Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 April 28, 2010 Randy Slater State of Tennessee Department of Environment & Conservation Division of Underground Storage Tanks Chattanooga Environmental Field Office 540 McCallie Avenue, Suite 550 Chattanooga, Tennessee 37402
Dear Mr. Slater:
SEQUOYAH NUCLEAR PLANT (SQN) FACILITY NO. 0-330628 - UPDATE TO CLEANUP OF DIESEL SPILL ASSOCIATED WITH -UNDERGROUND STORAGE TANKS (USTs) IDENTIFIED JUNE 26, 2009 Enclosed for your review is an update to the cleanup of diesel fuel from piping associated with SQN's USTs, per your conversation with Stephanie Howard on April 1, 2010.
Due to the regulatory nature of some of the piping exposed, SQN requests permission to backfill the area of the cleanup as soon as possible.
If you have any questions or need additional information, please contact Stephanie Howard at (423) 843-6700 or Ann Hurt at (423) 843-6714 of Sequoyah's Environmental staff.
Sincerely, Christopher R. Church Site Vice President Sequoyah Nuclear Plant cc:
U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Approximately 200 yd 3 of diesel-contaminated soil from the spill has been removed from the spill location. SQN is in the process of obtaining a special waste permit for disposal of this soil. The Division of Underground Storage Tanks will be notified when the soil has been disposed.
All analytical results for the soil remaining in the excavation area are below the detection limit. Figures 1, 2 and 3 show the excavation location. Attachment 2 contains the analytical results. Due to the thickness of the concrete footer (approx. 1.25 ft) for the Diesel Generator Building and the location of the conduit bank and metal z-piling, SQN believes an adequate barrier existed to prevent the downward migration of diesel fuel to groundwater and that groundwater monitoring is not necessary.
It should be noted that the area in the immediate vicinity of the spill contains a significant amount of buried piping. This piping is safety related and critical to the operation of the plant. SQN's Final Safety Analysis Report (FSAR) requires that buried safety-related pipe be protected from tornado generated missiles. In this case, eighteen inches of conventional unreinforced concrete and a twelve inch cushion of either compacted sand or fine-grained earth fill over the pipe provide the protection from tornado. generated missiles. To support the cleanup of the leak from the fuel line, an evaluation was documented that if the river temperature is below 77 degrees F, this section of ERCW piping and therefore the missile shield is not required. Past trend data shows that the river temperature will start approaching 77 degrees F around the first week in June.
For these reasons, SQN requests permission to backfill the excavation area as soon as possible.
Essential Raw Cooling Water High Pressure Fire Protection Figure 1. - Leak Location
SQN DIESEL SPILL SITE - CLEAN UP AREA OVERVIEW SQN-DSL SPL-E UST Building BIDRY 2
Aux.
Boiler Lines BND 2
z Overexcavated Area S
Eastem Edge of Excavation Missile shield line VUST Line Overexcavated Area Spill Sites Eastem Edge of Excavation SQN-DSL SPL-P
- N-X ----
N mommomm N
wall Figure 3. - Map View of Leak Area and Soil Sampling Locations I
- ESC L-A-S C-I'EN C
r-5
[11{}r he06 aro P
Rd.
1:.
Jul '.,
I'N 371 61 )
/fi
-i -, 8
] }0 ;V-5k!
197l 1 9-0 M.
Br.an Carico IVA-Sitle A 2aa1u7'11;V'1nt Wac*1:e /W P.O.
B 0 :
1 0 11 Muscle Shoals, AT, 30662-1010 Report Summary Thursday March 11, 201.0 Report Number: L447952 Samples Received: 03/05/10 Client Project: SQN DIESEL SPILL CLE
==
Description:==
TVASAWWW The aiialytical results in this report are based upon information supplied by you, the client, and are for your exclusive use.
If you have an questions regarding this data package, please do note hesLtate to carl.
Roberto Celia
,ESC Representative Entire Report Reviewed By:
L~aboraloro Cerlilicalieo, Nunibers A2LA GA NJ -
AZ 1461-01, AlHA
- 100789, AL -
- 40660, CA -
1-2327, CT -
PH-0197, FL E87487
- 923, IN -
C-TN-01, KY -
- 90010, KYUST -
- 0016, NC -
ENV375/DW21704, ND R-140 TN002,NJ NELAP -
- TN002, SC -
- 84004, TN -
- 2006, VA
- 00109, WV -
233
- 0612, MN 04,7-999-395, NY
- 11742, WI 998093910 1w,:,
I
, ii, in, i-;
,r, I y.,pp Iic:;?,le 1o tn h L est I e*lhCs
!;pe7-:i' o tnJ each 5":O07 o ao.,:,:rdiiTl, ino held
-'hibs ieaifl't fl;Cy ]t C?
