VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 January 5, 2009 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 Serial No.:
NAPS/JHL:
Docket No.:
License No.:
08-0763 RO 50-339 NPF-7 VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
NORTH ANNA POWER STATION UNIT 2 OWNER'S ACTIVITY REPORT In accordance with the reporting requirements of American Society of Mechanical Engineers (ASME) Code Case N-532-4, Dominion is submitting the Owner's Activity Report (Form OAR-i), for refueling outage (N2R1 9).
Should you have any questions regarding this submittal, please contact Mr. Page Kemp at (540) 894-2295.
Very truly yours, E. S. Hendrixson Director - Nuclear Station Safety and Licensing Commitments made in this letter: None Attachments 407 MiZA
cc:
U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW Suite 23 T85 Atlanta, Georgia 30303 NRC Senior Resident Inspector North Anna Power Station Mr. J. E. Reasor, Jr. (letter only)
Old Dominion Electric Cooperative Innsbrook Corporate Center 4201 Dominion Blvd.
Suite 300 Glen Allen, Virginia 23060 Mr. J. F. Stang, Jr.
NRC Project Manager U. S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Mail Stop 0-8G9A Rockville, MD 20852 Mr. M. M. Grace Authorized Nuclear Insurance Inspector North Anna Power Station
Serial No. 08-0763 Docket No. 50-339 ATTACHMENT 1 OWNERS ACTIVITY REPORT NORTH ANNA UNIT 2 FALL 2008 REFUELING OUTAGE (N2R19)
VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION
Sl~em, Form OAR-1 Owner's Activity Report Wftminion" I ~ ~ ~
~
~
~
~
~
Atahet1 RASS-0 ae1o Report Number:
N2R19 (Unit 2, 3rd Interval, 3 rd Period)
Plant North Anna Power Station Unit No.
2 Commercial service date 12/14/1980 Refueling outage no. N2R19 (if applicable)
Current inspection interval 3P (December 14, 2001 - December 13, 2010)
(1st, 2 n, 3r, 4tt, other)
Current inspection period 3 rd (June 14, 2008 - December.13, 2010)
(151, 2 hn, 3 rd)
Edition and Addenda of Section XI applicable to the inspection plans 1995 Edition with 1996 Addenda Date and revision of inspection plans April 2008, Revision 9 Edition and Addenda of Section XI applicable to repair/replacement activities, if different than the inspection plans Code Cases used:
N-323-1, N416-3, N-460, N-491-2, N-498-4, N-508-3, N-522, N-532-4, N-533-1, N-546, N-566-2, N-568, N-598, N-616, N-652-1, N-663, N-685, N-686, N-700 and N-706 (if applicable)
CERTIFICATE OF CONFORMANCE I certify that (a) the statements made in this report are correct; (b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI; and (c) the repair/replacement activities and evaluations supporting the completion of N2R19 conform to the requirements of Section XI.
(refueling outage number)
Signed qt k
"fl.'~/*!ý**
l*/**
Date
/.qO Oner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Virginia and employed by HSB CT of Hartford, CT have inspected the items described in this Owner's Activity Report, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair/replacement activities and evaluation described in this report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with t>inspection.
c w tisec Commissions VA 424-R Inspector's Signature National Board, State, Province and Endorsements Date
- 1..
2-11aominioW Form OAR-1 Owner's Activity Report
]
I Atahmn 1,.
ERA0S-0 Pg f7 Table I Items with Flaws or Relevant Conditions That Required Evaluation for Continued Service Examination Item Description Evaluation Description Category and Item Number Restraint 2-CH-R-265 on line 3"CH-Clearances on support were F-A / F 1.20A 481-1502-Q2 observed to be different than previously evaluated. Engineering Mechanics determined that the clearances were acceptable based on
.the previous evaluation performed.
Reference Engineering Evaluation 2008-002.
_V.
Fwýorm OAR-1 Owner's Activity Report Wftminion" 1V*
Atah
- ent, ER-AA-ISI-0 IPage 3] of 3 Table 2 Abstract of Repair/Replacement Activities Required for Continued Service Code Class Item Description Description of Work Date Repair/Replacement Completed Plan Number 2
Snubber Replaced snubber 11/17/08 2008-134 2-MS-HSS-562.02 2
Snubber Replaced snubber 10/2/08 2008-108 2-RH-HSS-100A 2
Snubber Replaced snubber 10/2/08 2008-103 2-SI-HSS-502 2
Snubber Replaced snubber 10/28/08 2008-102 2-SI-HSS-807B 2
Snubber Replaced snubber 12/4/08 2008-101 2-SI-HSS-800 2
Snubber Replaced snubber 10/2/08 2008-090 2-CH-HSS-401.09 2