1CAN030907 March 30, 2009 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

SUBJECT:

Steam Generator Tube Inspection Report - 1R21 Arkansas Nuclear One, Unit 1 Docket No. 50-313 License No. DPR-51

Dear Sir or Madam:

Entergy Operations, Inc. (Entergy) inspected the Arkansas Nuclear One, Unit 1 (ANO-1) steam generator (SG) tubes during the Fall 2008 refueling outage (1R21) in accordance with ANO-1 Technical Specification (TS) 5.5.9, Steam Generator Program. ANO-1 TS 5.6.7, Steam Generator Tube Inspection Reports, requires the results of the in-service inspection be submitted to the NRC within 180 days after the initial entry into MODE 4. Attached is the subject inspection report. This completes the reporting requirements of the ANO-1 TS for this inspection.

This submittal does not include any new commitments.

If you have any questions or require additional information, please contact me.

Sincerely, DBB/rwc Attachments:

1.

ANO-1 Steam Generator Inspection Report - 1R21

2.

SG A Wear Indications - 1R21

3.

SG B Wear Indications - 1R21 Entergy Operations, Inc.

1448 S.R. 333 Russellville, AR 72802 Tel 479-858-4710 David B. Bice Acting Manager, Licensing Arkansas Nuclear One

1CAN030907 Page 2 of 2 cc:

Mr. Elmo E. Collins Regional Administrator U. S. Nuclear Regulatory Commission Region IV 612 E. Lamar Blvd., Suite 400 Arlington, TX 76011-4125 NRC Senior Resident Inspector Arkansas Nuclear One P. O. Box 310 London, AR 72847 U. S. Nuclear Regulatory Commission Attn: Mr. Alan B. Wang MS O-7 D1 Washington, DC 20555-0001 Mr. Bernard R. Bevill Arkansas Department of Health Radiation Control Section 4815 West Markham Street Slot #30 Little Rock, AR 72205

to 1CAN030907 ANO-1 Steam Generator Inspection Report 1R21 to 1CAN030907 Page 1 of 9 ARKANSAS NUCLEAR ONE, UNIT 1 STEAM GENERATOR INSPECTION REPORT - 1R21 1

INTRODUCTION Arkansas Nuclear One, Unit 1 (ANO-1) Technical Specification (TS) 5.6.7, Steam Generator Tube Inspection Reports, requires Entergy Operations, Inc. (Entergy) to submit a 180-day report to the NRC that outlines the details of the steam generator (SG) tubing inspections that were performed during the reporting period. The report shall include:

1. The scope of inspections performed on each SG.
2. Active degradation mechanisms found.
3. Nondestructive examination techniques utilized for each degradation mechanism.
4. Location, orientation (if linear), and measured sizes (if available) of service induced indications.
5. Number of tubes plugged during the inspection outage for each active degradation mechanism.
6. Total number and percentage of tubes plugged to date.
7. The results of condition monitoring, including the results of tube pulls and in-situ testing.

The operating period for this report includes one outage, a refueling inspection (1R21), in December 2008 which was the second in-service inspection (ISI) following the SG replacement outage. This report details the result of that inspection.

2 DESIGN The replacement steam generators for ANO-1 are Enhanced Once-Through Steam Generators (EOTSG) manufactured by AREVA. The EOTSG is a straight shell and tube type heat exchanger installed in a vertical position with bottom supports and such emergency supports as required to accommodate normal and accident loads. The tubing consists of Inconel 690 thermally treated tubing that is 5/8" in diameter with a 0.037" wall thickness. The tubes are expanded full-depth hydraulically in the tubesheet. There are 15 tube supports that are constructed of stainless steel (SA 240 type 410) and are a broached trefoil-hole design.

to 1CAN030907 Page 2 of 9 3

REPORT REQUIREMENTS 3.1 The scope of inspections performed on each SG.

Table 3.1 lists the inspection scope of 1R21.

Table 3.1 1R21 Inspection Scope SG A Examination Inspections Extent Type Conducted Scope Tested Bobbin Initial 15595 100 TEC to TEH X-Probe/Plus Point 901 N/A N/A SG B Bobbin Initial 15596 100 TEC to TEH X-Probe/Plus Point 1035 N/A N/A TEC Tube End Cold TEH Tube End Hot to 1CAN030907 Page 3 of 9 3.2 Active degradation mechanisms found.

This was the second ISI following replacement of the SGs. The only mechanisms identified were mechanical wear at tube support plates, volumetric and fabrication induced indications. These are listed in Table 3.2.

Table 3.2 Indication List for 1R21 SG A SG B Mechanism Tubes Indications Tubes Indications Wear (TWD) 913 990 823 1029 Potential Loose Part (PLP) 0 0

5 5

Manufacturing Buff Mark (MBM) 4 4

2 2

Dent (DNT 1.0 Volt) 10 11 11 12 Tube-to-Tube Proximity (PTU) 25 0

0 Tube-to-Tie-Rod Proximity (PTR) 14 0

0 Tube-to-Tube and Tie-Rod (PTB) 12 0

0 to 1CAN030907 Page 4 of 9 3.3 Nondestructive examination techniques utilized for each degradation mechanism.

Mechanism Location Probe Detection ETSS POD

@ 90% CL Sizing ETSS NDE Technique Uncertainty

(%TW)

TSP Wear Bobbin 96043.1 Rev.1 0.866@23-100%TW 96043.1 Rev. 1 1.85%

MBM's Bobbin 96010.1 Rev. 7 0.886@0-4%TW 0.848@5-11%TW N/A N/A PLP Wear (Circ Groove)

+Point 27901.1 Rev. 0 0.931@31-100%TW 27901.1 Rev. 0 2.30%

PLP Wear (Axial Groove)

+Point 27902.1 Rev. 0 0.00@0-7%TW 0.952@8-100%TW 27902.1 Rev. 0 2.32%

PLP Wear (Tapered Football Shape)

+Point 27903.1 Rev. 0 0.069@0-20%TW 0.944@21-100%TW 27903.1 Rev. 0 2.11%

PLP Wear (Tapered Round Hole)

+Point 27904.1 Rev. 0 0.931@32-100%TW 27904.1 Rev. 0 1.99%

PLP Wear (Flat)

+Point 27905.1 Rev. 0 0.953@7-100%TW 27905.1 Rev. 0 2.05%

PLP Wear (Tapered)

+Point 27906.1 Rev. 0 0.00@0-10%TW 0.951@11-100%TW 27906.1 Rev. 0 1.43%

PLP Wear (45 Degree Tapered)

+Point 27907.1 Rev. 0 0.00@0-12%TW 0.952@13-100%TW 27907.1 Rev. 0 2.59%

TSP Wear

+Point 96910.1 Rev. 10 0.75@0-39%TW 0.924@40-100%TW 96910.1 Rev. 10 6.68%

ODSCC (expansion transitions)

X-Probe 20400.1 Rev. 5 0.811@42-100%TW N/A N/A ODSCC (support structures)

X-Probe 20402.1 Rev. 5 0.00@0-59%TW 0.825@60-100%TW N/A N/A to 1CAN030907 Page 5 of 9 Mechanism Location Probe Detection ETSS POD

@ 90% CL Sizing ETSS NDE Technique Uncertainty

(%TW)

ODSCC (freespan)

X-Probe 20403.1 Rev. 5 0.00@0-44%TW 0.858@45-100%TW N/A N/A PWSCC-circ (expansion transitions)

X-Probe 20500.1 Rev. 4 0.811@66-100%TW N/A N/A PWSCC-axial (expansion transition)

X-Probe 20501.1 Rev. 4 0.026@0-39%TW 0.873@40-100%TW N/A N/A PWSCC-axial

(<2 volt dent)

X-Probe 20502.1 Rev. 4 0.858@56-100%TW N/A N/A ETSS Examination Technical Specification Sheet POD Probability of Detection TW Through Wall 3.4 Location, orientation (if linear), and measured sizes (if available) of service induced indications.

The only service-induced mechanism is wear at the tube support plates. Due to the large number of indications, these are listed in Attachments 2 and 3 of this submittal for SG A and SG B, respectively.

to 1CAN030907 Page 6 of 9 3.5 Number of tubes plugged during the inspection outage for each active degradation mechanism.

There were eight tubes in SG A and five tubes in SG B plugged during the outage.

This is listed in Table 3.5 below. There were two tubes preventatively plugged during fabrication in SG A due to failed expander tooling and one tube in SG B during 1R20. This is listed in Table 3.6 Table 3.5 Tubes Plugged During 1R21 Row Tube Indication SG A 10 11 WAR 12 10 WAR 141 55 WAR 143 51 WAR 64 8

Preventative for Tie-Rod Bowing 65 8

Preventative for Tie-Rod Bowing 87 8

Preventative for Tie-Rod Bowing 88 8

Preventative for Tie-Rod Bowing SG B 1

6 WAR 4

11 WAR 10 14 WAR 17 83 WAR 67 1

WAR WAR Wear to 1CAN030907 Page 7 of 9 3.6 Total number and percentage of tubes plugged to date.

There are no sleeves installed in either generator. The plugging information is listed in Table 3.6.

Table 3.6 Cumulative Plugs in Service SG A Year Outage Installed Cumulative

% Plugged 2005 Fabrication 2

2

< 0.1 2005 Baseline 0

2

< 0.1 2007 1R20 0

2

< 0.1 2008 1R21 8

10

< 0.1 SG B Year Outage Installed Cumulative

% Plugged 2005 Fabrication 0

0 0

2005 Baseline 0

0 0

2007 1R20 1

1

< 0.1 2008 1R21 5

6

< 0.1 Note - 15597 total tubes so 0.1% = 15 tubes to 1CAN030907 Page 8 of 9 3.7 The results of condition monitoring, including the results of tube pulls and in-situ testing.

All condition monitoring requirements were met. There were no indications that exceeded performance criteria or in-situ screening limits. There were no tube pulls required.

An item of note was the fact that proximity indications were once again identified in SG A. Proximity is an indicator of tube bowing. The bowing resulted from stay rod bowing due to a compressive load applied during cool down from locking of the tube support plates in the upper shroud. This was originally presented to NRR in a presentation on August 29, 2007. It was agreed that another inspection would be performed in the next refueling outage (1R21) to validate the root cause. The amount of bowing did increase slightly from 1R20 to 1R21 but was in the expected range.

Tie-rod bowing was detected in 9 (of 52 total) tie-rod locations during 1R20. The bowing was limited to the two outermost tie-rod rings, the Z-side of the steam generator in SG A. In the Outermost Ring, bowing was seen in the 1st, 14th, and 15th spans. In the Second Outermost Ring (the next ring of tie-rods in), bowing was only seen in the 1st span. During 1R21, tie-rod bowing was again detected in the original 9 tie-rod locations plus one additional location at row 47. Again, the bowing was limited to the Z-side of the steam generator and only SG A. In the Outermost Ring, repeat bowing was seen in the 1st, 14th and 15th spans with the addition of new bowing in the 2nd and 13th spans. In the Second Outermost Ring, 1st span repeat bowing was observed with occurrence of new bowing in the 14th and 15th spans. While the bowing in the 2nd and 13th span appear to be new, those tubes with proximity signals actually exhibited threshold signals during the 1R20 outage. The magnitude of 1R21 bowing fell within the apparent root cause acceptance criteria for all but one tie-rod location in the Outermost Ring, namely the tie-rod in row 42 at the 15th span. In the Second Outermost Ring, tie-rod locations at row 47, row 66, row 86, and row 105 exceeded the root cause acceptance criteria in the 1st span. Row 86 also exceeded the root cause acceptance criteria in the 14th span. While in some cases the root cause acceptance was exceeded, the operability acceptance criteria were satisfied, with additional margin. AREVA revised its operability evaluation due to suspected locking in the eighth tube support plate in SG A. This locking at the eighth tube support plate actually reduces the bowing in the lower spans if additional forces are not exerted by tube support plates in the upper shroud area. Therefore preliminary models were revised to increase the compressive forces by reducing the free rotation of the tube support plate edges. AREVA prepared a revised operability evaluation to show that these new observations do not impact operability. The revised operability evaluation stems from the observations found during 1R21 that were not observed during the 1R20 inspection.

The growth rate of the tube support plate wear was considered moderately low. Listed in the table below is a summary of the tube support plate wear for 1R21:

to 1CAN030907 Page 9 of 9 SG A SG B Total Number of Tubes Examined 15595 15596

  1. of Wear Indications 990 1029
  1. of Tubes with Wear 913 823

% of Tubes with Wear 5.85%

5.28%

  1. New Wear Indications 524 685
  1. Repeat Wear Indications 466 344 New Average Depth 7.6 % TW 8.2 % TW New + Repeat Average Depth 7.7 % TW 9.1 % TW Maximum Depth 32 % TW 32 % TW
  1. of Indications > 40 % TW 0

0

  1. of Indications 20 % but 39 %

13 30

  1. of Indications > 1 % but 19 %

977 999 New + Repeat Average Growth 2.84 % TW / EFPY 4.34 % TW / EFPY 95 / 50 Growth (New Indications) 8.56 % TW / EFPY 9.99 % TW / EFPY 95 / 50 Growth (Repeat Indications) 3.57 % TW / EFPY 5.71 % TW / EFPY Max Growth (New Indications) 22.11 % TW / EFPY 19.97 % TW / EFPY Max Growth (Repeat Indications) 15.69 % TW / EFPY 14.27 % TW / EFPY

  1. Tubes Plugged 8

5 TW Through Wall EFPY Effective Full Power Years

to 1CAN030907 SG A Wear Indications - 1R21 to 1CAN030907 Page 1 of 25 SG A Wear Indications - 1R21 Item #

