Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 October 12, 2010 State of Tennessee Department of Environment and Conservation Division of Water Pollution Control Enforcement & Compliance Section 61h Floor, L & C Annex 401 Church Street Nashville, Tennessee 37243-1534
Dear Mr. Patrick Cromer:
SEQUOYAH NUCLEAR PLANT - DISCHARGE MONITORING REPORT FOR SEPTEMBER 2010 Enclosed is the September 2010 Discharge Monitoring Report for Sequoyah Nuclear Plant.
On September 22, 2010 at approximately 2130 EDT, a fire occurred while placing a non-polychlorinated biphenyl (PCB) transformer in service following routine maintenance. As a result of the fire, approximately 13,000 gallons of insulating oil spilled from the transformer into the surrounding gravel switchyard. The secondary containment for the switchyard is the Yard Drainage Pond. A permanent oil skimmer is located on the discharge of the Yard Drainage Pond prior to entry into the Diffuser Pond. TVA mobilized its Emergency Response Team and began recovering the spilled mineral oil. As of today, no oil has been released into Waters of U.S. (e.g., Diffuser Pond). This has been verified by both visual examination and oil and grease analysis. Cleanup continues at both the Yard Drainage Pond and the switchyard where the spill occurred.
If you have any questions or need additional information, please contact Stephanie Howard at (423) 843-6700 of Sequoyah's Environmental staff.
I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
Sincerely.,
Christophe R. Church Site Vice President Sequoyah Nuclear Plant Enclosure cc (Enclosure):
Chattanooga Environmental Field Office U.S. Nuclear Regulatory Commission Division of Water Pollution Control ATTN: DocumentControl Desk State Office Building, Suite 550 Washington, D.C. 20555 540 McCallie Avenue Chattanooga, Tennessee 37402-2013
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEQUOYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SON)
SODDY - DAISY TN 37384 Facility TVA - SEQUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) MAJOR DISCHARGE MONITORING REPORT (DMR)
(SUBR 01)
TN0026450
}101 G
F-FINAL PERMIT NUMBER LI1SHARGE NUMBER DIFFUSER DISCHARGE Form Approved.
OMB No. 2040-0004 IMrt" lD IrIr,1 nDI Pn I
EFFLUENT SuI From 0
T°A 1
- 3.
NO DISCHARGE
[:
NOTE: Read instructions before completinq this form.
ATTN: Stephanie A. Howard PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS ANALYSIS TEMPERATURE, WATER DEG.
SAMPLE
- 29.0 04 0
30/30 MODELD CENTIGRADE MEASUREMENT 00010 Z
0 0
REUREEPERMIT*
+/-;.
L2'****;**I
'***"*:;"4.
DEG. C.
SEE CK REQ" INSTREAM MONITORING DAL MX PERMI TEMPERATURE, WATER DEG.
SAMPLE 38.7 04 0
30 / 30 RCORDR CENTIGRADE MEASUREMENT 00010 1
0 0
"PERMIT:-
REPORT DEG.C.
SEE CKREQ REQUIREMENT :;.*-::, :*i:-*'*.:'***:*
EFFLUENT GROSS VALUE
.:R,.UIRMENT*-
.DAILY MX PERMIT TEMP. DIFF. BETWEEN SAMP. &
SAMPLE
- 2.2 04 0
30 / 30 CALCTD UPSTRM DEG.C MEASUREMENT 00016 1
S 0
..PERMI 330 DEG.C.
CONTIN CALCTD EFFLUENT GROSS VALUE E0-.o.I--
L-DAILYIMX.
UOUS: !,
PH SAMPLE 7.6 8.1 12 0
7/30 GRAB MEASUREMENT 00400 1
0 0
--- PERMIT,-
- 60 9.0 SU WEEKLY
- -GRAB' EFFLUENT GROSS VALUE RE-UIREMENT i!.'L.J'tx;'A.,
MINIMUM MAXIMUM SOLIDS, TOTAL SUSPENDED SAMPLE
- 7.
9 19 0
2 / 30 GRAB MEASUREMENT 00530 1
0 0
PERMIT
-' 30_
100.
MGIL N'
MONTHLYY
.GRAB 00530 1
0 0
- I*REQUIREM*/ENT'r 7"ý;:
' *-; t:
-",* d EFFLUENT GROSS VALUE RELEETMO AVGT DAILY MX OIL AND GREASE SAMPLE
<5
<5 19 0
2 / 30 GRAB MEASUREMENT 00556 1
0 0
rPRI:,
~
,,,,T52 GL MNHYGRAB EFFLUENT GROSS VALUE REQUIREMENT!