- eSpwOCIhcCeI,
--;?C:ipi in
- lull, vCiliOI-h(Ioii 1*55 a)pprwa;ai.
7 li-.C Lab 5<i c1:25e S WhI~c.7:
Ip i,-l, 7}
naal lDi sq
,13¢-e by' [LOC is*
psiC ni152CIld p}aI
{]l~au
{:
pl'o fi~l-'
ia I,.iloii1ali,
- l.na I,,',I iop'ut[ii ill<:
il'o,:,-ltsi<rr:
1],1O30:7*, 0,1 "01,
,arll, 07;*!:(l1l7.
- ESC L.AB 5-CIF'.EN'C E.S Mr. Brian Carrico TVA-Site Assessment Water/WW P.O. Box 1010 Muscle Shoals, AL 35662-1010 12065 Lebanon Rd.
Mt.
- Juliet, TN 37122 (615) 758-5858 1-800 767-5859 Fax (615) 756-5859 Tax I.D. 62-0814289 Est.
2970 REPORT OF ANALYSIS March 11, 2010 ESC Sample #
L447952-01 Site ID 0167301 Project # :
SQN DIESEL SPILL CLE Date Received March Description SQN D0 Sample ID SQN-D(
Collected By Brian Collection Date 03/03.
Parameter Benzene Toluene Ethylbenzene Total Xylenes Methyl tert-butyl ether Naphthalene Surrogate Recovery Toluene-d[8 Dibromofluoromethane 4-Bromofluorobenzene 05, 2010 iesel Spill Clean up Samples SLSPL-N BNDRY 1 Carrico
/10 13:07 Result BDL BDL BDL BDL BDL BDL 96.0
- 97. 6
- 97. 6 Det.
Limit 0.0050 0.025
- 0.0050 0.015 0.0050 0.025 Units mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
% Rec.
% Rec.
% Rec.
Method 8260B 8260B 8260B 8260B 8260B 8260B 8260B
'8260B 8260B Date 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10.
Dil.
5 5
5 5
5 5
5 5
5..
BDL - Below Detection Limit Det.
Limit -
Practical Quantitation Limit(PQL)
Note:
-The reported analytical results relate only to the sample submitted.
This report shall not be reproduced, except in full, without the written approval from ESC.
Reported: 03/11/10 14:18 Printed: 03/11/10 14:18 Page 2 of 5
- ESC L-A, S9 C
-IEN C ES Mr. Brian Carrico TVA-Site Assessment Water/WW P.O.
Box 1010 Muscle Shoals, AL 35662-1010 12065 Lebanon Rd.
Mt.
Juliet TN 37122 (615) 758-5858 1-800-767-5859 Fax 615) 758-5859 Tax I.D. 62-0814289 hSt.
aS/U REPORT OF ANALYSIS March 11, 2010 ESC Sample L447952-02 Site ID 0167301 Project #
SQN DIESEL SPILL CLE Date Received March Description SQN D0 Sample ID SQN-D)
Collected By Brian Collection Date 03/03, Parameter Benzene Toluene Ethylbenzene Total Xylenes Methyl tert-butyl.
ether Naphthalene Surrogate Recovery Toluene-d8 Dibromofluoromethane 4-Bromofluorobenzene 05, 2010 iesel Spill Clean up Samples SLSPL-N BNDRY 2 Carrico
/10 13:10 Result BDL BDL BDL BDL BDL BDL 100.
102.
- 98. 5 Det.
Limit 0.0050 0.025 0.0050 0.015 0.0050 0.025 Units mig/ kg mg/kg mg/kg mg/kg mg/kg mg/kg
% Rec;
% Rec.
% Rec.
Method 8260B 8260B 8260B 8260B 8260B 8260B 8260B "826DB 8260B Date 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10 03/07/10,
03/07/10 03/07/10 Dil.
5 5
5 5
5 5
5 5
5.
BDL - Below Detection Limit Det.
Limit -
Practical Quantiration Limit(PQL)
Note:
The reported analytical results relate only to the sample submitted.
This report shall not be reproduced, except in full, without the written approval from ESC.
Reported: 03/11/10 14:18 Printed: 03/11/10 14:18 Page 3 of 5
OESC L.A-a 5,C.i'E'N,C E'S Mr.
Brian Carrico TVA-Site Assessment Water/WW P.O.
