of alarm.
3. IF a fire alarm is present DISPATCH Site Protection.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5196 SERVICE AREA SUPPLY HVAC PNL 00C181 TROUBLE Alarm only for all except smoke detection.

IF smoke is detected by Smoke Detectors XSH-9022 OR XSH-9023 in the Service Area Supply System return air duct THEN the SAS System Fan 0AVH131 (0BVH131) will automatically trip.

REFERENCES:

H-93-0, Sht. 1 M-79-0, Sht. 1 M-93-0, Sht. 1 E-6790-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 48 of 54 Rev. 17 ATTACHMENT E2 RADWASTE &

SAE HVAC Window Location E6-E2 PNL 00C381 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH Radwaste Operator to Remote Control Panel 00C381 to determine cause of alarm.

NOTE The ORANGE DOT indicates the MCR annunciator will clear when the associated local panel annunciator is acknowledged. Thus with the MCR annunciator clear, the local panel may or may not be in alarm. IF the local panel is not acknowledged, the MCR annunciator will be lit and will not re-alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5191 RDWST SUPPLY SYS RCP-0C381 TRBL Alarm only for all except Smoke Detection.

IF smoke is detected in Exhaust air duct by Smoke Detector XSH-9018 THEN Fan VA308(0BV308) auto trips.

REFERENCES:

E-6790-0 H-92-0, Sht. 1 H-93-0, Sht. 1 M-93-0, Sht. 1 M-79-0, Sht. 1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 49 of 54 Rev. 17 ATTACHMENT E3 CHEM LAB EXH HVAC Window Location E6-E3 PNL 00C392 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. NOTIFY Chemistry Hot Lab IF required.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5198 CHEMISTRY LAB EXH HVAC IF a low flow condition exists on 0A(B)V307 the standby fan auto starts.

REFERENCES:

E-6790-0 H-93-0, Sht. 1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 50 of 54 Rev. 17 ATTACHMENT E5 FRVS RECIRC FAN Window Location E6-E5 TROUBLE OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DETERMINE which fan initiated the trouble alarm.
3. DISPATCH operator to determine the specific cause of the malfunction.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5474 FRVS RECIRC MOT AV213 &

EV213 IF low flow initiated the trouble alarm (AV-213), E(F)V213 auto starts.

D5451 FRVS RECIRC MOT BV213 &

FV213 IF low flow initiated the trouble alarm (BV-213), E(F)V213 auto starts.

D5475 FRVS RECIRC MOT CV213 IF low flow initiated the trouble alarm (CV-213), E(F)V213 auto starts.

D5476 FRVS RECIRC MOT DV213 IF low flow initiated the trouble alarm (DV-213), E(F)V213 auto starts.

REFERENCES:

H-83-0, Sht. 1 E-6787-0 J-105-0, Sht. 8

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 51 of 54 Rev. 17 ATTACHMENT F1 SOLID RADW SUPPLY/EXH Window Location E6-F1 PNL 00C380 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH Radwaste operator to Panel 00C380 to determine cause of the alarm.
3. IF a fire alarm is present DISPATCH Site Protection.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5744 SOLID RDWST HVAC RCP0C380 TRBL Alarm only for all except smoke detection.

IF smoke is detected in Solid Radwaste Area exhaust air duct by Smoke Detector XSH-9024 OR XSH-9028, THEN Fan 0A(B)V318 is auto trips.

REFERENCES:

E-6790-0 H-92-0, Sht. 1 M-91-0, Sht. 3 M-92-0, Sht. 2

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 52 of 54 Rev. 17 ATTACHMENT F2 RADWASTE TK FILTER HVAC Window Location E6-F2 PNL 00C385 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH Radwaste Operator to Panel 00C385 to determine cause of the alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5192 RDWST TK FLTR SY RCP Alarm only 0C385 TRBL

REFERENCES:

E-6790-0 H-92-0, Sht. 1

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 53 of 54 Rev. 17 ATTACHMENT F3 AUX BOILER BLDG HVAC Window Location E6-F3 PNL 00C591 OPERATOR ACTION:

1. NOTIFY SM/CRS of alarm condition.
2. DISPATCH operator to Panel 00C591 to determine cause of the alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D4169 BLR SUBSTA WTR PRETREAT HVAC Alarm only

REFERENCES:

H-95-0, Sht. 1 E-6792-0

HC.OP-AR.ZZ-0019(Q)

Hope Creek Page 54 of 54 Rev. 17 ATTACHMENT F4 ASPH STOR BLDG HVAC Window Location E6-F4 PNL 00C580 OPERATOR ACTION:

NOTIFY Radwaste operator of Local Panel 00C580 alarm.

INPUTS Digital Point/

Indication Nomenclature/Condition Automatic Action D5766 ASPH STOR BLDG HVAC0C580 TRBL Alarm Only

REFERENCES:

H-95-0, Sht. 1