-MOA
- DAILY M.X
,OH_
__G B
FLOW, IN CONDUIT OR THRU SAMPLE 1661 03 0
30 / 30 RCORDR TREATMENT PLANT MEASUREMENT 50050 1
0 0
PERMrrZ ****-**
REPORT MGD CONTIN RCORDR REOUIREMENT.-.:i-ALYM EFFLUENT GROSS VALUE' MR"-,-:-
'-_AYM.
UOUS:
NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my TELEPHONE DATE UlirectUIo or supervision in accordance with a system designed to assure that qualified personnel TEEP ON DATE_____________
Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the Sequoyah Site Vice President Sequoyah Site Vice President information, the information submitted is, to the best of my knowledge and belief, true,
__423 843-7001 10 10 07 accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT.
AREA NUMBER YEAR MO DAY TYPED OR PRINTED CODE COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments he; No closed mode operation. The following information is included in an attachment: 1. CCW data 2. veliger monitoring data EPA Form 3320-1 (REV 3/99)
Previous editions may be used Page 1 of 2
DMR Attachment CCW Data CCW TRENCH Extractable Petroleum Date/Time Collected Hydrocarbons Analysis Date/Time Analyst Method No water would come out of the pump. No sample could be obtained.
CCW CHANNEL Extractable Petroleum Date/Time Collected Hydrocarbons Analysis Date/Time Analyst Method 09/15/2010@ 1025
<0.10mg/I 09/17/2010@0108
'JDB EPH
Mean# of Sample Date M/3of
% Settlers Water Sample Date Asiatic
/0/m3 Temp. (')
Sampl Dae Z~.Clams/m3 11/03/2009 11/10/2009 11/17/2009 11/24/2009 12/01/2009 12/08/2009 01/05/2010 01/12/2010 01/19/2010 01/26/2010 02/02/2010 02/09/2010 02/16/2010 02/23/2010 03/02/2010 03/09/2010 03/16/2010 03/23/2010 03/30/2010 Apr-2010 May-2010 Jun-2010 Jul-2010 Aug-20 10 Sep-20 10 133 417 269 36 32 38 0
0 0
32 0
0 0
.11.7 0
0 0
14 0
0 6.1 0
50 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
16 11/03/2009 16 11/10/2009 16 11/17/2009 15 11/24/2009 13.5 12/01/2009 11 12/08/2009 6
01/05/2010 5
01/12/2010 6
01/19/2010 7.5 01/26/2009 7
02/02/2010 8
02/09/2010 5
02/16/2010 7
02/23/2010 6
03/02/2010 8
03/09/2010 10 03/16/2010 11 03/23/2010 14 03/30/2010 76 25
.0.
18 0
0 0
0 0
0 0
0 0
0 0
0 0
0
.0 Water SUB NOTES: %
LOCATION Gravid Asiatic COLLECTED BY Temp. (°C)
LOCATION Ca Clam 16 Inplant RCW CMW 16 Inplant RCW CMW 16 Inplant RCW CMW 15 Inplant RCW CMW 13.5 Inplant RCW WE 11 Inplant RCW CMW 6
Inplant RCW B
5 Inplant RCW 6
Inplant RCW P
7.5 Inplant RCW NRT 7
Inplant RCW MSW/WDT 8
Inplant RCW BL/TC 5
Inplant RCW BJ 7
Inplant RCW BJ 6
Inplant RCW PB 8
Inplant RCW MJW 10 Inplant RCW BC 11 Inplant RCW BC 14 Inplant RCW BAPO no samples collected no samples collected no samples collected no samples collected no samples collected no samples collected
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEOUOYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SON)
SODDY -
AISY. TN 37384 Facility TVA - SEQUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY ATTN: Stephanie A. Howard NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) MAJOR DISCHARGE MONITORING REPORT (DMR)
(SUBR 01)
TN0026450
[101
]F-FINAL PERMIT NUMBER LD-ISCHARGE NUMBElRJ DIFFUSER DISCHARGE L
M ON[TlRING_-_ E
.J J
EFFLUENT FromI 1o 9
o1 TO LE10_f W1
.. NO DISCHARGE NOTE: Read instruction.
Form Approved.
OMB No. 2040-0004 s before completinq this form.
PARAMETER FREQUENCY SAMPLE PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
.EX FREQUENCY OF ANALYSIS SAMPLE TYPE AVERAGE UNITS MINIMUM MAXIMUM UNITS AVERAGE MAXIMUM AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS CHLORINE, TOTAL RESIDUAL SAMPLE 0.017 0.045 19 0
37/30 GRAB MEASUREMENT 50060
.1 0
0
- PERMIT, 0.10
.1 M'IL EE.......
EFFLUENT GROSS VALUEREQUIREMENT 01
.1 GLVVE-'CLI&
EFFUEN GRSS ALU
~--~:
MO AVG ~ISM X DAYS TEMPERATURE - C, RATE OF SAMPLE 0
0 30/30 CALCTD CHANGE MEASUREMENT 62 3
0, 82234 1
0 0
PERMIT*
2-DEG
<4-'>';***'*;;<;;
- 1.
ONTIN.
CALCTD.
EFFLUENT GROSS VALUE
.UI.I R
T, DAILY MX ClHR
'...uous SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT PERMIT.4 ~
<14~
44
~REQUIREOMFNT~<
6-r 4 4 4
<4~444 SAMPLE MEASUREMENT SAMPLE MEASUREMENT 44PERMIT~.<(
74 REQUIREMENT 4"4 4-SAMPLE MEASUREMENT
<PERMIT<<4 444 4444 4
MEASUREMENT NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all altachments were prepared under my TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified personnel Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the Sequoyah Site Vice President information, the information submitted is, to the best of my knowledge and belief, true,
"_423 843-7001 10 10 07 Sequoyah Site Vice President accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE information, including the possibility of fine and imprisonment for knowing violations OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY TYPED OR PRINTED OFFICERORAUTHORIZEDAGENT AODEANUMBERYEARMO DAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Referenceallattachmentshet The following injections occurred: 1. Floguard MS6236 (max. calc. conc. was 0.038mg/L--limit 0.2mg/L) 2. Spectrus CT1300 (max. calc. conc. was 0040mg/L-limit 0.050mg/L) 3. Spectrus CT1300 (low
.detection level analytical method was <0.050mg/L--limit 0.050mg/L)
Page 2f 2
EPA Form 3320-1 (REV 3199)
Previous editions may be used Page 2 of 2
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEQUOYAH NUCLEAR PLANT Address P.O. BOX 2000
-(INTEROFFICE SB-2A-SQN)
SODDY - DAISY. TN 37384 Facilitv TVA - SEOUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY ATTN: Stephanie A. Howard NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) MAJOR DISCHARGE MONITORING REPORT (DMR)
(SUBR 01)
TN0026450 101 Q
F-FINAL PERMIT NUMBER
[ DISCHARGE NUMBER DIFFUSER DISCHARGE MONITnRINfLPERIOD IEFFLUENT From 10 07 01 To i0109 30 NO DiSCHARGE Z Form Approved.
OMB No. 2040-0004 NUO I R:
Iead instruclions before complelinq this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS ANALYSIS BORON, TOTAL SAMPLE
<0.20 1
0 3/92 MEASUREMENT 9
01022 1
0 0
~
-PERMIT
- ?.
REPORT<
q MG/L
"~~ORy
~~R EFFLUENT GROSS VALUE REOUIREMEN I; i:7>
TJ SAMPLE MEASUREMENT REQUIREMENT SAMPLE MEASUREMENT SAMPLE REAUIREMENT SAMPLE MEASUREMENT
~~REQUIREMENT SAMPLE MEASUREMENT
'-PE RMIT
'-?55.5,
~
ssi..
~
.5,>
5 5~
SAMPLE MEASUREMENT P.5,4"'
MEASURlEMENT NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my V/.s" TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified personnel Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the Sequoyah information, the information submitted is, to ihe best of my knowledge and belief, true, 423 843-7001 10 10 07 Sequoyah Site Vice President accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE
__l TYPEDORPRINTED information, including the possibility of fine and imprisonment for knowing violalions.
OFFICER OR AUTHORIZED AGENT NUMBER YEAR MO DAY TYPED OR PRINTED______________________________________________________
COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments het Boron was sampled on 7/7/10.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facilitv Name/Location if Different)
Name TVA - SEOUOYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SON)
SODDY - DAISY. TN 37384 FacilitY TVA - SEOUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES). MAJOR DISCHARGE MONITORING REPORT (DMR)
(SUBR 01)
Form Approved.
OMB No. 2040-0004 TN0026450 101 F-FINAL PMIT NUMBER DISCHARGE NUMBER BIOMONITORING FOR OUTFALL 101 I
I M)NITQPI N(, Pplllnn I
EFFLUENT Fromr A
10 0
I M
.. NO DISCHARGE E-]
__________________________From_
1_______
NO 1
09 1ea Intucin 1eor Tooetn thi rm ATTN: Stephanie A. Howard NOTE P: R~ead instructions before completing this form.*
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS ANALYSIS IC25 STATRE 7DAY CHR SAMPLE Monitoring 23 CERIODAPHNIA MEASUREMENT Not Required23 TRP3B 1
0 0
._ PERMITR.
45.2 PERCENT SEE COMPOS
'REQUIREMENT.
EFFLUENT GROSS VALUE
.W....-MINIMUM,
__PERMIT IC25 STATRE 7DAY CHR SAMPLE
'Monitoring 23 PIMEPHALES MEASUREMENT Not Required23 TRP6C 1
0 0
PERMI T-.*,
.**452 PERCENT SEE COMPOS EFFLUENT GROSS VALUE REQUIE N
MIMINU. '
PERMIT SAMPLE MEASUREMENT
~~PERMIT-SAMPLE MEASUREMENT SAMPLE MEASUREMENT
';REQUIREMENT,ý SAMPLE MEASUREMENT
-.I-PERMIT REQUIREMENT' SAMPLE MEASUREMENT NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified personnel Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the Sequoyah Site Vice Presid 8471 0
0 information, the information submitted is, to the best of my knowledge and belief, true, 423 843-7001 10 10 07 Sequoyah Site Vice President accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY TYPED OR PRINTED OFFCOERDOR__UTHORIZEDAGENTAREANUMBERYEARMODAY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments hef Toxicity was not sampled in September 2010.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEOUOYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SON)
SODDY - DAISY. TN 37384 Facility TVA - SEQUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
MAJOR DISCHARGE MONITORING REPORT (DMR)
L TN°0264u 0
_I103 G
PERMIT NUMBER I
DISCHARGE NUMBERI Form Approved.
OMB No. 2040-0004 (SUBR 01)
F - FINAL I
LOW VOL. WASTE TREATMENT POND EFFLUENT
ý__MQQN I-AN1fRING-P E R 10
.4 ATTN: Stephanie A. Howard From L E jLjo I ojjI o
TO E 0 0
I 30 NO DISCHARGE i]
NOTE: Read instructions before completing this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS ANALYSIS PH SAMPLE 7.2 8.4 12 0
15/ 30 GRAB MEASUREMENT 00400 1
0 0
PERMI.
6.0***.0*'
SU
-THREE/
GRAB iRE*QUIREMENTI i*
.* i:"*.:,
"i :i 6.
9 0/
EFFLUENT GROSS VALUE
- REQIREEN, II"!.MINIMUM M
MAIVUMV WEEK SOLIDS, TOTAL SUSPENDED SAMPLE 133 169 26 12 15 0
5/30 GRAB MEASUREMENT 19 00530 1
0 0
PERMITJ_1 250 LBSIDY 30-100 MGIL WEEKLY GRAB' REQUIREMENT WEEKLL..GRA EFFLUENT GROSS VALUE M0-AVG-..'
-,'DAILY MX!-
MO AVG DAILY MX OIL AND GREASE SAMPLE
<57
<64 26
<5
<6 19 0
5 / 30 GRAB MEASUREMENT 00556 1
0 0
PEMIT 50 LBS/DY WEEKLY GRAB EFFLUENT GROSS VALUE I-.E: MEOAAILY MX-MO AVG
.'"DAILY MX FLOW, IN CONDUIT OR THRU SAMPLE 1.283 1.590 03 0
30 30 TOTALZ TREATMENT PLANT MEASUREMENT 50050 1
0 0
P E.RMI*flY REP-TRT
_-REPoRT-MGD SEE TOTALZ EFFLUENT GROSS VALUE REOUIR-EM-EN...
MO AVG :*-F'.DILY:MXuj PERMIT SAMPLE MEASUREMENT PýREEPRUIREMENEE'TOTL-SAMPLE MEASUREMENT
.REQUIREMENT-.
SAMPLE MEASUREMENT SREQUIREMENTý'-
NAME/TITLE PRINCIPAL EXECUTIVE OFFICER diecon Cenitiy undero spervso~nalty OfinlaWacodacthat this documentwh asteand alldeigeattachmentso asrWerethapreparedquafednderpesnemY
?*' *.'-
TELEPHONE DATE Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or
-'7 persons who manage the system, or those persons directly responsible for gathering the Sequoyah Site Vice Prestdent 43 8370 0
0 SeuyhSt iePeiet inlormation, the information submitted is, to the best of my knowledge and belief, true, 423____843-7001_______10__10___07_
Sequyah ite ice resient accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE
________________________information, including the possibility of line and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY TYPED OR PRINTEDO COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all/attachments he, EPA~RýIEMRZ For 3301(E
/9 rvoseitosmyeue ae1o EPA Form 3320-1 (REV 3199)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEQUOYAH NUCLEAR PLANT Address P.0 BOX 2000 (INTEROFFICE SB-2A-SON)
SODDY - DAISY. TN 37384 Facilitv TVA - SEQUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
MAJOR Form Approved.
