Text
From:
BENNETT, STEVE A [sbenne2@entergy.com]
Sent:
Wednesday, October 27, 2010 10:04 AM To:
Kalyanam, Kaly
Subject:
FW: Corrections to NRC SER on Relief Approval for Leak Testing of Waterford Hatch Attachments:
NRC LLRT Relief SER Corrections.pdf Attached.
Steve A Bennett Office: 479-858-4683 Cell: 479-970-5875 From: BENNETT, STEVE A Sent: Thursday, September 23, 2010 8:21 AM To: 'Kalyanam, Kaly' Cc: STEELMAN, WILLIAM J
Subject:
Corrections to NRC SER on Relief Approval for Leak Testing of Waterford Hatch
- Kaly, We have noted several statements in the May 18, 2010 ASME Relief Request approval that reflected the precedent relief approval of Watts Bar instead of Waterford. I have attached a markup of the pages with what I would propose as corrected wording from our relief request.
Here is some explanation:
Page 5 - Waterford will be opening a preexisting hatch cover in the side of the steel containment for movement of the SGs and head. Watts Bar made two openings in their containment roof.
Page 6 - The reference to the 2001 Code through 2003 Addenda is correct. However, our Code of record is 1971 through Summer 1971 Addenda. I would just remove the Code of Record statement.
Page 6 - Per our relief we are proposing performing either an MT or a PT of the weld preparation surfaces which will be performed prior to actually installing the repair weld for the hatch cover. Watts Bar performed an exam of the weld back gouge which was performed after initial welding.
Page 6 - The Waterford test/accident pressure is 44psig. Watts Bar was 15 psig Page 6 - The reference to only the ASNT CP-189 NDE qualification standard is consistent with our relief request.
If you have questions, call or email me.
Steve Bennett 479-858-4683 (cell) 479-970-5875 E-mail Properties Mail Envelope Properties (7236666209BB3A4B9EF3FAF53D4EFCD9092CAB43)
Subject:
FW: Corrections to NRC SER on Relief Approval for Leak Testing of Waterford Hatch
Sent Date: 10/27/2010 10:04:06 AM Received Date: 10/27/2010 10:04:06 AM From: BENNETT, STEVE A Created By: sbenne2@entergy.com Recipients:
Kaly.Kalyanam@nrc.gov (Kalyanam, Kaly)
Tracking Status: None Post Office:
LITEXETSP001.etrsouth.corp.entergy.com Files Size Date & Time MESSAGE 187091 10/27/2010 NRC LLRT Relief SER Corrections.pdf 175158 Options Expiration Date:
Priority: olImportanceNormal ReplyRequested: False Return Notification: False Sensitivity: olNormal Recipients received: