CR Word Search Query Search Text = 'tritium' CR 2009107374 61512009 U1 RE-67 (grab CTMT atmosphere sample) tritium results are unusually highj, 6-5-09/02:42 H-3+6.17e-6 uCi/ml. 6 09/08:40 H.3=2.39e.6 uCi/ml after OPS performed a short CTMT vent. Previous values were E-8 uCi/mO range, We have also been detecting Xe-i Monday, May 03, 2010 in ri-was deletedin aýaa with Ohe Freedom oi InfrAohloon Ar.

Page 1 of 1 fr/iI

CR Word Search Query Search Text = 'radiation' CR 2009103743 414/2009 1 R22 OLL: Initial Reactor Cavity Surveys of the sand box areas revealed significantly higher dose rates on the reactor vessel hot and cold leg nozzles. Dose rates exceeded the threshold of a locked high radiation area and up to 1900 mR/hr contact and 15 CR 2009104343 4/11/2009 Westinghouse individual received a dose rate alarm of 232 mrem/hr while working in the Ul SFP room. n iscovered streaming radiation from light poles in fuel transfer condition CR 2009106771 5/211/2009 Checked dose rates around the area and found the Portable Demineralizer to have a dose rate of 18 mRem/Hr contact and 8 mRem/Hr at one foot. This CR is written to document the finding of an unposted Radiation area and the subsequent posting of that area CR 2009107310 613/2009 Discovered unposted high radiation area (HRA). While performing walkdown of resin transfer lines in the U2 139' CVCS valve hallway.

Monday, May 03, 2010 Page 1 of 2 Monday, May 03, 2010 Page I of 2

CR 2009108330 612912009 Radiation Monitor R-1 1 spiking into high alarm several times a shift for no apparent reason CR 2009108838 711212009 Vent stack radiation monitor R-29B channel #8 has been reading LO FAIL for some time. Reads 0.00 E+00 whenever polled for stp-1,0 Printout of the last 24 daily averages also shows same reading for each day's average.

Monday, May 03, 2010 Page 2 of 2 Monday, May 03, 2010 Page 2 of 2