Box 1010 Muscle Shoals, AL 35662-1010 12065 Lebanon Rd.
Mt.
- Juliet, TN 37122 (615) 758-5858 1-800-767-5859 Fax (615) 758-5859 Tax I.D.
62-0814289 Est.
1970 REPORT OF ANALYSIS March 11, 2010 ESC Sample #
L447952-03 Site ID 0167301 Project #
SQN DIESEL SPILL CLE Date Received March Description SQN D:
Sample ID SQN-D)
Collected By Brian Collection Date :
03/03 Parameter Benzene Toluene Ethylbenzene Total Xylenes Methyl tert-butyl ether Naphthalene Surrogate Recovery Toluene-d8 Dibromofluoromethane 4-Bromofluorobenzene 05, 2010 iesel Spill Clean up Samples SLSPL-S BNDRY-I Carrico
/10 13:21 Result BDL BDL BDL BDL BDL BDL 97.1 98.2 108.
Det. Limit 0.0050 0.025 0.0050 0.015 0.0050 0.025 Units mg/kg mg/kg mg/kg mg/kg mg/kg mg/kg
,% Rec.
% Rec.
% Rec.
Method 8260B 8260B 8260B 8260B 8260B 8260B
.8260B 8260B 8260B Date 03/10/10 03/10/10 03/10/30 03/10/10 03/10/10 03/10/10 03/10/ 10 03/10/10 03/10/10 Dil.
5 5
5 5
5 5
55.
.5 BDL -
Below Detection Limit Det.
Limit -
Practical Quantitation Limit(PQL)
Note:
The reported analytical results relate only to the sample submitted.
This report shall not be reproduced, except in full, without the written approval from ESC.
Reported: 03/11/10 14:18 Printed: 03/11/10 14:18 Page 4 of 5
- ESC L-A,a 8
-C-I,EN,C-E,S Mr.
Brian Carrico TVA-Site Assessment Water/WW P.O.
Box 1010 Muscle Shoals, AL 35662-1010 12065 Lebanon Rd.
Mt.
- Juliet, TN 37122 (615) 758-5858 1-800-767-5859 Fax (615) 758-5859 Tax I.D. 62-0814289 Est. 1970 REPORT OF ANALYSIS March 11, 2010 ESC Sample # :
L447952-04 Site ID 0167301 Project SQN DIESEL SPILL CLE Date Received March Description SQN D.
Sample ID SQN-D7 Collected By Brian Collection Date 03/03, Parameter Benzene Toluene Ethylbenzene Total Xylenes Methyl tert-butyl ether Naphthalene Surrogate Recovery Toluene-de Dibromofluoromethane 4-Bromofluorobenzene 05, 2010 iesel Spill Clean up Samples SLSPL-S BNDRY-2 Carrico
/10 13:23 Result BDL BDL-BDL BDL.
BDL BDL 96.8 98.0 106.
Det. Limit 0.0050 0.025 0.0050 0.015 0.0050 0.025.
Units mg/kg mg/ kg mg/kg mg/kg mg/kg mg/kg
% Rec.
.% Rec.
% Rec.
Method 8260B 8260B 8260B 8260B 8260B 8260B 8260B 8260B 8260B Date 03/10/10 03/10/10 03/10/10 03/10/10 03/10/10 03/10/10 03/10/10 03/10/10 03/10/10 Dil.
5 55 55 5
55 5
BDL - Below Detection Limit Det.
Limit -
Practical Quantitation Limit(PQL)
Note:
The reported analytical results relate only to the sample submitted..
This report shall not be reproduced, except in full, without the written approval from ESC.
Reported:
03/11/10 14:18 Printed:
03/11/10 14:18 Page 5 of 5
Summary of Remarks For Samples Printed 03/11/10 kt. 14:18:27 TSR Signing Reports: 400 R5 -
Desired TAT PO# 00059970-00006 changed to 61391 on 1/4/10 RC.
Sample: L447952-01 Account: TVASAWWW Received: 03/05/i0 13:30 Due Date: 03/15/10 00:00 RPT Date: 03/11/10 14:18 Sample: L447952-02 Account: TVASAWWW Received: 03/05/10 13:30 Due Date: 03/15/10 00:00 RPT Date: 03/11/10 14:18 Sample: L447952-03 Account: TVASAWWW Received: 03/05/10 13:30 Due Date: 03/15/10 00:00 RPT Date: 03/11/10 14:18 Sample: L447952-04 Account:
TVASAWWW Received: 03/05/10 13:30 Due Date: 03/15/10 00:00 RPT Date: 03/11/10 14:18