EN-08-036, Issuance of Final Significance Determination and Notice of Violation
ML081620472
Person / Time
Site: Cooper Entergy icon.png
Issue date: 06/10/2008
From:
NRC/OE
To:
Nebraska Public Power District (NPPD)
References
EA-07-204, EN-08-036
Download: ML081620472 (2)


Text

PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION June 10, 2008 EN-08-036 OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION Licensee:

Nebraska Public Power District (EA-07-204)

Cooper Nuclear Station Docket No. 05000298

Subject:

ISSUANCE OF FINAL SIGNIFICANCE DETERMINATION AND NOTICE OF VIOLATION This is to inform the Commission that a Notice of Violation associated with a White significance determination process finding will be issued on or around June 13, 2008, to Nebraska Public Power District, as a result of inspections at Cooper Nuclear Station. This White finding, an issue of low to moderate safety significance which may require additional U.S. Nuclear Regulatory Commission inspections, involves failure by the licensee to ensure that steps contained in two Emergency Procedures at Cooper Nuclear Station would work as written.

A Notice of Violation is included based on a violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the failure of the licensee to determine whether steps added to procedures were appropriate to the circumstances and would work as written. Specifically, the licensee failed to properly verify and validate steps in two quality-related Emergency Procedures to ensure that the steps would work to accomplish the necessary actions.

It should be noted that Cooper has committed to adopt National Fire Protection Association (NFPA) Standard 805 (NFPA 805) as allowed by 10 CFR 50.48(c). The Interim Enforcement Discretion Policy provides enforcement discretion for certain violations of the requirements in 10 CFR 50.48, Fire Protection, (or fire protection license conditions) that are identified as a result of a licensees transition to a new risk-informed, performance-based fire protection approach included in 10 CFR 50.48(c). However, Cooper failed to meet one of the conditions for receiving this enforcement discretion in that they failed to identify this problem by routine licensee efforts such as normal surveillance or quality assurance activities. Therefore, enforcement discretion will not be exercised and this violation will be cited.

It should be noted that the licensee has not been specifically informed of the enforcement action. The schedule of issuance and notification is:

Mailing of Final Significance Determination June 13, 2008 Telephone Notification of Licensee June 13, 2008 The State of Nebraska will be notified.

Contacts: Doug Starkey, OE, 301-415-3456 Nick Hilton, OE, 301-415-2741

PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION Electronic Distribution: EN-08-036, June 10, 2008 OWFN Chairman Klein Comm. Jaczko Comm. Lyons Comm. Svinicki SECY OCA PA IP OWFN DO DEDR DEDMRS OE OGC NRR NSIR OI STP TWFN OCFO OP CENTER NMSS OIG OCIO RES ACRS Regional Offices RI RII RIII RIV MAIL PUBLIC OE staff DISTRIBUTION: (Hard copy)