Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 0
February 21, 2008 L-2008-018 FIPL 10 CFR 50.4 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 Re:
St. Lucie Unit 2 Docket No. 50-389 Unit 2 SL2-17 Pressurizer Butt Weld Alloy 82/182 Mitigation Status and SWOL Inspection Results On January 31, 2007, Florida Power and Light Company (FPL) submitted letter L-2007-013 to notify the NRC of the actions taken or planned for inspecting or mitigating Alloy 82/182 butt welds on pressurizer connections for St. Lucie Unit 2. Additionally, via letters L-2007-045, L-2007-148, and L-2007-172, dated March 29, 2007, September 24, 2007, and October 24, 2007, respectively, FPL sought relief from certain requirements of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code to allow the use of full structural weld overlays (SWOLs) to mitigate select pressurizer Alloy 82/182 butt welds. Within the letters, FPL committed to provide the results of future inspections or mitigations of the St. Lucie Unit 2 -pressurizer butt welds within 60 days of startup from the outage in which they were performed. St.
Lucie Unit 2 commenced commercial power operations from the SL2-17 refueling outage on January 4, 2008.
As required by FPL letter L-2007-148 and the NRC SER for TAC NO. MD5114, dated December 12, 2007, Attachment 1 provides the report of the structural weld overlay (SWOL) Ultrasonic (UT) examinations and a discussion and reason for any repairs to the SWOL and/or base metal. Attachment 2 provides the results of future inspections or mitigations of pressurizer alloy 82/182 butt weld locations as committed to in L-2007-013.
Please contact Ken Frehafer at 772-467-7748 if there are any questions about this submittal.
Very truly yours, Gordon L. Johnston Site Vice President St. Lucie Plant Attachments GLJ/KWF an FPL Group company
St. Lucie Unit 2 Pressurizer Butt Weld Alloy 82/182 Mitigation Status and SWOL Inspection Results L-2008-018 Page 1 of 2 PSL-2 SL-2-17 Weld Overlay Installation Examination Results Surge Line to Hot Leg B Pipe Nozzle No Recordable Indications (NRI)
NRI NRI NRI Shutdown Cooling Outlet to Hot Leg A NRI NRI NRI NRI Pipe Shutdown Cooling Outlet to Hot Leg B NRI NRI NRI NRI Pipe Hot Leg A Drain NRI NRI NRI NRI PT of barrier layer identified numerous rejectable rounded and linear indications resulting in repair Pressurizer Surge Line NRI NRI NRI Nozzle (at pressurizer)
PT of barrier layer excavation -
NRI PT of barrier layer after repair-NRI
St. Lucie Unit 2 Pressurizer Butt Weld Alloy 82/182 Mitigation Status and SWOL Inspection Results L-2008-018 Page 2 of 2 Pressurizer Relief Line Nozzle PT of base metal identified one rejectable indication approximately 3/16" long near toe of safe end PT results after buffing - NRI PT of barrier layer identified one linear indication approximately 1/8 inch in length.
PT of barrier layer after buffing-NRI PT of SWOL excavation to remove volumetric (UT) indications - NRI Pre excavation final PT of surface-NRI Final PT of surface-NRI Three circumferential indications (3.0", 9.0", 5.5") in length by (0.20") in width of lack of bond (LOB) between the overlay and the base material at same axial location were identified. All indications were outside of structural and examination area. The indications were evaluated as rejectable in accordance with the acceptance criteria of FPL's relief request 10, revision 1. A repair of the indications was performed.
After repair, UT identified three remaining circumferential indications (0.3", 1.2", 0.3") in length by (0.20") in width of LOB.
between the overlay and the base material at the same axial location. The indications were evaluated as acceptable in accordance with Table IWB-3514-3 and FPL's relief request 10, revision 1. All indications are outside of structural and ISI examination area.
There was no reduction of the PSI or ISI angle beam UT coverage due to presence of the remaining LOB.
St. Lucie Unit 2 Pressurizer Butt Weld Alloy 82/182 Mitigation Status and SWOL Inspection Results L-2008-018 Page 1 of 1 St. Lucie Unit 2 Alloy 82/182 Pressurizer Butt Weld Inspection and Mitigation Summary Results The St, Lucie Unit 2 pressurizer has 6 piping nozzle welds that were originally made with alloy 82/182 as identified in the table below. During the SL2-17 refueling outage all 6 piping nozzle welds were mitigated by the method shown in the table below:
Nozzle Mitigation Completed (Note 1)
Function /
Susceptible
'Outage Mitigation performed (Note 2)
Designation Material Description Designation Surge Nozzle-to-safe SL 2-17 Structural Weld Overlay (SWOL)
RC-514-671 end weld only Spray Nozzle-to-safe SL 2-17 Cut out and replacement with Stainless RC-504-671 end weld only Steel (SS)
Safety Nozzle-to-safe SL 2-17 Cut out and replacement with SS 503-671-A end weld only Safety Nozzle-to-safe SL 2-17 Cut out and replacement with SS 503-671-D end weld only Safety Nozzle-to-safe SL 2-17 Cut out and replacement with SS 503-671-C end weld only Relief Nozzle-to-safe SL 2-17 Structural Weld Overlay RC-506-671 end weld only Notes:
- 1) Refueling Outage started 10-2007 and returned to service 1-4-2008.