0412612010 U.S. Nuclear Regulatory Commission Operations Center Event Report Page I General Information or Other (PAR)
Event#
45875 Rep Org: ENGINE SYSTEMS, INC.
Notification Date / Time: 04/26/2010 17:15 (EDT)
Supplier: ENGINE SYSTEMS, INC.
Event Date / Time: 03/23/2010 (EDT)
Last Modification: 04/26/2010 Region:
1 Docket #:
City:
ROCKY MOUNT Agreement State:
Yes County:
License #:
State: NC NRC Notified by: PAUL STEPANTSCHENK Notifications: JOHN ROGGE R1DO HQ Ops Officer: BILL HUFFMAN DAVID AYRES R2DO Emergency Class: NON EMERGENCY DAVID HILLS R3DO 10 CFR Section:
JEFF CLARK R4DO 21.21 UNSPECIFIED PARAGRAPH PART 21 COORDINATOR NRR EMD JACKET WATER PUMP WITH INCORRECT IMPELLER ORIENTATION The following is a summary of a report received from Engine Systems, Inc. via facsimile:
"Engine Systems Inc. (ESI) began a 10CFR21 evaluation on 03/23/10 following a corrective action request from Entergy - Grand Gulf. The request was written as the result of Grand Gulf having an EMD jacket water pump with an incorrect impeller. Specifically, the impeller installed in the pump was for rotation opposite of the pump housing.
The evaluation was concluded on 04/26/10 and was determined to be a reportable defect as defined by 10CFR21.
"EMD diesel engines utilized for emergency diesel generator sets use two engine jacket water centrifugal pumps (one for each bank) to circulate fluid throughout the engine for cooling. Each pump is mounted on the front of the engine and rotates in the opposite direction of the engine crankshaft. For single engine generator set applications (i.e. left hand rotation engine, viewed from the rear of the engine), the pumps used on each bank contain identical components; the only difference is the position of the impeller housing in relation to the pump shaft housing. When viewed from the front of the engine, these water pumps rotate counterclockwise (see Figure 1 below).
"For tandem generator set applications, one engine is left hand rotation and the other is right hand rotation. For each engine, the pumps used on each bank contain identical components and the only difference is the position of the impeller housing in relation to the pump shaft housing. However, for a right hand rotation engine the water pumps rotate clockwise when viewed from the front of the engine In summary, because these pumps use impellers that rotate in both clockwise and counter-clockwise directions, it is possible that an impeller could be installed with a design rotation opposite that required for the associated pump housing.
J3E(Cf LAk r0
04/26/2010 U.S. Nuclear Regulatory Commission Operations Center Event Report Paze General Information or Other (PAR)
Event#
45875 "A review has been performed to evaluate the impact on past supply of EMD water pumps. Historically, ESI has supplied a quantity of over 280 water pumps under 17 different EMD part numbers dating back to 1988. The pump returned by the customer [Grand Gulf] was supplied in January 1997. After reviewing the history of dedication activities performed on the water pumps it was found that dedication reports for EMD water pumps have always contained an inspection requirement to verify the correct operational rotation; however reports written prior to 2000 did not include a clear visual depiction of what the correct operational rotation is. It appears that this was an isolated incident where the inspector made an error when performing the inspection. Since April 2000, all EMD water pumps shipped were inspected to a dedication report that included a clear visual depiction of proper impeller geometry. This one incident is the only known instance of an EMD water pump with the incorrect impeller.
I "ESI recommends that as a precaution, all customers with an EMD water pump in stock which was supplied by ESI prior to April 2000 should perform a visual inspection to ensure the correct impeller is installed. A pump which has been installed on the diesel engine is considered acceptable based on successful operation of the diesel engine.
The impeller inspection is easily performed, without disassembly, by looking into the inlet port of the pump to confirm the orientation of the impeller matches the pump housing. A listing of the various part numbers supplied prior to April 2000 is included in Table [below].
