Table 3.1 Reactor Control and Safety Systems Set-Point Specifications.
SAFETY CHANNEL SET POINT FUNCTION Nuclear Safety Channel No. 1 Unit A) 5% of Full Scale Scram at levels (Startup Count Rate Channel) OR below the set points Low Power Unit B) 0.5 counts/second Nuclear Safety Channel No. 2 6 watts Scram at power (Log Power Channel)
(120% of licensed power) > 6 watts High Power Nuclear Safety Channel No. 2 Scram at source levels (Log Power Channel) 3.0 x 10-13 amperes
< 3 x 10-13 amperes Low Power Scram at periods Reactor Period 5 seconds
< 5 seconds Nuclear Safety Channel No. 3 6 watts Scram at power (Linear Power Channel)
(120% of licensed power) > 6 watts High Power Nuclear Safety Channel No. 3 Scram at levels (Linear Power Channel) 5% Full Scale
< 5% of Full Scale Low Power Manual Scram ----- Scram at operator option Alarm at or below level Area Radiation Monitor # 10 mR/hr set to meet requirements of 10 CFR 20 Unit A is the original AGN console Unit B is the ISU all solid state electronic control console Either Unit A or Unit B will be in service any time the reactor is operating 3.3 Limitations on Experiments Applicability This specification applies to experiments installed in the reactor and its experimental facilities.
Objective To prevent damage to the reactor or excessive release of radioactive materials in the event of an experiment failure.
Specification
- a. Experiments containing materials corrosive to reactor components or which contain liquid or gaseous, fissionable materials shall be doubly encapsulated.
- b. Explosive materials shall not be inserted into experimental facilities or the reactor or stored within the confines of the reactor facility.
AGN-201 Technical Specifications, Amendment No. 7 Page 11 of 31