DISCHARGE MONITORING REPORT (DMR)
(SUBR 01) 0MB No. 2040-0004 TN0026450.
I 107G F-FINAL L
PERMIT NUM1ER DISCHARGE NUMBER METAL CLEANING WASTE POND MnNITnRN R
EFFLUENT IJXEARI MIR I
DAYLAY From 0
0 0
To 1: 0 1 09 1 30 ]
NO DISCHARGE XX.
NOTE: Read instructions before completing this form.
ATTN: Stephanie A: Howard PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREOUENCY SAMPLE EX OF TYPE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS ANALYSIS PH SAMPLE MEASUREMENT 12
)0400 1 0
0 PERMIT-*.:,
- ******** *~..-.
, :-':.**¶*.***
00400 1
0 600 PEMI-::
FFLUETGROSVALUEREOuIREMENT-..--.
MINIMU.6.0 9.0 SU
- DAILY, GRAB EFFLUENT GROSS VALUE
_1-._-_
M U
-MINIMUM MAXIMUM SOLIDS, TOTAL SUSPENDED SAMPLE MEASUREMENT 19 00530 1
0 0
L.-PERMIT 3
3MGIL DAILY COMPOS REQUIREMENT :,
0 EFFLUENT GROSS.VALUE RUEN DAILYMX OIL AND GREASE SAMPLE MEASUREMENT 19 00556 1
0 0
D IPERMIT 1:.
MG/L D
EFFLUENT GROSS VALUE
,REQyIREMENT AIYM.,
DAILYLY-PHOSPHORUS, TOTAL (AS P)
SAMPLE MEASUREMENT 19 00665 1
0 0
4-: PERMITff7,... ------;
.*10 MG-L DAILY COM*OS EFFLUENT GROSS VALUE REQUIREMENT S.
,1.~~.
DAILY MX COPPER, TOTAL (AS CU)
SAMPLE MEASUREMENT 19 01042 1
0 0
PERMT*
'10 MG/L DAILY COMPOS EFFLUENT GROSS VALUE REOUIREM"NT DAILY,.
1 t
SAMPLE MEASUREMENT 19 01045 1
0 0
'PERMITz
- 11 MGIL
. DAILY COMPOS REOUIREMENT§ EFFLUENT GROSS VALUE DAILY MX' FLOW, IN CONDUIT OR THRU SAMPLE 03***
TREATMENT PLANT MEASUREMENT 03 50050 1
0 0
-tý,-:PERM fl--
-REPORT REPORT MGD DAILYj.CALCTD
- .REQUIREMENTý***:*?*::?*:
v,,.- ::*.n,.
,n k:":
EFFLUENT GROSS VALUE R
MO A.
NAME/TITLE PRINCIPAL EXECUTIVE OFFICER ICeritiy under penally of law that this document and all attachments were prepared under my
/
TELEPHONE DATE uiirection or supervision in accordance with a system designed to assure that qualified personnel Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the Sequoya Site Vice id r"
information, the information submitted is, to the best of my knowledge and belief, true, 423 843-7001 10 10 07 Sequoyah Site Vice President accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY TYPED OR PRINTED CODE COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments het No Discharge this Period EPA Form 3320-1 (REV 3/99)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEQUOYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SaN_
SODDY - DAISY TN.7384 Facilitv TVA - SEQUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY ATTN: Stephanie A. Howard NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
MAJOR DISCHARGE MONITORING REPORT' (DMR)
(SUBR 01).
110 G F -FINAL
[
PERMITNU!JMBER DISCHARGE NUMBER RECYCLED COOLING WATER Form Approved.
OMB No. 2040-0004 YER-MLI/TRRINcL EIR..
EFFLUENT From TO30
.h.I NO DISCHARGE
[
NO IT: Read instructions before completinq this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
EX FREQUENCY SAMPLE OF TYPE ANALYSIS AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS TEMPERATURE, WATER DEG.
SAMPLE CENTIGRADE MEASUREMENT 04 04 00010 Z
0 0
PERMIT.
DEG C
<i' 38.3.
