DCL-06-131, Special Report 06-04: Results of Steam Generator Tube Eddy Current Inspections During Unit 1 Thirteenth Refueling Outage

From kanterella
(Redirected from ML063380449)
Jump to navigation Jump to search

Special Report 06-04: Results of Steam Generator Tube Eddy Current Inspections During Unit 1 Thirteenth Refueling Outage
ML063380449
Person / Time
Site: Diablo Canyon Pacific Gas & Electric icon.png
Issue date: 11/27/2006
From: Jacobs D
Pacific Gas & Electric Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
DCL-06-131, OL-DPR-80
Download: ML063380449 (88)


Text

1 I a Pacific Gas and Electric Company' November 27, 2006 Donna Jacobs Vice President Nuclear Services Diablo Canyon Power Plant P. 0. Box 56 Avila Beach, CA 93424 805.545.4600 Fax: 805.545.4234 PG&E Letter DCL-06-131 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Docket No. 50-275, OL-DPR-80 Diablo Canyon Unit 1 Special Report 06-04: Results of Steam Generator Tube Eddy Current Inspections During Unit 1 Thirteenth Refueling Outage

Dear Commissioners and Staff:

In accordance with Diablo Canyon Power Plant Technical Specification 5.6.10.b, this Special Report provides the results of steam generator (SG) tube eddy current inspections performed during the Unit 1 Thirteenth Refueling Outage (1 R1 3).

SG inspections and repairs were completed in November 2005.

The enclosed tables provide the number and extent of tubes inspected in each SG, the location and percent through-wall penetration as applicable of each indication identified, and the identification of tubes plugged.

Pacific Gas and Electric Company (PG&E) Letter DCL-06-029, dated February 24, 2006, provided detailed 1 R13 condition monitoring and operational assessment reports for all degradation mechanisms, as supplemented by additional information in PG&E Letter DCL-06-080, dated June 23, 2006.

If you have any questions, please contact John Arhar at (805) 545-4629.

Sincerely, Jacobs A member of the STARS (Strategic Teaming and Resource Sharing)

Alliance Callaway

  • Comanche Peak
  • Diablo Canyon
  • Palo Verde
  • Wolf Creek

Document Control Desk November 27, 2006 Page 2 PG&E Letter DCL-06-131 ddm/469/A0603007 Enclosure cc:

Diablo Distribution cc/enc:

Terry W. Jackson, NRC, Senior Resident Inspector Bruce S. Mallett, NRC, Region IV Alan B. Wang, NRR, Project Manager State of California, Pressure Vessel Unit A member of the STARS (Strategic Teaming and Resource Sharing)

Alliance Callaway

  • Comanche Peak o Diabto Canyon e Palo Verde
  • Wolf Creek

Enclosure PG&E Letter DCL-06-131 SPECIAL REPORT 06-04 RESULTS OF STEAM GENERATOR TUBE EDDY CURRENT INSPECTIONS DURING UNIT 1 THIRTEENTH REFUELING OUTAGE

Enclosure PG&E Letter DCL-06-131 Introduction Technical Specification 5.6.10.b requires that the results of steam generator (SG) tube inspections be submitted to the NRC within 12 months following completion of the inspection. The report shall include:

1. Number and extent of tubes inspected,
2. Location and percent of wall thickness penetration for each indication of an imperfection, and
3. Identification of tubes plugged.

Table 1 provides the number and extent of tubes inspected in each SG. Table 2 provides the location and percent through-wall of each indication identified, and identifies the tubes that were plugged in the Unit 1 Thirteenth Refueling Outage (1 R1 3) and the reason for plugging. Some tubes were preventively plugged with no reportable indications in the tube.

Pacific Gas and Electric Company (PG&E) Letter DCL-06-029, dated February 24, 2006, provided detailed 1 R1 3 condition monitoring and operational assessment reports for all degradation mechanisms, as supplemented by additional information in PG&E Letter DCL-06-080, dated June 23, 2006.

Abbreviations and Terms The following provides a definition of abbreviations and terms that could be used in Tables 1 and 2. Some codes may not have been used because they were not applicable in this inspection. Bobbin distorted outside diameter support signals at the tube support plate (TSP) intersection, and bobbin inside diameter support signals at a dented TSP intersection that were not confirmed by Plus Point, are not reportable indications; however, they are included in this report for completeness. Historical free span indications that had eddy current signals traceable to preservice inspection data (e.g., manufacturing burnish mark) are not considered as reportable indications and are not included in this report.

Enclosure PG&E Letter DCL-06-131 Abbreviations and Terms (continued)

Abbreviation Term Description SG Steam Generator (SG)

Row Row Col Column Ind Indication Loc Location (or elevation) in SG Inch Distance above or below the center line of the TSP or the top of tubesheet, inches Deg Phase angle, degree Cal Calibration group Bobbin Differential inside diameter coil probe PP Plus Point rotating probe TSP (1 H, Tube support plate. There are 7 TSPs, identified by number from 1C,.

bottom to top of SG followed by H (hot leg) or C (cold leg).

TSH Top of tubesheet hot leg TSC Top of tubesheet cold leg TEH Tube end hot leg ID OD Location of indication on tube surface, either inside diameter (ID) or outside diameter (OD)

%TW (TWD)

Depth of indication as percent through-wall, associated with either cold leg thinning (CLT) at cold leg TSPs, or antivibration bar (AVB) wear in the U-bend region.

SAI Single axial indication Note: SAI may be left in service for the following reasons:

" Voltage-based ARC for axial outside diameter stress corrosion cracking (ODSCC) at TSP intersections C

" W* ARC for axial primary water stress corrosion cracking (PWSCC) in WEXTEX tubesheet

  • PWSCC ARC for axial PWSCC at dented TSP intersections SCI Single circumferential indication SVI Single volumetric indication (not associated with cold leg thinning)

VOL Volumetric indication (associated with cold leg thinning)

AONDB Axial ODSCC not detected by bobbin coil DIS Distorted ID signal at a dented TSP intersection DOS Distorted OD signal at TSP intersection FSI Free span indication DNI Ding with possible indication MBI Manufacturing burnish mark indication PLP Potential loose part indication PVN Permeability variation Enclosure PG&E Letter DCL-06-131 Table I Extent of Tube Inspections During 1 R13 Number and Scope Probe SG 1-1 SG 1-2 SG 1-3 SG 1-4 Full length (except Rows 1 Bobbin 100%

100%

100%

100%

and 2 U-bends)

Rows 1 to 10 U-bends Plus Point 100%

100%

100%

100%

Repeat PWSCC indications Plus Point 100%

100%

100%

100%

at dents and top of tubesheet PlusPoint_100%

100%_100%_100%

Hot leg top-of tubesheet Plus Point 100%

100%

100%

100%

>5 volt dented TSP Plus Point 100% 1 H to 4H, 100% 1H to 7C, 20% 1H to 7H 100% 1H to 6H, intersections (Note 1) 20% 5H to 7H 20% 6C 2

20% 7H

>2 and <5 volt dented TSP Plus Point 100% 1H to 4H, 100% 1H to 7C, 100% 1H to 6H, intersections (Note 1) 20% 5H 20% 6C 20% 1H 20% 7H 100% of DOS 100% of DOS 100% of DOS 100% of DOS Distorted OD bobbin signals Plus Point greater than or greater than or greater than or greater than or (DOS) at TSP intersections equal to 1.7 equal to 1.7 equal to 1.7 equal to 1.7 bobbin volts bobbin volts bobbin volts bobbin volts Distorted ID bobbin signals Plus Point 100%

100%

100%

100%

(DIS) at TSP intersections

>5 volt free span dings Plus Point 20%

20%

20%

20%

>2 volt dings at AVB Plus Point 20%

20%

20%

20%

structures TSP ligament indications Plus Point 100%

100%

100%

100%

Free span bobbin indications (FSI, MBI, DNI) that are new Plus Point 100%

100%

100%

100%

or exhibit growth or change Note 1: For each 20% sample, inspected at least 50 dents, or else inspected 100% if there were less than 50 dents.

Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 1

33 SAI 0.24 2H

-0.03 104 PP 57 OD 11 1

33 DOS 0.4 2H

-0.04 43 Bobbin 6

OD 11 1

38 DOS 0.93 3H 0.04 43 Bobbin 6

OD 11 1

53 DOS 0.46 2H

-0.02 51 Bobbin 4

OD 11 1

53 DOS 0.63 3H

-0.2 105 Bobbin 4

OD 11 1

53 DOS 0.3 4H

-0.04 83 Bobbin 4

OD 11 1

67 DOS 1.46 2H 0.06 83 Bobbin 4

OD 11 1

69 DOS 1.01 3H 0.02 129 Bobbin 4

OD 11 2

18 DOS 0.39 4H 0

74 Bobbin 6

OD 11 2

26 SAI 0.15 2H

-0.14 109 PP 28 OD 11 2

26 SAI 0.3 2H

-0.08 125 PP 28 OD 11 2

36 DOS 0.87 2H 0.04 44 Bobbin 6

OD 11 2

37 DOS 0.6 1H

-0.04 48 Bobbin 5

OD 11 2

41 SAI 0.26 TSH

-1.36 28 PP 28 ID 11 2

44 DOS 0.45 1H

-0.04 94 Bobbin 6

OD 11 2

53 DOS 0.33 1H 0.04 84 Bobbin 3

OD 11 2

53 DOS 0.47 2H 0

106 Bobbin 3

OD 11 2

54 DOS 1.06 3H

-0.02 72 Bobbin 4

OD 11 2

55 DOS 0.36 1H

-0.02 79 Bobbin 3

OD 11 2

55 DOS 0.41 2H

-0.08 95 Bobbin 3

OD 11 2

57 DOS 0.3 1H

-0.06 77 Bobbin 3

OD 11 2

58 SAI 0.59 1H

-0.04 99 Pp 51 OD 11 2

58 DOS 0.51 1H

-0.1 122 Bobbin 12 OD 11 2

59 SAI 0.46 1H

-0.17 94 Pp 51 OD 11 2

59 SAI 0.52 1H

-0.01 102 PP 51 OD 11 2

59 DOS 0.62 1H

-0.08 124 Bobbin 4

OD 11 2

61 DOS 0.61 1H

-0.04 105 Bobbin 3

OD 11 2

61 DOS 0.29 2H

-0.02 99 Bobbin 3

OD 11 2

62 SAI 0.48 1H

-0.25 116 PP 51 OD 11 2

62 DOS 0.42 1H

-0.22 97 Bobbin 3

OD 11 2

63 DOS 1.02 1H

-0.06 105 Bobbin 3

OD 11 2

64 DOS 0.68 1H

-0.2 130 Bobbin 4

OD 11 2

66 DOS 1.26 2H 0.04 97 Bobbin 4

OD 11 2

66 DOS 0.62 3H

-0.06 128 Bobbin 4

OD 11 2

67 DOS 0.46 1H 0

99 Bobbin 3

OD 11 2

68 DOS 1.19 2H

-0.24 92 Bobbin 4

OD 11 2

68 DOS 0.37 3H

-0.02 83 Bobbin 4

OD 11 2

71 DOS 0.38 2H

-0.04 125 Bobbin 3

OD 11 2

78 DOS 0.65 1H 0.1 49 Bobbin 4

OD 11 2

88 DOS 0.31 2H 0

107 Bobbin 6

OD 11 2

92 DOS 0.6 2H

-0.1 94 Bobbin 6

OD 11 3

2 DOS 0.43 1H

-0.08 43 Bobbin 5

OD 11 3

2 SAI 0.81 TSH

-1.22 21 Pp 11 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 3

3 DOS 0.83 2H

-0.06 64 Bobbin 6

OD 11 3

7 DOS 0.4 1 H 0

122 Bobbin 6

OD 11 3

18 DOS 0.58 1H 0.06 65 Bobbin 5

OD 11 3

22 DOS 0.6 2H

-0.06 51 Bobbin 5

OD 11 3

22 DOS 0.87 4H

-0.26 93 Bobbin 5

OD 11 3

28 SAI 0.64 2H

-0.12 15 PP 11 ID 11 3