Row Tube Indication

% TW TSP Loc 1

1 6

WAR 5

13S 0.35 2

1 16 WAR 6

10S 0.52 3

1 17 WAR 6

10S 0.51 4

1 19 WAR 8

10S 0.45 5

1 19 WAR 3

13S

-0.77 6

1 23 WAR 6

10S 0.51 7

2 4

WAR 6

13S

-0.66 8

3 5

WAR 9

13S

-0.71 9

4 24 WAR 5

10S 0.09 10 4

25 WAR 15 10S 0.08 11 5

19 WAR 8

10S

-0.66 12 5

19 WAR 4

12S

-0.77 13 5

20 WAR 13 10S

-0.66 14 5

23 WAR 10 10S

-0.65 15 5

24 WAR 4

12S

-0.71 16 5

25 WAR 9

12S

-0.71 17 5

26 WAR 11 10S

-0.64 18 5

28 WAR 6

10S

-0.65 19 5

28 WAR 15 10S 0.21 20 5

29 WAR 10 10S 0.13 21 6

6 WAR 12 10S

-0.60 22 6

9 WAR 10 10S

-0.60 23 6

13 WAR 6

10S

-0.66 24 6

15 WAR 13 10S

-0.63 25 6

18 WAR 9

10S

-0.63 26 6

19 WAR 12 10S

-0.66 27 6

21 WAR 4

12S

-0.77 28 6

26 WAR 5

12S

-0.74 29 6

29 WAR 8

09S

-0.67 30 6

30 WAR 7

12S

-0.76 31 6

32 WAR 7

12S

-0.76 32 6

33 WAR 4

10S 0.10 33 6

35 WAR 5

15S 0.34 34 6

41 WAR 7

09S 0.49 35 7

6 WAR 6

13S 0.51 36 7

9 WAR 10 10S

-0.63 37 7

10 WAR 22 10S

-0.65 to 1CAN030907 Page 2 of 25 Item #

Row Tube Indication

% TW TSP Loc 38 7

14 WAR 10 10S

-0.60 39 7

17 WAR 10 10S

-0.63 40 7

28 WAR 9

10S 0.45 41 7

32 WAR 9

09S

-0.58 42 7

32 WAR 10 12S 0.32 43 7

34 WAR 6

12S

-0.74 44 7

35 WAR 7

12S

-0.74 45 7

46 WAR 9

10S 0.16 46 8

11 WAR 8

10S

-0.58 47 8

16 WAR 13 09S

-0.60 48 8

17 WAR 15 09S

-0.60 49 8

19 WAR 11 09S

-0.57 50 8

20 WAR 12 09S

-0.63 51 8

29 WAR 8

12S

-0.70 52 8

35 WAR 8

09S 0.48 53 8

39 WAR 10 12S

-0.71 54 8

39 WAR 7

15S

-0.84 55 8

49 WAR 7

14S

-0.67 56 8

51 WAR 6

14S 0.24 57 9

9 WAR 16 10S

-0.60 58 9

10 WAR 5

10S 0.51 59 9

12 WAR 17 10S

-0.60 60 9

31 WAR 11 12S

-0.77 61 9

57 WAR 9

13S

-0.70 62 10 1

WAR 6

13S 0.50 63 10 9

WAR 20 10S

-0.58 64 10 10 WAR 12 10S

-0.58 65 10 11 WAR 28 10S

-0.58 66 10 12 WAR 6

10S 0.48 67 10 12 WAR 18 10S

-0.57 68 10 13 WAR 6

10S

-0.58 69 10 15 WAR 8

10S

-0.63 70 10 56 WAR 5

14S 0.29 71 10 61 WAR 9

13S 0.42 72 10 61 WAR 5

14S 0.24 73 10 62 WAR 7

14S 0.29 74 11 1

WAR 14 13S 0.53 75 11 6

WAR 7

10S 0.55 76 11 8

WAR 15 10S

-0.60 77 11 10 WAR 6

10S

-0.58 to 1CAN030907 Page 3 of 25 Item #

Row Tube Indication

% TW TSP Loc 78 11 11 WAR 10 10S

-0.60 79 11 12 WAR 27 10S

-0.60 80 11 13 WAR 7

10S

-0.60 81 11 14 WAR 14 10S

-0.54 82 11 14 WAR 6

12S

-0.63 83 11 15 WAR 7

10S

-0.62 84 11 27 WAR 6

15S 0.32 85 11 52 WAR 8

10S

-0.65 86 11 55 WAR 7

09S 0.42 87 11 64 WAR 6

10S

-0.03 88 12 2

WAR 6

13S 0.50 89 12 7

WAR 13 10S

-0.58 90 12 8

WAR 15 12S

-0.63 91 12 8

WAR 11 10S

-0.58 92 12 8

WAR 13 13S 0.47 93 12 9

WAR 12 10S

-0.60 94 12 10 WAR 32 10S

-0.55 95 12 11 WAR 21 10S

-0.63 96 12 12 WAR 7

10S

-0.63 97 12 13 WAR 13 10S

-0.60 98 12 15 WAR 6

10S 0.47 99 12 15 WAR 11 10S

-0.67 100 12 22 WAR 6

09S

-0.65 101 12 57 WAR 6

15S

-0.84 102 13 10 WAR 5

10S

-0.63 103 13 11 WAR 9

10S

-0.58 104 13 12 WAR 10 10S

-0.53 105 13 13 WAR 19 10S

-0.58 106 13 14 WAR 7

10S

-0.60 107 13 17 WAR 8

09S

-0.61 108 13 57 WAR 8

09S

-0.62 109 13 59 WAR 6

12S

-0.74 110 13 60 WAR 5

09S 0.45 111 14 11 WAR 9

10S

-0.58 112 14 12 WAR 5

12S

-0.64 113 14 15 WAR 9

11S

-0.66 114 14 15 WAR 12 10S

-0.57 115 14 16 WAR 12 10S

-0.64 116 14 17 WAR 6

07S

-0.54 117 14 74 WAR 8

10S

-0.03 to 1CAN030907 Page 4 of 25 Item #

Row Tube Indication

% TW TSP Loc 118 15 15 WAR 8

11S

-0.63 119 15 16 WAR 10 10S

-0.67 120 15 49 WAR 6

09S

-0.64 121 15 80 WAR 15 13S

-0.63 122 16 4

WAR 6

10S 0.25 123 16 74 WAR 7

09S 0.45 124 16 76 WAR 5

10S 0.16 125 17 5

WAR 20 10S

-0.60 126 17 68 WAR 9

10S

-0.74 127 18 21 WAR 3

09S

-0.68 128 18 77 WAR 7

09S 0.46 129 18 78 WAR 8

09S

-0.60 130 19 41 WAR 4

08S

-0.68 131 19 71 WAR 7

12S 0.38 132 19 80 WAR 13 09S

-0.67 133 19 82 WAR 10 10S 0.22 134 20 82 WAR 10 12S 0.34 135 20 85 WAR 6

14S 0.32 136 21 45 WAR 6

08S 0.39 137 21 82 WAR 5

10S

-0.73 138 21 84 WAR 6

10S 0.22 139 21 87 WAR 5

12S

-0.76 140 21 90 WAR 13 12S

-0.76 141 22 58 WAR 5

08S

-0.70 142 22 85 WAR 9

11S 0.37 143 22 85 WAR 9

10S 0.31 144 22 85 WAR 14 10S

-0.71 145 23 33 WAR 5

08S 0.47 146 23 40 WAR 6

08S

-0.63 147 23 44 WAR 5

08S

-0.63 148 23 85 WAR 18 10S

-0.61 149 23 86 WAR 25 10S

-0.72 150 23 89 WAR 9

12S 0.40 151 23 94 WAR 12 12S

-0.81 152 24 30 WAR 5

08S

-0.63 153 24 38 WAR 8

08S 0.48 154 24 48 WAR 8

08S

-0.62 155 24 53 WAR 5

08S 0.47 156 24 83 WAR 19 10S

-0.74 157 24 85 WAR 8

12S

-0.79 to 1CAN030907 Page 5 of 25 Item #

Row Tube Indication

% TW TSP Loc 158 24 86 WAR 7

10S 0.13 159 24 91 WAR 9

12S

-0.76 160 25 31 WAR 5

08S 0.47 161 25 34 WAR 6

08S

-0.63 162 25 40 WAR 6

08S 0.41 163 25 47 WAR 8

08S 0.47 164 25 54 WAR 7

08S 0.50 165 25 56 WAR 6

08S

-0.62 166 25 59 WAR 12 08S

-0.63 167 25 62 WAR 5

08S 0.45 168 25 63 WAR 5

08S

-0.65 169 26 42 WAR 6

08S 0.44 170 26 43 WAR 8

08S

-0.63 171 26 49 WAR 6

08S

-0.65 172 26 51 WAR 5

08S

-0.68 173 26 52 WAR 6

08S 0.45 174 26 52 WAR 5

08S

-0.56 175 26 54 WAR 6

08S 0.48 176 26 54 WAR 5

08S

-0.64 177 26 55 WAR 8

08S 0.47 178 26 56 WAR 4

08S

-0.62 179 26 65 WAR 9

08S

-0.65 180 26 65 WAR 5

08S 0.47 181 26 67 WAR 5

08S

-0.62 182 26 71 WAR 3

08S

-0.67 183 26 93 WAR 9

12S

-0.79 184 26 94 WAR 8

10S 0.16 185 26 95 WAR 6

10S 0.13 186 26 99 WAR 5

12S

-0.76 187 27 27 WAR 8

08S

-0.60 188 27 28 WAR 5

08S 0.47 189 27 29 WAR 6

08S 0.47 190 27 30 WAR 4

08S

-0.60 191 27 31 WAR 5

08S

-0.63 192 27 32 WAR 4

08S

-0.63 193 27 34 WAR 5

08S

-0.60 194 27 36 WAR 4

08S

-0.60 195 27 38 WAR 8

08S

-0.63 196 27 39 WAR 4

08S

-0.60 197 27 40 WAR 6

08S

-0.63 to 1CAN030907 Page 6 of 25 Item #

Row Tube Indication

% TW TSP Loc 198 27 41 WAR 5

08S

-0.63 199 27 43 WAR 5

08S

-0.63 200 27 45 WAR 3

08S

-0.65 201 27 46 WAR 8

08S

-0.63 202 27 49 WAR 5

08S

-0.63 203 27 51 WAR 6

08S 0.47 204 27 54 WAR 3

08S

-0.70 205 27 55 WAR 5

08S

-0.60 206 27 58 WAR 4

08S

-0.62 207 27 63 WAR 3

08S

-0.62 208 27 64 WAR 6

08S 0.45 209 27 66 WAR 6

08S 0.41 210 27 69 WAR 7

08S 0.43 211 27 71 WAR 5

08S 0.46 212 27 73 WAR 5

08S 0.46 213 27 94 WAR 10 12S

-0.83 214 27 95 WAR 12 12S

-0.82 215 27 97 WAR 7

10S 0.13 216 28 6

WAR 7

12S

-0.66 217 28 16 WAR 7

10S 0.53 218 28 28 WAR 7

08S 0.44 219 28 31 WAR 4

08S

-0.60 220 28 35 WAR 7

08S

-0.60 221 28 40 WAR 5

08S

-0.63 222 28 41 WAR 7

08S 0.50 223 28 41 WAR 10 08S

-0.60 224 28 42 WAR 5

08S

-0.63 225 28 54 WAR 7

08S 0.48 226 28 55 WAR 4

08S

-0.65 227 28 56 WAR 5

08S

-0.62 228 28 57 WAR 5

08S

-0.68 229 28 57 WAR 4

08S 0.44 230 28 96 WAR 6

12S

-0.82 231 28 97 WAR 5

12S

-0.76 232 29 30 WAR 7

08S 0.47 233 29 31 WAR 9

08S

-0.58 234 29 32 WAR 8

08S

-0.60 235 29 33 WAR 7

08S 0.47 236 29 33 WAR 9

08S

-0.60 237 29 34 WAR 7

08S

-0.60 to 1CAN030907 Page 7 of 25 Item #

Row Tube Indication

% TW TSP Loc 238 29 41 WAR 4

08S

-0.63 239 29 56 WAR 5

08S 0.47 240 29 56 WAR 6

08S

-0.68 241 29 57 WAR 6

08S 0.48 242 29 58 WAR 6

08S 0.50 243 29 60 WAR 7

08S 0.50 244 29 61 WAR 6

08S 0.48 245 29 62 WAR 4

08S

-0.62 246 29 63 WAR 6

08S 0.48 247 29 64 WAR 5

08S 0.47 248 29 66 WAR 7

08S 0.50 249 29 71 WAR 10 08S 0.41 250 29 72 WAR 6

08S 0.49 251 29 73 WAR 6

08S 0.51 252 29 97 WAR 14 12S 0.35 253 29 98 WAR 11 12S 0.34 254 29 98 WAR 4

12S

-0.81 255 29 99 WAR 5

12S

-0.81 256 30 31 WAR 8

08S

-0.60 257 30 32 WAR 4

08S

-0.60 258 30 33 WAR 9

08S

-0.60 259 30 34 WAR 6

08S

-0.63 260 30 36 WAR 5

08S

-0.63 261 30 37 WAR 8

08S

-0.60 262 30 56 WAR 3

08S

-0.62 263 30 67 WAR 6

08S 0.50 264 30 68 WAR 4

08S

-0.65 265 30 70 WAR 8

08S 0.51 266 30 72 WAR 5

08S 0.45 267 30 73 WAR 5

08S 0.50 268 30 77 WAR 5

08S 0.49 269 30 99 WAR 6

12S

-0.79 270 30 100 WAR 6

12S

-0.76 271 31 30 WAR 5

08S

-0.63 272 31 32 WAR 7

08S

-0.60 273 31 32 WAR 6

08S 0.52 274 31 33 WAR 5

08S 0.47 275 31 34 WAR 8

08S

-0.79 276 31 38 WAR 10 08S

-0.60 277 31 67 WAR 6

08S 0.53 to 1CAN030907 Page 8 of 25 Item #

Row Tube Indication

% TW TSP Loc 278 31 68 WAR 7

08S 0.45 279 31 70 WAR 6

08S 0.49 280 31 75 WAR 7

08S 0.46 281 31 79 WAR 6

08S 0.45 282 31 98 WAR 9

10S

-0.76 283 31 101 WAR 5

10S 0.10 284 32 10 WAR 7

10S 0.47 285 32 23 WAR 7

08S

-0.63 286 32 25 WAR 6

08S

-0.63 287 32 25 WAR 6

08S 0.50 288 32 29 WAR 8

08S

-0.54 289 32 29 WAR 7

08S 0.44 290 32 31 WAR 6

08S 0.50 291 32 32 WAR 5

08S 0.52 292 32 36 WAR 3

08S

-0.65 293 32 65 WAR 7

08S 0.45 294 32 67 WAR 4

08S 0.49 295 32 70 WAR 4

08S 0.49 296 32 73 WAR 5

08S 0.48 297 32 76 WAR 5

08S 0.46 298 32 98 WAR 6

11S 0.35 299 32 98 WAR 6

12S

-0.83 300 32 99 WAR 10 12S 0.34 301 32 100 WAR 7

10S 0.13 302 33 21 WAR 7

08S

-0.60 303 33 21 WAR 6

09S

-0.63 304 33 23 WAR 5

08S 0.47 305 33 29 WAR 7

08S

-0.59 306 33 30 WAR 8

08S 0.47 307 33 32 WAR 6

08S

-0.65 308 33 71 WAR 6

08S 0.49 309 33 72 WAR 6

08S 0.51 310 33 75 WAR 6

08S 0.52 311 33 76 WAR 7

08S 0.45 312 33 77 WAR 7

08S 0.49 313 33 78 WAR 7

08S 0.45 314 33 80 WAR 7

08S

-0.67 315 34 27 WAR 5

08S

-0.60 316 34 36 WAR 2

08S

-0.61 317 34 69 WAR 5

08S 0.51 to 1CAN030907 Page 9 of 25 Item #

Row Tube Indication

% TW TSP Loc 318 34 75 WAR 4

08S

-0.70 319 34 79 WAR 6

08S 0.48 320 34 82 WAR 5

08S 0.52 321 34 103 WAR 10 10S

-0.71 322 35 21 WAR 7

08S

-0.58 323 35 23 WAR 6

08S 0.47 324 35 24 WAR 5

08S

-0.58 325 35 76 WAR 6

08S 0.52 326 35 77 WAR 6

08S 0.51 327 35 82 WAR 9

08S 0.46 328 35 82 WAR 5

08S

-0.54 329 35 83 WAR 7

08S 0.48 330 35 84 WAR 7

08S 0.46 331 35 86 WAR 10 08S 0.49 332 35 87 WAR 5

08S 0.45 333 35 90 WAR 6

08S 0.43 334 35 106 WAR 9

11S 0.32 335 36 19 WAR 8

08S 0.50 336 36 21 WAR 6

08S 0.50 337 36 22 WAR 6

08S 0.47 338 36 25 WAR 2

