ML103260299

From kanterella
Jump to navigation Jump to search
Notification of Potential Part 21 Reportable Condition: Reverse Polarity on HPCI Turbine EG-R Hydraulic Actuators
ML103260299
Person / Time
Site: Hatch, Peach Bottom, Hope Creek  
Issue date: 11/19/2010
From: Porter D
GE-Hitachi Nuclear Energy Americas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
46429, MFN 10-343
Download: ML103260299 (7)


Text

1111912010 U.S. Nuclear Regulatory Commission Operations Center Event Report Pa,-e I General Information or Other (PAR)

Event#

46429 Rep Org: GE HITACHI NUCLEAR ENERGY Notification Date /Time: 11/19/2010 08:33 (EST)

Supplier: GE HITACHI NUCLEAR ENERGY Event Date / Time: 11/18/2010 (EST)

Last Modification: 11/19/2010 Region:

1 Docket #:

City:

WILMINGTON Agreement State:

Yes County:

License #:

State: NC NRC Notified by: DALE PORTER Notifications:

HAROLD GRAY R1DO HQ Ops Officer: PETE SNYDER ALAN BLAMEY R2DO Emergency Class: NON EMERGENCY NRR PART 21 GROUP EMAIL 10 CFR Section:

21.21 UNSPECIFIED PARAGRAPH POTENTIAL FOR REVERSE POLARITY ON HPCI TURBINE EG-R HYDRAULIC ACTUATORS "GE Hitachi Nuclear Energy (GEH) has completed an evaluation of the 'Reverse Polarity on HPCI EG-R Hydraulic Actuators,' and has concluded that this is a Reportable Condition in accordance with the requirements of 10 CFR 21.21 (d).

"Discussion:

"GEH provided a refurbished HPCI turbine EG-R Hydraulic Actuator, (GEH Part number DD213A8527P003), as a safety related component, to a domestic BWR/4. When the customer installed the EG-R Hydraulic Actuator at the plant, calibration and post maintenance testing found that the turbine governor valves went to the full open position when the proper response was a fully closed position. Troubleshooting of the newly installed component revealed that the polarity of the component was reversed. An improperly configured EG-R Hydraulic Actuator cannot be utilized in the system because the reversed polarity causes the turbine governor control valves to operate in a manner opposite to the expected response, and calibration of the component by plant personnel cannot be completed.

"GEH contracted Engine Systems Incorporated (ESI) to perform the repair/refurbishment of this EG-R Hydraulic Actuator. This particular EG-R Hydraulic Actuator is identified as GEH part number DD213A8527P003. The specific EG-R Hydraulic Actuator that was identified with this defective condition was identified as serial number 2288717.

"Conclusion:

"This condition would change the operational characteristics of the HPCI system and would create a Substantial Safety Hazard or a violation of a Technical Specification Safety Limit. As such this condition has been determined to be a Reportable Condition within the context of 10 CFR Part 21.21 (d).

11/19/2010 U.S. Nuclear Regulatory Commission Operations Center Event Report Page 2 General Information or Other (PAR)

Event #

46429 "ABWR and ESBWR Design Certification Documentation Applicability:

"The issues described above have been reviewed for applicability to documentation associated with 10CFR 52 and it has been determined that there is no affect on the technical information contained in either the ABWR certified design or the ESBWR design in certification.

"Recommended Action:

"GEH recommends that [the Hatch, Hope Creek and Peach Bottom] sites that have received EG-R Hydraulic Actuator(s) (GEH Part number DD213A8527P003), check warehouse inventory. If the EG-R Hydraulic Actuator remains 'in stock,' the potential exists that incorrect internal wiring could exist resulting in the EG-R Hydraulic Actuator not responding as expected. GEH recommends that if an EG-R Hydraulic Actuator (GEH Part number DD213A8527P003) is in warehouse stock, that the component be returned to GEH for verification of the internal wiring configuration."