DEGC DAILY GRAB-4 INSTREAM MONITORING EURMN DAILY MX-'
PH SAMPLE 12 MEASUREMENT 00400 1
0 0
PERMIT 6.0 9.0.
SU WEEKLY.
GRAB.
EFFLUENT GROSS VALUE RQIENTMINIMUM;4.<i.'
MAXIMUM SOLIDS, TOTAL SUSPENDED SAMPLE **
MEASUREMENT 19 00530 1
0 0
PERMIT "i*.**,
30 MG.L DAILY COMPOS0 EFFLUENT GROSS VALUE REQUIREMENT, i,,,,
DAILY Mx..
A OIL AND GREASE SAMPLE MEASUREMENT 19 00556 1
0 0
PERMIT 15***
MG DAILY GRAB~.A EFFLUENT GROSS VALUE REQUIREMENT 4
.4 DAILY MX~
FLOW, IN CONDUIT OR THRU SAMPLE TREATMENT PLANT MEASUREMENT 03 50050 1
0 0
,.PERMIT
.... R...RT
,T MGD
- 'ADAILY
--CALCTD" REQUIREMENT~
i EFFLUENT GROSS VALUE M
DAILYMX CHLORINE, TOTAL RESIDUAL SAMPLE MEASUREMENT 19 50060 1
0 0
PERMITF
-***~
- 4
~
01 GL
.9.WEL RB4 EFFLUENT GROSS VALUE
-REQUIREMENT
-0 1
MG/.--
AAA xE D AILY MX SAMPLE MEASUREMENT REQUI REMENT.
NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified personnel Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the Sequoyah Site Vice President 423 843-7001 10 10 07 information, the information submitted is, to the best of my knowledge and belief, true, 423_843-7001_10_10_07 Sequoyah Site Vice President accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY TYPED OR PRINTED OROD T
AEAR COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments het No Discharge this Period EPA Form 3320-1 (REV 3199)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEQUOYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SN)-
SODY - DAISY TN 37384 Facilitv TVA - SEQUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY ATTN: Stephanie A. Howard NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
MAJOR DISCHARGE MONITORING REPORT (DMR)
(SUBR 01)
TN0026450 I
D 110 T F-FINAL PERMIT NUM13ER DISCHARGENUMBERj RECYCLED COOLING WATER Form Approved.
OMB No. 2040-0004 MON[TRINCiERIQ D EFFLUENT EYA_4 YEAR MODAY NOD From ll o9 Io To 10 09 30I N
ISCHARGE xx Read instructions before completing this form.
INUV C PARAMETER NO.
FREQUENCY SAMPLE PARAMETER QUANTITY ORLOADING QUALITY OR CONCENTRATION NO.
EX FREOUENCY SAMPLE OF TYPE ANALYSIS AVERAGE MAXIMUM UNITS MINIMUM U N ITS AVERAGE MAXIMUM AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS IC25 STATRE 7DAY CHR SAMPLE CERIODAPHNIA MEASUREMENT 23 TRP3B-1 0
0 PERMIT.4-*2.
PERCENT 4SEMI cOMpOSý EFFLUENT GROSS VALUE 4REOUIREMENT1
-1 IIU<
~
NUL IC25 STATRE 7DAY CHR SAMPLE PIMEPHALES MEASUREMENT 23 TRP6C 1
0 0
PERMIT 45.2*4**'V****
4'}*
45 2 '-*4 PERCENT SEMI COMPiOS
,REASUIREMENT EFFLUENT GROSS VALUE REUEMN
.4 MINIMUM ANNUAL____
SAMPLE MEASUREMENT PERMIT REQUIREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT
-PERMIT:4 REQUIREMENT-
~14 j4.4, 4 ~1 4
44 SAMPLE MEASUREMENT
-4 PERMIT 4
4'.4.,
444.
4 44.4 4
4. RE:QUIREMENT:
>:,:,i"%
i**
4 44 4:.4:!:"*i~
)4 4
4 4 4:;;:**
- /
4 4
- .;:1 444.4 i ::::
SAMPLE MEASUREMENT NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this docmet and all attachmentswr prepared under my
,*ie/TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified personnel Christopher R. Church properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the S q oa ieVc r
SeuyhSt iePeiet information, the information submitted is, to the best of my knowledge and belief, true, Se uyhSt ie e t423 843-7001 10 10 07 SequyahSit Vie Pesient accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT
-AREA
ý NUMBER
- YEAR - MO DAY TYPED OR PRINTED CD E COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference allattachmentshef No Discharge this Period EPA Form 3320-1 (REV 3199)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Name TVA - SEOUGYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SON)
SODDY - DAISY TN 37384 Facility TVA - SEOUYAH NUCLEAR PLANT Locatio HAMILTON COUNTY ATTN: Stephanie A. Howard Different)
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
MAJOR DISCHARGE MONITORING REPORT (DMR)
(SUBR 01)
TN0026450 116.G F-FINAL PERMIT NUMBER
.DISCHARGE NUMBER BACKWASH Form Approved.
