Person / Time
Site: Pilgrim
Issue date: 12/19/2007
From:
Office of Nuclear Reactor Regulation
To:
Office of Nuclear Reactor Regulation
References
06-848-02-LR
Download: ML073610122 (3)


Text

From:

Perry Buckberg To:

<jlynch4@entergy.com>

Date:

12/19/2007 10:19:09 AM

Subject:

Salt Service Water System cc:

"Steve Bethay" <sbethay@entergy.com>,"James Davis"

<JAD@nrc.gov>,"Louise Lund" <LXL@nrc.gov>

Joe, It has come to my attention that NUREG-1891 may be in error with regards to some specific information on the SSW system piping.

The following paragraph from NUREG-1891 begins on page 3-37:

From an additional historical perspective, the SSW system has had leaks on the buried inlet (screenhouse to auxiliary bays) piping due to internal corrosion. The original piping material was rubber-lined carbon steel wrapped with reinforced fiberglass, coal tar saturated felt, and heavy Kraft paper. The leaks were determined to be results of the rubber lining degrading from contact with sea water. These pipes were replaced in 1995 and 1997 with the same external and internal coatings as for the original pipe.

Please confirm that the last sentence is in error, and that buried inlet pipes were replaced with titanium pipe with the same external coating as the original pipe. Thanks, Perry Buckberg Project Manager Nuclear Regulatory Commission Division of License Renewal phone: (301)415-1383 fax: (301)415-3031 phb1@nrc.gov

Hearing Identifier:

PilgrimRenewalNonPublic Email Number:

179 Mail Envelope Properties (477373F6.HQGWDO01.TWGWPO03.200.2000009.1.15B7EF.1)

Subject:

Salt Service Water System Creation Date:

12/19/2007 10:19:09 AM From:

Perry Buckberg Created By:

PHB1@nrc.gov Recipients "Steve Bethay" <sbethay@entergy.com>

"James Davis" <JAD@nrc.gov>

"Louise Lund" <LXL@nrc.gov>

<jlynch4@entergy.com>

Post Office Route TWGWPO03.HQGWDO01 nrc.gov Files Size Date & Time MESSAGE 1056 12/19/2007 10:19:09 AM TEXT.htm 2136 12/27/2007 9:44:22 AM Options Priority:

Standard Reply Requested:

No Return Notification:

None None Concealed

Subject:

No Security:

Standard

Joe, It has come to my attention that NUREG-1891 may be in error with regards to some specific information on the SSW system piping.

The following paragraph from NUREG-1891 begins on page 3-37:

From an additional historical perspective, the SSW system has had leaks on the buried inlet (screenhouse to auxiliary bays) piping due to internal corrosion. The original piping material was rubber-lined carbon steel wrapped with reinforced fiberglass, coal tar saturated felt, and heavy Kraft paper. The leaks were determined to be results of the rubber lining degrading from contact with sea water. These pipes were replaced in 1995 and 1997 with the same external and internal coatings as for the original pipe.