Summary of Public Exit Meeting - Joseph M. Farley Nuclear Plant - to Discuss the Results of an Extended Augmented Inspection Team Inspection for Additional Residual Heat Removal System Breaker Failure
ML073380955
Person / Time
Site: Farley  
Issue date: 12/04/2007
From: Scott Shaeffer
Division Reactor Projects II
To: Jerrica Johnson
Southern Nuclear Operating Co
References
Download: ML073380955 (4)


Text

December 4, 2007 Southern Nuclear Operating Company, Inc.

ATTN:

Mr. J. Randy Johnson Vice President - Farley Joseph M. Farley Nuclear Plant 7388 North State Highway 95 Columbia, AL 36319

SUBJECT:

PUBLIC EXIT MEETING

SUMMARY

- JOSEPH M. FARLEY NUCLEAR PLANT -

DOCKET NOS.: 50-348, 50-364

Dear Mr. Johnson:

This refers to the meeting conducted at the Houston County Administration Building in Dothan, AL on November 19, 2007, at 11:00 a.m. The meetings purpose was to discuss the results of an extended Augmented Inspection Team inspection for an additional Residual Heat Removal (RHR) system breaker failure at the Farley Nuclear Plant. Also at this meeting, the NRC discussed entry of both Farley Units into the Degraded Cornerstone column of the NRC Action Matrix. A list of attendees is available in NRCs document system (ADAMS) as accession number ML073330140.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter will be available electronically for public inspection in the NRC Public Document Room (PDR) or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS).

ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Should you have any questions concerning this meeting, please contact me at (404) 562-4521.

Sincerely,

/RA/

Scott M. Shaeffer, Chief Reactor Projects Branch Division of Reactor Projects Docket Nos.: 50-348, 50-364 License Nos.: NPF-2, NPF-8 cc w/encls: (See page 2)

OFFICE RII:DRP RII:DRP SIGNATURE CWR /RA/

SMS /RA/

NAME CRapp SShaeffer DATE 11/29/2007 12/04/2007 E-MAIL COPY?

YES NO YES NO YES NO YES NO YES NO YES NO YES NO

2 SNC, Inc.

cc w/encls:

Mr. B. D. McKinney, Licensing Manager Southern Nuclear Operating Company, Inc.

Electronic Mail Distribution Mr. Jeffrey T. Gasser Executive Vice President Southern Nuclear Operating Company, Inc.

Electronic Mail Distribution Mr. M. Stanford Blanton Balch and Bingham Law Firm Electronic Mail Distribution Dr. D. E. Williamson State Health Officer Alabama Department of Public Health Electronic Mail Distribution Mr. William D. Oldfield, SAER Supervisor Joseph M. Farley Nuclear Plant Electronic Mail Distribution Mr. Mark Culver, Chairman Houston County Commission P. O. Box 6406 Dothan, AL 36302 David H. Jones Vice President - Engineering Southern Nuclear Operating Company, Inc.

P.O. Box 1295 Birmingham, AL 35201-1295 Moanica Caston Southern Nuclear Operating Company, Inc.

Bin B-022 P. O. Box 1295 Birmingham, AL 35201-1295 L. M. Stinson, Vice President, Fleet Operations Support Southern Nuclear Operating Company, Inc.

11028 Hatch Parkway North Baxley, GA 31513

3 SNC, Inc.

Letter to J. Randy Johnson from Scott M. Shaeffer dated December 4, 2007

SUBJECT:

PUBLIC MEETING

SUMMARY

- JOSEPH M. FARLEY NUCLEAR PLANT -

DOCKET NOS.: 50-348, 50-364 Distribution w/encl:

K. Cotton, NRR C. Evans, RII L. Slack, RII RIDSNRRDIRS OE Mail PUBLIC