9106024965 ATC 2nd FLOOR 09:45:11 a.m.

11-19-2010 1 /5 HITACHI GE Hitachi Nuclear Energy Dale E. Porter GE-Hilachi Nuclear Energy Americas LLC Safety Evaluation Program Manager 3901 Castle Hayne Rd.,

Wilmington, NC 28401 USA T 910 819-4491 November 18, 2010 Dale.Porter@GE.Com MFN 10-343 Attn: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001

Subject:

Part 21 Reportable Condition Notification:

Reverse Polarity on HPCI Turbine EG-R Hydraulic Actuators GE Hitachi Nuclear Energy (GEH) has completed an evaluation of the "Reverse Polarity on HPCI EG-R Hydraulic Actuators", and has concluded that this is a Reportable Condition in accordance with the requirements of IOCFR 21.21 (d).

Discussion GEH provided a refurbished HPCI turbine EG-R Hydraulic Actuator, (GEH Part number DD213A8527P003), as a safety related component, to a domestic BWR/4. When the customer installed the EG-R Hydraulic Actuator at the plant, calibration and post maintenance testing found that the turbine governor valves went to the full open position when the proper response was a fully closed position.

Troubleshooting of the newly installed component revealed that the polarity of the component was reversed.

An improperly configured EG-R Hydraulic Actuator cannot be utilized in the system because the reversed polarity causes the turbine governor control valves to operate in a manner opposite to the expected response, and calibration of the component by plant personnel cannot be completed.

GEH contracted Engine Systems Incorporated (ESI) to perform the repair/refurbishment of this EG-R Hydraulic Actuator. This particular EG-R Hydraulic Actuator is identified as GEH part number DD213A8527P003. The specific EG-R Hydraulic Actuator that was identified with this defective condition was identified as serial number 2288717.

Conclusion This condition would change the operational characteristics of the HPCI system and would create a Substantial Safety Hazard or a violation of a Technical Specification Safety Limit.

As such this condition has been determined to be a Reportable Condition within the context of 1 OCFR Part 21.21(d).

9106024965 ATC 2nd FLOOR 09:45:57 a.m.

11-19-2010 2/5 MFN 10-343 Page 2 of 2 ABWR and ESBWR Design Certification Documentation Applicability The issues described above have been reviewed for applicability to documentation associated with 10CFR 52 and it has been determined that there is no affect on the technical information contained in either the ABWR certified design or the ESBWR design in certification.

Recommended Action GEH recommends that sites that have received EG-R Hydraulic Actuator(s) (GEH Part number DD213A8527P003), as identified in Attachment 1 and 2, check warehouse inventory.

If the EG-R Hydraulic Actuator remains "in stock", the potential exists that incorrect internal wiring could exist resulting in the EG-R Hydraulic Actuator not responding as expected.

GEH recommends that if an EG-R Hydraulic Actuator (GEH Part number DD213A8527P003) is in warehouse stock, that the component be returned to GEH for verification of the internal wiring configuration.

Additional information as required by §21.21(d)(4) is provided in Attachment 2.

If you have any questions, please call me at (910) 819-4491.

Sincerely, Dale E. Porter Safety Evaluation Program Manager GE-Hitachi Nuclear Energy Americas LLC Attachments:

1. US Plants With Potentially Affected HPCI EG-R Actuators
2. Reportable Condition Notification Information per §21.21(d)(4) cc:

S. S. Philpott, USNRC S. J. Pannier, USNRC

0. Tabatabai-Yazdi, USNRC J. G. Head, GEH P. L. Campbell, GEH Washington PRC 10-10 File eDRF 0000-0125-3972

9106024965 ATC 2nd FLOOR 09:46:34 a.m.

11-19-2010 3/5 MFN 10-343 Page 1 of 1 Attachment I US Plants With Potentially Affected HPCI EG-R Actuators Utility Plant x

x x

Exelon Generation Co.

PSEG Services Corp.

Southern Nuclear Operating Co.