OMB No. 2040-0004 r
EFFLUENT I
Iyts.JI~LLbsIx.HM.u~...r.g.iu~ 'i-'
FromI Y0109 0A 1
TO MO I DA_
NO DISCHARGE L To L 09NOTE:
Read instructions before completing this form.
OUANTITY OR LOADING OUALITY OR CONCENTRATION NO.
FREQUENCY AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS ANALYSIS PARAMETER SAMPLE TYPE DEBRIS, FLOATING (SEVERITY)
SAMPLE 0
9A 0
1,30 VISUAL MEASUREMENT 01345 1
0 0
PE'RMIT :'
- NN***,.:
.REPORT i
PASS=.
SEE VISUAL*
EFFLUENTGROSS VALUE FAIL=1 PERMIT OIL AND GREASE VISUAL SAMPLE 0
9 0
1 / 30 VISUAL MEASUREMENT 84066 1
0 0
PERMIT N
REP ORT".
YES=1
~****
,)'
)
- N SEE VISUAL EFFLUENT GROSS VALUE REQUIREMENT MOTTL NO=O PERMIT" SAMPLE MEASUREMENT REbUIREMENTSI NN'N
~
- ~
SAMPLE MEASUREMENT PERMIT
,REQUIREMENT, SAMPLE MEASUREMENT N PERMITN
'N yNNN
).NN REQUIREMENT N~"
A
"~
~
R"I4).
3 N
SAMPLE MEASUREMENT PERMIT NN
'REQUIREMENT N
NN.,A NNNN)N N
NNN SAMPLE MEASUREMENT Christopher R. Church lproperty gather and evaluate the information submitted. Based on my inquiry of the person or*
lpersons who manage the system, or those persons directly responsible for gathering theSeZ a
SieV c r scl n linformation, tire information submitted is, to the best of iny knowledge and belief, true, h St Vi eP sd nt423 843-7001 1
0 0
Sequoyah Site Vice President accurate, and complete. I am aware tha N
here are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE NYPDnfNrmation, includng the possibility f fineandimprisonmentfor knwingviolations.A COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Refunerpenl allattachrentsmye Operations performs visual inspections for floating debris and oil and grease during all backwashes.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used
. Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facilitv Name/Location if Different)
Name TVA - SEOUOYAH NUCLEAR PLANT Address P.O. BOX 2000 (INTEROFFICE SB-2A-SON)
SODDY - DAISY TN 37384 Facility TVA - SEOUOYAH NUCLEAR PLANT Locatio HAMILTON COUNTY ATTN: Stephanie A. Howard NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
MAJOR DISCHARGE MONITORING REPORT (DMR)
(SUBR 01)
TN0026450 117 GI F-FINAL PERMIT NUM*E*R D
DCHARGE NUMBER BACKWASH LN'N'MO N1TQRtNG-PER[QJL..
I EFFLUENT
_Y E
ý 11Y_
M AY-A..
NO DISCHARGE From 10 09 0
o i
9 30 ODSCAG Form Approved.
OMB No. 2040-0004 NU I T: Read instructions before completinq this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
EX FREOUENCY SAMPLE OF TYPE ANALYSIS AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS DEBRIS, FLOATING (SEVERITY)
SAMPLE 0
0 1/30 VISUAL MEASUREMENT 9A 01345 1
0 0
PERMIT,.*N.4NN REPORT PASS,'
SEEE-VISI.[IAL EFFLUENT GROSS VALUE REQUIREMENT N
.<N4 MOTAL FAIL=1 PERMIT OIL AND GREASE VISUAL SAMPLE 1****
/ 30 VISUAL MEASUREMENT 84066 1
0 0
.4 NPERMIT REPORT***
-N YES=1
-~--~--*"N SEE" VISUAL EFFLUENT GROSS VALUE MOROAMESUIREMENT SAMPLE MEASUREMENT SAMPLE MEQASURMENT SAMPLE MEASUREMENT
, PER MIT>
4
-N N
'N
"-NN N-'N SAMPLE MEASUREMENT
'REQUIREMENT N
N
'>NNifNNN44 N
N
.N--N;NN Chitpe R
h rh-oprygte andevauat teioraon' sumte asdo yiqur ftepesno SAMPLE MEASUREMENT PERMIT
-N N
N' NN
'NN REQUIREMENT '?
