ML070610440

From kanterella
Jump to navigation Jump to search
2006 Annual Report
ML070610440
Person / Time
Site: Crane  
Issue date: 02/23/2007
From: Dougherty T
AmerGen Energy Co
To:
Document Control Desk, Office of Nuclear Material Safety and Safeguards, Office of Nuclear Reactor Regulation
References
5928-07-20013
Download: ML070610440 (10)


Text

Amer~en.

AmerGen Energy Company, LLC Three Mile island Unit 1 Route 441 South, P.O. Box 480 Middletown, PA 17057 Telephone: 717-948-8ooo An Exelon Company February 23, 2007 5928-07-20013 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555 THREE MILE ISLAND UNIT 1 (TMI-1) AND UNIT 2 (TMI-2)

OPERATING LICENSE NO. DPR-50, DOCKET NO. 50-289 POSSESSION ONLY LICENSE NO. DPR-73, DOCKET NO. 50-320

SUBJECT:

2006 ANNUAL REPORT Attached is the 2006 Annual Report for TMI-1 and TMI-2. This report is being submitted in accordance with TMI-1 Technical Specifications Sections 6.9.1..B.2 through 6.9.1.B.5 and 6.17 and in accordance with TMI-2 Technical Specification 6.8.1.3(a).

The attachments to this letter contain the following information: -, - - -

A tabulation of exposures received by workers at the TMI Station, according to work and job functions (per TMI-2 T.S.

section 6.8.1.3(a)).

Aircraft movement data from the Harrisburg International Airport (per TMI-1 T.S. section 6.9.1.B.2).

Leak reduction program test information (per TMI-1 T.S.

6.9.A1 B.3).

Pressurizer power operated relief valve and :pressurizer safety valve challenges (per TMI-1 T.S. section 6.9.1.B.4).

bfmss Co I

5928-07-20013 Page 2 of 2 - -

Results of specific activity analysis - primary coolant system (per TMI-1 T.S. section 6.9.1.B.5).

Major TMI-1 changes to radioactive waste treatment systems (per T.S. section 6.17)

Sincerely, Thomas J. DOL Plant Manager TJD/awm Attachments cc:

TMI-1 Senior Resident Inspector Administrator, Region I TMI-1 Project Manager TMI-2 Project Manager GPUN TMI-2 Cognizant Officer File 07004

ATTACHMENT I TABULATION OF TMI WORKER EXPOSURES BY WORK AND JOB FUNCTION JANUARY 1, 2006 THROUGH DECEMBER 31, 2006

THREE MILE ISLAND NUCLEAR STATION MIDDLETOWN, PA 17057 LICENSE NUMBERS: DPR - 50 AND DPR - 73 STANDARD FORMAT FOR REPORTING NUMBER OF PERSONNEL AND MAN-REM BY WORK AND JOB FUNCTION FOR THE PERIOD 01/01/06 THRU 12/31/06 NUMBER OF PERSONS WITH MONITORED EXPOSURE TOTAL MAN-REM STATION UTILITY CONTRACTORS STATION UTILITY EMPLOYEES EMPLOYEES AND OTHERS EMPLOYEES EMPLOYEES WORK FUNCTION JOB FUNCTION REACTOR OPERATIONS AND SURVEILLANCE MAINTENANCE PERSONNEL OPERATING PERSONNEL HEALTH PHYSICS PERSONNEL SUPERVISORY PERSONNEL ENGINEERING PERSONNEL ROUTINE MAINTENANCE MAINTENANCE PERSONNEL OPERATING PERSONNEL HEALTH PHYSICS PERSONNEL SUPERVISORY PERSONNEL ENGINEERING PERSONNEL INSERVICE INSPECTION MAINTENANCE PERSONNEL OPERATING PERSONNEL HEALTH PHYSICS PERSONNEL SUPERVISORY PERSONNEL ENGINEERING PERSONNEL SPECIAL MAINTENANCE MAINTENANCE PERSONNEL OPERATING PERSONNEL HEALTH PHYSICS PERSONNEL SUPERVISORY PERSONNEL ENGINEERING PERSONNEL WASTE PROCESSING MAINTENANCE PERSONNEL OPERATING PERSONNEL HEALTH PHYSICS PERSONNEL SUPERVISORY PERSONNEL ENGINEERING PERSONNEL REFUELING MAINTENANCE PERSONNEL OPERATING PERSONNEL HEALTH PHYSICS PERSONNEL SUPERVISORY PERSONNEL ENGINEERING PERSONNEL NUMBER OF INDIVIDUALS MAINTENANCE PERSONNEL OPERATING PERSONNEL HEALTH PHYSICS PERSONNEL SUPERVISORY PERSONNEL ENGINEERING PERSONNEL TOTAL INDIVIDUALS 72 sb 4i 27 26 47 3

16 0

0 06 0

0 0

0 0

0 19 0

b2 0

b 0

0 163 130

_70%

...135 5 85

ýNOTE:

8 29 0.687 2

0 0.277 1

6 0.915 1

13 0.139 3

1 0.024 7

35 0.263 0

0 0.001 1

0 0.018 0

5 0.063 0

0 0.000 0

0 0.000 0

0 0.000 0

0 0.000 0

0 0.000 0

0 0.000

.0 0

0.000 0

0 0.000 0

0 0.000 0

0 0.000 0

0 0.000 1

20 0.173 0

0 0.000 0

0 0.424 0

1 0.000 0

0 0.000 0

0 0.000 0

0 0.000 0

0 0.000 0

0 0.000 0

0 0.000 "40 219 1,123 9

3 0.278 3

41 1.357 26 202 0.202 11 16 0.024 89 481 2.984 THERMOLUMINESCENT DOSIMETER (TLD) ACTUAL DOSE FOR THE PERIOD IS 5.155 REM 0.037 0.026 0.004 0.000 0.000 0.027 0.000 0.011 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.005 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.069 0.026 0.015 0.000 0.000 0.110 CONTRACTOR AND OTHERS 0.138 0.000 0.000 0.043 0.000 0.353 0.000 0.000 0.093 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.393 0.000 0.000 0.040 0.000 0.000 0.000 0.000 0.000 0.000 1.884 0.000 0.000 0.176 0.000 2.060

5928-07-20013 Page 1 of 1 ATTACHMENT 2 AIRCRAFT MOVEMENTS AT THE HARRISBURG INTERNATIONAL AIRPORT (HIA)

JANUARY 1, 2006 THROUGH DECEMBER 31, 2006

1.

Total Aircraft Movements - 69,462

2.

Estimated total number of movements of aircraft larger than 200,000 pounds - 814 This estimate is composed of two parts, 791 movements of civilian aircraft, and 23 movements of military aircraft.

5928-07-20013 ATTACHMENT 3 TECHNICAL SPECIFICATION 6.9.1.B.3 PERIODIC LEAK REDUCTION PROGRAM TEST RESULTS The results of the TMI-1 2006 periodic Leak Reduction Program Tests, which included visual inspections, are summarized in Table 1. These tests were performed in accordance with the referenced procedures. (See Note 1 for procedure titles.)

TABLE 1 2006 LEAK REDUCTION PROGRAM TEST RESULTS FOR TMI-1 SURVEILLANCE DATE OF LEAKING LEAK RATE LEAK RATE RESULTING PROCEDURES PERFORMANCE COMPONENT AS-FOUND AS-LEFT MAINTENANCE I.D.

sccm*

sccm*

UNDERTAKEN OP-TM-823-252 03-05-06 AH-V1C/D 5,680 5,680 04-16-06 AH-VIC/D 3,098 3,098 None required 10-22-06 AH-V-1C/D 3,032 3,032 (See Note 2) 1303-11.17A 03-19-06 Eq. Hatch 1,020 1,020 None required 12-03-06 Pers. Hatch 851 851 1300-6V 01-10-06 None N/A None required 1303-11.29 03-24-06 None N/A None required OP-TM-212-04-20-06 None N/A None required 251 (B) 1303-11.28 08-02-06 None N/A.

None required OP-TM-212-09-28-06 None N/A None required 251 (A)

  • sccm standard cubic centimeters per minute Note 1:

OP-TM-823-252, "LLRT-of Purge Supp)-y Pe-netration Valves":,

1303-11.17A,. "RB Local Leak Rate Testing - RB Access Hatches" 1.300-6V, "RB Penetration Piping Leakage Exam.for IST" 1303-11.29, "Waste Gas Disposal System Leak Check" OP-TM-212-251 (B), "DH Leakage Exam for IST" A 1303-11.28, ":DH Leakage Exam for IST" OP-TM-212-251 (A), "DH Leakage Exam for IST" Note 2:

'The 4/16/06 LLRT was performed as PMT following actuator maintenance, not to address excessive LLRT results.

5928-07-20013 Page 1 of 1 ATTACHMENT 4 PRESSURIZER POWER OPERATED RELIEF VALVE AND PRESSURIZER SAFETY VALVE CHALLENGES IN 2006 There were no challenges to the pressurizer power operated relief valve or either of the two pressurizer safety valves during the entire calendar year of 2006.

5928-07-20013 Page 1 of 2 ATTACHMENT 5 RESULTS OF SPECIFIC ACTIVITY ANALYSIS-PRIMARY COOLANT SYSTEM Technical Specification 6.9.1..B.5 requires annual reporting of certain information regarding the results of specific activity analyses in which the primary coolant exceeded the limits of Technical Specification (TS) 3.1.4.1. The limits of TS 3.1.4.1 were not exceeded at TMI-1 at any time during the year 2006. The figure of RCS activity for 2006 shows that the limit of 0.35 microcurie/gram dose equivalent 1-131 was not exceeded in 2006.

5928-07-20013 Page 2 of 2 TMI-1 Dose Equivalent Iodine (DEI) in 2006 1.0OE+00 1.OOE-01 1.OOE-02 1.OOE-03 C-)

0d DEI

____TS Limit 1.OOE-04 2-Jan 1-Feb 3-Mar 2-Apr 2-May 1-Jun 1 -Jul 31-Jul Date 30-Aug 29-Sep 29-Oct 28-Nov 28-Dec

5928-07-20013 Page 1 of 1 ATTACHMENT 6 MAJOR CHANGES TO RAD WASTE TREATMENT SYSTEMS Technical Specification Section 6.17 requires reporting of "Major Changes to Radioactive Waste Treatment Systems." Major changes are interpreted to mean changes that would alter how the system functions or changes that would affect operational exposures, offsite dose rates or integrated doses. There were no major changes to the liquid, gaseous, or solid radioactive waste treatment systems at TMI-1 during the year of 2006.