January 12, 2007 Mr. Jeffrey S. Forbes Site Vice President Arkansas Nuclear One Entergy Operations, Inc.
1448 S. R. 333 Russellville, AR 72802
SUBJECT:
ARKANSAS NUCLEAR ONE, UNIT 1 - REQUEST FOR ADDITIONAL INFORMATION - RELOCATION OF INVERTER Y-28 AND PANEL C-540 REQUIREMENTS FROM THE TECHNICAL SPECIFICATIONS TO THE TECHNICAL REQUIREMENTS MANUAL (TAC NO. MD2982)
Dear Mr. Forbes:
By letter dated August 31, 2006, Entergy Operations, Inc., requested an amendment to the Arkansas Nuclear One, Unit 1, Technical Specifications (TS). The proposed change would relocate TS 3.8.7 requirements associated with 120 volt inverter Y-28 and TS 3.8.9 requirements associated with 120 volts alternating current electrical power distribution subsystem panel C-540 to the technical requirement manual.
The staff of the Nuclear Regulatory Commission has reviewed the proposed request and finds that additional information is needed to complete its evaluation. A request for additional information is enclosed.
In order to complete our timely review of your amendment request, we request your response within 30 days from the date of this letter. If you have any questions, please contact me at 301-415-1447.
Sincerely,
/RA/
Farideh E. Saba, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-313
Enclosure:
Request for Additional Information cc w/encl: See next page
December 2006 Arkansas Nuclear One cc:
Executive Vice President
& Chief Operating Officer Entergy Operations, Inc.
P.O. Box 31995 Jackson, MS 39286-1995 General Manager Plant Operations Entergy Operations, Inc.
Arkansas Nuclear One 1448 SR 333 Russellville, AR 72802 Director, Nuclear Safety Assurance Entergy Operations, Inc.
Arkansas Nuclear One 1448 SR 333 Russellville, AR 72802 Manager, Licensing Entergy Operations, Inc.
Arkansas Nuclear One 1448 SR 333 Russellville, AR 72802 Director, Nuclear Safety & Licensing Entergy Operations, Inc.
1340 Echelon Parkway Jackson, MS 39213-8298 Section Chief, Division of Health Radiation Control Section Arkansas Department of Health and Human Services 4815 West Markham Street, Slot 30 Little Rock, AR 72205-3867 Section Chief, Division of Health Emergency Management Section Arkansas Department of Health and Human Services 4815 West Markham Street, Slot 30 Little Rock, AR 72205-3867 Senior Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 310 London, AR 72847 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-8064 County Judge of Pope County 100 W. Main Street Russellville, AR 72801 Vice President, Operations Support Entergy Operations, Inc.
P.O. Box 31995 Jackson, MS 39286-1995
ML070090655 OFFICE NRR/LPL4/PM NRR/LPL4/LA NRR/LPL4/BC NAME FSaba LFeizollahi DTerao DATE 1/11/07 1/11/07 1/12/07
ENCLOSURE REQUEST FOR ADDITIONAL INFORMATION ENTERGY OPERATIONS, INC.
ARKANSAS NUCLEAR ONE, UNIT 1 TAC NO. MD2982 DOCKET NO. 50-313 1.
Define the term vital equipment. Once the requirements for the 120 volt inverter, Y-28, are moved to the technical requirements manual, will Y-28 still be considered a vital inverter?
- 2.
On Page 2 of Section 3.0 of the attachment to the amendment request dated August 31, 2006, Entergy states that panel C-540 provides power to some alternate shutdown instrumentation. Please provide detailed information on the affected alternate shutdown instrumentation. In addition, provide justification that the operators response when establishing fire-related compensatory measures upon loss of C-540 has no adverse effects.