ML070400053

From kanterella
Jump to navigation Jump to search

Correction Letter - Amendments for Primary Containment Leakage Testing Program - Amendment No. 166 - Tech Spec Page 5.5-13
ML070400053
Person / Time
Site: LaSalle  Constellation icon.png
Issue date: 02/08/2007
From:
NRC/NRR/ADRO/DORL/LPLIII-2
To:
Shared Package
ML070400144 List:
References
TAC MD1298
Download: ML070400053 (1)


Text

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.13 Primary Containment Leakage Rate Testing Program (continued)

2.

NEI 94 1995, Section 9.2.3: The first Unit 2 Type A test performed after December 8, 1993 Type A test shall be performed prior to startup following L2R12.

3.

The potential valve atmospheric leakage paths that are not exposed to reverse direction test pressure shall be tested during the regularly scheduled Type A test.

The program shall contain the list of the potential valve atmospheric leakage paths, leakage rate measurement

method, and acceptance criteria.

This exception shall be applicable only to valves that are not isolable from the primary containment free air space.

b.

The peak calculated primary containment internal pressure for the design basis loss of coolant accident, Pa, is 39.9 psig.

c.

The maximum allowable primary containment leakage rate, La, at P,,

is 0.635% of primary containment air weight per day.

d.

Leakage rate acceptance criteria are:

1.

Primary containment overall leakage rate acceptance criterion is

  • 1.0 La.

During the first unit startup following testing in accordance with this program, the leakage rate acceptance criteria are

  • 0.60 La for the combined Type B and Type C tests, and
  • 0.75 La for Type A tests.
2.

Air lock testing acceptance criteria are:

a)

Overall air lock leakage rate is

  • 0.05 L, when tested at > P,.

b)

For each door, the seal leakage rate is

  • 5 scf per hour when the gap between the door seals is pressurized to Ž 10 psig.
e.

The provisions of SR 3.0.3 are applicable to the Primary Containment Leakage Rate Testing Program.

(continued)

LaSalle 1 and 2 5.5-13 Amendment No. 179 / 166