Peach Bottom 2 &3 Hope Creek Hatch 1 & 2

9106024965 ATC 2nd FLOOR 09:46:52 a.m.

11-19-2010 4/5 MFN 10-343 Page 1 of 2 Reportable Condition Notification Information per §21.21(d)(4)

(i)

Name and address of the individual or individuals informing the Commission:

Dale E. Porter Safety Evaluation Program Manager, GE Hitachi Nuclear Energy 3901 Castle Hayne Road, Wilmington, NC 28401 (ii) identification of the facility, the activity, or the basic component supplied for such facility or such activity within the United States which fails to comply or contains a defect:

The basic component that failed is an EG-R Hydraulic Actuator that is part of the HPCI turbine speed control system.

This component is identified as GE Hitachi Nuclear Energy Part Number DD213A8527P003.

(iii)

Identification of the firm constructing the facility or supplying the basic component which falls to comply or contains a defect:

The EG-R Hydraulic Actuator is rebuilt by GEH supplier Engine Systems Incorporated (ESI) and supplied by GEH to the plants listed in item vi below.

(iv)

Nature of the defect or failure to comply and the safety hazard which is created or could be created by such a defect or failure to comply:

The defect is reversed #1 and #4 wires internal to the EG-R Hydraulic Actuator. The reversed wires result in a reversed polarity, which controls the null setting.

This setting results in the HPCI turbine governor control valves moving in the opposite direction than expected and ultimately closing and preventing HPCI turbine operation.

If present, this defect will be identified during initial post maintenance testing and calibration of the governor system associated with its installation.

(v)

The date on which the information of such defect or failure to comply was obtained:

A Potential Reportable Condition evaluation was initiated by GEH in accordance with 10CFR Part 21 and GEH procedures on October 7, 2010.

(vi)

In the case of a basic component which contains a defect or failure to comply, the number and the locations of these components in use at, supplied for, being supplied for, or may be supplied for, manufactured, or being manufactured for one or more facilities or activities subject to the regulations in this part:

9106024965 ATC 2nd FLOOR 09:47:38 a.m.

11-19-2010 5/5 MFN 10-343 Page 2 of 2 GEH has determined that the EG-R Hydraulic Actuator DD213A8527P003 has been supplied to the following customers:

Part Number Plant EGR GEH Customer Ship Serial #

PO #

PO #

Date DD213A8527P003 Hatch 2431079 01022750 6048020 6/11/01 DD213A8527P003 Hatch 11920471 01024821 6049829 10/09/01 DD213A8527P003 Hatch 11920473 437003332 6072891 4/7/08 (Item 2)

(Item 2)

DD213A8527P003 Hatch 2288717 437003332 6072891 4/14/08 (Item 1)

(item 1)

DD213A8527P003 Hope 2431080 31003977 4500282564 3/30/06 1 Creek DD213A8527P003 Peach 11412667 01026215 90 187581 1/14/02 Bottom I

(vii)

The corrective action which has been, is being, or will be taken; the name of the individual or organization responsible for the action; and the length of time that has been or will be taken to complete the action:

GEH contacted ESI to determine the cause of the reversed wiring. ESI stated that they had previously identified the potential for reversed wiring that controls the null setting. ESI revised Dedication Report GA-WOOD-GOV-RR-1 Rev 2 on December 4, 2008 to visually inspect wiring and ensure it is connected correctly to verify that the HPCI governor control valves operate as expected.

(viii)

Any advice related to the defect or failure to comply about the facility, activity, or basic component that has been, is being, or will be given to purchasers or licensees:

If the EG-R Hydraulic Actuator has been installed and functional testing completed successfully, the functional testing provides complete verification and assurance that the EG-R Hydraulic Actuator contains the correct wiring configuration.

GEH recommends that sites that have received EG-R Hydraulic Actuator(s) (GEH Part number DD213A8527P003) check warehouse inventory to determine if that EG-R Hydraulic Actuator is "in stock". The potential exists that incorrect internal wiring could exist resulting in the EG-R Hydraulic Actuator not responding as expected.

GEH recommends that if an EG-R Hydraulic Actuator (GEH Part number DD213A8527P003) is in warehouse stock, that the component be returned to GEH for verification of the internal wiring configuration.

(ix)

In the case of an early site permit, the entities to whom an early site permit was transferred.

There are no early site permit concerns.