N4NN./I.NNN'Nii224~
4 N
~
N-NN SAMPLE MEASUREMENT N-~NPERMITN iN N'N N-NN NN N-N N
'NN-N REQUIREMENTEORNRNTEDO NA ETTEPRN IA XCUIEO FCE Netf N-N-nltNflwtatti ouen n
l atcmnsweepeaedudrm ELP O
EDT in' in accordanNce witN a syte N'ige N' assur tha Nulfe pesone Chisop e N.
Ch rc th' N-d N'laeteifrain umte.Bsdo iqiyo h
esno N-o m
nageN)
N-e
-N--
rtoe esn iety epnil ogteigte' SApLersn euoa i
ieP d
MEASUREMENTd NA ETTEPICPLEEUIEOFCR inCermtify, icunder g penall ibliy of la fhttinouen and allpattaments fo nwere preparedonderFFCE my AUTHORZED TELTA E
PHONUMER DATEMO DA
____D ORN-PRNE--Icp COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments her Operations performs visual inspections for floating debris and oil and grease during all backwashes.
EPA Form 3320-1 (REV 3199)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name TVA - SEOUOYAH NUCLEAR PLANT Address P.O. BOX 200O (INTEROFFICE SB-2A-SN).
SODDY - DAISY. TN 37384 Facility TVA - SEQUOVYAH NUCLEAR PLANT Locatio HAMILTON COUNTY ATTN: Stephanie A. Howard NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
MAJOR Form Approved.
DISCHARGE MONITORING REPORT (DMR)
(SUBR 01) 0MB No. 2040-0004 TN0026450 118 G F-FINAL S PE-TNUMBER DISCIHARGENUMBER]
WASTEWATER & STORM WATER From 10 09 0 1oIo To 30i7 5ý9J EFFLUENT NO DISCHARGE
[XXj NOTE: Read instructions before completinq this form.
- ENTRATION NO.
FREQUENCYI SAMPLE EX OF TYPE PARAMETER QUANTITY OR LOADING QUALITY OR CONC AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM UNITS ANALYSIS OXYGEN, DISSOLVED (DO)
SAMPLE MEASUREMENT 19 00300 1
0 0
P-E
,RMIT
-fMGL~TtNIC/
)iRAB EFFLUENT GROSS VALUE
. REQIREEN DAILYMN WEEK SOLIDS, TOTAL SUSPENDED SAMPLE MEASUREMENT 19 00530 1
0 0
a--PERMIT
~
~
l MI
<TIE
.GA REQUIREMENT M/
WC/
GIRý EFFLUENT GROSS VALUE
.av,____DAILY MIX WEEK___
SOLIDS, SETTLEABLE SAMPLE MEASUREMENT 25 00545 1
0 0
PERMIT j
~
-MjT****,:*.*;"*
'I MLILONCE/
GRAB EFFLUENT GROSS VALUE REURMN ML-0-'
t
'MNI1~
FLOW, IN CONDUIT OR THRU SAMPLE TREATMENT PLANT MEASUREMENT 03 50050 1
0 0
PIERaIT,.
.'E P
MGD 1
i NCE/
STIMV"A EFFLUENT GROSS VALUE
- ',MO AVG DAILY MXi'a-'"
BATCH O
VJ SAMPLE MEASUREMENT PERMIT
~
~
-~a REQUIREMENT
.,i SAMPLE MEASUREMENT a.PERMIT a,-
-~
REQUIREMENT'
-,j
~
.- ~--
.~
- ~-
SAMPLE MEASUREMENT
-,-PEIRMITr-,
3/4K
"~I i--
REQUIREMENT
"-K
-7 a
,~
1 K<
-'a NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my TELEPHONE DATE irection..
saperviston in accordance with a system designed to assure that qualified personnel Christopher R. Church properly gather and evaluate the information submitted, Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the Sequoyah Site tce rest nt information, the information submitted is, to the best of my knowledge and belief, true, 423 843-7001 10 10 07 Sequoyah Site Vice President accuiate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE" information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA NUMBER YEAR MO DAY TYPED OR PRINTED OFIE OOUHOIEDAET AEA NME YAR O
DY COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference allattaclhments hel During this reporting period, there has been no flow from the Dredge Pond other than that resulting from rainfall.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used Page 1 of 1