From:

Ann Marie Stone To:

George Dick; Mahesh Chawla; Nirodh Shah; Peter Snyder; Richard Skokowski; Steven Ray Date:

2/10/04 4:44PM

Subject:

Re: AMAG at Braidwood At least for BW, that means they were operating below 102%; however, I believe BY operated above 102% (...........

AM

>>> Steven Ray 02/10/04 03:28PM >>>

Tom Joyce, Braidwood PM and SVP, told me today that, based on the results of the Byron tracer testing, they are 99% sure that they are going to completely abandon all efforts of ever getting-AMAG back in service here.

The results show that the venturies have always been the most accurate measure of flow and the actual power they were opperating at with AMAG was even higher than they reported in the LERs, because in the LERs they assumed that the combined header AMAG readings were accurate.

46.0 $Nq&