Response to Generic Letter 2006-03: Potentially Nonconforming Hemyc and MT Fire Barrier Configurations
ML070250184
Person / Time
Site: Sequoyah  Tennessee Valley Authority icon.png
Issue date: 01/31/2007
From: Moroney B
NRC/NRR/ADRO/DORL/LPLII-2
To: Singer K
Tennessee Valley Authority
Moroney B, NRR/DORL, 415-3974
References
GL-06-003, GL-92-008, TAC MD1632, TAC MD1633
Download: ML070250184 (3)


Text

January 31, 2007 Mr. Karl W. Singer Chief Nuclear Officer and Executive Vice President Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801

SUBJECT:

SEQUOYAH NUCLEAR PLANT, UNITS 1 AND 2 - RESPONSE TO GENERIC LETTER 2006-03: POTENTIALLY NONCONFORMING HEMYC AND MT FIRE BARRIER CONFIGURATIONS (TAC NOS. MD1632 AND MD1633)

Dear Mr. Singer:

The Nuclear Regulatory Commission (NRC) acknowledges the receipt of your response to Generic Letter (GL) 2006-03, Potentially Nonconforming Hemyc and MT Fire Barrier Configurations. Under oath or affirmation, in your response dated June 7, 2006, you stated that Hemyc or MT fire barrier materials are not used at the Sequoyah Nuclear Plant (SQN),

Units 1 and 2.

Also, you stated that SQN uses fire barriers other than Hemyc or MT, which are designed and installed as approved by the NRC staff. Your responses to GL 92-08, Thermo-Lag 330-1 Fire Barriers, described the fire barriers used to separate redundant safe shutdown trains located within the same fire area at SQN. Your June 25, 1997, letter described the corrective actions planned for fire barriers in response to GL 92-08. Your letter of June 30, 1999, stated that SQNs corrective actions associated with GL 92-08 had been completed. The basis for stating that these other fire barriers meet NRC requirements should be maintained on site, and will be subject to inspection during the normal NRC inspection process.

If you have any questions, please contact me at (301) 415-3974.

Sincerely,

/RA/

Brendan T. Moroney, Project Manager Plant Licensing Branch II-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-327 and 50-328 cc: See next page

ML070250184 NRR-106 OFFICE LPL2-2/PM LPL2-2/LA AFPB/BC LPL2-2/BC NAME BMoroney CSola SWeerakody SBailey DATE 1/30/07 1/26/07 1/31/07 1/31/07

Mr. Karl W. Singer SEQUOYAH NUCLEAR PLANT Tennessee Valley Authority cc:

Mr. Ashok S. Bhatnagar, Senior Vice President Nuclear Operations Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Preston D. Swafford, Senior Vice President Nuclear Support Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Larry S. Bryant, Vice President Nuclear Engineering & Technical Services Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 General Counsel Tennessee Valley Authority 6A West Tower 400 West Summit Hill Drive Knoxville, TN 37902 Mr. John C. Fornicola, Manager Nuclear Assurance Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Ms. Beth A. Wetzel, Manager Corporate Nuclear Licensing and Industry Affairs Tennessee Valley Authority 4X Blue Ridge 1101 Market Street Chattanooga, TN 37402-2801 Mr. Robert H. Bryan, Jr., General Manager Licensing and Industry Affairs Tennessee Valley Authority 4X Blue Ridge 1101 Market Street Chattanooga, TN 37402-2801 Mr. Randy Douet, Site Vice President Sequoyah Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Soddy Daisy, TN 37384-2000 Mr. Glenn W. Morris, Manager Licensing and Industry Affairs Sequoyah Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Soddy Daisy, TN 37384-2000 Mr. David A. Kulisek, Plant Manager Sequoyah Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Soddy Daisy, TN 37384-2000 Senior Resident Inspector Sequoyah Nuclear Plant U.S. Nuclear Regulatory Commission 2600 Igou Ferry Road Soddy Daisy, TN 37379 Mr. Lawrence E. Nanney, Director Division of Radiological Health Dept. of Environment & Conservation Third Floor, L and C Annex 401 Church Street Nashville, TN 37243-1532 County Mayor Hamilton County Courthouse Chattanooga, TN 37402-2801 Ms. Ann P. Harris 341 Swing Loop Road Rockwood, TN 37854