SUBJECT:

LETTER REPORT FOR 23 WATER SAMPLES FROM THE VICINITY OF THE BRAIDWOOD NUCLEAR GENERATING STATION, BRAIDWOOD, ILLINOIS

[INSPECTION REPORT NO. 050-00456/2007-0061 (RFTA NO.07-005)

DCN: 1766-LR-01-0

Dear Mr. Snell:

The Oak hdge Institute for Science and Education (ORISE) received 23 water samples associated with the Braidwood Nuclear Generating Station on December 28,2007. The sample analysis was delayed until authorization was received from the Office of Nuclear Reactor Regulation on February 29, 2008.

The samples were analyzed for tritium to an averaged minimum detectable concentration of 180 pCi/L using a liquid scindation analyzer. The sample identifications and collection data are presented in Table 1. The tritium data are presented in Table 2. The pertinent procedure references are provided in the specific tables.

ORISEs Quality Control (QC) requirements were met for these analyses. The QC files are available for your review upon request.

hly contact information is listed below. You may also contact Wade Ivey at 865.576.9184 with any questions or comments.

Sincerely, Dale Condra, Manager Laboratory RDC:\\WI:km Enclosures C:

T. Carter, NRC/FSME/DWMEP T-8F5 E. &ox-Dah, NRC/NMSS/TWFN 8A23 File 1766 E. Abelquist, ORISE S. Roberts, ORISE Voice: 865.241.3242 Fax: 865.41.3248 E-mail: Dale.Condra@orau.org RECEIVED APR 0 3 2008

TABLE 1 SAMPLE IDENTIFICATIONS AND COLLECTION DATA BRAIDWOOD NUCLEAR GENERATING STATION BRAIDWOOD, ILLINOIS Collection Date Braldmood Nuclear Generaung Station 1766-1.R-01-0

TABLE 2 ORISE Sample ID TRITIUM CONCENTRATIONS IN WATER SAMPLES BY LIQUID SCINTILLATION ANALYSIS AP2, REVISION 16 AND CP4, REVISION 3 BRAIDWOOD NUCLEAR GENERATING STATION BRAIDWOOD, ILLINOIS NRC Region I11 Tritium Concentrations Sample ID (PCi/L) 1766WOOOl 1766W0002 BD-07-6-01 17,130 f 8309, 180b BD-07-6-02 10

+_

110, 180 1766W0003 I

BD-07-6-03 I

170 t 110, 180 1766W0004 1766W0005 BD-07-6-04 90 f 110, 180 BD-07-6-05 110 f 110, 180 1766W0006 I

BD-07-6-06 I

40 t 110, 180 1766W0007 1766W0008 1766W0009 BD-07-6-07 80 f 110, 180 BD-07-6-08 130 f 110, 180 BD-07-6-09 440 f 120, 180 1766W0010 I

BD-07-6-10 I

3,670

+_

250, 180 1766W0011 1766W0012

~

~~

~~~

BD-07-6-11 8,110 440, 180 BD-07-6-12 3,630 2 250, 180 1766W0013 1

BD-07-6-13 I

10 & 110, 180 1766W0014 1766W0015 1766W0016 BD-07-6-14 260 f 110, 180 BD-07-6-15 70 f 110, 180 BD-07-6-16 4,780 f 290, 180 1766W0017 I

BD-07-6-17 I

250 f 110, 170 1766W0018 1766W0019 1766W0020 BD-07-6-18 1,260 f 150, 170 BD-07-6-19 560 f 120, 170 BD-07-6-20 100 f 100, 170 1766W0021 I

BD-07-6-21 1

120

+_

100, 170 1766W0022 1766W0023

~

~~

~

BD-07-6-22 350 f 110, 170 BD-07-6-23 530 120, 170 dUncertaintics represent the 95% confidence level, based on total propagated uncertainties.

bXI1lCs arc prcsentcd after the comma.