November 21, 2007 Mr. Tom E. Tynan Vice President - Vogtle Vogtle Electric Generating Plant 7821 River Road Waynesboro, GA 30830

SUBJECT:

VOGTLE ELECTRIC GENERATING PLANT, UNITS 1 AND 2, REQUEST FOR ADDITIONAL INFORMATION (RAI) REGARDING THE REVISION TO EMERGENCY ACTION LEVEL THRESHOLD VALUES (TAC NOS. MD6872 AND MD6873)

Dear Mr. Tynan:

By letter dated September 27, 2007, Southern Nuclear Operating Company (the licensee) submitted the revision to emergency action level threshold values and basis to support measurement uncertainty recapture power uprate for Vogtle Electric Generating Plant, Units 1 and

2. The Nuclear Regulatory Commission (NRC) staff is reviewing the submittal and has determined that additional information is required to complete its evaluation.

The NRC staffs RAI is enclosed. The licensee is required to provide a response to the RAI within 30 days.

Sincerely,

/RA/

Siva P. Lingam, Project Manager Plant Licensing Branch II-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-424 and 50-425

Enclosure:

RAI cc w/encl: See next page

ML073190577

  • transmitted by e-mail dated OFFICE NRR/LPL2-1/PM NRR/LPL2-1/LA NSIR/DPR/DDRP/BC NRR/LPL2-1/BC NAME SLingam:nc MO=Brien KWilliams EMarinos DATE 11/7/07 11/9/07 10/26/07*

11/21/07

Enclosure REQUEST FOR ADDITIONAL INFORMATION REGARDING THE REVISION TO EMERGENCY ACTION LEVEL THRESHOLD VALUES AND BASIS TO SUPPORT MEASUREMENT UNCERTAINTY RECAPTURE POWER UPRATE VOGTLE ELECTRIC GENERATING PLANT, UNITS 1 AND 2 DOCKET NOS. 50-424 AND 50-425 By letter dated September 27, 2007 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML072740102), Southern Nuclear Operating Company, Inc.

(the licensee), submitted revision to emergency action level (EAL) threshold values and basis to support measurement uncertainty recapture power uprate for Vogtle Electric Generating Plant, Units 1 and 2. In order to complete the review of the documents listed above, the Nuclear Regulatory Commission (NRC) staff needs the following requests for additional information (RAIs).

The licensee should address the RAIs and revise EALs as applicable. A complete, clean, EAL basis document shall be provided as an attachment to the licensees response. The clean document should include EAL basis document section for EALs RU1, RA1, RS1, RG1, and SU4.

1. RU1: The calculation tables provided in the EAL basis for EAL RU1 appear to be the same as originally approved which is inconsistent with the licensees submittal. Please revise the calculation tables or provide an explanation for the apparent inconsistency.
2. RS1/RG1: The calculation tables provided in the EAL basis for EAL RS1, which also covers EAL RG1, appear to be the same as originally approved which is inconsistent with the licensees submittal. Please revise the calculation tables or provide an explanation for the apparent inconsistency.
3. RA1.2: According to the EAL basis document, the value should be 100 times that of RU1.

This appears not to be the case. Please provide an explanation or revise the EAL.

The NRC staff discussed the above RAIs with the licensee on October 26, 2007, through conference call, and the licensee agreed to revise the applicable EALs.

Vogtle Electric Generating Plant, Units 1 & 2 cc:

Mr. Tom E. Tynan Vice President - Vogtle Vogtle Electric Generating Plant 7821 River Road Waynesboro, GA 30830 Mr. N. J. Stringfellow Manager, Licensing Southern Nuclear Operating Company, Inc.

P.O. Box 1295 Birmingham, AL 35201-1295 Mr. Jeffrey T. Gasser Executive Vice President Southern Nuclear Operating Company, Inc.

P.O. Box 1295 Birmingham, AL 35201-1295 Mr. Steven M. Jackson Senior Engineer - Power Supply Municipal Electric Authority of Georgia 1470 Riveredge Parkway, NW Atlanta, GA 30328-4684 Mr. Reece McAlister Executive Secretary Georgia Public Service Commission 244 Washington St., SW Atlanta, GA 30334 Mr. Harold Reheis, Director Department of Natural Resources 205 Butler Street, SE, Suite 1252 Atlanta, GA 30334 Attorney General Law Department 132 Judicial Building Atlanta, GA 30334 Mr. Laurence Bergen Oglethorpe Power Corporation 2100 East Exchange Place P.O. Box 1349 Tucker, GA 30085-1349 Arthur H. Domby, Esquire Troutman Sanders Nations Bank Plaza 600 Peachtree Street, NE Suite 5200 Atlanta, GA 30308-2216 Resident Inspector Vogtle Plant 8805 River Road Waynesboro, GA 30830 Office of the County Commissioner Burke County Commission Waynesboro, GA 30830