ES-401 Written Examination Review Worksheet Form ES-401-9

3. Psychometric Flaws
4. Job Content Flaws
5. Other Q#
1.

LOK (F/H)

2.

LOD (1-5)

Stem Focus Cues T/F Cred.

Dist.

Partial Job-Link Minutia

  1. /

units Back-ward Q=

K/A SRO Only

6.

B/M/N

7.

U/E/S

8.

Explanation 1

F 2

Y N

S 2

H 3

Y M

S Will EDG load a bus after an OC condition? Load shedding occur?

RE: Yes, bus is deenergized and picked up by EDG.

3 H

3 Y

M S

4 F

1 X

N N

U OP Bkrs open after 30 seconds? Closed not a creditable distractor with question as is? K/A is ability question not a knowledge question. Question too easy. RE: Changed second bullet to when breaker opens..

5 H

2 N

S 6

H 3

Y N

S 7

H 2

Y N

S 8

H@

2 Y

B S

9 H

2 Y

B S

10 F

2 Y

M S

11 H

3 Y

M S

Licensee provided TS Bases as reference to RO question, RE:

Licensee has included same information in lesson plans for ROs.

TS Bases provided to NRC review for information only. Ref to TS basis (and TS basis) removed.

12 F@

2 Y

N S

13 F

2 Y

B S

14 F

3 Y

B S

15 F

3 Y

B S

K/A asks for effect to NPSH not vortexing! RE: Same symptoms but different causes. RE: Keep question as is!

16 H@

3 Y

B S

17 F

3 Y

B S

18 F

3 Y

N S

1

ES-401 Written Examination Review Worksheet Form ES-401-9

3. Psychometric Flaws
4. Job Content Flaws
5. Other Q#
1.

LOK (F/H)

2.

LOD (1-5)

Stem Focus Cues T/F Cred.

Dist.

Partial Job-Link Minutia

  1. /

units Back-ward Q=

K/A SRO Only

6.

B/M/N

7.

U/E/S

8.

Explanation 19 H

2 Y

B S

20 H@

2 N

M S

K/A requires using EOPS in conjunction with AOPs. AOPs not included in stem or distractors. RE: Actions in distractors are from AOPs. Will keep question as is.

21 H

3 Y

N S

Is this information that would be know by an RO. RE: Yes 22 H@

2 Y

N S

23 F

3 Y

N S

24 H

2 Y

B S

25 H@

3 Y

M S

26 F

2 Y

N S

27 F

3 Y

B S

28 H

3 Y

B S

29 H@

2 X

Y M

E Per the explanation, distractor C is correct, not distractor A as indicated. Why is B not correct? RE: Information provided to support correct answer is in error. Will change justification for correct answer. Since Q & A were correct, changed this from U to E

30 H

3 Y

N S

31 H

2 Y

B S

32 H@

2 Y

B S

33 F

2 Y

M S

Why is A incorrect. Chief believed that rods would indicate 00 post-scram? RE: If ind. Rod scram sw. held in position, rod would indicate on full core display, not 00 34 H

2 Y

M S

35 F

2 Y

M S

36 H@

2 Y

B S

37 H

3 Y

M S

2

ES-401 Written Examination Review Worksheet Form ES-401-9

3. Psychometric Flaws
4. Job Content Flaws
5. Other Q#
1.

LOK (F/H)

2.

LOD (1-5)

Stem Focus Cues T/F Cred.

Dist.

Partial Job-Link Minutia

  1. /

units Back-ward Q=

K/A SRO Only

6.

B/M/N

7.

U/E/S

8.

Explanation 38 F

2 Y

B S

39 F

2 Y

B S

40 H

2 Y

B S

41 F@

3 Y

B S

42 H

2 Y

M S

43 H

2 Y

N S

44 F

2 Y

N S

45 F@

3 Y

B S

46 H

3 Y

M S

47 H

3 Y

N S

48 F@

2 Y

B E

Remove is after DG. RE: Comment incorporated.

49 H

3 Y

M S

50 F

2 Y

M S

Need procedural guidance for 11 oclock position. RE: provided in QCOP 6600-02, step F.2.j!

51 F

2 Y

M S

52 F

2 Y

M S

Is 1B SWP normally selected for standby? RE: Yes, its the only SWP with an auto start feature.

53 F@

2 Y

B S

54 F@

2 Y

B S

55 H

4 Y

B S

What value, Blocks to Full on RWM? K/A ask effect of loss of malfunction of RWM. RE: Malfunction is in DFWLC which inputs to RWM. Blocks to Full disabled = doesnt enforce rod blocks above 10% pwr.

56 H@

2 Y

B S

57 H@

2 Y

B S

3

ES-401 Written Examination Review Worksheet Form ES-401-9

3. Psychometric Flaws
4. Job Content Flaws
5. Other Q#
1.

LOK (F/H)

2.

LOD (1-5)

Stem Focus Cues T/F Cred.

Dist.

Partial Job-Link Minutia

  1. /

units Back-ward Q=

K/A SRO Only

6.

B/M/N

7.

U/E/S

8.

Explanation 58 F

2 Y

B S

59 F

2 Y

B S

60 H@

2 Y

N S

61 H

2 Y

N S

62 H

2 Y

M S

63 F@

3 Y

B S

64 H

2 Y

N S

65 F

2 Y

B S

66 F

2 Y

M S

67 F@

2 Y

B S

68 H

2 Y

M S

69 F

3 Y

B S

70 F

2 Y

M S

71 F@

2 Y

N S

72 F

2 Y

N S

73 F

2 Y

B S

74 H

3 Y

M S

75 F@

2 Y

B E

Switch B and A distractors so that they are in order from least significant to most significant! RE: Comment incorporated.

1 H

3 Y

Y N

S Per QCOA 0202-04, D.2 actions to insert CRAM rods appears to be correct action! Why is distractor A incorrect? RE: Insert ALL CRAM rods is in correct! Only insert enough to get out of Region II.

4

ES-401 Written Examination Review Worksheet Form ES-401-9

3. Psychometric Flaws
4. Job Content Flaws
5. Other Q#
1.

LOK (F/H)

2.

LOD (1-5)

Stem Focus Cues T/F Cred.

Dist.

Partial Job-Link Minutia

  1. /

units Back-ward Q=

K/A SRO Only

6.

B/M/N

7.

U/E/S

8.

Explanation 2

H 3

Y Y

N S

3 M

4 Y

Y N

S 4

H 2

Y Y

N S

5 H@

2 Y

Y N

S 6

H 2

Y Y

N S

7 H

3 Y

Y N

S 8

H 2

Y Y

M S

9 H@

2 Y

Y N

S 10 H

3 Y

Y N

S K/A asks for H concentrations and H monitoring availability. RE:

Providing H concentration provides no additional information to question. Stem already has SRO in QGA 200-5, Hydrogen Control.

11 H

3 Y

Y N

S 12 F@

3 Y

Y N

S If RCIC flow controller placed in Manual at 400 gpm, would that still render RCIC inoperable? D distractor, would RCIC eventually need to be declared inoperable for this condition? RE: Yes, RCIC is still inoperable. Yes, RCIC eventually would be declared inop.

Stem asks for IMMEDIATE actions!

13 H

3 N

Y N

S K/A A2 requires predicting impact and procedure to correct. TS is used as procedure but no predicting of impact in answer. RE: In order to deduce the correct TS, applicant would need to know what impact was.

14 H

3 N

Y N

U K/A A2 requires predicting impact AND procedure to correct control or mitigate. Missing procedure reference. RE: Procedure references were pulled out to make the question look neater.

Reference procedures put back in distractors.

15 H@

3 Y

Y N

S 16 H

2 Y

Y N

S 17 H

2 Y

Y M

S 18 H@

2 Y

Y N

S 5

ES-401 Written Examination Review Worksheet Form ES-401-9

3. Psychometric Flaws
4. Job Content Flaws
5. Other Q#
1.

LOK (F/H)

2.

LOD (1-5)

Stem Focus Cues T/F Cred.

Dist.

Partial Job-Link Minutia

  1. /

units Back-ward Q=

K/A SRO Only

6.

B/M/N

7.

U/E/S

8.

Explanation 19 H

2 Y

Y M

S 20 F

3 Y

Y B

S 21 F@

2 Y

Y B

E Remove temporary from stem since answer contains temporary.

RE: Will replace with portable.

22 F

2 Y

Y M

S 23 F

2 Y

Y B

S 24 F

2 Y

Y N

S 25 H@

3 X

Y Y

B U

Last bullet in stem states,.. ready to provide SAMG decision making. Correct distractor includes entering into SAMGs. Clue in stem (SAMG) needs to be deleted. RE: moved bullet from stem to distractor A.

Instructions

[Refer to Section D of ES-401 and Appendix B for additional information regarding each of the following concepts.]

1.

Enter the level of knowledge (LOK) of each question as either (F)undamental or (H)igher cognitive level.

2.

Enter the level of difficulty (LOD) of each question using a 1 - 5 (easy - difficult) rating scale (questions in the 2 - 4 range are acceptable).

3.

Check the appropriate box if a psychometric flaw is identified:

The stem lacks sufficient focus to elicit the correct answer (e.g., unclear intent, more information is needed, or too much needless information).

The stem or distractors contain cues (i.e., clues, specific determiners, phrasing, length, etc).

The answer choices are a collection of unrelated true/false statements.

The distractors are not credible; single implausible distractors should be repaired, more than one is unacceptable.

One or more distractors is (are) partially correct (e.g., if the applicant can make unstated assumptions that are not contradicted by stem).

4.

Check the appropriate box if a job content error is identified:

The question is not linked to the job requirements (i.e., the question has a valid K/A but, as written, is not operational in content).

The question requires the recall of knowledge that is too specific for the closed reference test mode (i.e., it is not required to be known from memory).

The question contains data with an unrealistic level of accuracy or inconsistent units (e.g., panel meter in percent with question in gallons).

The question requires reverse logic or application compared to the job requirements.

5.

Check questions that are sampled for conformance with the approved K/A and those that are designated SRO-only (K/A and license level mismatches are unacceptable).

6.

Enter question source: (B)ank, (M)odified, or (N)ew. Check that (M)odified questions meet criteria of ES-401 Section D.2.f.

7.

Based on the reviewers judgment, is the question as written (U)nsatisfactory (requiring repair or replacement), in need of (E)ditorial enhancement, or (S)atisfactory?

8.

At a minimum, explain any U ratings (e.g., how the Appendix B psychometric attributes are not being met).

6

ES-401 Written Examination Review Worksheet Form ES-401-9 7

@ - Denotes 30 initial review questions that verified references, K/A conformance, level of difficulty and level of knowledge.