Issue date: 07/16/2008
From: Medenciy C
Wolf Creek
To: Tam Tran
Office of Nuclear Reactor Regulation
References
Download: ML082110422 (1)


Text

From:

Medenciy Charlie M [chmeden@WCNOC.com]

Sent:

Wednesday, July 16, 2008 1:37 PM To:

Tam Tran

Subject:

Electrical Control Circuits Mr. Tran, On July 15, 2008, you requested that Wolf Creek Generating Station (WCGS) confirm that scoping for equipment relied on to meet the Station Blackout Rule for License Renewal included :

1) switchyard circuit breakers that connect to offsite system transformers,
2) the startup transformer, 3)the intervening overhead or underground circuits between circuit breaker and transformer and transformer and on site electrical system, and
4) the associated control circuits and structures.

As explained during the teleconference, the associated control circuits and structures along with all the other components listed are included in the scoping and subject to the applicable aging management program. For additional clarification of the components please refer to WCGS submittal ET 08-0022, dated March 29, 2008.

If you have any questions concerning this matter, please contact me at (620) 364-8831 x 4842, or Lorrie Bell at (620) 364-8831 x 4573.

Sincerely, Charles Medenciy Licensing Engineer Wolf Creek Generating Station Email scanned by DoubleCheck http://www.nmgi.com/doublecheck/

E-mail Properties Mail Envelope Properties (3B1E4069EF8A1B40B2C87403A57C61FA0119F110)

Subject:

Electrical Control Circuits Sent Date: 7/16/2008 1:37:34 PM Received Date: 7/16/2008 1:37:34 PM From: Medenciy Charlie M

Created By: chmeden@WCNOC.com Recipients:

Tam.Tran@nrc.gov (Tam Tran)

Tracking Status: None Post Office:

wc-email.wcnoc.com Files Size Date & Time MESSAGE 11791 7/16/2008 Options Expiration Date:

Priority: olImportanceNormal ReplyRequested: False Return Notification: False Sensitivity: olNormal Recipients received: