From:

Goodwin, Cameron Sent:

Wednesday, June 02, 2010 3:16 PM To:

'ken.nicely@exeloncorp.com'

Subject:

LaSalle NETCO Insert Question Good afternoon.

The reviewers were talking after the meeting yesterday and another question came up.

RAI As described in Section 6.0, the primary fuel storage rack model appears to be three infinite slabs of the bottom, middle and top limiting assembly lattices, with a periodic boundary condition utilized below the bottom slab and above the top slab. The applicant should provide justification for use of this non-physical model of the spent fuel storage racks. The justification should address why this non-physical model is conservative compared to reality.

If you are able to address this in the package coming in that would be great.

Thank you, Cameron Mrs. Cameron Goodwin Division of Operating Reactor Licensing LaSalle Project Manager Phone: (301)415-3719 Email: Cameron.Goodwin@nrc.gov E-mail Properties Mail Envelope Properties ()

Subject:

LaSalle NETCO Insert Question Sent Date: 6/2/2010 3:13:47 PM Received Date: 6/2/2010 3:15:00 PM From: Goodwin, Cameron Created By: Cameron.Goodwin@nrc.gov Recipients:

ken.nicely@exeloncorp.com ('ken.nicely@exeloncorp.com')

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 11525 6/2/2010 Options Expiration Date:

Priority: olImportanceNormal ReplyRequested: True Return Notification: False Sensitivity: olNormal Recipients received: