LR-N10-0281, Response to Request for Additional Information - Risk Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program

From kanterella
(Redirected from ML102230417)
Jump to navigation Jump to search

Response to Request for Additional Information - Risk Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program
ML102230417
Person / Time
Site: Hope Creek 
Issue date: 07/28/2010
From: Braun R
Public Service Enterprise Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LR-N10-0281
Download: ML102230417 (4)


Text

PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, New Jersey 08038-0236 JUL 28 2010 0 PSEG Nuclear LLC LR-N 10-0281 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Hope Creek Generating Station Facility Operating License No. NPF-57 NRC Docket No. 50-354

Subject:

Response to Request for Additional Information-Risk Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program

Reference:

(1) Letter from PSEG to NRC, "Application for Technical Specification Change Regarding Risk Informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a Licensee Controlled Program," dated March 19, 2010 (ML100900224)

(2) Email from NRC to PSEG, "Draft Request for Additional Information," dated July 2, 2010 (ML101830347)

In Reference 1 PSEG Nuclear LLC (PSEG) submitted a license amendment request (H 10-01) for the Hope Creek Generating Station. Specifically, the proposed change would modify HCGS Technical Specifications (TS) by relocating specific surveillance frequencies to a licensee-controlled program, the Surveillance Frequency Control Program, with the implementation of Nuclear Energy Institute (NEI) 04-10, "Risk Informed Method for Control of Surveillance Frequencies."

The changes are consistent with NRC-approved Industry Technical Specifications Task Force Standard Technical Specification Change Traveler, TSTF-425, Revision 3 "Relocate Surveillance Frequencies to Licensee Control - RITSTF Initiative 5b."

In Reference 2 the NRC requested additional information regarding PSEG's license amendment request. The information requested by the NRC and PSEG's responses are in Attachment 1. No new regulatory commitments are established by this submittal.

If you have any questions or require additional information, please contact Mrs. Erin West at (856) 339-5411.

95-2168 REV. 7/99

U 2 82010 Document Control Desk Page 2 LR-N 10-0281 I declare under penalty of perjury that the foregoing is true and correct.

Executed on (Date)

Sir, Robert C. Braun Sr. Vice President - Nuclear Operations Attachments (1)

S. Collins, Regional Administrator - NRC Region I R. Ennis, Project Manager - USNRC NRC Senior Resident Inspector - Hope Creek P. Mulligan, Manager IV, NJBNE Commitment Coordinator - Hope Creek PSEG Commitment Coordinator - Corporate

ATTACHMENT 1 HOPE CREEK GENERATING STATION DOCKET NO. 50-354 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION REGARDING PROPOSED LICENSE AMENDMENT FOR RISK-INFORMED JUSTIFICATION FOR THE RELOCATION OF SPECIFIC SURVEILLANCE FREQUENCY REQUIREMENTS RAI #1 Table 2.2-1 of Attachment 2 of the application dated March 19, 2010, identifies supporting requirements from the Probabilistic Risk Assessment (PRA) standard for internal events which are not at capability category II as required to support this application. Only four supporting requirements are identified. Does Table 2.2-1 identify all supporting requirements not met at capability category II for the HCGS internal events PRA model, or do the four items represent those judged by the licensee to be relevant to this application? The licensee should clarify the scope of the items in Table 2.2-1 and identify and disposition any other supporting requirements not at capability category II, if applicable.

PSEG Response:

Section 2.2.3 of Attachment 2 of the submittal (Ref. 1) identifies the Supporting Requirements (SR) in Table 2.2-1 as all of the Supporting Requirements (SRs) not meeting capability category II. Thus, there are no other supporting requirements not at capability category II.

RAI #2 With regards to supporting requirement DA-D1, the Table 2.2-1 entry identifies that not all component failure data is based on plant-specific experience, but the importance of this item to the application is not discussed. Instead, it is stated that a majority of important systems use plant-specific data, and then the requirement of Nuclear Energy Institute 04-10 to perform sensitivity studies is identified. The licensee needs to more specifically identify the scope of this deficiency in plant data and characterize why it is not significant for the calculation of risk associated with surveillance frequency extensions for those systems to which the deficiency applies.

PSEG Response:

The systems using plant specific experience for failure rates are those monitored by the MSPI program: HPCI, RCIC, EDGs, RHR, SACS and SSWs. Additionally, plant specific testing and maintenance unavailability data is used for these and other systems. The remainder of the systems use generic data from sources such as NUREG /CR 6928 (Ref. 2). As indicated in the submittal, NEI 04-10 recognizes that the failure rates used in the Surveillance Test Interval (STI) assessments are a key part of the PRA calculations. The NEI 04-10 methodology therefore requires a specific sensitivity on the failure rate for all STI evaluations. This required sensitivity and any other sensitivities arising from assumptions or limitations of the modeling will ensure that a STI is only extended if there is high assurance that the change in risk is acceptable.

References:

1. Application for Technical Specification Change Regarding Risk-informed Justification for the Relocation of Specific Surveillance Frequency Requirements to a licensee Controlled Program, March, 10 2010
2. NUREG/CR 6928 Industry-Average Performance for Components and Initiating Events at U.S.

Commercial Nuclear Power Plants