08S

-0.61 339 36 27 WAR 5

08S

-0.60 340 36 78 WAR 8

08S 0.51 341 36 82 WAR 6

08S 0.48 342 36 84 WAR 6

08S 0.49 343 36 87 WAR 8

08S 0.45 344 36 89 WAR 8

08S 0.47 345 36 107 WAR 7

11S 0.32 346 37 7

WAR 5

10S 0.57 347 37 24 WAR 10 08S 0.47 348 37 84 WAR 6

08S 0.48 349 37 85 WAR 10 08S 0.46 350 37 86 WAR 9

08S 0.44 351 37 87 WAR 11 08S 0.41 352 37 88 WAR 6

08S 0.49 353 38 20 WAR 8

08S 0.53 354 38 23 WAR 5

08S

-0.61 355 38 24 WAR 7

08S 0.56 356 38 25 WAR 5

08S

-0.63 357 38 26 WAR 7

08S

-0.60 to 1CAN030907 Page 10 of 25 Item #

Row Tube Indication

% TW TSP Loc 358 38 27 WAR 5

08S

-0.60 359 38 85 WAR 8

08S 0.48 360 38 88 WAR 6

08S 0.46 361 38 89 WAR 9

08S 0.48 362 38 109 WAR 7

10S

-0.76 363 38 110 WAR 9

11S 0.34 364 39 23 WAR 5

08S 0.53 365 39 25 WAR 7

08S 0.53 366 39 25 WAR 4

08S

-0.58 367 39 27 WAR 10 08S 0.57 368 39 89 WAR 8

08S 0.45 369 39 111 WAR 6

12S

-0.79 370 40 19 WAR 8

08S 0.51 371 40 19 WAR 8

08S

-0.59 372 40 23 WAR 7

08S

-0.56 373 40 24 WAR 7

08S

-0.61 374 40 25 WAR 9

08S

-0.61 375 40 28 WAR 5

08S

-0.63 376 40 89 WAR 5

08S 0.52 377 40 91 WAR 9

08S 0.48 378 40 92 WAR 9

08S 0.46 379 41 21 WAR 4

08S

-0.58 380 41 23 WAR 7

08S

-0.58 381 41 26 WAR 6

08S

-0.61 382 41 27 WAR 10 08S

-0.63 383 41 28 WAR 6

08S

-0.61 384 41 29 WAR 5

08S

-0.58 385 41 93 WAR 8

08S 0.46 386 41 94 WAR 7

08S 0.48 387 42 20 WAR 4

08S

-0.59 388 42 24 WAR 5

08S

-0.63 389 42 25 WAR 7

08S

-0.58 390 42 87 WAR 7

08S 0.48 391 43 14 WAR 5

08S 0.54 392 43 20 WAR 9

08S

-0.63 393 43 21 WAR 5

08S

-0.61 394 43 24 WAR 5

08S

-0.60 395 44 15 WAR 6

08S 0.50 396 44 24 WAR 8

08S

-0.63 397 44 95 WAR 8

08S 0.50 to 1CAN030907 Page 11 of 25 Item #

Row Tube Indication

% TW TSP Loc 398 44 96 WAR 6

08S 0.48 399 44 97 WAR 7

08S 0.46 400 45 20 WAR 6

08S

-0.58 401 45 20 WAR 6

09S

-0.59 402 45 24 WAR 14 09S

-0.60 403 45 91 WAR 5

08S 0.47 404 45 96 WAR 6

08S 0.45 405 45 97 WAR 8

08S 0.46 406 46 22 WAR 8

08S 0.54 407 46 23 WAR 10 08S

-0.56 408 46 23 WAR 6

08S 0.51 409 46 92 WAR 6

08S 0.47 410 46 94 WAR 6

08S 0.47 411 46 96 WAR 6

08S 0.47 412 46 117 WAR 5

12S

-0.63 413 47 21 WAR 9

08S

-0.59 414 47 23 WAR 8

08S

-0.62 415 47 82 WAR 6

08S 0.50 416 47 118 WAR 6

14S 0.25 417 48 22 WAR 6

08S

-0.62 418 48 27 WAR 8

08S

-0.56 419 48 98 WAR 7

08S 0.45 420 48 104 WAR 6

07S

-0.50 421 49 8

WAR 7

09S 0.54 422 49 17 WAR 11 08S

-0.51 423 49 91 WAR 7

08S 0.47 424 49 93 WAR 7

08S 0.50 425 49 100 WAR 7

08S 0.48 426 49 102 WAR 8

07S 0.48 427 49 102 WAR 6

08S

-0.43 428 50 92 WAR 5

08S 0.44 429 50 94 WAR 7

08S 0.51 430 51 18 WAR 6

08S

-0.66 431 51 99 WAR 7

09S

-0.58 432 51 104 WAR 7

08S 0.46 433 52 16 WAR 5

08S

-0.43 434 52 18 WAR 6

08S

-0.64 435 52 107 WAR 5

08S 0.51 436 52 118 WAR 8

10S

-0.73 437 53 19 WAR 8

08S

-0.61 to 1CAN030907 Page 12 of 25 Item #

Row Tube Indication

% TW TSP Loc 438 53 20 WAR 4

08S

-0.64 439 53 20 WAR 8

08S 0.51 440 53 22 WAR 8

08S

-0.61 441 53 26 WAR 8

08S

-0.60 442 53 122 WAR 4

14S 0.24 443 53 123 WAR 9

14S 0.22 444 54 19 WAR 9

08S 0.49 445 54 20 WAR 10 08S

-0.54 446 54 21 WAR 7

08S

-0.56 447 54 21 WAR 8

08S 0.54 448 54 22 WAR 7

08S

-0.56 449 54 23 WAR 7

08S

-0.66 450 54 24 WAR 8

08S

-0.59 451 54 26 WAR 10 08S

-0.58 452 54 106 WAR 7

08S 0.48 453 54 109 WAR 7

08S

-0.65 454 54 109 WAR 9

08S 0.48 455 54 119 WAR 5

10S

-0.68 456 54 121 WAR 9

11S 0.32 457 54 123 WAR 6

12S

-0.76 458 55 8

WAR 6

09S 0.53 459 55 19 WAR 9

08S

-0.56 460 55 23 WAR 12 08S

-0.56 461 55 99 WAR 6

08S 0.47 462 55 101 WAR 7

08S 0.46 463 55 104 WAR 5

08S

-0.66 464 55 119 WAR 18 11S 0.32 465 55 122 WAR 8

09S 0.39 466 55 122 WAR 12 09S

-0.68 467 55 122 WAR 14 11S 0.37 468 56 7

WAR 8

10S 0.57 469 56 7

WAR 5

09S

-0.54 470 56 19 WAR 6

08S 0.57 471 56 20 WAR 6

08S

-0.56 472 56 20 WAR 10 08S 0.51 473 56 23 WAR 8

08S

-0.51 474 57 21 WAR 10 08S

-0.63 475 57 21 WAR 7

08S 0.50 476 57 105 WAR 12 08S

-0.66 477 57 107 WAR 5

09S

-0.74 to 1CAN030907 Page 13 of 25 Item #

Row Tube Indication

% TW TSP Loc 478 57 109 WAR 7

08S 0.38 479 58 20 WAR 6

08S 0.57 480 58 21 WAR 6

08S 0.54 481 58 21 WAR 5

08S

-0.57 482 58 22 WAR 7

08S

-0.60 483 58 23 WAR 9

08S

-0.60 484 58 24 WAR 8

08S 0.54 485 58 104 WAR 7

07S 0.47 486 59 20 WAR 7

08S

-0.61 487 59 124 WAR 9

11S 0.33 488 59 126 WAR 5

12S

-0.79 489 60 21 WAR 6

08S 0.57 490 60 23 WAR 7

08S

-0.51 491 60 24 WAR 11 08S

-0.63 492 60 103 WAR 6

08S 0.44 493 60 108 WAR 11 08S 0.47 494 60 125 WAR 10 12S

-0.82 495 61 21 WAR 4

08S 0.53 496 61 22 WAR 9

08S

-0.59 497 61 22 WAR 7

08S 0.53 498 61 23 WAR 8

08S

-0.59 499 61 125 WAR 6

10S 0.31 500 61 125 WAR 12 11S 0.31 501 62 98 WAR 7

08S 0.47 502 62 122 WAR 9

09S 0.44 503 63 19 WAR 7

08S

-0.60 504 63 22 WAR 9

08S

-0.59 505 63 22 WAR 5

08S 0.49 506 63 110 WAR 7

08S 0.46 507 63 111 WAR 8

08S 0.46 508 64 22 WAR 5

08S

-0.61 509 64 100 WAR 10 07S 0.51 510 64 106 WAR 7

08S 0.46 511 65 21 WAR 11 08S

-0.59 512 65 27 WAR 7

08S 0.53 513 65 110 WAR 7

09S

-0.57 514 65 110 WAR 7

07S 0.46 515 66 21 WAR 7

08S

-0.46 516 66 22 WAR 7

08S

-0.61 517 66 28 WAR 6

08S

-0.61 to 1CAN030907 Page 14 of 25 Item #

Row Tube Indication

% TW TSP Loc 518 66 108 WAR 6

08S 0.49 519 66 123 WAR 8

10S 0.33 520 67 2

WAR 8

13S 0.55 521 67 22 WAR 7

08S

-0.65 522 67 23 WAR 8

08S

-0.56 523 67 102 WAR 6

07S

-0.63 524 67 105 WAR 8

07S 0.47 525 67 105 WAR 7

10S 0.38 526 67 105 WAR 7

09S

-0.66 527 67 124 WAR 7

11S 0.36 528 67 125 WAR 8

09S 0.38 529 68 22 WAR 10 08S

-0.53 530 68 24 WAR 6

08S 0.54 531 68 111 WAR 7

09S

-0.67 532 69 4

WAR 7

10S 0.22 533 69 110 WAR 8

10S 0.41 534 69 126 WAR 11 11S 0.28 535 70 1

WAR 6

11S 0.58 536 70 4

WAR 8

10S 0.29 537 70 26 WAR 9

08S

-0.58 538 70 103 WAR 9

08S 0.51 539 70 104 WAR 10 06S

-0.56 540 70 104 WAR 14 09S

-0.62 541 70 114 WAR 7

09S

-0.66 542 71 1

WAR 7

11S

-0.54 543 71 5

WAR 12 09S

-0.51 544 71 21 WAR 7

08S 0.54 545 71 23 WAR 14 08S

-0.60 546 71 24 WAR 6

08S

-0.59 547 71 26 WAR 9

08S

-0.61 548 71 105 WAR 8

09S

-0.69 549 71 107 WAR 7

08S 0.49 550 71 114 WAR 6

09S

-0.66 551 72 1

WAR 10 13S

-0.55 552 72 22 WAR 9

08S

-0.56 553 72 24 WAR 8

08S

-0.58 554 72 25 WAR 9

08S

-0.56 555 72 103 WAR 7

08S 0.51 556 72 109 WAR 8

10S

-0.69 557 72 109 WAR 7

08S 0.46 to 1CAN030907 Page 15 of 25 Item #

Row Tube Indication

% TW TSP Loc 558 72 114 WAR 5

08S 0.47 559 72 125 WAR 12 11S 0.38 560 73 2

WAR 6

11S 0.61 561 73 17 WAR 8

08S

-0.51 562 73 18 WAR 6

08S

-0.54 563 73 25 WAR 12 08S

-0.56 564 73 105 WAR 8

08S 0.51 565 73 115 WAR 7

07S 0.45 566 73 126 WAR 4

14S 0.31 567 74 6

WAR 7

09S 0.54 568 74 27 WAR 6

08S

-0.58 569 74 108 WAR 7

08S 0.50 570 74 109 WAR 8

07S 0.47 571 74 109 WAR 6

08S 0.44 572 74 110 WAR 7

08S 0.44 573 74 110 WAR 8

07S 0.50 574 74 116 WAR 5

09S

-0.68 575 75 6

WAR 5

09S

-0.54 576 75 21 WAR 8

08S

-0.56 577 75 26 WAR 7

08S

-0.58 578 75 105 WAR 5

08S

-0.60 579 75 105 WAR 7

07S 0.51 580 75 107 WAR 7

08S 0.50 581 75 108 WAR 11 08S

-0.76 582 75 109 WAR 5

07S 0.47 583 75 109 WAR 7

08S 0.47 584 75 111 WAR 7

08S 0.50 585 75 112 WAR 4

06S

-0.60 586 75 113 WAR 7

06S

-0.60 587 76 5

WAR 5

09S 0.51 588 76 20 WAR 6

08S

-0.61 589 76 101 WAR 7

08S 0.44 590 76 102 WAR 7

06S

-0.61 591 76 105 WAR 9

08S

-0.66 592 76 107 WAR 7

08S 0.44 593 76 108 WAR 7

08S 0.44 594 76 110 WAR 10 08S 0.44 595 76 111 WAR 8

08S 0.42 596 76 122 WAR 9

12S

-0.78 597 76 123 WAR 13 11S 0.33 to 1CAN030907 Page 16 of 25 Item #

Row Tube Indication

% TW TSP Loc 598 76 124 WAR 9

12S 0.28 599 77 2

WAR 19 11S 0.59 600 77 6

WAR 6

09S 0.54 601 77 22 WAR 8

08S 0.53 602 77 104 WAR 7

08S 0.52 603 77 109 WAR 9

08S 0.47 604 77 112 WAR 12 08S 0.41 605 77 118 WAR 5

10S

-0.72 606 77 132 WAR 18 10S 0.35 607 78 17 WAR 9

08S

-0.46 608 78 103 WAR 8

08S 0.47 609 78 115 WAR 7

07S

-0.63 610 78 131 WAR 7

10S

-0.70 611 79 3

WAR 7

13S 0.51 612 79 6

WAR 6

09S 0.57 613 79 28 WAR 9

08S

-0.55 614 79 30 WAR 7

08S 0.58 615 79 111 WAR 11 08S 0.45 616 79 113 WAR 9

08S 0.45 617 80 5

WAR 10 09S 0.57 618 80 109 WAR 5

08S 0.44 619 80 113 WAR 7

08S 0.44 620 81 1

WAR 5

13S 0.58 621 81 3

WAR 5

13S 0.54 622 81 18 WAR 6

08S

-0.58 623 81 25 WAR 7

08S 0.51 624 81 114 WAR 8

08S 0.44 625 81 115 WAR 10 08S 0.47 626 81 124 WAR 11 09S

-0.67 627 81 128 WAR 7

12S 0.34 628 82 22 WAR 7

08S

-0.53 629 82 111 WAR 7

08S 0.47 630 82 113 WAR 7

08S 0.46 631 82 115 WAR 6

09S

-0.71 632 82 117 WAR 7

08S 0.46 633 83 2

WAR 6

13S 0.51 634 83 6

WAR 5

10S 0.54 635 83 18 WAR 8

08S

-0.53 636 83 20 WAR 11 08S

-0.64 637 83 23 WAR 13 08S

-0.56 to 1CAN030907 Page 17 of 25 Item #

Row Tube Indication

% TW TSP Loc 638 83 24 WAR 6

08S

-0.56 639 83 114 WAR 6

08S 0.42 640 84 6

WAR 9

09S 0.57 641 84 17 WAR 6

08S

-0.59 642 84 18 WAR 7

08S

-0.59 643 84 22 WAR 12 08S

-0.53 644 84 22 WAR 7

08S 0.54 645 84 23 WAR 10 08S

-0.56 646 84 24 WAR 7

08S

-0.56 647 84 111 WAR 8

08S 0.44 648 84 113 WAR 8

08S 0.47 649 84 116 WAR 7

09S

-0.70 650 84 116 WAR 8

08S 0.45 651 85 6

WAR 7

09S 0.57 652 85 6

WAR 7

09S

-0.51 653 85 23 WAR 8

08S 0.54 654 85 112 WAR 6

08S 0.47 655 86 6

WAR 7

09S 0.57 656 86 22 WAR 8

08S 0.52 657 86 112 WAR 7

08S 0.47 658 86 114 WAR 7

08S 0.45 659 87 4

WAR 5

10S 0.54 660 87 5

WAR 7

09S 0.54 661 87 113 WAR 8

08S 0.47 662 88 5

WAR 8

09S 0.54 663 88 22 WAR 8

08S

-0.51 664 88 23 WAR 8

08S 0.50 665 88 111 WAR 6

08S 0.47 666 88 115 WAR 6

08S 0.44 667 89 3

WAR 5

10S 0.06 668 89 23 WAR 6

08S

-0.58 669 89 23 WAR 8

08S 0.58 670 89 24 WAR 9

08S 0.54 671 90 3

WAR 6

10S 0.16 672 90 4

WAR 7

09S 0.54 673 90 5

WAR 5

09S 0.57 674 91 22 WAR 8

08S

-0.58 675 91 24 WAR 9

08S

-0.61 676 91 25 WAR 11 08S

-0.56 677 92 4

WAR 9

09S 0.57 to 1CAN030907 Page 18 of 25 Item #

Row Tube Indication

% TW TSP Loc 678 92 21 WAR 8

08S

-0.58 679 92 22 WAR 8

08S

-0.58 680 92 23 WAR 11 08S

-0.56 681 92 24 WAR 10 08S

-0.61 682 93 1

WAR 8

13S 0.54 683 93 22 WAR 14 08S

-0.56 684 93 23 WAR 9

08S

-0.58 685 93 24 WAR 8

08S 0.51 686 93 24 WAR 7

08S

-0.63 687 93 107 WAR 6

08S 0.47 688 94 1

WAR 6

13S 0.54 689 94 2

WAR 6

13S 0.54 690 94 24 WAR 10 08S

-0.63 691 94 111 WAR 7

08S 0.46 692 94 111 WAR 3

07S

-0.66 693 95 21 WAR 8

08S

-0.59 694 95 23 WAR 6

08S

-0.58 695 95 109 WAR 6

08S 0.45 696 95 111 WAR 7

08S 0.47 697 96 19 WAR 6

08S

-0.59 698 96 23 WAR 8

08S

-0.56 699 96 107 WAR 8

08S 0.45 700 97 21 WAR 9

08S

-0.51 701 97 22 WAR 6

08S

-0.61 702 97 23 WAR 10 08S

-0.61 703 98 4

WAR 16 09S 0.52 704 98 5

WAR 8

10S

-0.57 705 98 8

WAR 14 09S 0.54 706 98 22 WAR 7

08S

-0.58 707 98 24 WAR 10 08S

-0.58 708 98 105 WAR 5

08S 0.48 709 99 8

WAR 10 09S 0.54 710 99 9

WAR 10 09S 0.53 711 99 20 WAR 8

08S

-0.60 712 99 107 WAR 6

08S

-0.64 713 99 107 WAR 7

08S 0.48 714 99 114 WAR 12 09S

-0.73 715 99 117 WAR 9

09S 0.39 716 99 118 WAR 8

09S 0.45 717 99 119 WAR 10 09S 0.43 to 1CAN030907 Page 19 of 25 Item #

Row Tube Indication

% TW TSP Loc 718 100 1

WAR 6

13S

-0.60 719 100 8

WAR 7

10S

-0.57 720 100 113 WAR 6

09S

-0.67 721 101 1

WAR 8

13S

-0.57 722 101 7

WAR 6

10S

-0.62 723 101 23 WAR 9

08S

-0.68 724 101 102 WAR 7

08S

-0.67 725 101 102 WAR 7

08S 0.45 726 101 111 WAR 12 09S 0.39 727 101 112 WAR 5

10S

-0.03 728 102 5

WAR 6

10S

-0.62 729 102 9

WAR 11 09S 0.51 730 103 5

WAR 8

10S

-0.54 731 103 9

WAR 12 09S 0.50 732 103 9

WAR 11 09S

-0.59 733 103 19 WAR 7

08S

-0.59 734 103 103 WAR 8

08S 0.45 735 104 8

WAR 10 09S 0.52 736 104 8

WAR 8

09S

-0.52 737 104 9

WAR 8

09S

-0.57 738 104 23 WAR 5

08S

-0.64 739 104 25 WAR 6

08S

-0.56 740 104 30 WAR 10 08S

-0.64 741 105 7

WAR 6

09S 0.58 742 105 8

WAR 7

09S

-0.54 743 105 8

WAR 7

09S 0.45 744 105 24 WAR 6

08S

-0.56 745 105 28 WAR 6

08S

-0.61 746 106 5

WAR 10 10S 0.47 747 106 23 WAR 7

08S

-0.57 748 106 23 WAR 7

08S 0.52 749 106 24 WAR 5

08S

-0.59 750 106 25 WAR 7

08S

-0.61 751 106 27 WAR 8

08S

-0.58 752 106 112 WAR 7

10S

-0.70 753 106 119 WAR 8

10S

-0.76 754 107 3

WAR 7

10S 0.25 755 107 5

WAR 9

09S 0.54 756 107 6

WAR 12 09S

-0.54 757 107 26 WAR 8

08S

-0.62 to 1CAN030907 Page 20 of 25 Item #

Row Tube Indication

% TW TSP Loc 758 107 29 WAR 7

08S

-0.64 759 107 88 WAR 8

08S 0.48 760 107 112 WAR 7

10S

-0.70 761 107 113 WAR 6

10S

-0.64 762 107 114 WAR 6

10S

-0.70 763 107 115 WAR 7

10S

-0.70 764 108 5

WAR 9

09S

-0.54 765 108 21 WAR 8

08S

-0.53 766 108 26 WAR 11 08S

-0.58 767 108 28 WAR 14 08S

-0.63 768 108 109 WAR 5

10S

-0.70 769 109 24 WAR 11 08S

-0.58 770 109 96 WAR 7

08S 0.50 771 109 98 WAR 5

08S 0.48 772 110 25 WAR 9

08S

-0.61 773 110 26 WAR 8

08S

-0.63 774 110 28 WAR 10 08S

-0.64 775 110 80 WAR 6

08S 0.49 776 111 20 WAR 8

08S

-0.61 777 111 25 WAR 6

08S

-0.59 778 111 26 WAR 6

08S

-0.64 779 111 27 WAR 7

08S

-0.63 780 111 29 WAR 12 08S

-0.64 781 111 30 WAR 10 08S

-0.56 782 111 32 WAR 10 08S

-0.56 783 112 23 WAR 6

08S 0.50 784 112 27 WAR 8

08S

-0.61 785 112 27 WAR 7

08S 0.53 786 112 29 WAR 10 08S

-0.53 787 112 32 WAR 7

08S

-0.59 788 112 95 WAR 11 08S 0.45 789 112 98 WAR 5

08S 0.48 790 113 5

WAR 7

09S 0.53 791 113 24 WAR 5

08S

-0.58 792 113 26 WAR 7

08S

-0.58 793 113 30 WAR 7

08S

-0.61 794 113 110 WAR 7

10S

-0.68 795 114 4

WAR 5

10S

-0.54 796 114 30 WAR 5

08S

-0.68 797 114 31 WAR 6

08S

-0.66 to 1CAN030907 Page 21 of 25 Item #

Row Tube Indication

% TW TSP Loc 798 114 108 WAR 7

10S

-0.67 799 115 6

WAR 5

09S 0.56 800 115 27 WAR 11 08S

-0.56 801 115 29 WAR 9

08S

-0.64 802 115 108 WAR 5

10S

-0.67 803 115 109 WAR 11 10S 0.14 804 115 110 WAR 12 10S 0.08 805 116 5

WAR 22 09S 0.51 806 116 6

WAR 6

09S 0.53 807 116 26 WAR 5

08S 0.50 808 116 26 WAR 8

08S

-0.70 809 116 109 WAR 8

10S 0.06 810 117 7

WAR 6

09S 0.53 811 117 22 WAR 6

08S 0.50 812 117 28 WAR 7

08S

-0.58 813 117 29 WAR 8

08S

-0.53 814 117 107 WAR 8

10S 0.08 815 118 106 WAR 4

10S 0.14 816 119 6

WAR 8

09S 0.53 817 119 25 WAR 10 08S

-0.59 818 119 27 WAR 7

08S

-0.61 819 119 30 WAR 10 08S

-0.60 820 119 31 WAR 8

08S

-0.61 821 119 34 WAR 3

08S

-0.61 822 119 44 WAR 7

08S

-0.64 823 119 44 WAR 13 07S 0.50 824 119 70 WAR 5

08S 0.47 825 119 101 WAR 6

10S

-0.70 826 120 24 WAR 7

08S

-0.61 827 120 78 WAR 7

08S

-0.64 828 120 78 WAR 12 08S 0.47 829 120 80 WAR 7

08S 0.44 830 120 98 WAR 7

10S

-0.75 831 120 101 WAR 8

10S 0.17 832 120 102 WAR 7

10S 0.03 833 121 8

WAR 14 09S 0.49 834 121 26 WAR 9

08S

-0.55 835 121 30 WAR 5

08S 0.48 836 121 31 WAR 6

08S

-0.62 837 121 33 WAR 6

08S

-0.61 to 1CAN030907 Page 22 of 25 Item #

Row Tube Indication

% TW TSP Loc 838 121 80 WAR 6

08S 0.45 839 121 100 WAR 8

10S

-0.67 840 121 101 WAR 7

10S 0.11 841 122 1

WAR 10 10S 0.45 842 122 8

WAR 8

09S 0.50 843 122 34 WAR 6

08S

-0.61 844 122 34 WAR 4

08S 0.49 845 122 34 WAR 5

07S 0.51 846 122 63 WAR 8

08S 0.50 847 122 72 WAR 3

07S

-0.60 848 123 8

WAR 5

09S 0.53 849 123 29 WAR 8

08S

-0.59 850 123 65 WAR 5

08S 0.48 851 123 71 WAR 5

08S 0.48 852 123 74 WAR 5

08S 0.50 853 123 99 WAR 4

10S 0.11 854 124 8

WAR 7

09S 0.53 855 124 9

WAR 13 09S 0.50 856 124 28 WAR 6

08S

-0.61 857 124 30 WAR 4

08S

-0.62 858 124 31 WAR 5

08S

-0.62 859 124 32 WAR 6

08S

-0.64 860 124 36 WAR 4

08S

-0.67 861 124 38 WAR 6

08S

-0.64 862 124 42 WAR 2

08S

-0.64 863 124 76 WAR 5

08S

-0.65 864 125 1

WAR 6

13S 0.52 865 125 8

WAR 4

09S 0.54 866 125 28 WAR 5

08S 0.56 867 125 45 WAR 4

08S

-0.63 868 125 53 WAR 3

08S

-0.63 869 125 54 WAR 9

08S

-0.65 870 125 54 WAR 6

09S

-0.67 871 125 56 WAR 5

08S 0.48 872 125 58 WAR 4

08S

-0.65 873 125 73 WAR 5

08S 0.50 874 125 93 WAR 12 10S

-0.67 875 126 40 WAR 5

08S

-0.64 876 126 42 WAR 6

08S

-0.64 877 126 50 WAR 5

08S

-0.63 to 1CAN030907 Page 23 of 25 Item #

Row Tube Indication

% TW TSP Loc 878 126 54 WAR 4

08S

-0.63 879 126 55 WAR 3

08S

-0.63 880 126 56 WAR 3

08S

-0.63 881 126 57 WAR 6

08S

-0.60 882 127 41 WAR 6

08S 0.54 883 127 50 WAR 7

08S

-0.61 884 127 64 WAR 8

08S 0.45 885 127 88 WAR 7

09S 0.47 886 127 89 WAR 4

10S

-0.67 887 127 91 WAR 8

10S

-0.70 888 127 98 WAR 9

13S

-0.80 889 128 1

WAR 14 13S 0.47 890 128 2

WAR 10 12S

-0.60 891 128 2

WAR 6

14S 0.53 892 128 48 WAR 5

08S

-0.61 893 128 83 WAR 12 09S 0.44 894 128 84 WAR 7

09S 0.46 895 129 9

WAR 20 09S 0.47 896 129 10 WAR 6

14S 0.42 897 129 40 WAR 5

08S

-0.67 898 129 49 WAR 6

08S

-0.53 899 130 2

WAR 7

13S 0.50 900 130 9

WAR 10 09S 0.49 901 130 10 WAR 10 09S 0.45 902 130 33 WAR 3

08S

-0.61 903 130 34 WAR 4

08S

-0.64 904 130 37 WAR 5

08S

-0.67 905 130 39 WAR 5

08S

-0.64 906 130 45 WAR 7

08S

-0.69 907 130 49 WAR 5

08S

-0.66 908 130 51 WAR 4

08S

-0.63 909 131 1

WAR 7

14S

-0.60 910 131 8

WAR 9

09S 0.50 911 131 9

WAR 6

09S 0.50 912 131 36 WAR 5

08S

-0.67 913 131 84 WAR 6

10S 0.08 914 131 85 WAR 4

10S 0.06 915 132 8

WAR 16 09S 0.49 916 132 30 WAR 4

08S

-0.61 917 132 38 WAR 5

08S

-0.61 to 1CAN030907 Page 24 of 25 Item #

Row Tube Indication

% TW TSP Loc 918 132 46 WAR 5

08S 0.50 919 133 1

WAR 7

13S 0.42 920 133 2

WAR 5

13S 0.50 921 133 2

WAR 6

14S

-0.63 922 133 9

WAR 6

09S 0.47 923 133 10 WAR 7

09S 0.45 924 133 37 WAR 5

08S

-0.61 925 133 81 WAR 13 11S 0.42 926 134 1

WAR 13 14S

-0.60 927 134 9

WAR 7

09S 0.50 928 134 79 WAR 16 11S 0.42 929 135 1

WAR 8

13S 0.50 930 135 1

WAR 6

14S

-0.58 931 135 9

WAR 9

09S 0.51 932 136 8

WAR 8

09S 0.51 933 137 8

WAR 9

09S 0.45 934 137 12 WAR 7

09S 0.50 935 138 13 WAR 4

09S 0.49 936 138 74 WAR 6

12S

-0.78 937 139 14 WAR 7

10S

-0.67 938 139 15 WAR 6

10S

-0.64 939 139 57 WAR 7

09S

-0.50 940 139 63 WAR 8

11S 0.45 941 140 1

WAR 8

13S

-0.65 942 140 7

WAR 10 10S

-0.61 943 140 9

WAR 7

10S

-0.64 944 140 13 WAR 7

14S

-0.70 945 140 13 WAR 8

10S

-0.62 946 140 16 WAR 7

09S

-0.68 947 140 58 WAR 5

11S 0.42 948 140 60 WAR 8

11S 0.47 949 140 61 WAR 13 11S 0.50 950 140 62 WAR 11 11S

-0.67 951 140 66 WAR 6

10S 0.44 952 141 11 WAR 9

10S

-0.64 953 141 14 WAR 11 09S 0.42 954 141 16 WAR 6

09S 0.46 955 141 55 WAR 28 11S 0.39 956 141 59 WAR 10 11S 0.45 957 141 60 WAR 18 11S 0.48 to 1CAN030907 Page 25 of 25 Item #

Row Tube Indication

% TW TSP Loc 958 142 12 WAR 9

10S

-0.65 959 142 13 WAR 13 10S

-0.67 960 142 53 WAR 23 11S 0.42 961 142 57 WAR 9

11S 0.49 962 142 60 WAR 7

11S 0.45 963 142 62 WAR 8

11S 0.48 964 143 10 WAR 10 10S

-0.65 965 143 41 WAR 10 09S 0.44 966 143 51 WAR 31 11S 0.45 967 143 52 WAR 18 11S 0.45 968 143 53 WAR 9

11S 0.50 969 143 55 WAR 8

10S 0.39 970 144 18 WAR 12 09S 0.44 971 144 35 WAR 10 09S 0.47 972 144 41 WAR 12 09S 0.44 973 144 47 WAR 12 11S 0.48 974 145 32 WAR 8

09S 0.47 975 145 36 WAR 10 11S 0.45 976 145 44 WAR 9

11S 0.50 977 145 46 WAR 3

10S 0.00 978 145 47 WAR 9

11S 0.50 979 146 10 WAR 11 10S

-0.67 980 146 15 WAR 7

10S

-0.67 981 147 6

WAR 13 10S

-0.67 982 147 7

WAR 17 10S

-0.65 983 147 8

WAR 15 10S

-0.67 984 147 13 WAR 5

10S

-0.67 985 147 29 WAR 5

10S 0.03 986 147 30 WAR 9

11S 0.45 987 148 13 WAR 7

10S

-0.64 988 148 22 WAR 9

10S 0.42 989 148 25 WAR 7

10S 0.17 990 151 23 WAR 6

13S 0.36

to 1CAN030907 SG B Wear Indications - 1R21 to 1CAN030907 Page 1 of 26 SG B Wear Indications - 1R21 Item #

Row Tube Indication

% TW TSP Loc 1

1 1

WAR 9

11S

-0.67 2

1 3

WAR 20 11S

-0.72 3

1 4

WAR 13 11S

-0.56 4

1 5

WAR 25 11S

-0.70 5

1 6

WAR 28 11S

-0.58 6

1 8

WAR 17 11S

-0.69 7

1 16 WAR 27 11S

-0.64 8

1 17 WAR 10 11S

-0.74 9

1 18 WAR 13 11S

-0.72 10 1

19 WAR 9

11S

-0.74 11 1

20 WAR 13 11S

-0.64 12 1

24 WAR 16 11S

-0.70 13 2

2 WAR 10 10S 0.47 14 2

2 WAR 11 11S 0.49 15 2

3 WAR 6

10S 0.52 16 2

4 WAR 21 11S

-0.70 17 2

5 WAR 5

10S 0.49 18 2

5 WAR 11 11S

-0.72 19 2

6 WAR 11 11S

-0.69 20 2

7 WAR 11 11S

-0.67 21 2

21 WAR 12 11S

-0.67 22 2

22 WAR 16 11S

-0.64 23 2

23 WAR 16 11S

-0.66 24 2

24 WAR 12 11S

-0.71 25 2

26 WAR 16 11S

-0.67 26 2

28 WAR 11 11S

-0.67 27 2

31 WAR 7

12S

-0.71 28 3

1 WAR 6

11S 0.52 29 3

2 WAR 14 11S

-0.64 30 3

3 WAR 5

10S 0.49 31 3

4 WAR 7

10S 0.49 32 3

5 WAR 13 10S

-0.67 33 3

6 WAR 7

11S 0.47 34 3

8 WAR 5

08S

-0.66 35 3

8 WAR 11 10S

-0.67 36 3

9 WAR 10 10S 0.36 37 3

9 WAR 12 14S

-0.78 to 1CAN030907 Page 2 of 26 Item #

Row Tube Indication

% TW TSP Loc 38 3

9 WAR 14 12S 0.31 39 3

10 WAR 5

10S

-0.64 40 3

11 WAR 9

08S 0.50 41 3

12 WAR 10 12S

-0.75 42 3

12 WAR 5

10S

-0.72 43 3

34 WAR 9

10S 0.51 44 3

35 WAR 6

10S 0.59 45 4

1 WAR 5

10S 0.49 46 4

2 WAR 4

10S 0.52 47 4

8 WAR 17 12S 0.00 48 4

10 WAR 8

10S

-0.80 49 4

10 WAR 26 12S 0.00 50 4

10 WAR 13 11S 0.36 51 4

11 WAR 16 10S

-0.69 52 4

11 WAR 6

14S

-0.80 53 4

11 WAR 31 11S 0.00 54 4

37 WAR 20 10S 0.48 55 5

3 WAR 8

10S 0.50 56 5

8 WAR 13 12S

-0.78 57 5

11 WAR 10 11S 0.41 58 5

11 WAR 12 10S

-0.67 59 5

11 WAR 15 12S 0.00 60 5

12 WAR 23 12S 0.00 61 5

12 WAR 8

11S 0.39 62 5

12 WAR 14 10S

-0.67 63 5

12 WAR 8

14S

-0.83 64 5

23 WAR 10 10S

-0.72 65 5

26 WAR 6

10S 0.06 66 5

27 WAR 6

10S 0.13 67 6

3 WAR 5

10S 0.54 68 6

4 WAR 5

10S 0.49 69 6

4 WAR 7

10S

-0.67 70 6

7 WAR 11 10S

-0.72 71 6

8 WAR 12 10S

-0.64 72 6

30 WAR 7

10S 0.11 73 6

39 WAR 9

11S 0.39 74 6

43 WAR 7

10S 0.53 75 6

44 WAR 7

10S 0.53 76 6

45 WAR 11 12S 0.30 77 6

46 WAR 13 11S 0.48 to 1CAN030907 Page 3 of 26 Item #

Row Tube Indication

% TW TSP Loc 78 6

47 WAR 14 10S 0.48 79 7

39 WAR 14 11S 0.42 80 7

40 WAR 6

10S 0.50 81 7

40 WAR 10 11S 0.36 82 7

47 WAR 7

10S 0.51 83 7

48 WAR 10 10S 0.56 84 7

49 WAR 11 12S 0.38 85 7

49 WAR 11 11S 0.51 86 7

49 WAR 6

10S 0.51 87 7

50 WAR 10 10S 0.56 88 8

1 WAR 8

11S

-0.71 89 8

1 WAR 9

10S 0.50 90 8

4 WAR 6

10S 0.50 91 8

6 WAR 16 10S

-0.67 92 8

7 WAR 15 10S

-0.64 93 8

38 WAR 11 10S 0.44 94 8

39 WAR 13 10S 0.42 95 8

39 WAR 10 13S 0.31 96 8

47 WAR 10 11S 0.46 97 8

50 WAR 7

10S 0.53 98 8

51 WAR 16 10S 0.48 99 8

53 WAR 6

10S 0.53 100 8

54 WAR 7

10S 0.53 101 8

54 WAR 12 12S

-0.67 102 9

1 WAR 9

10S 0.47 103 9

4 WAR 14 10S

-0.67 104 9

5 WAR 11 10S

-0.67 105 9

12 WAR 9

10S

-0.72 106 9

28 WAR 10 10S 0.31 107 9

54 WAR 6

10S 0.56 108 9

55 WAR 5

10S 0.53 109 9

56 WAR 6

10S 0.53 110 9

57 WAR 14 11S 0.53 111 9

58 WAR 25 10S 0.51 112 9

59 WAR 7

10S 0.53 113 9

59 WAR 9

11S

-0.63 114 9

59 WAR 7

11S 0.61 115 9

60 WAR 16 10S 0.51 116 9

60 WAR 11 12S

-0.71 117 10 2

WAR 10 10S 0.52 to 1CAN030907 Page 4 of 26 Item #

Row Tube Indication

% TW TSP Loc 118 10 4

WAR 10 10S 0.52 119 10 9

WAR 15 10S

-0.67 120 10 14 WAR 29 10S

-0.72 121 10 15 WAR 8

14S

-0.80 122 10 29 WAR 7

08S

-0.74 123 10 45 WAR 5

14S 0.28 124 10 57 WAR 6

10S 0.44 125 10 59 WAR 12 13S

-0.82 126 10 59 WAR 8

10S 0.56 127 10 61 WAR 8

12S 0.36 128 10 62 WAR 11 11S 0.44 129 10 65 WAR 11 10S 0.51 130 11 2

WAR 9

11S 0.47 131 11 2

WAR 5

11S

-0.73 132 11 7

WAR 11 10S

-0.67 133 11 8

WAR 17 10S

-0.67 134 11 9

WAR 17 10S

-0.70 135 11 14 WAR 22 10S

-0.54 136 11 15 WAR 11 10S

-0.73 137 11 31 WAR 11 14S

-0.75 138 11 46 WAR 6

13S

-0.81 139 11 49 WAR 8

14S

-0.75 140 11 58 WAR 9

10S 0.53 141 11 60 WAR 5

10S 0.48 142 11 61 WAR 6

10S 0.50 143 11 62 WAR 6

10S 0.41 144 12 1

WAR 6

11S

-0.71 145 12 1

WAR 8

10S 0.45 146 12 2

WAR 7

10S 0.39 147 12 6

WAR 7

10S

-0.70 148 12 7

WAR 16 10S

-0.62 149 12 9

WAR 10 10S

-0.67 150 12 10 WAR 11 10S

-0.67 151 12 11 WAR 9

10S

-0.70 152 12 12 WAR 18 10S

-0.69 153 12 13 WAR 16 10S

-0.67 154 12 15 WAR 25 10S

-0.69 155 12 67 WAR 9

11S

-0.67 156 12 69 WAR 10 10S 0.50 157 13 6

WAR 10 10S

-0.65 to 1CAN030907 Page 5 of 26 Item #

Row Tube Indication

% TW TSP Loc 158 13 10 WAR 6

14S

-0.84 159 13 13 WAR 6

10S 0.48 160 13 15 WAR 11 10S

-0.72 161 13 16 WAR 10 10S

-0.70 162 13 56 WAR 8

14S 0.28 163 13 60 WAR 11 10S 0.47 164 13 69 WAR 7

13S 0.28 165 13 74 WAR 12 10S 0.48 166 13 74 WAR 18 10S

-0.64 167 14 62 WAR 11 10S 0.41 168 14 68 WAR 8

10S 0.44 169 14 69 WAR 6

10S 0.50 170 14 75 WAR 16 11S 0.47 171 14 77 WAR 9

10S 0.52 172 15 7

WAR 27 10S

-0.71 173 15 25 WAR 7

10S 0.39 174 15 65 WAR 13 10S 0.47 175 15 67 WAR 11 10S 0.44 176 15 67 WAR 6

13S

-0.72 177 15 69 WAR 10 10S 0.47 178 15 72 WAR 7

14S

-0.75 179 15 72 WAR 10 14S 0.36 180 15 78 WAR 9

08S

-0.70 181 15 79 WAR 15 10S 0.43 182 15 80 WAR 11 11S

-0.68 183 15 80 WAR 12 10S

-0.60 184 16 75 WAR 9

10S 0.47 185 16 81 WAR 19 10S 0.49 186 17 82 WAR 26 10S 0.46 187 17 82 WAR 11 11S

-0.68 188 17 83 WAR 8

13S

-0.76 189 17 83 WAR 29 10S 0.32 190 17 84 WAR 11 10S

-0.66 191 17 84 WAR 10 11S

-0.71 192 18 1

WAR 8

11S

-0.71 193 18 8

WAR 5

10S 0.43 194 18 19 WAR 6

14S 0.29 195 18 54 WAR 7

08S

-0.58 196 18 54 WAR 5

08S 0.50 197 18 78 WAR 14 10S 0.44 to 1CAN030907 Page 6 of 26 Item #

Row Tube Indication

% TW TSP Loc 198 18 83 WAR 14 10S 0.45 199 18 84 WAR 11 11S

-0.69 200 18 85 WAR 17 10S

-0.63 201 19 1

WAR 6

11S

-0.77 202 19 42 WAR 9

08S 0.46 203 19 49 WAR 5

08S

-0.73 204 19 80 WAR 13 10S 0.47 205 19 87 WAR 12 10S 0.47 206 20 7

WAR 6

10S

-0.74 207 20 11 WAR 4

10S 0.43 208 20 29 WAR 7

08S 0.45 209 20 50 WAR 6

07S

-0.68 210 20 51 WAR 15 08S 0.44 211 20 51 WAR 8

09S

-0.69 212 20 51 WAR 6

07S

-0.69 213 20 51 WAR 7

08S

-0.61 214 20 54 WAR 7

08S 0.47 215 20 80 WAR 5

14S 0.33 216 20 81 WAR 5

14S

-0.75 217 20 82 WAR 8

10S 0.47 218 20 84 WAR 5

13S 0.33 219 21 7

WAR 19 10S

-0.71 220 21 8

WAR 13 10S

-0.76 221 21 42 WAR 6

08S 0.46 222 21 47 WAR 7

08S 0.50 223 21 48 WAR 6

08S 0.53 224 21 57 WAR 6

08S 0.47 225 21 58 WAR 10 08S 0.47 226 21 60 WAR 7

07S 0.44 227 21 89 WAR 9

10S

-0.70 228 22 36 WAR 6

08S 0.46 229 22 36 WAR 6

08S

-0.69 230 22 38 WAR 9

07S 0.48 231 22 41 WAR 11 08S 0.43 232 22 41 WAR 7

06S

-0.71 233 22 41 WAR 5

08S

-0.71 234 22 56 WAR 8

07S 0.47 235 22 57 WAR 7

08S 0.47 236 22 58 WAR 7

08S 0.51 237 22 58 WAR 4

09S

-0.68 to 1CAN030907 Page 7 of 26 Item #

Row Tube Indication

% TW TSP Loc 238 22 60 WAR 8

08S 0.47 239 22 62 WAR 7

08S 0.44 240 22 63 WAR 5

08S 0.45 241 22 66 WAR 11 08S 0.43 242 22 93 WAR 13 11S

-0.76 243 22 93 WAR 10 10S

-0.75 244 23 2

WAR 16 11S

-0.68 245 23 5

WAR 7

10S

-0.68 246 23 38 WAR 6

08S 0.49 247 23 45 WAR 14 08S 0.48 248 23 51 WAR 6

08S 0.53 249 23 56 WAR 5

08S 0.45 250 23 59 WAR 8

08S 0.47 251 24 1

WAR 12 11S

-0.71 252 24 5

WAR 9

10S

-0.70 253 24 11 WAR 3

10S 0.39 254 24 41 WAR 8

08S 0.51 255 24 43 WAR 10 08S 0.46 256 24 44 WAR 15 08S 0.50 257 24 45 WAR 7

08S

-0.63 258 24 45 WAR 16 08S 0.46 259 24 49 WAR 4

08S

-0.67 260 24 49 WAR 5

08S 0.47 261 24 51 WAR 7

08S 0.47 262 25 1

WAR 11 10S

-0.73 263 25 36 WAR 10 08S 0.42 264 25 41 WAR 5

08S

-0.72 265 25 44 WAR 8

07S 0.47 266 25 52 WAR 13 08S 0.45 267 25 53 WAR 8

07S 0.47 268 25 53 WAR 6

08S 0.47 269 25 55 WAR 6

08S 0.50 270 25 72 WAR 7

08S 0.47 271 26 1

WAR 16 11S

-0.73 272 26 31 WAR 7

08S 0.48 273 26 33 WAR 5

08S 0.46 274 26 34 WAR 4

08S 0.48 275 26 39 WAR 14 06S 0.45 276 26 45 WAR 8

07S 0.47 277 26 46 WAR 8

07S 0.48 to 1CAN030907 Page 8 of 26 Item #

Row Tube Indication

% TW TSP Loc 278 26 46 WAR 11 08S 0.48 279 27 13 WAR 12 14S

-0.90 280 27 27 WAR 8

08S 0.48 281 27 34 WAR 5

07S 0.46 282 27 48 WAR 6

07S 0.51 283 27 48 WAR 6

08S 0.46 284 27 56 WAR 8

08S 0.50 285 27 67 WAR 7

08S 0.50 286 27 68 WAR 6

08S 0.53 287 28 42 WAR 9

08S 0.47 288 28 49 WAR 8

08S 0.48 289 28 62 WAR 6

08S 0.47 290 28 66 WAR 6

08S 0.50 291 28 67 WAR 5

08S 0.50 292 28 68 WAR 6

08S 0.53 293 28 78 WAR 7

08S 0.44 294 28 82 WAR 5

08S 0.41 295 29 67 WAR 9

07S

-0.50 296 30 32 WAR 5

08S 0.49 297 30 33 WAR 9

08S 0.47 298 30 34 WAR 6

08S 0.48 299 30 36 WAR 8

08S 0.48 300 30 77 WAR 5

08S 0.44 301 30 77 WAR 6

07S 0.47 302 30 79 WAR 5

08S 0.47 303 30 82 WAR 6

08S 0.41 304 31 2

WAR 13 10S

-0.70 305 31 23 WAR 4

08S 0.41 306 31 33 WAR 15 08S 0.49 307 31 33 WAR 8

10S

-0.75 308 31 34 WAR 13 08S 0.45 309 31 36 WAR 6

10S

-0.70 310 31 36 WAR 13 08S 0.45 311 31 37 WAR 14 08S 0.46 312 31 37 WAR 7

06S

-0.53 313 31 77 WAR 6

08S

-0.64 314 31 78 WAR 9

08S 0.42 315 31 79 WAR 6

08S 0.48 316 31 98 WAR 5

08S

-0.73 317 32 30 WAR 12 08S 0.49 to 1CAN030907 Page 9 of 26 Item #

Row Tube Indication

% TW TSP Loc 318 32 32 WAR 7

08S

-0.62 319 32 77 WAR 5

08S 0.45 320 32 100 WAR 10 10S 0.45 321 33 87 WAR 9

08S 0.50 322 33 88 WAR 5

07S 0.47 323 33 89 WAR 8

08S 0.47 324 34 85 WAR 7

08S 0.44 325 34 90 WAR 5

08S 0.50 326 36 37 WAR 5

07S 0.48 327 36 38 WAR 5

08S 0.45 328 36 40 WAR 5

08S 0.45 329 37 24 WAR 6

08S 0.50 330 37 27 WAR 5

08S 0.51 331 37 31 WAR 7

09S 0.41 332 37 31 WAR 10 08S 0.46 333 37 91 WAR 5

08S 0.50 334 37 93 WAR 7

08S

-0.66 335 37 114 WAR 9

11S

-0.67 336 38 1

WAR 11 10S 0.37 337 38 38 WAR 5

08S 0.39 338 38 39 WAR 7

08S 0.53 339 38 111 WAR 11 10S 0.46 340 38 115 WAR 6

10S

-0.64 341 39 25 WAR 7

08S 0.46 342 39 27 WAR 8

08S 0.46 343 39 28 WAR 5

08S 0.48 344 39 28 WAR 5

07S 0.48 345 40 31 WAR 6

08S 0.47 346 41 22 WAR 7

08S 0.47 347 41 23 WAR 3

09S

-0.70 348 41 25 WAR 4

08S

-0.74 349 41 113 WAR 11 10S 0.47 350 41 114 WAR 8

14S

-0.75 351 41 114 WAR 9

11S

-0.75 352 42 24 WAR 6

08S 0.44 353 42 25 WAR 5

08S 0.50 354 43 100 WAR 11 08S 0.50 355 44 1

WAR 7

10S 0.37 356 44 25 WAR 4

08S 0.54 357 45 29 WAR 6

08S 0.50 to 1CAN030907 Page 10 of 26 Item #

Row Tube Indication

% TW TSP Loc 358 45 114 WAR 11 09S

-0.67 359 45 115 WAR 5

10S 0.50 360 45 116 WAR 8

10S 0.42 361 46 2

WAR 7

10S 0.53 362 46 103 WAR 10 07S 0.47 363 46 114 WAR 9

14S

-0.77 364 46 115 WAR 9

10S 0.45 365 46 116 WAR 4

10S 0.48 366 47 2

WAR 7

10S 0.45 367 47 7

WAR 6

10S 0.14 368 47 111 WAR 9

09S

-0.65 369 47 114 WAR 8

10S 0.47 370 47 117 WAR 7

13S

-0.81 371 48 20 WAR 8

09S

-0.68 372 48 38 WAR 6

08S 0.47 373 48 113 WAR 9

09S

-0.64 374 48 115 WAR 6

14S 0.28 375 48 115 WAR 5

10S 0.48 376 48 116 WAR 11 13S

-0.81 377 48 121 WAR 11 11S 0.50 378 49 7

WAR 4

13S 0.27 379 49 20 WAR 7

08S 0.50 380 49 102 WAR 7

08S 0.47 381 49 113 WAR 10 09S 0.45 382 49 113 WAR 7

09S

-0.67 383 49 115 WAR 9

13S

-0.76 384 50 8

WAR 6

13S 0.26 385 50 20 WAR 6

08S 0.42 386 50 105 WAR 8

08S 0.50 387 50 113 WAR 6

09S

-0.64 388 51 120 WAR 7

10S 0.55 389 52 4

WAR 8

13S 0.24 390 52 4

WAR 12 10S

-0.65 391 52 114 WAR 6

13S

-0.70 392 52 120 WAR 11 13S

-0.70 393 52 121 WAR 15 13S

-0.69 394 52 121 WAR 7

10S 0.57 395 53 1

WAR 5

06S 0.49 396 53 117 WAR 11 10S 0.40 397 53 118 WAR 13 10S 0.45 to 1CAN030907 Page 11 of 26 Item #

Row Tube Indication

% TW TSP Loc 398 53 118 WAR 6

13S

-0.71 399 53 119 WAR 15 10S 0.45 400 53 120 WAR 9

10S 0.52 401 53 120 WAR 8

14S

-0.72 402 53 121 WAR 16 10S 0.51 403 53 122 WAR 9

10S 0.51 404 53 124 WAR 5

10S 0.54 405 54 22 WAR 5

08S 0.46 406 54 118 WAR 9

13S

-0.73 407 54 123 WAR 9

10S 0.50 408 54 123 WAR 13 11S 0.45 409 54 124 WAR 12 12S 0.41 410 54 125 WAR 8

12S 0.33 411 55 4

WAR 7

13S

-0.78 412 55 26 WAR 5

08S 0.48 413 55 116 WAR 12 13S

-0.75 414 55 124 WAR 7

09S 0.44 415 55 125 WAR 13 10S 0.54 416 56 25 WAR 5

08S 0.45 417 56 112 WAR 8

08S 0.50 418 56 125 WAR 5

10S 0.51 419 56 126 WAR 8

10S 0.51 420 56 127 WAR 8

12S

-0.72 421 57 17 WAR 7

08S 0.45 422 57 20 WAR 5

08S 0.48 423 57 22 WAR 5

08S 0.46 424 57 126 WAR 6

10S 0.39 425 57 127 WAR 8

10S 0.52 426 58 18 WAR 6

09S

-0.64 427 58 126 WAR 12 11S 0.47 428 58 127 WAR 7

10S 0.47 429 58 129 WAR 6

12S

-0.70 430 59 124 WAR 8

09S 0.47 431 59 125 WAR 10 11S 0.44 432 59 126 WAR 9

10S 0.48 433 59 127 WAR 9

10S 0.49 434 60 19 WAR 10 08S 0.45 435 60 125 WAR 14 11S 0.45 436 60 125 WAR 20 14S 0.37 437 60 127 WAR 9

10S 0.49 to 1CAN030907 Page 12 of 26 Item #

Row Tube Indication

% TW TSP Loc 438 61 125 WAR 5

09S 0.50 439 61 125 WAR 9

14S

-0.67 440 61 126 WAR 8

10S 0.46 441 61 127 WAR 13 10S 0.48 442 61 129 WAR 10 12S

-0.66 443 61 129 WAR 5

11S

-0.66 444 61 130 WAR 8

10S 0.49 445 62 5

WAR 8

14S

-0.81 446 62 110 WAR 10 08S 0.50 447 62 124 WAR 10 10S 0.48 448 63 4

WAR 20 11S 0.39 449 63 125 WAR 12 09S 0.48 450 63 126 WAR 9

10S 0.46 451 63 128 WAR 11 12S 0.36 452 63 129 WAR 11 12S 0.37 453 64 125 WAR 10 10S 0.45 454 64 129 WAR 12 10S 0.43 455 65 110 WAR 10 10S 0.45 456 65 114 WAR 6

