Re: Secondary system water usage
Dear Duke:
Current city water use, averaged over a year, is measured at about 37,000 gallons per day, rather than 51,000 gallons/day. The usage includes about 7000 gallons/day of measured blowdown, and about 30,000 gallons/day evaporation.
The blowdown number (7000) is lower than the one that you quoted (13,000) from the SAR written in 1999. The new cooling towers and their cleanup system produced a reduction in the daily blowdown.
On the other hand, the daily evaporation is about the same. The 38,000 gal./day that you quoted from our 2004 correspondence is a maximum. The 30,000 here is averaged over the year.
Many thanks, Edward Lau Superintendent, MIT Research Reactor 617-253-4211 E-mail Properties Mail Envelope Properties (201004132134.o3DLYR3L024582)
Subject:
Re: Secondary system water usage Sent Date:
4/15/2010 4:02:53 PM Received Date:
4/13/2010 10:16:13 PM From:
Edward Lau Created By:
eslau@MIT.EDU Recipients:
William.Kennedy@nrc.gov (Kennedy, William)
Tracking Status: None eslau@MIT.EDU (eslau@MIT.EDU)
Tracking Status: None pdsame@MIT.EDU (pdsame@MIT.EDU)
Tracking Status: None allanon@MIT.EDU (allanon@MIT.EDU)
Tracking Status: None bernardj@MIT.EDU (bernardj@MIT.EDU)
Tracking Status: None wbm@MIT.EDU (wbm@MIT.EDU)
Tracking Status: None Post Office:
biohazard-cafe.mit.edu
Files Size Date & Time MESSAGE 2698 4/15/2010 Options Expiration Date:
Priority:
olImportanceNormal ReplyRequested:
False Return Notification:
False Sensitivity:
olNormal Recipients received: