1 IPRenewal NPEmails From:
Kimberly Green Sent:
Wednesday, May 13, 2009 1:09 PM To:
STROUD, MICHAEL D; Tyner, Donna Cc:
IPRenewal NPEmails; James Davis; David Wrona
Subject:
Draft RAI 3.4.2-2 related to the IP2 AFW pump room fire event open item Attachments:
DRAI for AFW pump room.doc Mike and Donna, Attached is the draft RAI related to the IP2 AFW pump room fire event open item. Please review and let me know if a telephone call is needed. The purpose of the call would be to clarify the staff's request.
- Thanks, KimberlyGreen SafetyPM (301)4151627 kimberly.green@nrc.gov
Hearing Identifier:
IndianPointUnits2and3NonPublic_EX Email Number:
1193 Mail Envelope Properties (83F82891AF9D774FBBB39974B6CB134F92A80D4E17)
Subject:
Draft RAI 3.4.2-2 related to the IP2 AFW pump room fire event open item Sent Date:
5/13/2009 1:08:41 PM Received Date:
5/13/2009 1:08:43 PM From:
Kimberly Green Created By:
Kimberly.Green@nrc.gov Recipients:
"IPRenewal NPEmails" <IPRenewal.NPEmails@nrc.gov>
Tracking Status: None "James Davis" <James.Davis@nrc.gov>
Tracking Status: None "David Wrona" <David.Wrona@nrc.gov>
Tracking Status: None "STROUD, MICHAEL D" <MSTROUD@entergy.com>
Tracking Status: None "Tyner, Donna" <dtyner@entergy.com>
Tracking Status: None Post Office:
HQCLSTR01.nrc.gov Files Size Date & Time MESSAGE 369 5/13/2009 1:08:43 PM DRAI for AFW pump room.doc 29178 Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received:
D-RAI 3.4.2-2:
By letter dated January 27, 2009, Entergy responded to RAI 3.4.2-1, and provided clarifying details regarding the passive, long-lived component types, materials, environments, aging effects and aging management programs for systems, structures and components that support the auxiliary feedwater (AFW) pump room fire event at Indian Point Nuclear Generating Unit No. 2 (IP2) that were not already within the scope of license renewal for 10 CFR 54.4(a)(1) or (a)(2).
The staff reviewed the response and determined that the systems contain passive, long-lived components made of materials that when exposed to the stated environments may experience aging effects as described in the GALL Report, which must be managed during the period of extended operation in accordance with 10 CFR 54.21(a)(3).
By letter dated May 1, 2009, Entergy submitted a revised commitment list which included a new commitment (Commitment 39) to install a fixed automatic fire suppression system for IP2 in the AFW pump room which would make the suppression configuration of the room similar to that of the AFW pump room at Unit 3.
Because the planned installation is not yet part of the current licensing basis, the staff cannot make a finding consistent with the requirement in 10 CFR 54.29(a). Therefore, the staff requests that the applicant provide information to demonstrate that the effects of aging will be adequately managed so that the intended function(s) will maintained consistent with the CLB for the period of extended operation as required by 10 CFR 54.21(a)(3). Specifically, the staff requests that the applicant list all aging effects and the AMPs needed to manage the aging effects for the component types provided in the January 27, 2009 letter.