MR-4-2007-0003, Partial Loss of Offsite Power at Diablo Canyon
ML071340397
Person / Time
Site: Diablo Canyon  
Issue date: 05/14/2007
From: Vincent Gaddy
NRC Region 4
To:
References
MR-4-2007-0003
Download: ML071340397 (1)


Text

Morning Report Date: MAY 14, 2007 PRIORITY ATTENTION REQUIRED MORNING REPORT - REGION IV Licensee/Facility:

Notification:

4-2007-0003 05/12/2007 MR Number:

PACIFIC GAS & ELECTRIC CO.

[1] W-4-LP, [2] W-4-LP Date:

Diablo Canyon Call / Fax from SRI Avila Beach, California 050-00275 050-00323 Dockets:

PARTIAL LOSS OF OFFSITE POWER AT DIABLO CANYON

Subject:

On May 12, 2007, at 10:25 a.m. PDT, offsite electrical startup power (230 kV) was lost to Diablo Canyon, Units 1 and 2.

Unit 1 was in a refueling outage with the reactor core off-loaded to the spent fuel pool. One of three diesel generators was also unavailable due to maintenance. On the loss of startup power the remaining two diesel generators auto-started and powered their respective loads. Control room operators restarted the spent fuel pool cooling pump and restored spent fuel pool cooling. Spent fuel pool cooling was interrupted for approximately 4 minutes and spent fuel pool temperature remained unchanged. No emergency declaration was required since Unit 1 was defueled.

Unit 2 remained at 100 percent with auxiliary power supplying Unit 2 equipment. The loss of startup power caused all diesel generators to auto-start; however, the electrical loads remained on the normal electrical power supply which was not affected by the loss of offsite startup power.

The loss of the startup power to the plant was due to a fault on a 230 kV transmission line at Morro Bay substation. As per design, protective relaying sensed the fault and locked out startup power to the Diablo Canyon switchyard.

At approximately 2:30 p.m. PDT, repairs were completed and electrical startup power was restored to both units.

This Morning Report is being submitted for information only. The NRC resident inspectors monitored licensee response to the event.

Discussion:

Contact:

Email:

Phone No:

Org:

GADDY, VINCENT G VGG@nrc.gov (817) 320-2422 R4