Listing of Water Pump P/Ns Supplied Prior to April 2000 Part Number Rotation Bank Type of Engine 40004235 LH RIGHT 16 & 20-645E4 & E4B 40004234 LH LEFT 16 & 20-645E4 & E4B 8347607 LH LEFT 16 & 20-645E4 & E4B 8364236 RH RIGHT 16 & 20-645E4 & E4B 8364237 RH LEFT 16 & 20-645E4 & E4B 8269664 LH RIGHT 12-645E4 & E4B 9336390 LH LEFT 12-645E4 & E4B 8269638 LH LEFT 12-645E4 & E4B 8324588 RH RIGHT 12-645E4 & E4B 8324589 RH LEFT 12-645E4 & E4B NOTE: The ESI report did not provide an information on specific nuclear power plant licensees that may possess these components.
- 252-446-3830 1/
7 6-4-26-10; 05: 09PM; (EJ ENGINE SYSTEMS, INC 1220 S. Washington St., Rocky Mount, NC 2780 P.O. Box 1928, Rocky Mount, NC 27802-1928 Telephone: 2521977-2720 Fax: 252/446-1134 TELEFAX Date:
Company:
Fax Number:
Verification No.:
Reference:
From:
Page:
April 26, 2010 NRC Operations Center 301/816-5151 301/816-5100 Report No. 10CFR21 -0100, Rev. 0 Paul Stepantschenko 1 of 7
Dear Sir:
Following this cover is a copy of our report 10CFR21 -0100, Rev.0, for a 10CFR21 reportable notification on an EMD water pump, P/N 8324589.
A copy of this report will be mailed to the NRC Document Control Desk and to all users with safety related EMD diesel engines.
Should you have questions, please let us know.
Sincerely, ENGINE SYSTEMS, INC.
Paul Stepantschenko Quality Assurance Manager Quality Performance With Pride
04-26-10;05:09PM; I
- 252-446-3830 2/
7
'ES11 ENGINE SYSTEMS, INC.
175 Freight Road, Rocky Mount, NC 27804 Telephone: 252/977-2720 Fax: 252/446-1134 Report No.
10CFR21-0100 Rev. 0:
04/26/10 10CFR21 REPORTING OF DEFECTS AND NON-COMPLIANCE COMPONENT:
SYSTEM:
CONCLUSION:
EMD water pumps EMD Emergency Diesel Generator - jacket water system Reportable in accordance with 1 OCFR21.
Prepared By:
Reviewed By:
Engineering Manager Quality Assurance Manager Date:
/___
Date:
Quality Performance With Pride
04-26-10;05:O9PM;
- 252-446-3830 3/
7 Report No.
10CFR21-01 00 Record of Revisions Page:
1 of 1 REV DATE PAGE DESCRIPTION 0
04/26/10 Initial issue.
04-26-10; 05: 09PM;
- 262-446-3830 4/
7 Report No.
10CFR21 -0100 Revision:
0 Date:
04/26/10 Page:
1 of 4 COMPONENT:
EMD water pump P/N 8324589
SUMMARY
Engine Systems Inc. (ESI) began a 10CFR21 evaluation on 03/23/10 following a corrective action request from Entergy - Grand Gulf. The request was written as the result of Grand Gulf having an EMD jacket water pump (P/N 8324589, S/N 96M1464V) with an incorrect impeller.
Specifically, the impeller installed in the pump was for rotation opposite of the pump housing. ESI supplied the jacket water pump to Grand Gulf in January 1997. ESI does not know if the pump has been in storage since that time or if any rework activities have been performed on the pump.
The evaluation was concluded on 04/26/10 and was determined to be a reportable defect as defined by 10CFR21.
DISCUSSION:
EMD diesel engines utilized for emergency diesel generator sets use two engine jacket water centrifugal pumps (one for each bank) to circulate fluid throughout the engine for cooling. Each pump is mounted on the front of the engine and rotates in the opposite direction of the engine crankshaft. For single engine generator set applications (i.e. left hand rotation engine, viewed from the rear of the engine), the pumps used on each bank contain identical components; the only difference is the position of the impeller housing in relation to the pump shaft housing. When viewed from the front of the engine, these water pumps rotate counterclockwise (see Figure 1 below).
For tandem generator set applications, one engine is left hand rotation and the other is right hand rotation. For each engine, the pumps used on each bank contain identical components and the only difference is the position of the impeller housing in relation to the pump shaft housing.
However, for a right hand rotation engine the water pumps rotate clockwise when viewed from the front of the engine (see Figure 2 below).
Right Bank Left Bank Figure 1 Water Pumps for LH Rotation Engine Figure 2 Water Pumps for RH Rotation Engine
04-26--10;06:09PM;
- 252-446-3830 5/
7 Report No.
IOCFR21-0100 Revision:
0 Date:
04/26/10 Page:
2 of 4 It was reported by Grand Gulf that "while troubleshooting low Div IIl DJ jacket water pressure it was discovered that the wrong impeller was supplied in the P81 C007A pump. The supplied impeller was intended to rotate in the opposite direction as the pump rotation. This appears to be the cause of low jacket water pressure in the A engine."
Subsequently, the water pump was returned to ESI for further inspection. It was apparent from a visual inspection that the incorrect impeller was installed for this pump. P/N 8324589 corresponds to a right hand rotation, left bank water pump for use on a 12-cylinder EMD 645E4 or E4B engine.
As shown in Photos 1 and 2 below, the housing corresponds to a right hand rotation pump, but the impeller is for left hand rotation. Figure 3 shows the correct impeller for a right hand rotation pump.
Photo 1: Water Pump Returned by Customer (note impeller fin orientation)
Figure 3: Correct Housing and Fin Orientation for RH Rotation Photo 2: Close-up of Water Pump (note impeller fin orientation)
04-26-10; 05:
09PM;
- 252-446-3830 6/
7 Report No.
10CFR21-01000 Revision:
0 Date:
04/26/10 Page:
3 of 4 EVALUATION OF PREVIOUS SHIPMENTS:
A review has been performed to evaluate the impact on past supply of EMD water pumps.
Historically, ESI has supplied a quantity of over 280 water pumps under 17 different EMD part numbers dating back to 1988. The pump returned by the customer was supplied in January 1997.
After reviewing the history of dedication activities performed on the water pumps it was found that dedication reports for EMD water pumps have always contained an inspection requirement to verify the correct operational rotation; however reports written prior to 2000 did not include a clear visual depiction of what the correct operational rotation is. It appears that this was an isolated incident where the inspector made an error when performing the inspection. Since April 2000, all EMD water pumps shipped were inspected to a dedication report that included a clear visual depiction of proper impeller geometry. This one incident is the only known instance of an EMD water pump with the incorrect impeller.
As noted above, ESI supplied this water pump in 1997. Since that time ESI is unaware if any rework or refurbishment activities have been performed on the pump but it was noted that paint had chipped off the heads of the capscrews, indicating that the screws had been removed at some time. There exists a possibility that the pump impeller may have been previously removed.
AFFECTED USERS:
Based on the above review of previous EMD water pump shipments, it appears that this was an isolated incident. However, there exists the potential that an incorrect impeller was installed in an EMD water pump supplied by ESI prior to April 2000. Therefore, this notification is applicable to all users with safety related EMD diesel engines.
CORRECTIVE ACTION:
ESI recommends that as a precaution, all customers with an EMD water pump in stock which was supplied by ESI prior to April 2000 should perform a visual inspection to ensure the correct impeller is installed.
A pump which has been installed on the diesel engine is considered acceptable based on successful operation of the diesel engine. The impeller inspection is easily performed, without disassembly, by looking into the inlet port of the pump to confirm the orientation of the impeller matches the pump housing.
A listing of the various part numbers supplied prior to April 2000 is included in Table 1. Figures 4 and 5 contain visual guidance to ensure the impeller corresponds to the installed pump housing.
04-26-10;05:09PM;
- 262-446--3830 7/
7 Report No.
Revision:
Date:
Page:
04/26/10 4 of 4 Part Number Rotation Bank Type of Engine 40004235 LH RIGHT 16 & 20-645E4 & E4B 40004234 LH LEFT 16 & 20-645E4 & E4B 8347607 LH LEFT 16 & 20-645E4 & E4B 8364236 RH RIGHT 16 & 20-645E4 & E4B 8364237 RH LEFT 16 & 20-645E4 & E4B 8269664 LH RIGHT 12-645E4 & E4B 9336390 LH LEFT 12-645E4 & E4B 8269638 LH LEFT 12-645E4 & E4B 8324588 RH RIGHT 12-645E4 & E4B 8324589 RH LEFT 12-645E4 & E4B Table 1: Listing of Water Pump PINs Supplied Prior to April 2000 HSNG.