08S 0.47 457 65 128 WAR 11 12S 0.37 458 66 109 WAR 6

08S 0.48 459 66 119 WAR 10 09S 0.45 460 67 1

WAR 32 11S 0.31 461 67 1

WAR 26 10S

-0.65 462 67 6

WAR 6

13S

-0.76 463 67 125 WAR 8

09S

-0.67 464 67 129 WAR 6

10S 0.45 465 67 130 WAR 11 12S 0.39 466 67 130 WAR 7

13S

-0.84 467 68 7

WAR 20 14S 0.19 468 68 111 WAR 7

08S 0.53 469 68 113 WAR 9

08S 0.53 470 68 114 WAR 6

08S 0.50 471 68 117 WAR 12 09S 0.47 472 68 124 WAR 7

09S 0.47 473 68 126 WAR 5

09S

-0.67 474 68 130 WAR 7

12S 0.37 475 68 131 WAR 9

10S

-0.66 476 68 131 WAR 10 10S 0.46 477 69 114 WAR 10 08S 0.50 to 1CAN030907 Page 13 of 26 Item #

Row Tube Indication

% TW TSP Loc 478 70 6

WAR 8

13S 0.31 479 70 20 WAR 7

08S 0.47 480 70 114 WAR 5

08S 0.53 481 70 124 WAR 8

09S 0.44 482 70 130 WAR 9

12S 0.28 483 70 131 WAR 5

09S

-0.63 484 71 1

WAR 5

12S

-0.78 485 71 116 WAR 7

08S 0.50 486 71 121 WAR 8

09S 0.45 487 71 132 WAR 8

10S

-0.73 488 72 128 WAR 8

12S 0.37 489 72 131 WAR 12 12S 0.25 490 72 131 WAR 11 11S 0.38 491 72 131 WAR 8

10S

-0.73 492 72 131 WAR 6

09S

-0.65 493 73 120 WAR 12 09S 0.45 494 73 126 WAR 8

09S

-0.64 495 73 127 WAR 7

09S

-0.70 496 73 131 WAR 14 09S

-0.63 497 73 132 WAR 7

12S 0.35 498 73 132 WAR 25 10S

-0.73 499 73 132 WAR 7

08S

-0.67 500 73 132 WAR 4

08S 0.48 501 74 114 WAR 9

08S 0.50 502 74 117 WAR 10 09S

-0.67 503 74 124 WAR 13 13S

-0.78 504 74 127 WAR 10 12S 0.34 505 74 128 WAR 6

09S

-0.63 506 74 131 WAR 11 12S 0.28 507 75 5

WAR 9

10S

-0.06 508 75 25 WAR 6

08S 0.50 509 75 126 WAR 4

09S 0.47 510 75 126 WAR 6

09S

-0.64 511 75 127 WAR 12 13S

-0.74 512 75 129 WAR 7

12S 0.36 513 75 131 WAR 8

11S 0.39 514 75 132 WAR 8

12S 0.38 515 76 4

WAR 5

10S

-0.06 516 76 124 WAR 8

14S 0.31 517 77 1

WAR 15 11S

-0.72 to 1CAN030907 Page 14 of 26 Item #

Row Tube Indication

% TW TSP Loc 518 77 18 WAR 4

08S 0.45 519 77 126 WAR 4

09S 0.45 520 77 126 WAR 7

09S

-0.67 521 77 127 WAR 6

09S

-0.67 522 77 132 WAR 14 09S

-0.67 523 79 126 WAR 5

09S 0.47 524 79 126 WAR 6

09S

-0.58 525 80 4

WAR 13 10S 0.00 526 80 114 WAR 7

08S 0.50 527 80 115 WAR 9

08S 0.56 528 80 126 WAR 6

09S

-0.67 529 81 5

WAR 5

10S 0.14 530 81 6

WAR 5

14S 0.25 531 81 113 WAR 8

08S 0.48 532 81 113 WAR 7

07S

-0.59 533 81 132 WAR 8

09S

-0.71 534 82 4

WAR 13 10S 0.03 535 82 22 WAR 6

08S 0.47 536 82 112 WAR 4

08S 0.50 537 82 115 WAR 7

08S 0.50 538 82 116 WAR 7

08S 0.53 539 82 126 WAR 7

09S 0.47 540 82 131 WAR 5

12S

-0.79 541 83 4

WAR 9

10S 0.00 542 83 5

WAR 8

10S 0.14 543 83 23 WAR 4

08S 0.53 544 83 25 WAR 4

08S 0.50 545 83 127 WAR 6

09S

-0.64 546 84 4

WAR 10 10S 0.11 547 84 112 WAR 6

08S 0.53 548 84 126 WAR 5

09S 0.44 549 85 29 WAR 4

08S 0.53 550 85 111 WAR 6

08S 0.53 551 85 125 WAR 15 14S 0.28 552 85 125 WAR 10 09S

-0.64 553 85 129 WAR 9

09S

-0.73 554 85 129 WAR 11 07S

-0.61 555 86 4

WAR 7

10S 0.14 556 86 20 WAR 4

08S 0.45 557 86 20 WAR 4

08S

-0.70 to 1CAN030907 Page 15 of 26 Item #

Row Tube Indication

% TW TSP Loc 558 86 25 WAR 6

08S 0.50 559 86 109 WAR 4

08S 0.50 560 87 3

WAR 11 10S 0.17 561 87 25 WAR 5

08S 0.52 562 87 28 WAR 4

08S 0.50 563 88 4

WAR 7

10S 0.11 564 88 110 WAR 7

08S 0.50 565 88 112 WAR 7

08S 0.48 566 88 122 WAR 7

09S 0.44 567 89 111 WAR 7

08S 0.50 568 89 126 WAR 10 14S 0.31 569 90 109 WAR 5

08S 0.45 570 90 124 WAR 7

14S 0.28 571 91 110 WAR 5

08S 0.48 572 91 111 WAR 10 08S 0.50 573 91 112 WAR 6

08S 0.50 574 91 126 WAR 6

14S 0.31 575 92 24 WAR 5

08S

-0.72 576 92 112 WAR 10 08S 0.50 577 92 129 WAR 9

12S

-0.67 578 93 21 WAR 5

08S 0.53 579 93 23 WAR 6

08S 0.47 580 93 111 WAR 5

08S 0.50 581 93 125 WAR 5

09S 0.45 582 93 125 WAR 10 14S 0.31 583 93 128 WAR 10 12S

-0.75 584 94 109 WAR 7

08S 0.50 585 94 111 WAR 7

08S 0.48 586 94 112 WAR 8

08S 0.47 587 94 115 WAR 7

09S 0.45 588 94 126 WAR 4

09S 0.45 589 95 107 WAR 7

08S 0.51 590 95 108 WAR 5

08S 0.50 591 95 111 WAR 5

08S 0.51 592 95 112 WAR 8

08S 0.48 593 95 117 WAR 6

09S 0.37 594 96 109 WAR 8

08S 0.50 595 96 110 WAR 5

08S 0.51 596 96 111 WAR 6

08S 0.50 597 96 114 WAR 5

09S 0.37 to 1CAN030907 Page 16 of 26 Item #

Row Tube Indication

% TW TSP Loc 598 96 116 WAR 6

09S 0.42 599 96 118 WAR 8

09S 0.45 600 96 124 WAR 9

14S 0.31 601 97 22 WAR 6

08S 0.50 602 97 23 WAR 6

08S 0.50 603 97 26 WAR 6

08S 0.53 604 97 109 WAR 8

08S 0.50 605 97 116 WAR 10 09S 0.42 606 97 116 WAR 6

09S

-0.65 607 97 119 WAR 7

09S 0.45 608 97 124 WAR 10 14S 0.34 609 98 107 WAR 7

08S 0.53 610 98 109 WAR 7

08S 0.45 611 98 109 WAR 7

08S

-0.64 612 98 110 WAR 5

08S 0.50 613 98 117 WAR 7

09S 0.47 614 98 117 WAR 10 11S

-0.62 615 98 118 WAR 8

11S

-0.75 616 98 120 WAR 8

11S

-0.63 617 98 122 WAR 10 14S 0.28 618 98 124 WAR 4

10S 0.20 619 99 105 WAR 6

08S 0.48 620 99 107 WAR 5

08S

-0.70 621 99 115 WAR 8

09S 0.42 622 99 116 WAR 10 11S

-0.73 623 99 116 WAR 5

13S

-0.76 624 99 124 WAR 6

12S 0.36 625 99 124 WAR 11 13S 0.39 626 100 3

WAR 11 10S 0.28 627 100 7

WAR 9

10S 0.08 628 100 21 WAR 6

08S 0.50 629 100 108 WAR 6

08S 0.50 630 100 114 WAR 10 09S 0.42 631 100 115 WAR 10 09S 0.46 632 100 115 WAR 10 11S

-0.73 633 100 118 WAR 7

14S 0.34 634 100 123 WAR 10 12S 0.31 635 101 20 WAR 8

08S 0.47 636 101 23 WAR 6

08S 0.50 637 101 104 WAR 5

08S 0.53 to 1CAN030907 Page 17 of 26 Item #

Row Tube Indication

% TW TSP Loc 638 101 106 WAR 5

08S 0.51 639 101 112 WAR 14 11S

-0.65 640 101 117 WAR 6

14S 0.31 641 101 120 WAR 11 13S 0.31 642 101 120 WAR 11 12S 0.42 643 102 7

WAR 9

10S 0.08 644 102 105 WAR 4

08S 0.51 645 102 113 WAR 9

11S

-0.73 646 103 110 WAR 6

08S 0.48 647 103 113 WAR 6

09S

-0.64 648 104 99 WAR 7

10S 0.42 649 104 104 WAR 6

08S 0.51 650 104 105 WAR 6

08S 0.48 651 104 106 WAR 5

08S 0.48 652 104 108 WAR 6

08S 0.45 653 104 112 WAR 4

09S 0.42 654 104 113 WAR 9

11S

-0.73 655 104 114 WAR 4

11S

-0.70 656 104 118 WAR 6

14S 0.26 657 105 29 WAR 5

08S 0.53 658 105 104 WAR 6

08S 0.47 659 105 106 WAR 6

08S 0.45 660 105 115 WAR 6

10S 0.31 661 106 102 WAR 5

08S 0.53 662 106 106 WAR 8

08S 0.48 663 106 114 WAR 5

14S 0.17 664 107 100 WAR 5

08S 0.51 665 107 101 WAR 7

08S 0.50 666 107 102 WAR 6

08S 0.48 667 107 104 WAR 5

08S 0.48 668 107 113 WAR 9

11S 0.39 669 107 114 WAR 6

14S 0.37 670 107 117 WAR 7

11S

-0.76 671 107 117 WAR 8

11S 0.37 672 108 2

WAR 8

10S 0.14 673 109 23 WAR 7

08S 0.47 674 109 26 WAR 5

08S 0.50 675 109 98 WAR 5

08S 0.50 676 109 99 WAR 5

08S 0.53 677 110 22 WAR 7

08S 0.47 to 1CAN030907 Page 18 of 26 Item #

Row Tube Indication

% TW TSP Loc 678 110 24 WAR 6

08S 0.50 679 110 25 WAR 9

08S 0.50 680 110 106 WAR 6

09S 0.42 681 110 109 WAR 9

14S 0.34 682 111 19 WAR 8

08S 0.45 683 111 98 WAR 8

08S 0.45 684 112 28 WAR 8

08S 0.50 685 112 98 WAR 6

08S 0.51 686 113 1

WAR 15 12S

-0.66 687 113 24 WAR 5

08S 0.44 688 113 95 WAR 6

08S 0.51 689 113 96 WAR 6

08S 0.48 690 114 22 WAR 5

08S 0.47 691 114 110 WAR 8

11S

-0.68 692 114 115 WAR 7

13S 0.22 693 115 23 WAR 5

08S

-0.64 694 115 93 WAR 8

08S 0.49 695 115 95 WAR 7

08S 0.39 696 115 97 WAR 7

08S 0.48 697 116 27 WAR 11 08S 0.47 698 116 113 WAR 21 10S 0.28 699 116 113 WAR 13 11S 0.34 700 117 112 WAR 10 11S 0.36 701 117 112 WAR 7

11S

-0.73 702 117 112 WAR 17 10S

-0.62 703 118 28 WAR 7

08S 0.48 704 118 106 WAR 9

11S

-0.76 705 118 111 WAR 10 11S 0.39 706 118 111 WAR 12 13S 0.36 707 118 111 WAR 7

13S

-0.70 708 118 111 WAR 9

10S

-0.80 709 119 26 WAR 5

08S

-0.64 710 119 86 WAR 19 08S

-0.57 711 119 86 WAR 15 08S 0.49 712 119 87 WAR 6

08S 0.48 713 119 87 WAR 5

08S

-0.64 714 120 22 WAR 6

08S 0.50 715 120 30 WAR 5

08S 0.50 716 120 50 WAR 5

08S 0.56 717 120 100 WAR 5

11S

-0.70 to 1CAN030907 Page 19 of 26 Item #

Row Tube Indication

% TW TSP Loc 718 120 104 WAR 9

11S 0.36 719 121 106 WAR 9

11S 0.37 720 122 99 WAR 6

09S

-0.65 721 122 104 WAR 10 12S

-0.68 722 122 104 WAR 6

12S 0.30 723 122 104 WAR 9

11S 0.39 724 122 105 WAR 24 11S 0.29 725 122 105 WAR 14 10S

-0.70 726 122 105 WAR 20 12S

-0.71 727 123 21 WAR 4

08S 0.50 728 123 31 WAR 5

08S 0.50 729 123 31 WAR 5

08S

-0.64 730 123 88 WAR 6

09S 0.45 731 123 98 WAR 10 09S

-0.64 732 124 1

WAR 11 12S

-0.72 733 124 30 WAR 7

08S 0.50 734 124 32 WAR 5

08S 0.47 735 124 40 WAR 6

08S 0.53 736 124 98 WAR 4

11S

-0.78 737 124 102 WAR 7

12S

-0.68 738 124 102 WAR 10 12S 0.40 739 124 103 WAR 16 10S

-0.70 740 125 1

WAR 5

11S

-0.77 741 125 1

WAR 8

12S

-0.75 742 125 1

WAR 10 12S 0.36 743 125 31 WAR 10 08S 0.47 744 125 68 WAR 7

08S 0.48 745 125 70 WAR 8

08S 0.48 746 125 86 WAR 10 08S 0.44 747 125 86 WAR 6

08S

-0.61 748 125 96 WAR 5

09S

-0.63 749 125 101 WAR 13 12S 0.25 750 126 1

WAR 10 12S

-0.77 751 126 1

WAR 12 12S 0.36 752 126 40 WAR 5

08S 0.50 753 126 73 WAR 5

08S 0.48 754 126 76 WAR 9

08S 0.48 755 126 76 WAR 7

08S

-0.64 756 126 99 WAR 9

12S 0.37 757 127 1

WAR 12 12S

-0.72 to 1CAN030907 Page 20 of 26 Item #

Row Tube Indication

% TW TSP Loc 758 127 69 WAR 8

08S 0.51 759 127 75 WAR 7

08S 0.48 760 127 93 WAR 11 11S

-0.72 761 127 97 WAR 11 12S

-0.69 762 127 97 WAR 8

11S

-0.75 763 127 98 WAR 18 11S 0.27 764 127 98 WAR 6

07S 0.41 765 127 98 WAR 12 12S 0.38 766 127 98 WAR 7

12S

-0.76 767 128 28 WAR 5

07S 0.50 768 128 28 WAR 5

08S 0.47 769 128 64 WAR 6

08S 0.47 770 128 70 WAR 5

08S 0.45 771 128 87 WAR 7

11S

-0.75 772 128 91 WAR 7

12S 0.38 773 128 91 WAR 10 12S

-0.74 774 129 28 WAR 6

08S 0.48 775 129 29 WAR 7

08S 0.50 776 129 83 WAR 9

09S 0.42 777 129 90 WAR 7

14S 0.25 778 129 93 WAR 6

12S 0.35 779 129 94 WAR 13 12S 0.35 780 130 32 WAR 11 08S 0.50 781 130 34 WAR 7

10S

-0.72 782 130 38 WAR 10 08S 0.44 783 130 38 WAR 7

06S 0.49 784 130 41 WAR 6

08S 0.50 785 130 48 WAR 6

08S 0.50 786 130 49 WAR 5

08S 0.45 787 130 86 WAR 7

12S 0.33 788 130 92 WAR 10 12S

-0.66 789 130 92 WAR 8

10S

-0.75 790 130 93 WAR 13 11S 0.37 791 131 59 WAR 7

08S 0.48 792 131 82 WAR 5

09S

-0.63 793 131 83 WAR 9

09S 0.45 794 131 86 WAR 7

12S 0.39 795 131 87 WAR 9

12S 0.33 796 131 90 WAR 12 12S

-0.71 797 132 38 WAR 12 08S 0.50 to 1CAN030907 Page 21 of 26 Item #

Row Tube Indication

% TW TSP Loc 798 132 82 WAR 7

11S

-0.62 799 132 82 WAR 11 09S 0.44 800 132 83 WAR 5

10S 0.25 801 132 88 WAR 7

13S 0.25 802 132 88 WAR 8

13S

-0.70 803 132 88 WAR 7

12S 0.31 804 132 88 WAR 11 11S

-0.78 805 132 89 WAR 12 11S 0.39 806 132 89 WAR 21 10S

-0.68 807 132 89 WAR 9

12S

-0.71 808 133 80 WAR 10 14S 0.28 809 133 84 WAR 7

12S

-0.72 810 133 86 WAR 8

11S 0.33 811 133 86 WAR 5

12S

-0.78 812 133 87 WAR 8

13S 0.33 813 133 87 WAR 12 12S

-0.61 814 133 88 WAR 13 12S

-0.69 815 133 88 WAR 9

11S 0.39 816 134 1

WAR 5

12S 0.45 817 134 79 WAR 15 13S 0.34 818 134 84 WAR 14 10S

-0.68 819 134 84 WAR 11 11S

-0.76 820 134 84 WAR 9

08S 0.44 821 134 84 WAR 19 12S

-0.71 822 134 85 WAR 12 12S

-0.69 823 134 85 WAR 13 10S

-0.70 824 135 78 WAR 13 14S 0.28 825 135 82 WAR 17 12S 0.33 826 135 82 WAR 9

12S

-0.67 827 135 82 WAR 13 11S

-0.74 828 135 83 WAR 8

13S 0.38 829 135 83 WAR 12 13S

-0.65 830 135 83 WAR 7

11S

-0.79 831 135 83 WAR 9

11S 0.37 832 135 83 WAR 10 12S

-0.64 833 135 84 WAR 10 12S

-0.69 834 135 84 WAR 10 13S

-0.65 835 136 7

WAR 13 13S 0.36 836 136 76 WAR 6

14S 0.25 837 136 77 WAR 8

13S 0.39 to 1CAN030907 Page 22 of 26 Item #

Row Tube Indication

% TW TSP Loc 838 136 77 WAR 11 12S 0.45 839 136 79 WAR 8

13S

-0.74 840 136 80 WAR 10 12S

-0.69 841 136 81 WAR 14 12S

-0.69 842 136 81 WAR 13 13S 0.35 843 136 81 WAR 13 10S

-0.68 844 136 81 WAR 17 11S 0.32 845 136 81 WAR 10 13S

-0.68 846 136 81 WAR 9

11S

-0.76 847 137 1

WAR 7

12S 0.36 848 137 8

WAR 5

11S

-0.70 849 137 8

WAR 7

12S 0.33 850 137 65 WAR 8

09S

-0.64 851 137 69 WAR 9

11S

-0.68 852 137 77 WAR 8

13S

-0.70 853 137 77 WAR 8

10S

-0.71 854 137 78 WAR 9

12S

-0.79 855 137 79 WAR 15 13S

-0.70 856 137 80 WAR 6

11S 0.37 857 138 62 WAR 10 11S

-0.73 858 138 69 WAR 11 11S

-0.73 859 138 75 WAR 9

12S

-0.75 860 138 76 WAR 9

12S

-0.67 861 138 76 WAR 9

13S

-0.66 862 138 77 WAR 7

11S 0.35 863 139 7

WAR 5

10S

-0.78 864 139 57 WAR 6

09S

-0.53 865 139 64 WAR 9

12S 0.42 866 139 64 WAR 9

12S

-0.70 867 139 68 WAR 9

11S

-0.76 868 139 72 WAR 8

12S

-0.72 869 139 72 WAR 13 12S 0.38 870 139 74 WAR 7

12S 0.44 871 139 74 WAR 16 12S

-0.69 872 140 10 WAR 13 15S 0.23 873 140 12 WAR 7

15S 0.22 874 140 55 WAR 12 13S 0.28 875 140 56 WAR 10 12S 0.36 876 140 56 WAR 10 11S

-0.70 877 140 59 WAR 12 13S

-0.69 to 1CAN030907 Page 23 of 26 Item #

Row Tube Indication

% TW TSP Loc 878 140 65 WAR 7

14S 0.23 879 140 69 WAR 13 12S

-0.67 880 141 9

WAR 14 15S 0.26 881 141 10 WAR 10 15S 0.28 882 141 12 WAR 7

15S

-0.87 883 141 14 WAR 6

12S 0.37 884 141 16 WAR 7

14S

-0.73 885 141 55 WAR 8

11S

-0.74 886 141 56 WAR 6

10S 0.17 887 141 58 WAR 10 13S

-0.74 888 141 58 WAR 7

14S

-0.74 889 141 59 WAR 10 13S

-0.75 890 141 60 WAR 7

14S 0.31 891 141 61 WAR 9

14S 0.28 892 141 61 WAR 9

13S

-0.63 893 141 62 WAR 6

14S 0.23 894 141 62 WAR 9

13S

-0.68 895 141 63 WAR 12 13S

-0.70 896 141 63 WAR 8

14S 0.37 897 141 64 WAR 5

12S 0.42 898 141 68 WAR 11 12S

-0.70 899 142 23 WAR 9

14S

-0.73 900 142 53 WAR 10 11S

-0.67 901 142 54 WAR 6

10S 0.22 902 142 64 WAR 9

12S

-0.67 903 142 64 WAR 19 12S 0.38 904 142 64 WAR 6

11S

-0.70 905 142 65 WAR 11 10S

-0.69 906 142 65 WAR 9

11S

-0.80 907 143 7

WAR 9

13S

-0.68 908 143 12 WAR 7

13S 0.31 909 143 13 WAR 6

13S 0.36 910 143 21 WAR 10 14S

-0.76 911 143 56 WAR 8

13S 0.36 912 143 56 WAR 7

13S

-0.69 913 144 9

WAR 7

15S

-0.81 914 144 38 WAR 5

09S

-0.64 915 144 40 WAR 15 09S

-0.62 916 144 48 WAR 14 13S

-0.69 917 144 52 WAR 14 13S

-0.64 to 1CAN030907 Page 24 of 26 Item #

Row Tube Indication

% TW TSP Loc 918 144 52 WAR 7

13S 0.41 919 145 15 WAR 7

10S

-0.73 920 145 16 WAR 6

11S

-0.72 921 145 33 WAR 8

13S 0.28 922 145 47 WAR 6

14S

-0.80 923 145 47 WAR 11 13S

-0.69 924 146 1

WAR 8

11S

-0.70 925 146 7

WAR 7

12S

-0.70 926 146 12 WAR 9

12S 0.42 927 146 20 WAR 5

10S 0.00 928 146 24 WAR 9

11S

-0.75 929 146 25 WAR 12 11S

-0.63 930 146 32 WAR 9

10S 0.08 931 146 33 WAR 7

10S 0.08 932 146 37 WAR 5

10S 0.08 933 146 40 WAR 7

11S

-0.70 934 146 44 WAR 8

10S 0.05 935 147 21 WAR 6

14S

-0.81 936 147 26 WAR 6

11S

-0.70 937 147 26 WAR 7

13S

-0.70 938 147 27 WAR 8

10S 0.08 939 147 28 WAR 5

10S 0.00 940 147 29 WAR 8

10S 0.08 941 147 41 WAR 9

13S 0.36 942 147 42 WAR 6

14S 0.21 943 147 42 WAR 7

11S

-0.73 944 148 23 WAR 6

12S 0.39 945 148 25 WAR 9

10S 0.06 946 148 26 WAR 7

12S 0.39 947 148 26 WAR 5

10S 0.11 948 148 32 WAR 5

13S 0.36 949 149 6

WAR 13 12S

-0.69 950 149 9

WAR 7

12S

-0.70 951 149 17 WAR 6

13S 0.40 952 149 31 WAR 7

11S

-0.70 953 150 5

WAR 17 12S

-0.69 954 150 5

WAR 7

13S

-0.70 955 150 6

WAR 12 12S

-0.67 956 150 6

WAR 6

13S

-0.64 957 150 7

WAR 13 12S

-0.70 to 1CAN030907 Page 25 of 26 Item #

Row Tube Indication

% TW TSP Loc 958 150 7

WAR 11 10S 0.42 959 150 8

WAR 6

12S

-0.69 960 150 9

WAR 9

12S 0.42 961 150 9

WAR 10 12S

-0.69 962 150 10 WAR 6

13S

-0.70 963 150 12 WAR 9

10S

-0.70 964 150 16 WAR 6

12S 0.39 965 150 16 WAR 11 10S

-0.69 966 150 20 WAR 8

12S 0.34 967 150 20 WAR 13 12S

-0.67 968 150 21 WAR 11 12S 0.32 969 150 22 WAR 7

11S

-0.67 970 150 23 WAR 12 11S

-0.73 971 150 23 WAR 9

12S 0.39 972 150 24 WAR 9

12S

-0.67 973 150 24 WAR 11 11S

-0.73 974 150 25 WAR 10 13S

-0.64 975 150 25 WAR 11 13S 0.34 976 150 25 WAR 15 12S 0.39 977 150 25 WAR 9

11S

-0.74 978 150 26 WAR 9

13S

-0.71 979 150 26 WAR 10 13S 0.34 980 150 26 WAR 10 11S

-0.74 981 150 26 WAR 18 12S 0.36 982 150 27 WAR 23 12S 0.31 983 150 27 WAR 19 11S

-0.67 984 150 27 WAR 10 12S

-0.68 985 150 29 WAR 9

13S

-0.70 986 150 30 WAR 11 12S 0.36 987 150 30 WAR 9

12S

-0.70 988 151 1

WAR 13 12S

-0.69 989 151 1

WAR 8

10S 0.45 990 151 2

WAR 21 12S

-0.69 991 151 2

WAR 10 12S 0.39 992 151 2

WAR 9

11S

-0.67 993 151 3

WAR 8

13S

-0.71 994 151 3

WAR 17 12S

-0.64 995 151 4

WAR 22 11S 0.39 996 151 4

WAR 19 10S 0.44 997 151 5

WAR 16 12S

-0.67 to 1CAN030907 Page 26 of 26 Item #

Row Tube Indication

% TW TSP Loc 998 151 5

WAR 15 10S 0.47 999 151 6

WAR 9

10S 0.47 1000 151 6

WAR 11 12S

-0.64 1001 151 7

WAR 5

13S 0.31 1002 151 8

WAR 9

10S 0.44 1003 151 8

WAR 12 11S

-0.71 1004 151 8

WAR 12 12S

-0.72 1005 151 9

WAR 12 10S

-0.65 1006 151 9

WAR 10 13S 0.35 1007 151 12 WAR 10 12S

-0.69 1008 151 12 WAR 9

12S 0.32 1009 151 15 WAR 13 11S

-0.70 1010 151 15 WAR 8

11S 0.39 1011 151 15 WAR 5

13S

-0.71 1012 151 15 WAR 7

13S 0.30 1013 151 15 WAR 17 12S

-0.68 1014 151 15 WAR 24 12S 0.32 1015 151 16 WAR 10 13S 0.35 1016 151 16 WAR 10 11S

-0.63 1017 151 16 WAR 13 12S

-0.66 1018 151 16 WAR 8

13S

-0.71 1019 151 16 WAR 8

12S 0.39 1020 151 17 WAR 9

12S

-0.73 1021 151 17 WAR 11 11S

-0.70 1022 151 17 WAR 11 13S

-0.61 1023 151 17 WAR 9

13S 0.34 1024 151 18 WAR 9

11S

-0.70 1025 151 19 WAR 19 11S

-0.70 1026 151 19 WAR 9

12S

-0.68 1027 151 19 WAR 16 12S 0.32 1028 151 21 WAR 18 12S

-0.71 1029 151 24 WAR 10 12S 0.42