RPS Instrumentation 3.3.1.1 Table 3.3.1.1-1 (page 3 of 3).

Reactor Protection System Instrumentation APPLICABLE CONDITIONS MODES OR REQUIRED REFERENCED OTHER CHANNELS FROM SPECIFIED PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION D.1 REQUIREMENTS VALUE

8. Scram Discharge Volume Water Level-High (continued)
b. Float Switch 1,2 H SR 3.3.1.1.12 < 763 ft. 3-1/4 I SR 3.3.1.1.13 inches msl for SR 3.3.1.1.15 1Cl-NO13A,B and 5 763 ft.

1-11/16 inches msl for lC1-N013C,D (a) 4 I SR 3.3.1.1.12 5 < 763 ft. 3-1/4 SR 3.3.1.1.13 inches msl for SR 3.3.1.1.15 lCl1-NO13A,B and S 763 ft.

1-11/16 inches msl for ICII-N013C,D

9. Turbine Stop Valve Closure > 33.3% RTP 4 E SR 3.3 .1.1.9 < 7% closed SR 3.3.1.1.13 SR 3.3.1.1.15 SR 3.3.1.1.16 SR 3.3.1.1.17
10. Turbine Control Valve Ž 33.3% RTP 4 E SR 3.3.1.1.9 > 465 psig Fast Closure, Trip Oil SR 3.3.1.1.13 Pressure-Low SR 3.3.1.1.15 SR 3.3.1.1.16 SR 3.3.1.1.17
11. Reactor Mode 1,2 4 H SR 3.3.1.1.12 NA Switch-Shutdown Position SR 3.3.1.1.15 (a) 5 4 I SR 3.3.1.1.12 NA SR 3.3.1.1.15
12. Manual Scram 1,2 H SR 3.3.1.1.9 NA SR 3.3.1.1.15 5 (a) 4 SR 3.3.1.1.9 NA SR 3.3.1.1.15 (a) With any control rod withdrawn from a core cell containing one, or more fuel assemblies.

CLINTON 3 .3-9 Amendment No. 179