ML081270203

From kanterella
Jump to navigation Jump to search
Summary of Facility Changes, Tests and Experiments
ML081270203
Person / Time
Site: North Anna  Dominion icon.png
Issue date: 04/25/2008
From: Stoddard D
Virginia Electric & Power Co (VEPCO)
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
08-0125A
Download: ML081270203 (3)


Text

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 28261 April 25,.2008 United States Nuclear Regulatory Commission Serial No.

08-0125A Attention: Document Control Desk NAPS/JHL Washington, D. C. 20555 Docket Nos. 50-338 50-339 License Nos. NPF-4 NPF-7 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)

NORTH ANNA POWER STATION UNITS 1 AND 2

SUMMARY

OF FACILITY CHANGES. TESTS AND EXPERIMENTS Dominion letter dated March 28, 2008 (Serial No. 08-0125) provided a summary description of Facility -Changes, Tests and Experiments identified in Regulatory Evaluations implemented at the North Anna Power Station during 2007 in accordance with 10 CFR 50.59(d)(2). It was recently identified that a summary description for one evaluation was not included in the previous submittal. The summary description for this evaluation is provided in the attachment to this letter.

If you have any questions, please contact Page Kemp at (540) 894-2295.

Very truly yours, Daniel G. Stoddard Site Vice President Attachment cc:

U. S. Nuclear Regulatory Commission Region II Atlanta Federal Center 61 Forsyth St., SW, Suite 23T85 Atlanta, Georgia 30303 NRC Senior Resident Inspector North Anna Power Station

-IT q~/

ATTACHMENT 10 CFR 50.59

SUMMARY

DESCRIPTION OF FACILITY CHANGES, TESTS AND EXPERIMENTS North Anna Power Station Units 1 and 2 Virginia Electric and Power Company (Dominion)

NORTH ANNA UNITS I & 2 10 CFR 50.59

SUMMARY

DESCRIPTION OF FACILITY CHANGES, TESTS AND EXPERIMENTS REGULATORY EVALUATION: 07-SE-ST-01 Document Evaluated: Special Test Procedure, O-ST-FP-001, Low Pressure C02 Blower Door Test Brief

Description:

A blower door test in accordance with NFPA 2001, 12A and ASTM E779, Standard Test Method for Determining Air Leakage Rate by Fan Pressurization will be performed. The test is being performed to determine if an overpressure condition may exist within the Cable Vaults on a fire protection C02 system discharge.

The test is conducted by installing a fan in a doorway to the area being tested. The fan is used to develop both a positive and negative pressure in the tested area. Leakage is determined through calculation using pressure and flow readings at the fan.

Reason for Change: Determine if an overpressure condition may exist within the Cable Vaults on a fire protection C02 system discharge.

Summary: The test is being performed to determine if an overpressure condition may exist within the Cable Vaults on a fire protection C02 system discharge. The test pressure will not pose a threat to the integrity of the walls, seals, or doors.. Although the increase in pressure has no adverse impact on the boundary or equipment, the pressurization may cause Control Room pressures to temporarily go out of specification. Also, the cable vault ventilation, position of dampers, the C02 system for the cable vaults, and some doors will be in abnormal conditions during testing. The test procedure contains steps to enter the appropriate Technical Specification or Technical Requirements Manual actions and establish compensatory measures, as appropriate.