RCS PIV Leakage 3.4.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.6.1 NOTE--------------------

Not required to be performed in MODE 3.

Verify equivalent leakage of each RCS PIV is

  • 0.5 gpm per nominal inch of valve size In accordance up to a maximum of 5 gpm, at an RCS with Inservice pressure 2 1000 psig and S 1025 psig.

Testing Program CLINTON 3.4-16 Amendment No.

176