ML092430391

From kanterella
Jump to navigation Jump to search
EN-09-044, Northern States Power Company
ML092430391
Person / Time
Site: Prairie Island 
Issue date: 08/31/2009
From: Gerald Gulla
NRC/OE
To:
Gulla G. 415-2872
References
EA-09-167 EN-09-044
Download: ML092430391 (2)


Text

PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION August 31, 2009 EN-09-044 OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION Licensee:

Northern States Power Company - Minnesota (EA-09-167)

Prairie Island Nuclear Generating Plant, Unit 2 Docket No. 05000306

Subject:

ISSUANCE OF FINAL SIGNIFICANCE DETERMINATION This is to inform the Commission that a White Significance Determination Process (SDP) finding will be issued on or about September 3, 2009, to Northern States Power Company - Minnesota as a result of inspections at the Prairie Island Nuclear Generating Plant, Unit 2. This White finding, an issue with low to moderate safety significance, which may require additional NRC inspections, involved the licensees failure to design the component cooling water system such that it would be protected from the impact of a high energy line break, seismic event, or tornado event.

On August 10, 2009, Northern States Power Company - Minnesota indicated they did not contest the characterization of the risk significance of this finding and they declined the opportunity to discuss this issue in a Regulatory Conference or to provide a written response.

Corrective actions are currently in place.

A Notice of Violation is included based on a violation of 10 CFR 50, Appendix B, Criterion III, Design Control, which requires, in part, that measures be established to assure that the design basis for safety-related functions of structures, systems, and components are correctly translated into specifications, drawings, procedures, and instructions. Further, Criterion III requires that the design control measures provide for verifying or checking the adequacy of designs.

Contrary to this requirement, the licensee failed to implement design control measures to ensure that the design basis for the component cooling water system was correctly translated into specifications, drawings, procedures, and instructions. Specifically, the licensee failed to ensure that the safety-related function of the component cooling water system was maintained following a high energy line break, seismic event, or tornado event in the turbine building.

It should be noted that the licensee has not been specifically informed of the enforcement action.

The schedule of issuance and notification is:

Mailing of Final Significance Determination September 3, 2009 Telephone Notification of Licensee September 3, 2009 The State of Minnesota will be notified.

Contacts: Gerry Gulla, OE, (301) 415-2872 Greg Bowman, OE, (301) 415-2939

PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION Distribution: EN-09-044, August 31, 2009 OWFN Chairman Jaczko Comm. Klein Comm. Svinicki SECY OCA OPA OIP OWFN EDO DEDR DEDMRT OE OGC NRR OI NSIR TWFN OCFO OP CENTER NMSS OIG OIS RES ACRS FSME Regional Offices RI RII RIII RIV MAIL PUBLIC OE staff Electronic DISTRIBUTION:

C. Carpenter, OE N. Hilton, OE G. Bowman, OE G. Gulla, OE OE r/f EN binder Publicly Available X Non-Sensitive X ML092430391 OFFICE OE:ES OE:BC NAME G. Gulla G. Bowman DATE 08/31/09 08/31/09 OFFICIAL RECORD COPY