ML101540003

From kanterella
Jump to navigation Jump to search
Additional RAI for LaSalle AST
ML101540003
Person / Time
Site: LaSalle  
Issue date: 06/02/2010
From: Goodwin C
Plant Licensing Branch III
To: Nicely K
Exelon Corp
References
Download: ML101540003 (1)


Text

From:

Goodwin, Cameron Sent:

Wednesday, June 02, 2010 3:13 PM To:

'ken.nicely@exeloncorp.com'

Subject:

LaSalle AST Per UFSAR Section 9.5.4.1.1 (Rev. 18), the usable diesel fuel volume required to support each Division 1 and 2 diesel generator continuous operation at rated load for 7 days is 32,200 gallons. Division 1 diesels will now be loaded above the continuous rating due to the load increase needed for the AST amendment. Provide a detailed discussion addressing how the EDG 7 day fuel supply requirement is satisfied as a result of this AST amendment.

Thank you, Cameron Mrs. Cameron Goodwin Division of Operating Reactor Licensing LaSalle Project Manager Phone: (301)415-3719 Email: Cameron.Goodwin@nrc.gov E-mail Properties Mail Envelope Properties ()

Subject:

LaSalle AST Sent Date: 6/2/2010 3:12:02 PM Received Date: 6/2/2010 3:13:00 PM From: Goodwin, Cameron Created By: Cameron.Goodwin@nrc.gov Recipients:

ken.nicely@exeloncorp.com ('ken.nicely@exeloncorp.com')

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 10343 6/2/2010 Options Expiration Date:

Priority: olImportanceNormal ReplyRequested: True

Return Notification: False Sensitivity: olNormal Recipients received: