Text
From:
Poole, Justin Sent:
Monday, November 02, 2009 10:39 AM To:
'Hale, Steve'; COSTEDIO, JAMES
Subject:
Point Beach Nuclear Plant, Units 1 and 2 - Request for Additional Information from Instrumentation and Control Branch RE: Nonconservative Technical Specifications
- Steve, By letter to the U.S. Nuclear Regulatory Commission (NRC) dated April 7, 2009, (Agencywide Documents Access and Management System (ADAMS) Accession No. ML091250564), FPL Energy Point Beach, LLC, submitted a request to change technical specifications due to correcting non-conservative setpoints. This was originally part of the extended power uprate request but was separated out by the NRC staff.
The NRC staff is reviewing your submittal and has determined that additional information is required to complete the review. The specific information requested is addressed below.
During a discussion with your staff on October 28, 2009, it was agreed that you would provide the additional information within 30 days of the date of this letter.
The NRC staff considers that timely responses to requests for additional information help ensure sufficient time is available for staff review and contribute toward the NRC=s goal of efficient and effective use of staff resources. If circumstances result in the need to revise the requested response date, please contact me at (301) 415-2048.
Sincerely, Justin C. Poole Project Manager NRR/DORL/LPL3-1 U.S. Nuclear Regulatory Commission (301)415-2048 email: Justin.Poole@nrc.gov
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
- 1. On Tables 3.3.1-1, RPS Instrumentation, and 3.3.2-1, ESFAS Instrumentation, the Allowable Value column was changed to Limiting Safety System Setting. However, some values on that column remained the same. Please provide justification for these values staying the same.
- 2. Please provide the data source for the parameters, including the As-Found and As-Left values, used in the LSSS calculations.
- 3. Please provide the representative calculations used to obtain the LSSS values.