Results of the Sixteenth Steam Generator Tube Inservice Inspection
ML101100676
Person / Time
Site: Wolf Creek 
Issue date: 04/08/2010
From: Garrett T
Wolf Creek
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ET 10-0012
Download: ML101100676 (67)


Text

WGLF CREEK

'NUCLEAR OPERATING CORPORATION Terry J. Garrett Vice President, Engineering April 8, 2010 ET 10-0012 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555

Subject:

Docket No. 50-482:

Results of the Sixteenth Steam Generator Tube Inservice Inspection Gentlemen:

Attachment I, the Steam Generator Tube Inspection Report, is being submitted in accordance with Wolf Creek Generating Station (WCGS) Technical Specification (TS) 5.6.10, "Steam Generator Tube Inspection Report."

This report provides the results of WCGS's sixteenth steam generator (SG) tube inservice inspection. The Steam Generator Tube Inspection Report includes the following:

a. The scope of inspections performed on each SG;
b. Active degradation mechanisms found;
c. Nondestructive examination techniques utilized for each degradation mechanism;
d. Location, orientation (if linear), and measured sizes (if available) of service induced indications;
e. Number of tubes plugged during the inspection outage for each active degradation mechanism;
f.

Total number and percentage of tubes plugged to date; and

g. The results of condition monitoring, including the results of tube pulls and in-situ testing; The following items are also included in accordance with the One-time Alternate Repair Criteria, H*, which was approved to support WCGS's Refueling Outage 17 and the subsequent operating cycle:
h. Following completion of an inspection performed in Refueling Outage 17 (and any inspections performed in the subsequent operating cycle) the primary to secondary LEAKAGE rate observed in each SG (if it is not practical to assign the LEAKAGE to an individual SG, the entire primary to secondary LEAKAGE should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report; P.O. Box 411/ Burlington, KS 66839 / Phone: (620) 364-8831 An Equal Opportunity Employer M/F/HC/VET

ET 10-0012 Page 2 of 2

i.

Following completion of an inspection performed in Refueling Outage 17 (and any inspections performed in the subsequent operating cycle) the calculated accident induced leakage rate from the portion of the tubes below 13.1 inches from the top of the tubesheet for the most limiting accident in the most limiting SG.

In addition, if the calculated accident induced leakage rate from the most limiting accident is less than 2.50 times the maximum operational primary to secondary leak rate, the report should describe how it was determined; and

j.

Following completion of an inspection performed in Refueling Outage 17 (and any inspections performed in the subsequent operating cycle) the results of monitoring for the tube axial displacement (slippage).

If slippage is discovered, the implications of discovery and corrective action shall be provided.

Enclosures 1 and 2 contain all service-induced indications identified in SGs A and D during WCGS's Refueling Outage 17.

No commitments are contained in this correspondence.

If you have any questions concerning this matter, please contact me at (620) 364-4084, or Mr.

Richard Flannigan at (620) 364-4117.

Sincerely, Terry J. Garrett TJG/rlt Attachment : Steam Generator A Service-Induced Indications : Steam Generator D Service-Induced Indications cc:

E. E. Collins (NRC), w/a, w/e G. B. Miller (NRC), w/a, w/e B. K. Singal (NRC), w/a, w/e Senior Resident Inspector (NRC), w/a, w/e

Attachment to ET 10-0012 Page 1 of 7 STEAM GENERATOR TUBE INSPECTION REPORT This report is being submitted pursuant to Technical Specification (TS) 5.6.10, "Steam Generator Tube Inspection Report," to report the results of the sixteenth steam generator (SG) tube inservice inspection.

Summary The sixteenth SG tube inservice inspection was completed by Westinghouse Electric Corporation on October 27, 2009, during Refueling Outage 17 (RF17). Initial entry into MODE 4 was achieved on November 16, 2009.

Refueling Outage 17 was the second inspection of the third sequential inspection interval (60 Effective Full Power Months (EFPMs)), and is the approximate midpoint of the third inspection interval. At the Start of Refueling Outage 17 the SGs had operated for a total of 247.16 EFPMs (20.6 Effective Full Power Years (EFPYs)).

Permanent approval of an alternate repair criteria, H*, for indications within the tubesheet could not be achieved prior to Refueling Outage 17. As a result, a One-time Alternate Repair Criteria, H*, was approved which revised TS 5.5.9, "Steam Generator (SG) Program" and TS 5.6.10, "Steam Generator Tube Inspection Report" for Wolf Creek Generating Station's (WCGS's)

Refueling Outage 17 and the subsequent operating cycle. The following alternate tube repair criteria, H*, shall be applied as an alternative to the 40% depth-based criteria:

H* is the distance from the top of the tubesheet (TTS) into the tubesheet expansion region that tubes must be free of stress corrosion flaws to assure that the tubes do not pull out of the tubesheet under the limiting loads with appropriate factors of safety.

For WCGS, the H*

distance is 13.1 inches. All defects below the H* distance are not relevant to the integrity of the tube.

Therefore, inspection and repair below the H* distance is not required by technical specification. For Refueling Outage 17 and the subsequent operating cycle, tubes with service-induced flaws located greater than 13.1 inches below the top of the tubesheet do not require plugging. Tubes with service-induced flaws located in the portion of the tubesheet from the top of the tubesheet to 13.1 inches below the top of the tubesheet shall be plugged upon detection.

No corrosion related tube degradation mechanisms were detected in any region of the SGs.

Wear at Anti-Vibration Bar (AVB) intersections is an existing damage mechanism.

Secondary side maintenance and inspections were also performed.

The condition of the SGs has met all industry and regulatory structural and leakage integrity requirements.

Section 1 of this report describes the scope of inspections performed, including the nondestructive examination techniques utilized for each degradation mechanism.

Section 2 contains the location, orientation (if linear), and measured sizes (if available) of service induced indications.

Section 3 contains the inspection results, which include:

a. Active degradation mechanisms found;

Attachment to ET 10-0012 Page 2 of 7 STEAM GENERATOR TUBE INSPECTION 'REPORT

b. Number of tubes plugged during the inspection outage for each active degradation mechanism;
c. Total number and percentage of tubes plugged to date;
d. The results of condition monitoring, including the results of tube pulls and in-situ testing;
e. The primary to secondary leakage rate observed in each SG;
f.

The calculated accident leakage rate from the portion of the tube below 13.1 inches from the top of the tubesheet for the most limiting accident in the most limiting SG; and

g. The results of monitoring for the tube axial displacement (slippage).

Attachment to ET 10-0012 Page 3 of 7 STEAM GENERATOR TUBE INSPECTION REPORT Section 1: Scope and Examination Techniques of Inspections Performed The actual inspections performed during Refueling Outage 17 exceeded both the TS minimum requirements and the requirements of the Electric Power Research Institute (EPRI) Pressurized Water Reactor (PWR) Steam Generator Examination Guidelines. The following primary side inspections were performed:

100% Bobbin examination of tubes in SGs A and D, full length except for Rows 1 and 2, which are inspected with the bobbin from tube end to tube support plate (TSP) #7 on both the hot leg (HL) and cold leg (CL).

50% Row 1 and Row 2 U-bends, mid-range Plus Point examination in SG A and SG D.

Hot leg tubesheet +3"/-13.1", mid-range Plus Point examination of SGs A and D: 55%

of tubes, including 100% of the peripheral tubes, 2 pitches into the bundle.

Cold leg tubesheet peripheral tubes, +/- 3", mid-range Plus Point examination of SGs A and D: 100% of peripheral tubes; 2 pitches into the bundle.

Dings (freespan) > 5 volts: 50% of all previously identified and new dings >5 volts in the hot leg (including the U-bends) with the mid-range Plus Point probe in SGs A and D.

Dents (structures) > 2 volts: 50% of all previously identified and new dents >2 volts in the hot leg (including the U-bends) with the mid-range Plus Point probe in SGs A and D.

Plus Point examination of all "I-code" indications that are not resolved after history review.

Visual inspection of all plugs in SGs A and D.

Plus Point examination of a 5% sample of bobbin indications that have not changed since the prior inspection ("H" and "S" codes).

Plus Point inspection to bound (all surrounding tubes, at least one pitch removed) the tubes exhibiting possible loose parts (PLP) signals during the inspection.

Plus Point inspection of a sample of tubes to support the scale profiling effort.

In addition, the following secondary side maintenance and inspections were performed:

Sludge Lancing of SGs A and D.

Foreign Object Search and Retrieval (FOSAR) of SGs A and D to locate, identify, and retrieve foreign objects that were present on the steam generator tubesheet. FOSAR was also performed to inspect for any Possible Loose Parts (PLP) identified during the Eddy Current Program.

In-Bundle Inspection (IBI) of SGs A and D to inspect the condition of the top of the tubesheet and to augment the FOSAR effort.

Upper Steam Drum Inspection in SG A to evaluate the condition of the upper steam drum components with regard to damage of any kind.

Attachment to ET 10-0012 Page 4 of 7 STEAM GENERATOR TUBE INSPECTION REPORT Section 2: Indication Listing The following Enclosures contain all service-induced indications for SGs A and D.

This encompasses the location, orientation (if linear), and measured sizes (if available) of service induced indications : Steam Generator A Service-Induced Indications : Steam Generator D Service-Induced Indications The key below provides a description of the abbreviations used in the tables.

COL Column PER Percent LOCN Location INCH1 Distance from location

  1. H, #C

(# = Support Plate Number) Hot Leg or Cold Leg Side AV#

Anti-Vibration Bar (# = number)

TSH Tube Sheet Hot Leg FBC Flow Baffle Cold Leg FBH Flow Baffle Hot Leg

Attachment to ET 10-0012 Page 5 of 7 STEAM GENERATOR TUBE INSPECTION REPORT Section 3: Inspection Results Active Degradation Mechanisms Found The inspection results indicate that wear at AVB locations is an active degradation mechanism in SGs A and D. Other existing degradation mechanisms include wear at the flow distribution baffle and wear due to foreign objects.

Identification of Tubes Plug.ged Steam Generator A:

Row 40 40 44 48 49 50 18 Column 47 75 44 81 51 71 81 Attribution AVBWear AVBWear AVBWear AVBWear AVBWear AVBWear Administrative -

Geometric anomaly Steam Generator D:

Row 41 45 45 46 48 48 49 49 49 49 Column Attribution 59 AVBWear 25 AVBWear 81 AVBWear 31 AVBWear 39 AVBWear 60 AVBWear 29 AVBWear 30 AVBWear 67 AVBWear 91 AVBWear Administrative -

Geometric anomaly 16 Total Number of Tubes Plugged in Each Steam Generator Steam Generator Total Number of Tubes Plugged A

B C

D

  • 42 53 28 128 Total Percentage Plugged 0.75%

0.94%

0.50%

2.28%

  • An additional 3 plugs are installed in SG A cold leg only, due to tubesheet drilling errors during manufacturing. No tubes are installed in those locations.

Attachment to ET 10-0012 Page 6 of 7 STEAM GENERATOR TUBE INSPECTION REPORT Results of Condition Monitorinq The examination results confirm that the Wolf Creek Generating Station (WCGS) SGs currently meet all industry and regulatory structural and leakage integrity guidance. No indications were found to exceed structural limits. No tube pulls or in-situ testing were required.

AVB wear is an existing degradation mechanism.

The maximum observed indication (51% through wall depth (TWD) at an AVB location) meets the structural and leakage requirements.

Two geometric anomalies were reported from the top of tubesheet plus point program.

The plus point data indicated possible degradation in the signals but this was not confirmed by use of the Ghent probe. Both indications were co-located at the site of an axially oriented, linear geometric response running to, and through, the expansion region. The linear responses are seen in the historical data and are likely related to original SG manufacturing. The indication in SG D was present in historic data. The indication in SG A could not be found in the historic data; however, the previous data quality did not support detection of a low level signal such as this.

The analyst consensus is that these indications are related to geometric variations and are not indications of degradation.

Nevertheless, Wolf Creek conservatively chose to administratively plug these tubes.

" Wear at the flow distribution baffle (FDB) is an existing degradation mechanism that is not progressing. FDB wear is attributed to a prior application of pressure pulse cleaning of the SGs.

No new indications were reported as expected; all indications were previously reported at RF13 and RF15. The magnitude of the wear does not challenge the performance requirements for condition monitoring.

Wear detected at three TSP intersections in SG D is an existing degradation mechanism that is not progressing. This degradation mechanism is not an operational degradation mechanism but is the result of previous transient foreign objects interacting with the tubes. The current indications of wear at the tube support plates meet the performance criteria for condition monitoring.

" Volumetric indications detected at the TTS have not changed since the prior inspection at RF13 and RF15. One previously reported TTS volumetric indication was not found at RF17. The reported changes in depth are small and within the normal variability of the sizing technique. The likely source of these indications is wear due a transient foreign object at a prior time. No new wear indications from foreign objects were detected. No foreign objects were found among the tubes with volumetric indications and their neighboring tubes. The largest indication is 17% TWD, which poses no challenge to the condition monitoring performance criteria.

No corrosion related degradation mechanisms were observed.

No degradation indications were observed related to potential precursor signals such as dents and dings, or to interferences such as permeability variations, etc.

" Leakage is not an issue for any indication detected. There is currently no leakage in the SGs.

All plugs were found to be in acceptable condition based on visual inspection.

No precursor signals (e.g., Distorted Support Indication (DSI)) were found in tubes identified as potentially having an elevated residual stress condition.

No tube-to-tube contact wear was found on any tubes adjacent to tubes that were previously identified as potentially requiring stabilization due to continuing wear after

Attachment to ET 10-0012 Page 7 of 7 STEAM GENERATOR TUBE INSPECTION REPORT plugging for AVB wear. Therefore, in accordance with evaluations documented in the Degradation Assessment, stabilization of any previously plugged tubes was not required.

The commitment for H* to calculate accident induced leakage by a prescribed method was met. Because there is no existing normal operating leakage at WCGS and there are no damage mechanisms for which leakage is predicted, the predicted accident induced leakage for WCGS is zero.

No adjustment to the administrative shutdown leakage limit is required.

The commitment for H* to monitor for tube slippage was met. The absence of tube slippage was determined by confirming that there were no tube severances below the H* distance.

Sludge lancing activities removed 21.5 pounds from SG A and 22 pounds from SG D.

Foreign object search and retrieval (FOSAR) activities in SGs A and D identified and removed some minor foreign objects. Possible loose part (PLP) indications reported by eddy current testing were further evaluated by visual inspection and bounded using the Plus Point probe.

No degradation was associated with any PLP indication.

Minor foreign objects remaining in the SG are bounded by a prior analysis and are acceptable for continued operation. The analysis concluded that the.known foreign objects will not limit operation of the SGs.

" Secondary side visual inspection activities performed at the top of the tubesheet in SGs A and D were successful in gathering additional information which is used to determine future maintenance and cleaning strategies. No immediate concerns were identified.

Upper steam drum inspections in SG A collected additional data used for monitoring and trending of upper steam drum components. No immediate concerns were identified.

Analysis of the data collected for scale profiling is currently on-going. This information is used in conjunction with visual inspection data to continue trending the condition of the secondary side of the steam generators in order to plan future maintenance and cleaning strategies. No immediate concerns are expected from this analysis.

to ET 10-0012 Steam Generator A Service-Induced Indications

SG A

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20 ROW COL PER LOCN INCHI1


+

1 25 8

11 AVI

.001 28 9

11 AV5

.001 27 10 11 AV5

.001 30 10 10 AV2

.001 30 10 14 AV5

.001 30 10 11 AV6

.001 35 14 11 AV1

.001 38 19 12 AV4

.001 40 19 12 AV2

.001 40 19 14 AV5

.001 35 20 15 AV3

.001 40 20 12 AV5

.001 42 22 17 AV5

.00!

38 25 14 AV2

.0 39 25 14 AV2

.001 45 25 28 AV2

.001 45 25 22 AV3

.00 45 25 19 AV4

.001 45 25 32 AV5

.001 27 26 18 AV5

.001 45 26 24 AV3

.00!

45 26 29 AV4

.001 45 26 16 AV5

.001 39 27 16 AV3

.001 40 27 16 AV2

.001 ROW COL PER LOCN INCH11 I

ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 1110312009 13:32:20

--+----

-+-------

+

1 ROW COL PER LOCN INCH11 I-

+

48 27 14 AV4

.001 48 27 13 AV5

.001 44 28 13 AV3

.001 44 28 19 AV5

.00 37 29 17 AV6

.001 38 29 17 AV2

.001 38 29 14 AV3

.001 40 29 11 AV2

.001 41 29 14 AV4

.001 41 29 14 AV4

.00 41 30 20 AV4

.001 45 30 21 AV2

.00 45 30 29 AV3

.001 45 30 15 AV4

.001 45 30 17 AV5

.001 50 30 11 AV5

.001 23 31 12 AV1

.001 41 31 16 AV2

.00 41 31 20 AV4

.001 44 31 15 AV4

.001 37 32 10 AV4

.001 41 32 13 AV2

.001 41 32 27 AV3

.001 41 32 18 AV4

.001 I

I 45 32 17 AV2

.001 45 32 23 AV3

.001 45 32 37 AV4

.001 45 32 30 AV5

.001

. ROW COL PER LOCN INCH11 2

ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20 1 ROW COL PER LOCN INCH1I

+---

-+----+---------+------

1 45 32 15 AV6

.001 47 32 17 AV2 I00 47 32 36 AV3

.001 47 32 28 AV4

.001 47 32 16 AV5

.001 47 32 12 AV6

.001 34 33 14 AV4

.001 38 33 15 AV3

.001 45 33 31 AV4

.001 45 34 14 AV2

.001 45 34 20 AV4

.001 47 34 18 AV3

.001 47 34 11 AV4

.001 I50 34 14 AV1

.00 50 34 19 AV2

.001 50 34 11 AV3

.001 48 35 11 AV2

.001 48 35 18 AV3

.001 48 35 17 AV4

.001 48 35 21 AV5

.001 33 36 20 AV2

.001 33 36 16 AV3

.001 33 36 15 AV5

.001 35 36 18 AV5

.001 43 36 15 AV3

.001 43 36 16 AV4

.001 45 36 20 AV2

.001 47 36 15 AV2

.001

+---

--+---

-+-- -

-+------

I ROW COL PER LOCN INCH11

+--------.---

-+-----+-------.+

3 ST Max

SG

- A Service Induced Ind catiohs Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20

.-- +

+----.----+--

+

1 ROW COL PER LOCN INCH11 1 36 37 12 AV3

.001 36 37 12 AV4

.001 37 37 14 AV5

.00 38 37 14 AV5

.001 45 37 19 AV2

.001 45 37 29 AV3

.001 45 37 14 AV4

.001 45 37 13 AV6

.001 48 37 22 AV3

.001 30 38 18 AV5

.00 40 38 19 AV4

.001 41 38 15 AV4

.001 I

43 38 16 AV2

.001 43 38 39 AV3

.00 43 38 19 AV4

.00I 43 38 20 AV5

.001 45 38 15 AV1

.001 45 38 25 AV3

.001 45 38 22 AV4

.001 48 38 13 TSH

.031 39 39 20 AV3

.001 39 39 24 AV4

.001 39 39 17 AV5

.001 39 39 22 AV6

.001 39 39 22 AVI

.00 44 39 22 AV2

.001 44 39 17 AV3

.001 I44 39 33 AV4

.001 44 39 27 AV5

.001 44 39 16 AV6

.001

+---------------+---

ROW COL PER LOCN INCH11

+..

4 ST Max

SG A

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/0312009 13:32:20 1 ROW COL PER LOCN INCH11

~------------------------------

38 40 19 AV2

.001 38 40 20 AV3

.001 38 40 16 AV5

.001 38 40 14 AV6

.001 41 40 18 AV2

.001 41 40 15 AV5

.001 41 40 20 AV6

.001 43 40 13 AV5

.001 44 40 12 AV1

.001 44 40 16 AV2

.001 44 40 11 AV3

.001 45 40 18 AV3

.001 45 40 30 AV4

.001 45 40 13 AV5

.001 46 40 16 AV1

.00 46 40 32 AV2

.001 46 40 38 AV4

.001 46 40 34 AV5

.001 27 41 18 AV2

.001 27 41 24 AV5

.00I 28 41 13 AV2

.001 28 41 18 AV5

.001 38 41 13 AV2

.001 38 41 29 AV3

.001 38 41 22 AV4

.001 40 41 17 AV3

.00 40 41 14 AV4

.001 44 41 17 AV4

.001 44 41 32 AV5

.00 44 41 17 AV6

.001 45 41 17 AV2

.001

+----+

-+-----.

I ROW COL PER LOCN INCH11

-+-------

5 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 1110312009 13:32:20


+

~IROW COL PER LOCN INCH11 1 45 41 35 AV3

.001 45 41 28 AV4

.001 45 41 27 AV5

.001 45 41 19 AV6

.001 26 42 13 AV2

.0@I 26 42 14 AV5

.001 27 42 19 AV5

.001 30 42 16 AV2

.001 36 42 16 AV1

.001 36 42 20 AV2

.001 36 42 17 AV3

.001 36 42 18 AV4

.001 36 42 29 AV5

.001 36 42 11 AV6

.001 40 42 15 AV2

.001 40 42 18 AV3

.001 40 42 24 AV4

.001 40 42 18 AV5

.001 40 42 14 AV6

.001 56 42 11 AV6

.001 28 43 11 AV2

.001 36 43 23 AV2

.001 36 43 13 AV5

.001 41 43 12 AV2

.001 41 43 22 AV3

.001 41 43 11 AV4

.001 41 43 30 AV5

.001 41 43 13 AV6

.001 30 44 20 AV5

.001 35 44 12 AV5

.001 4------------

4------------------------+

ROW COL PER LOCN INCH11

÷....

6 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20

.ROW COL PER LOCN INCH11

+--.----

38 44 16 AV5

.001 41 44 20 AV2

.00 41 44 26 AV3

.001 41 44 24 AV4

.001 41 44 18 AV5

.001 41 44 14 AV6

.001 43 44 17 AV3

.001 43 44 17 AV5

.001 44 44 41 AV2

.001 44 44 31 AV3

.001 44 44 27 AV4

.001 44 44 30 AV5

.001 44 44 27 AV6

.001 28 45 27 AV6

.001 28 45 16 AV6

.001 35 45 19 AV1

.001 35 45 21 AV2

.001 36 45 10 AV1

.001 36 45 21 AV2

.001 36 45 16 AV3

.00 36 45 22 AV4

.001 36 45 26 AV5

.001 36 45 20 AV6

.001 37 45 16 AV2

.001 37, 45 13 AV6

.001 38 45 16 AV3

.001 38 45 11 AV4

.001 38 45 19 AV5

.001 39 45 36 AV4

.001 39 45 23 AV5

.001 40 45 13 AV2

.001 40 45 13 AV3

.001 IA 38.

45

19.

V5

.01 I ROW COL PER LOCN INCH11 1..

9.

45 36..

AV4.--....-

7 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20 ROW COL PER LOCN INCH11 4---

1 40 45 15 AV4

.001 41 45 16 AV5

.00 41 45 12 AV6

.001 43 45 11 AV3

.001 44 45 21 AV3

.001 44 45 22 AV4

.00 44 45 18 AV5

.001 44 45 11 AV6

.001 26 46 13 AV2

.001 26 46 16 AV5

.001 28 46 21 AV2

.001 28 46 34 AV5

.001 28 46 15 AV6

.001 30 46

.22 AV2

.001 33 46 14 AV3

.001 34 46 12 AV3

.001 35 46 13 AV2

.001 35 46 14 AV3

.001 35 46 14 AV4

.001 39 46 34 AV2

.001 39 46 27 AV3

.001 39 46 29 AV4

.001 43 46 13 AV2

.001 43 46 15 AV3

.001 43 46 32 AV4

.001 43 46 15 AV5

.001 43 46 14 AV6

.001 44 46 22 AV2

.001 44 46 28 AV3

.001 44 46 17 AV4

.001

+---

-+-----.+

ROW COL PER LOCN INCH11

+----+----+-

+-------.

+

8 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO0XVIISAP 20091001

  • l ROW COL PER LOCN INCH11

-- ÷----+-- - -

+

11/03/2009 13:32:20 1 44 46 15 AV5 49 49 50 50 50 I 32 34 34 34 36 36 37 37 37 39 39 39 40 40 40 40 40 40 42 42 44 26 36 46 46 46 46 46 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 47 48 48 26 AV3 20 AV4 15 AV2 27 AV3 22 AV4 15 AV5 23 AV2 18 AV3 24 AV5 12 AV3 15 AV5 22 AV3 33 AV4 22 AV5 15 AV2 15 AV4 16 AV5 28 AV1 43 AV2 42 AV3 26 AV4 21 AV5 14 AV6 16 AV5 15 AV6 21 AV2 15 AV5 19 AV5

.00

.00I

.00I

.00

.00I

.00I

.00I

.00

.00I

.00I

.00I

.00

.00I

.00I

.00I

.00I

  • 001

.00I

.00I

.00I

.00I

.00I

.00I

.00

  • 001

.00I

.00I

.00I

.00I

+--.

1 ROW COL PER LOCN INCH11

+----+----.----+-

-I-.------4..

9 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20

  • IROW COL PER LOCN INCH11

+

37 48 18 AV2

.001 37 48 13 AV3

.001 37 48 12 AV5

.081 38 48 27 AV2

.00 38 48 25 AV3

.001 38 48 15 AV4

.001 38 48 14 AV5

.001 40 48 18 AV5

.001 40 48 16 AV6

.001 44 48 11 AV2

.001 22 49 15 AV2

.00 22 49 10 AV6

.001 24 49 15 AV2

.00J 36 49 19 AV2

.00]

I36 49 17 AV3.

36 49 19 AV4

.001 36 49 17 AV3

.001 40 49 18 AV2

.001 40 49 25 AV3

.00J 40 49 16 AV4

.001 40 49 12 AV5

.001 36 50 17 AV2

.001 36 50 17 AV3

.001 36 50 20 AV4

.001 36 50 16 AV5

.001 36 50 11 AV6

.001 38 50 17 AV4

.00 39 50 13 AV4

.001 27 51 13 AV5

.001 49 51 18 AV1

.001 49 51 49 AV2

.001

-4.-.....

+

I ROW COL PER LOCN INCH11

+-.--

+

10 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2109 13:32:20

~----------------------------+-

..ROW COL PER LOCN INCH11

+----. - ---+- +----- - -+-----+

1 49 51 35 AV3

.08 49 51 32 AV4

.001 49 51 35 AV5

.001 49 51 19 AV6

.001 36 52 12 AV2

.001 38 52 22 AV3

.00 38 52 17 AV4

.001 38 52 15 AV5

.001 40 52 23 AV2

.001 40 52 16 AV3

.00 40 52 29 AV4

.001 40 52 29 AV5

.001 40 52 20 AV6

.001 43 52 20 AV2

.001 33 53 18 AV2

.001 3

43 53 15 AV3

.001 33 53 11 AV4

.00 33 53 13 AV5

.001 34 53 17 AV2

.001 36 53 17 AV6

.001 38 53 14 AV3

.001 40 53 11 AV3

.001 41 53 11 AV3

.001 42 53 19 AV2

.001 42 53 15 AV3

.001 42 53 14 AV4

.001 42 53 28 AV5

.001 49 53 18 AV5

.001 49 53 14 AV6

.00 I 42 53 15 AV3

.081------

IRO COL PER LOCN INCH1 11 ST Max

SG - A Service Induced Indications Wolf Creek I RFO XVIISAP 20091001 11/03/2009 13:32:20

+- -

-+-....-

+-

RO CLPER LOCN INCH11 4--

35 54 19 AV2

.001 35 54 15 AV3

.001 36 54 21 AV3

.001 36 54 17 AV5

.001 37 54 15 AV2

.001 40 54 12 AV2

.001 41 54 15 AV4

.001 41 54 33 AV5

.001 41 54 10 AV6

.001 42 54 15 AV4

.001 42 54 22 AV5

.00O 18 55 18 AV1

.008 36 55 17 AV5

.001 38 55 11 AVI

.001 38 55 16 AV2

.008 38 55 30 AV3

.008 38 55 32 AV4

.001 42 55 13 AV4

.001 50 55 21 AV2

.001 35 56 15 AV2

.001 44 56 22 AV2

.00 44 56 28 AV3

.001 44 56 23 AV4

.001 44 56 20 AV5

.001 23 57 16 AVI

.001 23 57 20 AV5

.001 42 57 17 AV3

.001

+.-------------------+

1 ROW COL PER LOCN INCHI) 12 ST Max

SG

- A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20 I ROW COL PER LOCN INCH11 4--

+--------

+

19-- 58 19..

+A....+

19 58 19 AV1

.001 19 58 19 AV6

.00 31 58 19 AV2

.001 41 58 27 AV2

.0I 41 58 18 AV3

.001 43 58 31 AV2

.001 43 58 25 AV3

.001 43 58 26 AV4

.001 43 58 25 AV5

.001 34 59 10 AV4

.001 39 59 14 AV3

.001 39 59 16 AV5

.001 41 59 18 AV2

.001 41 59 26 AV3

.001 41 59 19 AV4

.001 44 59 29 AV2

.001 44 59 32 AV3

.001 44 59 19 AV4

.001 44 59 17 AV6

.001 44 60 21 AV3

.001 44 60 18 AV4

.001 44 60 13 AV5

.001 34 61 22 AV4

.00 34 61 12 AV5

.001 38 61 11 AV3

.001 42 61 19 AV2

.001 J 50 61 13 AV4

.00 50 61 11 AV5

.00 36 62 13 AV2

,00 1 ROW COL PER LOCN INCH11

+----+----+----+---

+

13 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20

  • .ROW COL PER LOCN INCH11

-....I+

36 63 11 AV2

.001 36 63 12 AV3

.001 44 63 10 AV2

.001 37 64 16 AV2

.00 37 64 15 AV3

.001 37 64 17 AV4

.001 37 64 10 AV5

.001 57 64 17 AV2

.001 40 65 12 AV2

.001 44 66 13 AV3

.00 51 66 20 AV2

.001 51 66 11 AV3

.001 38 67 15 AV5

.001 42 68 19 AV3

.001 49 68 20 AV2

.001 49 68 15 AV3

.001 40 70 17 AV1

.001 40 70 33 AV3

.001 40 70 28 AV4

.00I 40 70 14 AV5

.001 40 70 12 AV6

.001 50 70 29 AV2

.001 27 71 15 AV2

.001 50 71 25 AV2

.001 50 71 42 AV3

.001 50 71 44 AV4

.001 50 71 46 AV5

.001

+- --

+-----

I ROW COL PER LOCN INCH11

+....

..-+-..

- - -+

14 ST Max

SG

- A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20 ROW COL PER LOCN INCHll

~------------------------------

3 74..

13.. A....--

1 37 74 13 AVI

.001 37 74 31 AV3

.00l 37 74 31 AV4

.001 37 74 31 AV5

.001 37 74 12 AV6

.00 39 75 23 AV3

.001 40 75 34 AVM

.800 40 75 19 AV2

.001 40 75 37 AV3

.001 40 75 36 AV4

.001 40 75 40 AV5

.001 41 75 22 AV2

.001 41 75 27 AV3

.001 41 75 26 AV4

.001 41 75 35 AV5

.001 41 75 18 AV6

.001 O

42 75 23 AV

.001 44 7

44 75 25 AV3

.001 44 75 28 AV4

.001 44 75 27 AV5

.001 I44 75 21 AV6

.001 39 76 22 AV2

.001 39 77 15 AV3

.001 44 77 23 AV4

.001 44 77 16 AV5

.001 58 77 10 AV6

.001 34 78 19 AV2

.I00 34 78 11 AV3

.001 34 78 22 AV5

.001 39 78 14 AV3

.00 39 78 14 AV5

.001

.I ROW COL PER LOCN INCH11

+--------------4--

15 ST Max

SG

- A Service Induced Indl*at'ins Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20

+---- -+------

I ROW COL PER LOCN INCH11

+------------------------------

1 39 78 16 AV6

.001 39 79 15 AV3

.081 39 79 21 AV4

.001 39 79 14 AV5

.001 27 80 17 ýAV5

.001 34 80 15 AV1

.001 34 80 18 AV2

.001 40 80 19 AV2

.001 28 81 13 AV2

.001 28 81 13 AV5

.001 39 81 15 AV2

.001 39 81 18 AV4

.001 39 81 16 AV5

.001 1 44 81 13 AV2

.001 46 81 13 AV2

.001 46 81 10 AV3

.001 46 81 12 AV5

.00 48 81 32 AV2

.00 48 81 27 AV3

.001 48 81 18 AV4

.001 48 81 40 AV5

.001 56 81 11 AV5

.001 27 82 11 AV2

.001 27 82 17 AV5

.001 36 82 14 AV2

.001 39 82 11 AV2

.001 39 82 15 AV4

.001 40 82 20 AV2

.001 I ROW COL PER LOCN INCH11

+- ---

+----+--------+------

+

16 ST Max

SG A

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20 I ROW COL PER LOCN INCH11 1 40 82 16 AV3

.001 40 82 17 AV4

.001 40 82 17 AV5

.001 36 83 17 AV1

.00 46 83 15 AVI

.001 46 83 14 AV2

.00I 25 84 10 AV2

.001 34 84 17 AV2

.00 34 84 17 AV3

.001 34 84 12 AV4

.00I 34 84 13 AV5

.001 36 84 14 AV5

.001 39 84 11 AV1

.001 39 84 35 AV2

.00 I

39 84 35 AV3

.001 39 84 24 AV4

.001 39 84 25 AV5

.001 39 84 22 AV6

.001 44 84 14 AV3

.001 44 84 11 AV4

.001 44 84 14 AV3

.00I 45 84 17 AV4

.001 53 84 13 AV5

.00j 33 85 16 AV4

.001 39 85 15 AV2

.001 39 85 34 AV3

.00 39 85 36 AV4

.001 39 85 23 AV5

.I0 39 85 14 AV6

.001 54 85 12 AV5

.001

.ROW COL PER LOCN INCH11

+

17 ST Max

SG A

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20 I ROW COL PER LOCN INCH11 I

I 1 25 86 13 AV5

.001 30 86 13 AV5

.001 31 86 22 AV5

.00 36 86 11 AV2

.00 46 86 14 AV1

.001 46 86 19 AV2

.00 46 86 27 AV3

.001 46 86 15 AV4

.001 26 87 14 AV5

.001 30 87 18 AV5.0 39 87 17 AV1

.001 39 87 13 AV2

.001 39 87 16 AV3

.001 39 87 34 AV4

.001 39 87 16 AV5

.001 39 87 17 AVN

.001 44 87 17 AV2

.00 44 87 15 AV3

.00 50 87 20 AV6

.001 50 87 16 AV2

.001 50 87 18 AV3

.001 50 87 21 AV4

.001 50 87 24 AV5

.001 50 87 18 AV1

.001 50 87 16 AV2

.001 50 87 17 AV3

.001 50 87 20 AV4

.001 50 87 24 AV5

.001 20 88 17 AV6

.001 30 88 19 AV2

.001 1 ROW COL PER LOCN INCH11 18 ST Max

SG

- A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20

.--- -+....

+....+--

+---------+

ROW COL PER LOCN INCH11 1 30 88 18 AV5

.001 38 89 23 AV5

.001 39 89 16 AV4

.001 44 89 18 AV2

.0@

44 89 20 AV3

.001 44 89 30 AV4

.001 44 89 19 AV5

.001 44 89 21 AV6

.001 50 90 16 AV4

.001 50 90 32 AV5

.001 35 91 17 AV1

.001 35 91 25 AV4

.001 36 91 24 AV2

.001 36 91 28 AV4

.001 36 91 13 AV4

.001 36 91 22 AV6

.001 41 91 12 AV6

.001 26 92 18 AV5

.001 35 92 18 AV3

.00 35 92 13 AV4

.001 35 92 15 AV5

.001 35 92 14 AV6

.001 36 92 11 AV2

.001 36 92 10 AV5

.001 44 92 17 AV3

.00 44 92 26 AV4

.001 38 93 18 AV5

.001 39 93 17 AV2

.001 39 93 29 AV3

.001

- 39...

93-29----

I ROW COL PER LOCN INCH11

+....

...÷.... ÷ 19 ST Max

SG

- A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 1110312009 13:32:20

~------------------------------

  • IROW COL PER LOCN INCHiI

- - -+- --.------

+---

+

39 93 18 AV4

.001 39 93 15 AV5

.001 39 94 14 AV3

.00 39 94 16 AV5

.001 20 95 15 AV6

.001 38 95 16 AV4

.00 38 95 20 AV5

.001 39 95 14 AV2

.001 39 95 18 AV3

.001 39 95 22 AV4

.001 39 95 13 AV5

.001 39 96 19 AV3

.00 39 96 19 AV4

.001 48 96 13 AV3

.001 48 96 14 AV5

.001 27 97 12 AV1

.001 27 97 18 AV2

.001 35 97 18 AV4

.001 37 97 14 AV2

.001 37 97 16 AV3

.001 37 97 12 AV4

.00 37 97 19 AV5

.001 37 98 12 AV2

.001 37 98 18 AV3

.001 38 98 20 AV3

.001 38 98 23 AV4

.001 39 98 11 AV3

.001 35 99 16 AV5

.001

+--------------+--

+--------+

I ROW COL PER LOCN INCH11

+---

-+

--- +---

-+------÷

+

20 ST Max

SG - A Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:32:20


.--- ---+--

.I ROW COL PER LOCN INCH11


4 1 38 99 16 AV2

.001 38 99 24 AV4

.001 37 100 13 AV3

.00 37 100 17 AV4

.001 37 100 14 AV3

.001 37 100 16 AV4

.001 39 101 16 AV3

.001 39 101 21 AV4

.001 39 101 17 AV5

.001 39 102 17 AV4

.001 40 102 21 AV3

.001 40 102 18 AV4

.001 40 102 17 AV5

.001 40 103 15 AV3

.001 40 103 15 AV4

.001 O 40 103 17 AV6

.00 43 103 15 AV3

.001 38 106 175 AV4

.001 38 106 14 AV5

.001 26 109 18 AV2

.001 27 109 19 AV2 eel 36 109 16 AV4

.001 36 110 18 AV2

.001 36 110 16 AV3

.001 36 110 29 AV4

.001 36 110 37 AV5

.001 36 110 20 AV6

.001

+--+

4 4.

ROW COL PER LOCN INCH11

+--------------+---------------

Tubes: 272 Records: 607 21 ST Max to ET 10-0012 Steam Generator D Service-Induced Indications

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+- ----

---+------------.------+

. ROW COL PER LOCN INCHIJ

+---

-+-

--- +----+-

- -+----------------+

27 8

11 AV1

.001 27 8

18 AV6

.001 29 10 12 AV1

.00 29 10 12 AV2

.001 29 10 25 AV5

.001 30 10 16 AV2

.001 30 10 26 AV5

.001 32 11 13 AV2

.001 32 11 19 AV6

.001 33 11 19 AV2

.00 33 11 18 AV5

.001 33 11 22 AV6

.001 31 12 10 AV5

.001 32 12 18 AV5

.001 32 12 12 AV6

.001 33 12 16 AV1

.00 33 12 20 AV2

.001 33 12 36 AV4

.001 33 12 31 AV5

.001 33 12 13 AV6

.001 34 12 12 AV6

.001 31 13 11 AV3

.001 31 13 10 AV5

.001 34 13 35 AV3

.001 34 13 17 AV4

.001 34 13 14 AV6

.001 32 14 25 AV4

.001 32 14 13 AV5

.001 32 14 15 AV6

.001 33 14 15 AV2

.001 I

33-- 14 15.. AV2...

. ROW COL PER LOCN INCH11


+

1 ST Max

SG D

Service Induced Indications Wolf Creek 1 RFO XVIISAP 26691061 11/03/2609 13:36:14


+

ROW COL PER LOCN INCH11

+---

+-

33 14 15 AV3

.661 33 14 20 AV4

.001 34 14 15 AV2

.001 34 14 15 AV6

.001 35 14 12 AV1

.001 35 14 21 AV5

.001 35 14 12 AV6

.001 36 14 14 AV6

.001 33 15 21 AV4

.001 35 15 14 AV2

.001 35 15 17 AV4

.001 36 15 24 AV5

.001 33 16 13 AV3

.001 33 16 14 AV4

.061 36 16 12 AV3

.001 36 16 26 AV4

.001 36 16 14 AV5

.001 36 16 12 AV6

.001 37 16 20 AV3

.001 37 16 22 AV4

.061 37 16 16 AV5

.001 37 16 22 AV6

.001 38 16 23 AV3

.001 38 16 32 AV4

.601 38 16 19 AV6

.001 35 17 26 AV2

.001 35 17 29 AV3

.001 37 17 17 AV3

.001 37 17 29 AV4

.001 37 17 18 AV5

.001 9

  • ROW COL PER LOCN INCH11

+-....-

2 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

  • ROW COL PER LOCN INCH11

+.--

+ ----

+-------------------

37 17 14 AV6

.001 38 17 14 AV1

.00 38 17 13 AV2

.001 38 17 14 AV4

.001 38 17 18 AV6

.001 34 18 14 AV4

.001 35 18 10 AV3

.00 35 18 14 AV5

.001 37 18 14 'AV1

.00 37 18 15 AV3

.001 37 18 13 AV4

.001 37 18 11 AV5

.001 38 18 15 AV4

.001 38 18 11 AV5

.001 38 18 13 AV6

.001 39 18 16 AV2

.001 39 18 19 AV3

.001 41 18 17 AV1

.001 41 18 19 AV3

.001 41 18 20 AV4

.001 41 18 17 AV5

.001 26 19 23 4H

-.591 30 19 14 AV5

.001 33 19 21 AV3

.001 37 19 15 AV1

.001 37 19 27 AV3

.001 37 19 16 AV4

.001 38 19 17 AV1

.001 38 19 31 AV3

.001 38 19 15 AV4

.001

---37 --19 --27 ---------

0-1 I ROW COL PER LOCN INCH11

+

3 ST Max

SG -

D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+.+.--------------------------

IROW COL PER LOCN INCHIl

+-------------------------+

38 19 16 AV5

.001 38 19 16 AV6

.001 39 19 31 AV2

.I00 39 19 22 AV3

.001 39 19 19 AV5

.001 39 19 18 AV6

.001 40 19 16 AV2

.001 140 19 16 AV4

,00 40 19 12 AV5

.001 40 19 10 AV6

.001 32 29 10 AV3

.001 37 20 11 AV2

.001 37 20 7

AV3

.00-37 20 13 AV4

.001 1 39 20 26 AV2

,001 39 20 34 AV3

.00 39 20 11 AV4

.001 40 20 34 AV4

.001 40 20 16 AV6

.001 31 21 13 TSH

. 061 37 21 20 AV2

.001 37 20 17 AV4

.001 38 21 19 AV2

.001 38 21 15 AV3

.001 138 21 21 AV4

.001 39 21 20 AV3

.001 39 21 18 AV5

.001 40 21 16 AV4

.001 40 21 18 AV5

.001 40 21 16 AV6

.001

.+- - --

+-

+

1 ROW COL PER LOCN INCHiI 4-----.

4 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11

+----.----+

+------..+

38 19 16 AV5

.001 38 19 16 AV6

.001 39 19 31 AV2

.00 39 19 22 AV3

.001 39 19 19 AV5

.001 39 19 18 AV6

.001 1 40 19 16 AV2

.001 40 19 16 AV4

.001 40 19 12 AV5

.001 40 19 10 AV6

.00@

32 20 10 AV3

.001 37 20 11 AV2

.001 37 20 7

AV3

.001 37 20 13 AV4

.001 39 20 26 AV2

.00 I 39 20 34 AV3

.001 39 20 11 AV4

.001 40 20 20 AV4

.00 40 20 16 AV6

.001 31 21 13 TSH

.061 37 2

37 21 20 AV2

.001 37 21 17 AV4

.001 38 21 19 AV2

.001 I38 21 15 AV3

.001 38 21 21 AV4

.001 39 21 20 AV3

,00 39 21 18 AV5

.001 40 21 16 AV4

.001 40 21 18 AV5

.001 40 21 16 AV6

.001

-+- -----

- -. -+- - - -.------

+

I ROW COL PER LOCN INCH11

+....

4 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 1110312009 13:36:14 1 ROW COL PER LOCN INCH11

~-------------------------------

41 21 15 AVI

.001 41 21 14 AV2

.001 41 21 23 AV5

.001 38 22 11 AV2

.00 38 22 17 AV3

.001 38 22 13 AV4

.001 38 22 15 AV6

.001 40 22 12 AV3

.001 41 22 22 AV2

.001 41 22 28 AV3

.00 41 22 28 AV5

.001 41 22 20 AV6

.001 42 22 13 AV4

.001 42 22 17 AV5

.001 42 22 13 AV6

.001 30 23 16 AV2

.001 35 23 20 AV3

.001 38 23 18 AV5

.001 38 23 17 AV6

.001 40 23 15 AV4

.001 40 23 25 AV5

.001 I

I 45 23 12 AV3

.001 39 24 17 AV2

.001 39 24 19 AV4

.001 42 24 19 AV2

.001 42 24 20 AV4

.001 42 24 11 AV6

.001 39 25 22 AV3

.00 39 25 15 AV5

.001

-- 39.. 24 19..-

4-I ROW COL PER LOCN INCH11

+-----------------------------.

5 ST Max

SG D

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11 4-------

+---------

4-------------------+

S 41-- 25 18.. AV3...

1 41 25 18 AV3

.001 41 25 20 AV5

.00 43 25 21 AV2

.001 43 25 37 AV3

.001 43 25 29 AV4

.001 43 25 15 AV5

.001 43 25 20 AV6

.001 44 25 28 AV3

.001 44 25 28 AV4

.001 44 25 19 AV5

.001 44 25 15 AV6

.001 45 25 11 AV1

.00 45 25 12 AV2

.001 45 25 26 AV3

.001 45 25 38 AV5

.001 45 25 43 AV6

.001 47 25 29 AV4

.001 47 25 17 AV6

.001 32 26 14 AV6

.001 37 26 19 AV2

.001 37 26 14 AV5

.00 37 26 15 AV6

.001 42 26 14 AV2

.001 47 26 26 AV5

.001 47 26 29 AV6

.001 48 26 23 AV3

.001 48 26 31 AV4

.00 48 26 23 AV5

.001 48 26 28 AV6

.001 41 27 20 AV2

.001 41 27 18 AV4

.00 41 27 15 AV5

.00

+-.

+--

1 ROW COL PER LOCN INCH11 6

ST Max

SG

- D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+

1 ROW COL PER LOCN INCH11 43 27 18 AV2

.001 43 27 33 AV3

.001 43 27 14 AV4

.001 43 27 21 AV5

.001 43 27 20 AV6

.001 44 27 13 AV4

.00 44 27 11 AV5

.001 45 27 12 AV4

.001 45 27 11 AV5

.001 47 27 15 AV5

.001 47 27 15 AV6

.001 37 28 21 AV6

.001 42 28 27 AV2

.00 42 28 21 AV3

.001 42 28 17 AV4

.001 42 28 22 AV6

.001 45 28 26 AV2

.001 45 28 25 AV3

.00 45 28 17 AV4

.001 45 28 36 AV5

.001 45 28 33 AV6

.001 46 28 26 AV5

.001 46 28 22 AV6

.001 47 28 24 AV2

.001 47 28 24 AV3

.001 47 28 35 AV5

,00 47 28 27 AV6

.001 48 28 31 AV5

.001 48 28 25 AV6

.00 1

29 5

FBC

-. 331 1 ROW COL PER LOCN INCH11

..-- -+----

+ ---.

+-------------------

7 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11 4-

- ----4-----4-------------------+

1 44 29 19 AV3

.001 46 29 18 AV4

.I01 46 29 15 AV5

.001 48 29 13 AV6

.001 49 29 41 AV2

.00 49 29 19 AV3

.001 49 29 40 AV4

.001 49 29 23 AV5

.001 49 29 26 AV6

.001 50 29 12 AV4

.001 50 29 18 AV5

.001 1

30 14 FBC

.301 42 30 26 AV2

.00 42 30 30 AV3

.001 42 30 22 AV5

.001 43 30 16 AV2

.001 43 30 24 AV5

.001 46 30 28 AV3

.001 49 30 26 AV1

.001 49 30 41 AV2

.00 49 30 43 AV3

.001 49 30 27 AV4

.001 49 30 28 AV5

.001 49 30 31 AV6

.001 50 30 36 AV6

.001 1

31 9

FBC

.301 1

31 2

FBH

-. 381 1

31 3

FBH

.111 46 31 17 AV1

.00 46 31 25 AV2

.001 4------------

4------------------------+

I ROW COL PER LOCN INCH11 8

ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+--------+----+ -------------------

ROW COL PER LOCN INCH11 46 31 35 AV3

.00 46 31 45 AV4

.001 46 31 42 AV5

.001 47 31 18 AV2

.001 47 31 14 AV3

.001 47 31 16 AV4

.00 47 31 37 AV5

.00 49 31 21 AV3

.001 49 31 11 AV4

.00 49 31 24 AV5

.00 49 31 18 AV6

.00 50 31 23 AV4

.00 50 31 29 AV5

.00 50 31 12 AV6

.00 1

32 5

FBC

-.311 1

32 3

FBH

-. 381 1

32 4

FBH

.331 32 32 23 AV3

.00 41 32 21 AV3 eel 41 32 23 AV4

.00 47 32 31 AV4

.00 47 32 37 AV5

.00 47 32 14 AV6

.00 49 32 20 AV1

.00 49 32 33 AV3

.00 49 32 27 AV4

.00 49 32 22 AV5

.001 49 32 24 AV6

.001 50 32 28 AVM

.00 50 32 33 AV2

.00 50 32 26 AV3

.00 50 32 35 AV4

.00 50 32 28 AV5

.001 I ROW COL PER LOCN INCH11 9

ST Max

wqý-

r-1%rTV-w4w,,jý

-14" 7

SG - D Service Induced Indications Wolf Creek 1 RFO XVII.SAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11

~-------------------------------.

1 50 32 14 AV6

.001 1

33 7

FBC

-. 331 1

33 10 FBC

.301 1

33 3

FBH

-.401 1

33 3

FBH

.371 37 33 22 AV2

.001 37 33 26 AV3

.001 37 33 10 AV4

.001 47 33 14 AV2

.00 47 33 13 AV3

.001 47 33 24 AV4

.001 47 33 22 AV5

.001 47 33 24 AV6

.001 48 33 19 AV2

.001 48 33 16 AV3

.001 48 33 19 AV4

.001 48 33 11 AV5

.001 52 33 27 AV6

.001 33 34 19 AV1

.00 33 34 18 AV2

.001 33 34 18 AV3

.001 33 34 19 AV4

.001 33 34 27 AV5

.001 35 34 22 AV3

.001 48 34 12 AVI

.001 48 34 38 AV2

.001 48 34 38 AV3

.001 48 34 23 AV4

.001 48 34 32 AV5

.001 48 34 12 AV6

.001 35 35 21 AV2

.00 35 35 21 AV4

.00I I 35.

35

21.

.+

V..4 -

0


+

I ROW COL PER LOCN INCH11

+----.----+----

+..

+

10 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+ -

+

-+---------------+

+

. ROW COL PER LOCN INCH11

-+--

-+- --

+- ---

+-----+

1 37 35 27 AV4

.001 37 35 27 AV5

.001 37 35 13 AV6

.001 39 35 13 AV2

.00 45 35 23 AV2

.001 45 35 22 AV3

.001 45 35 22 AV4

.001 45 35 24 AV5

.001 53 35 17 AV2

.001 53 35 37 AV3

.001 53 35 26 AV5

.001 54 35 18 AV5

.001 41 36 11 AV2

.001 43 36 17 AV2

.001 43 36 15 AV4

.001 43 36 12 AV5

.001 47 36 14 AV4

.00 47 36 11 AV6

.001 39 37 23 AV2

.001 39 37 27 AV3

.001 39 37 27 AV4

.001 39 37 23 AV5

.00I 41 37 26 AV3

.00 41 37 20 AV4

.001 42 37 18 AV4

.001 43 37 15 AV4

.00 43 37 17 AV5

.001 49 37 18 AV2

.001 49 37 28 AV3

.001 49 37 24 AV4

.001 I ROW COL PER LOCN INCH11

+---

-+-

+--

-- +-

+

11 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11

+--------------------------

1 49 37 17 AV5

.001 49 37 17 AV6

.001 50 37 17 AV6

.001 51 37 22 AV2

.001 54 37 16 AVM

.001 54 37 11 AV5

.001 40 38 15 AV5

.001 42 38 14 AV2

.001 42 38 16 AV4

.001 42 38 15 AV5

.001 43 38 19 AV2

.001 43 38 35 AV4

.001 43 38 31 AV5

.001 46 38 20 AV3

.001 46 38 16 AV4

.001 46 38 18 AV5

.001 49 38 12 AV3

.00 49 38 22 AV4

.001 49 38 14 AV5

.001 51 38 15 AV4

.001 51 38 14 AV5

.001 44 39 17 AV2

.00 44 39 18 AV4

.001 45 39 19 AV3

.001 46 39 16 AV2

.001 46 39 23 AV4

.00 46 39 21 AV5

.001 48 39 22 AVM

.00 48 39 23 AV2

.001 1 ROW COL PER LOCN INCH11 12 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 ROW COL PER LOCN INCH11 1 48 39 23 AV3

.001 1 48 39 38 AV4

.001 1 48 39 41 AV5

.001 48 39 25 AV6

.001 49 39 16 AV2

.001 49 39 18 AV3

.001 52 39 26 AV3

.001 52 39 38 AV4

.001 52 39 26 AV5

.001 38 40 30 AV2

.001 38 40 16 AV4

.001 38 40 17 AV5

.001 41 40 19 AV3

.001 41 40 19 AV4

.001 41 40 18 AV6

.081 O

39 41 18 AVI

.001 39 41 23 AV2

.00*

39 41 31 AV3

.001 39 41 30 AV4

.001 39 41 22 AV5

.001 42 41 21 AV2

.001 42 41 31 AV3

.001 42 41 24 AV4

.001 42 41 26 AV5

.001 42 41 23 AV6

.001 51 41 25 AV1

.00 51 41 25 AV2

.001 51 41 37 AV3

.001 25 42 13 AV2

.001 25 42 14 AV5

.001 37 42 14 AV3

.001 37 42 25 AV4

.001

+

1 ROW COL PER LOCN INCH11

+ -

+

13 ST Max

SG D

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+

1 ROW COL PER LOCN INCH11

+----+--

+-----+

1 41 42 14 AV4

.001 43 42 11 AV5

.001 45 42 15 AV2

.001 47 42 21 AV4

.00 47 42 29 AV5

.001 47 42 17 AV6

.001 41 43 36 AV2

.001 41 43 35 AV3

.001

,41 43 18 AV4

.001 41 43 32 AV5

.001 43 43 28 AV2

.00 43 43 14 AV3

.001 45 43 22 AV3

.001 45 43 33 AV4

.001 45 43 29 AV5

.001 45 43 24 AV6

.001 42 44 17 AV4

,00 42 44 13 AV5

.001 43 44 21 AV2

.001 43 44 33 AV3

.001 43 44 19 AV5

.001 43 44 20 AV6

.001 33 45 15 AV4

.001 44 45 13 AV5

.001 46 45 17 AV3

.00 46 45 17 AV4

.001 46 45 16 AV6

.001 51 45 22 AV4

.001 44 46 12 AVi

.001

~----------------------------+-

I ROW COL PER LOCN INCH1I 14 ST Max

  • :i a~

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+-----------------------------

ROW COL PER LOCN INCH11

- -- +-- -------

+----.

+

+

44 46 15 AV2

.001 44 46 20 AV5

.001 45 46 18 AV2

.001 45 46 16 AV3

.008 45 46 16 AV4

.001 45 46 18 AV5

.001 45 46 19 AV6

.001 41 47 26 AV2

.001 41 47 21 AV4

.001 41 47 14 AV5

.001 41 47 24 AV6

.001 50 47 12 AV2

.001 50 47 13 AV3

.001 50 47 13 AV4

.001 50 47 19 AV5

.001 50 47 14 AV6

.001 41 48 18 AV3

.001 44 48 24 AV5

.001 44 49 19 AV2

.001 44 49 15 AV4

.001 44 49 24 AV5

.001 44 49 13 AV6

.001 45 49 10 AV4

.00I 45 49 10 AV5

.00@

49 49 17 AV2

.001 58 49 19 AV1

.001 40 50 30 AV3

.001 40 50 30 AV4

.001 40 50 30 AV5

.001 48 50 17 AVI

.001 48 50 36 AV3

.001 I ROW COL PER LOCN INCH1I

+--

15 ST Max

SG D

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14


+

  • ROW COL PER LOCN INCH11

+------

+

1 48 50 35 AV4

.001 1 48 50 36 AV5

.001 1 48 50 11 AV6

.001 51 50 15 AVM

.001 52 50 14 AV2

.001 52 50 18 AV3

.001 52 50 13 AV4

.001 52 50 16 AV5

.001 50 51 14 AV1

.001 50 51 30 AV2

.001 50 51 23 AV4

.001 50 51 19 AV5

.001 50 51 10 AV6

.001 41 52 19 AV2

.001 41 52 15 AV3

.001 41 52 19 AV4

.001

01 44 52 18 AV2

.001 52 52 26 AV2

.00 52 52 36 AV3

.00I 59 52 11 AVM

.001 59 52 11 AV5

.001 25 53 17 AV2

.001 25 53 16 AV5

.00I 30 53 10 AV2

.001 30 53 11 AV5

.00 36 53 17 AV2

.001 36 53 17 AV5

.001 37 53 15 AV4

.001 37 53 21 AV5

.001 39 53 13 AV3

.001

+

I ROW COL PER LOCN INCH11

+----+-------------...

+

16 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCHI1

+---

-+-------------------+

33 54 16 AV2

.001 35 54 17 AV3

.00 35 54 19 AV4

.00 35 54 21 AV5

.001 38 54 23 AV3

.001 38 54 29 AV4

.00 38 54 29 AV5

.001 50 54 12 AV2

.001 50 54 14 AV4

.001 50 54 18 AV6

.00 51 54 14 AV2

.001 51 54 16 AV3

.001 51 54 25 AV4

.001 51 54 17 AV5

.001 I

25 55 16 AV1

.001 25 55 16 AV2

.001 39 55 14 AV1

.001 39 55 11 AV2

.001 I

39 55 17 AV4

.001 39 55 11 AV5

.00 39 55 11 AV6

.001 41 55 16 AV2

.001 41 55 29 AV3

.001 41 55 29 AV4

.001 41 55 21 AV5

.001 41 55 16 AV6

.001 45 55 17 AV2

.001 45 55 14 AV3

.001 45 55 25 AV4

.001 45 55 10 AV5

.001 45 55 11 AV6

.001 48 55 21 AV3

.001 I

45.

55 25..

+

AV4.

+....

01 I ROW COL PER LOCN INCHiI 17 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+.-

-. --- -4. ---

+

I...

+...

+---------------+

I ROW COL PER LOCN INCH11

+

4----

4-----4-------------------+

+....

I+

+....----------

52 55 18 AV2

.001 34 56 39 AV2

.001 34 56 24 AV3

.001 34 56 10 AV4

.001 34 56 35 AV5

.001 44 56 25 AV6

.001 45 56 16 AVI

.001 45 56 37 AV2

.001 45 56 31 AV3

.001 45 56 34 AV4

.001 45 56 31 AV5

.001 45 56 18 AV6

.001 50 56 12 AV1

.00 50 56 16 AV2

.001 50 56 30 AV3

.001 I

50 56 36 AV4

.001 50 56 24 AV5

.001 50 57 16 AV2

.001 50 57 12 AV3

.001 35 58 10 AV2

.001 36 58 10 AV4

.001 41 58 13 AV2

.001 41 58 19 AV4

.00 41 58 23 AV2

.001 50 58 20 AV3

.001 50 58 20 AV4

.00f 50 58 15 AV5

.001 50 58 12 AV6

.00i 41 59 47 AV2

.00 41 59 22 AV3

.001 41 59 17 AV4

.001 I

41.. 59 17.. AV....4÷.

.0 1 ROW COL PER LOCN INCH11 18 ST Max

SG

- D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11 1 41 59 20 AV5

.001 50 59 25 AV2

.001 50 59 23 AV4

.001 50 59 17 AV5

.001 50 59 14 AV6

.001 35 60 14 AV3

.001 35 60 26 AV5

.001 40 60 15 AV4

.001 48 60 15 AV1

.I0 48 60 17 AV2

.001 48 60 42 AV3

.001 48 60 31 AV4

.001 48 60 28 AV5

.001 48 60 27 AV6

.001 33 61 17 AV2

.001 33 61 18 AV3

.001 35 61 12 AV2

.001 35 61 20 AV3

.001 44 61 13 AV2

.001 44 61 34 AV3

.001 44 61 21 AV4

.001 44 61 12 AV6

.001 44 61 29 5H

-. 531 55 62 36 AV1

.001 55 62 33 AV2

.001 55 62 18 AV3

.001 40 63 17 AV2

.001 41 63 10 AV5

.001 33 64 15 AV2

.001 33 64 14 AV3

.001 33 64 20 AV4

.001

-..-+ -...

--... -+-... -+....

+

. ROW COL PER LOCN INCH11

+

19 ST Max

SG - 0 Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11103/2009 13:36:14 ROW COL PER LOCN INCHIJ

+

33 64 14 AV5

.001 38 64 13 AV2

.00 38 64 14 AV3

.001 41 64 21 AV3

.001 41 64 19 AV5

.001 41 64 15 AV5

.331 44 64 11 AV2

.001 47 64 15 AV2

.001 15 65 27 5H

.001 40 65 10 AV2

.001 45 65 11 AV2

.001 31 66 17 AV2

.00 31 66 13 AV6

.001 33 66 12 AV2

.001 33 66 11 AV3

.001 41 66 12 AV1

.001 41 66 23 AV2

.001 41 66 25 AV3

.001 41 66 27 AV4

.001 41 66 22 AV5

.001 41 66 31 AV6

.001 4 6I 44 66 14 AV2

.001 I44 66 16 AV3

.001 I

I 44 67 18 AV2

,001 44 67 20 AV3

.001 44 67 18 AV4

.001 49 67 28 AV2

.00 49 67 51 AV3

.001 49 67 51 AV4

.001

+

.+

I ROW COL PER LOCN INCH11

+----+

-+-----

+

20 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

  • ROW COL PER LOCN INCH11

-+-----------------

+

49 67 42 AV5

.001 49 67 26 AV6

.001 34 68 16 AV2

.00 40 68 16 AV2

.001 45 68 20 AV2

.001 46 68 28 AV2

.00I 46 68 20 AV3

.00!

50 68 16 AV4

.001 31 69 10 AV1

.001 31 69 11 AV2

.001 31 69 14 AV5

.001 34 69 16 AV2

.00 34 69 14 AV3

.001 36 69 11 AV3

.001 52 69

.18 AV1

.001 30 70 12 AV1

.001 30 70 12 AV2

.001 33 70 11 AV2

.00 39 70 11 AV2

.001 44 70 18 AV1

.001 44 70 24 AV2

.001 44 70 15 AV3

.001 44 70 26 AV5

.001 44 70 25 AV6

.001 45 70 16 AV2

.001 46 70 30 AV2

.001 46 70 24 AV3

.001 I ROW COL PER LOCN INCH1I

+..

..- ÷-...

.-÷---

21 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/83/2009 13:36:14

-+-----+

. ROW COL PER LOCN INCH11

+----+----.----+--.----------

50 70 27 AV2

.001 50 70 25 AV3

.001 55 70 14 AV3

.00I 57 70 21 AV5

.001 58 70 18 AV2

.001 36 71 36 AV

.00.

36 71 28 AV2

.001 36 71 24 AV3

.001 36 71 22 AV4

.001 36 71 29 AV5

.001 36 71 15 AV6

.001 24 72 16 AV2

.001 32 72 29 AVI

.00 I 32 72 15 AV2

.001 32 72 18 AV5

.001 34 72 13 AV2

.001 36 73 17 AV2

.001 36 73 11 AV4

.00I 36 73 21 AV5

.001 58 73 13 AV2

.001 39 74 17 AV3

.001 39 74 13 AV4

.001 45 74 17 AV1

.001 45 74 15 AV2

.001 48 74 29 AV2

.001 48 74 15 AV3

.001 39 75 17 AV2

.001 39 75 18 AV3

.001

+

I ROW COL PER LOCN INCH11 22 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2e09 13:36:14

+

.I ROW CaL PER.LOCN INCH11 4.---

-4.-----+-

1 39 75 17 AV4

.00 39 75 17 AV5

.001 44 75 17 AV1

.ee 44 75 23 AV2

.00 44 75 16 AV3

.001 44 75 21 AV4

.001 44 75 16 AV5

.00 36 76 18 AV1

.001 36 76 19 AV2

.001 52 76 16 AV1 eel 52 76 16 AV2

.001 52 76 14 AV3

.00 57 76 28 AV4

.00 57 76 37 AV5

.00 44 77 23 AV3

.Ae 44 77 11 AV4

.001 39 78 29 AV3

.Il 39 78 18 AV4

.001 39 78 21 AV5

.001 41 78 20 AV2

.001 46 78 20 AV2

.00 50 78 16 AV1

.e0 50 78 20 AV2

.001 50 78 31 AV3

.001 50 78 17 AV4

.001 28 79 16 AV2

.001 28 79 15 AV5

.00 33 79 18 AV5

.001 39 79 23 AV2

.00 1 ROW COL PER LOCN INCH11

+----+----+------

+

23 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

÷ 1 ROW COL PER LOCN INCH11

+---------

1 42 79 23 AV3

.001 36 80 13 AV3

.001 36 80 16 AV4

.001 37 80 11 AV2

.001 39 80 25 AV2

.001 39 80 17 AV4

.001 50 80 16 AV2

.001 50 80 14 AV3

.001 50 80 14 AV4

.001 56 80 15 AV4

.001 37 81 13 AV2

.001 37 81 20 AV3

.001 37 81 15 AV4

.001 43 81 13 AV2

.001 43 81 27 AV3

.001 43 81 12 AV4

.001 43 81 19 AV5

.001 45 81 37 AV2

.001 45 81 51 AV3

.001 45 81 44 AV4

.001 45 81 21 AV5

.001 47 81 24 AV3

.001 49 81 23 AV2

.001 51 81 38 AV2

.00I 51 81 17 AV3

.001 51 81 23 AV4

.001 51 81 22 AV5

.001 51 81 10 AV6

.001 24 82 16 AV2

.001 24 82 15 AV6

.001

~----------------------------.9.

I ROW COL PER LOCN INCH11

+-..

24 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 1110312009 13:36:14 1 ROW COL PER LOCN INCH11 4-

+--------------------

+...

I+

+..

+

43 82 19 AV2

.001 43 82 24 AV4

.001 45 82 16 AV2

.001 45 82 38 AV3

.001 45 82 15 AV5

.001 45 82 11 AV6

.001 49 82 21 AV2

.001 39 83 31 AV3

.001 39 83 25 AV4

.001 39 83 15 AV5

.001 39 83 15 AV6

.001 40 83 25 AV3

.001 44 83 17 AV2

.00 48 83 15 AV2

.001 48 83 19 AV4

.001 20 84 22 AV6

.001 32 84 17 AV3

.00 32 84 16 AV6

.001 41 84 17 AVM

.001 41 84 25 AV3

.001 41 84 21 AV4

.001 41 84 21 AV5

.001 46 84 17 AV2

.00 46 84 35 AV3

.001 46 84 23 AV4

.001 24 85 21 AV6

.001 35 85 15 AV3

.001 35 85 18 AV4

.001 I ROW COL PER LOCN INCH11

+ - - - -. - - - -- - - - -

25 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1-1 ROW COL PER LOCN INCH11

+----+----------+--------------

1 46 85 17 AV3

.001 46 85 20 AV4

.001 49 85 24 AV2

.00 49 85 16 AV3

.001 49 85 21 AV4

.001 49 85 20 AV5

.001 50 85 28 AV4

.001 50 85 25 AV5

.001 50 85 19 AV6

.001 26 86 18 AV5

.001 40 86 23 AV3

.001 41 86 21 AV4

.001 28 87 17 AV2

.001 30 87 16 AV2

.001 36 87 18 AV1

.001 38 87 15 AV3

.001 40 87 19 AV1

.001 40 87 22 AV2

.001 40 87 22 AV3

.001 40 87 34 AV4

.001 40 87 15 AV5

.001 47 87 14 AV1

.001 50 87 20 AU

.00I 50 87 21 AV5

.001 20 88 22 AV1

.001 35 88 15 AV3

.001 38 88 17 AV2

.001

~------------------------------

I ROW COL PER LOCN INCH11

+----+--

+------..+

26 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+ --

+----+---------+----------------

1 ROW COL PER LOCN INCH11

+....+

+....---

+-

1 38 88 18 AV3

.001 43 88 15 AVM

.001 45 88 12 AV2

.00 45 88 16 AV3

.001 45 88 20 AV4

.001 45 88 32 AV5

.001 49 88 20 AV3

.001 49 88 21 AV4

.001

'50 88 21 AV2

.001 50 88 16 AV3

.001 50 88 17 AV4

.001 50 88 21 AV5

.001 53 88 12 AV2

.001 36 89 18 AV3

.001 38 89 25 AV3

.001 38 89 28 AV4

.001 38 89 23 AV5

.001 39 89 18 AV2

.001 47 89 13 MV

.001 50 89 22 AV3

.001 50 89 16 AV4

.001 50 89 17 AV5

.001 1

90 4

FBC

-. 331 1

90 8

FBC

.361 36 90 22 AV3

.001 36 90 17 AV4

.001 36 90 22 AV6

.001 39 90 20 AVM

.001 39 90 21 AV2

.001

÷.. 0 89 16 AV4.

.1 1

ROW COL PER LOCN INCH11 1... 90 8...-+

B÷ C

36I 27 ST Max

SG - 0 Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

.----------------------------- +

1 ROW COL PER LOCN INCH11 39 90 14 AV5

.001 45 90 20 AV3

.00f 53 90 24 AV4

.001 53 90 21 AV5

.001 53 90 24 AV6

.001 1

91 7

FBC

-. 361 1

91 5

FBH

.001 32 91 19 AV5

.001 36 91 18 AV2

.00 36 91 17 AV4

.001 37 91 13 AV3

.001 49 91 42 AV2

.00 49 91 15 AV3

.001 49 91 19 AV4

.001 49 91 24 AV5

.001 I

1 92 9

FBC

-. 361 19 92 16 AV6

.001 40 92 18 AV1

.00 40 92 24 AV3

.001 40 92 18 AV5

.001 43 92 13 AV2

.001 43 92 28 AV3

.001 43 92 14 AV4

.00 43 92 15 AV5

.001 45 92 15 AV3

.00 45 92 20 AV4

.001 45 92 23 AV5

.001 49 92 25 AV2

.001 49 92 13 AV3

.001 I 49.

92 13 AV3.

.1

~----------------------------+-

1 ROW COL PER LOCN INCH11


+

28 ST Max

- -!1 SG

- 0 Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11 1 49 92 23 AV4

.001 1 49 92 17 AV5

.001 1

93 9

FBC

.301 45 93 14 AV3

.001 45 93 22 AV4

.001 45 93 22 AV5

.001 45 93 16 AV6

.001 1

94 2

FBC

.251 39 94 15 AV3

.001 41 94 32 AV2

.00 41 94 29 AV3

.001 41 94 24 AV4

.001 41 94 21 AV5

.001 41 94 11 AV6

.001 43 94 29 AV2

.001 43 94 16 AV3

.001 43 94 18 AV4

.001 43 94 23 AV5

.001 44 94 16 AV3

.00 44 94 17 AV4

.001 35 95 10 AV1

.001 35 95 13 AV5

.001 38 95 26 AV2

.00@

40 95 18 AV5

.001 40 95 25 AV6

.001 41 95 20 AV2

.00 41 95 15 AV4

.001 41 95 23 AV5

.001 44 95 19 AV2

.001 44 95 27 AV3

.001

+

1 ROW COL PER LOCN INCH11

-+

29 ST Max

  • -*r,-

~ * -.1z

  • =

SG D

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

-+

1 ROW COL PER LOCN INCH11

+- ----------------

+ -----

+

I45 95 11 AV

.00 1 45 95 17 AV2

.001 45 95 17 AV3

.001 45 95 27 AV4

.001 45 95 33 AV5

.001 45 95 21 AV6

.001 45 95 18 AV2

.00 41 96 18 AV2

.001 41 96 33 AV3

.001 41 96 15 AV5

.001 I44 96 22 AV2

.001 44 96 31 AV3

.001 44 96 17 AV4

.001 44 96 18 AV6

.001 45 96 18 AV2

.00 45 96 28 AV5

.001 27 97 17 TSH

-. 721 38 97 18 AV4

.00 38 97 16 AV5

.001 40 97 18 AV3

.001 40 97 20 AV4

.001 41 97 22 AV3

.001 41 97 33 AV4

.001 46 97 25 AV3

.001 40 98 26 AV2

.001 40 98 27 AV3

.001 40 98 21 AV4

.001 40 98 18 AV6

.001 38 99 20 AV2

.00 38 99 19 AV3

.001 41 99 18 AV2

.001

~----------------------------+-

I ROW COL PER LOCN INCH11

+- ----

+- -----------

+

30 ST Max

SG

- D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

. ROW COL PER LOCN INCHI1

+

1 41 99 16 AV3

.001 41 99 12 AV4

.001 41 99 15 AV6

.001 43 99 12 AV5

.001 34 100 13 AV3

.001 38 100 20 AV2

.001 38 100 19 AV3

.001 38 100 15 AV4

.001 38 100 21 AV5

.001 40 100 21 AV2

.001 40 100 17 AV6

.001 41 100 29 AV2

.00 41 100 25 AV3

.001 41 100 25 AV4

.001 41 100 19 AV5

.001 42 100 19 AV3

.001 42 100 30 AV4

.001 36 101 17 AV2

.001 38 101 29 AV3

.00 38 101 24 AV4

.001 38 101 16 AV5

.001 38 102 14 AV3

.001 40 102 20 AV2

.00 40 102 36 AV3

.001 40 102 35 AV4

.001 26 103 15 AV5

.001 34 103 11 AV3

.001 34 103 10 AV4

.001 34 103 17 AV6

.001 I

+....

---....--- +

I ROW COL PER LOCN INCH11

+

31 ST Max

SG D

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

+~ -~....

-- 4.-. -..

1 ROW COL PER LOCN INCH11 1 36 103 12 AV3

.001 36 103 17 AV4

.001 38 103 11 AV2

.00 38 103 18 AV3

.001 38 103 34 AV4

.001 38 103 25 AV5

.001 40 103 20 AV2

.001 40 103 30 AV3

.00 40 103 27 AV4

.001 40 103 14 AV5

.001 40 103 17 AV6

.001 43 103 13 AV4

.001 32 104 18 AV5

.001 34 104 17 AV3

.001 34 104 15 AV4-

.001 I 35 104 15 AV4

.001 35 104 16 AV5

.001 38 104 20 AV3

.001 40 104 39 AV2

.001 40 104 29 AV3

.001 40 104 17 AV4

.001 40 104 24 AV5

.001 40 104 17 AV6

.001 30 105 13 AV2

.001 33 105 11 AV3

.001 33 105 14 AV5

.001 35 105 13 AV6

.001 38 105 33 AV3

.001 38 105 22 AV4

.001 38 105 10 AV6

.001 l

ROW COL PER LOCN INCH1I

+----

+

+

32 ST Max

SG - D Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14 1 ROW COL PER LOCN INCH11

+

34 106 15 AV4

.001 34 106 17 AV6

.001 34 106 17 AV6

.001 35 106 21 AV2

.001 35 106 19 AV3

.001 35 106 15 AV4

.001 35 106 17 AV6

.001 36 106 16 AV4

.00 36 106 15 AV5

.001 40 106 13 AV4

.001 35 107 23 AV3

.001 35 107 19 AV4

.00 35 107 16 AV5

.001 35 107 13 AV6

.00 36 107 19 AV4

.001 36 107 18 AV5

.001 35 108 29 AV4

.001 35 108 15 AV5

.00 35 108 17 AV6

.001 37 108 14 AV6

.001 38 108 16 AV6

.001 28 109 13 AV5

.001 32 109 13 AV5

.001 32 109 14 AV6

.001 33 109 16 AV3

.001 33 109 16 AV4

.001 33 109 22 AV5

.001 34 109 14 AV2

.001 34 109 10 AV4

.001

+

I ROW COL PER LOCN INCH11

-+------

33 ST Max

SG D

Service Induced Indications Wolf Creek 1 RFO XVIISAP 20091001 11/03/2009 13:36:14

  • ROW COL PER LOCN INCH11

- 34.. 109 12..

34 109 12 AV5

.001 34 109 14 AV6

.00 36 109 12 AV6

.001 29 110 14 AV5

.001 32 110 14 AV5

.001 35 110 16 AV3

.00 35 110 30 AV4

.001 35 110 19 AV6

.001 29 111 14 AV2

.00 30 111 14 AV2

.001 30 111 16 AV6

.001 32 111 14 AV6

.001 27 113 18 AV2

.001 30 113 21 AV5

.001 24 115 20 AVI

.001 26 115 13 AV1

.001 27 115 11 AV1

.001 27 115 16 AV6

.001 22 116 18 AV6

.001 21 118 10 AVi

.001

~-----------------------------+

I ROW COL PER LOCN INCH11

+----.----+-----

Tubes: 416 Records: 1005 34 ST Max