28 DIS 1.17 2H

-0.16 21 Bobbin 5

ID 11 3

39 DOS 0.34 4H

-0.08 76 Bobbin 6

OD 11 3

41 SAI 0.3 1H 0

110 Pp 27 OD 11 3

41 DOS 0.32 1H 0.02 94 Bobbin 5

OD 11 3

41 DOS 0.31 2H

-0.04 41 Bobbin 5

OD 11 3

45 DOS 1.2 1H

-0.08 102 Bobbin 5

OD 11 3

47 DOS 0.29 1H 0.02 126 Bobbin 6

OD 11 3

48 DOS 0.8 1H 0

72 Bobbin 6

OD 11 3

48 DOS 0.32 3H

-0.06 96 Bobbin 6

OD 11 3

50 DOS 0.34 1H

-0.02 68 Bobbin 5

OD 11 3

50 DOS 0.49 3H

-0.14 144 Bobbin 5

OD 11 3

52 DOS 0.39 1H 0

94 Bobbin 3

OD 11 3

52 DOS 0.26 2H 0.02 103 Bobbin 3

OD 11 3

52 DOS 0.65 4H

-0.04 61 Bobbin 3

OD 11 3

53 DOS 0.36 1H

-0.02 40 Bobbin 4

OD 11 3

54 DOS 0.46 1H

-0.1 110 Bobbin 3

OD 11 3

56 DOS 1

1H

-0.06 101 Bobbin 3

OD 11 3

59 DOS 1.47 1H 0

86 Bobbin 3

OD 11 3

60 SAI 0.3 1H 0.05 102 PP 63 OD 11 3

60 SAI 0.51 1H 0.06 94 PP 63 OD 11 3

60 SAI 0.88 1H 0.08 90 PP 63 OD 11 3

60 DOS 1.88 1H 0.04 85 Bobbin 4

OD 11 3

61 DOS 0.2 2H

-0.08 98 Bobbin 4

OD 11 3

62 SAI 0.23 1H

-0.05 114 Pp 51 OD 11 3

62 DOS 0.17 1H

-0.06 147 Bobbin 4

OD 11 3

63 DOS 1.2 1H

-0.12 79 Bobbin 4

OD 11 3

64 DOS 0.28 1H 0

83 Bobbin 3

OD 11 3

69 DOS 1.26 1H 0.04 97 Bobbin 4

OD 11 3

80 DOS 1.4 2H 0.2 112 Bobbin 3

OD 11 3

88 DOS 0.77 1H

-0.02 126 Bobbin 5

OD 11 3

94 VOL 0.21 2C 0.06 130 PP 74 OD 11 3

94 TWD 5

0.29 2C

-0.06 139 Bobbin 9

OD 11 4

6 PVN 11.46 5C 8.49 15 Bobbin 4

11 4

7 DOS 0.21 1H

-0.06 85 Bobbin 5

OD 11 4

8 DOS 0.56 1H 0

74 Bobbin 6

OD 11 4

16 DIS 0.56 6H

-0.06 27 Bobbin 6

ID 11 4

17 DOS 0.82 1H 0.06 60 Bobbin 5

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 4

20

SAL, 0.22 1H 0

104 PP 26 OD 11 4

20 DOS 0.2 1H

'-0.04 92 Bobbin 6

OD 11 4

20 DOS 0.73 2H

-0.1 41 Bobbin 6

OD 11 4

24 DOS 0.53 4H

-0.16 78 Bobbin 6

OD 11 4

29 DOS 0.41 2H

-0.1 107 Bobbin 5

OD 11 4

31 DOS 0.24 2H

-0.08 100 Bobbin 5

OD 11 4

32 DOS 0.88 2H

-0.2 111 Bobbin 6

OD 11 4

41 SAI 0.43 1H

-0.02 6

PP 11 ID 11 4

44 SAI 0.18 TSH

-0.07 97 PP 28 OD SAI-OD @TSH-0.07 11 4

45 DOS 1.01 1H

-0.06 46 Bobbin 6

OD 11 4

47 SAI 0.18 1H 0.03 114 PP 26 OD 11 4

47 DOS 0.46 1H

-0.04 54 Bobbin 5

OD 11 4

49 DOS 0.92 1H 0.02 84 Bobbin 6

OD 11 4

49 DOS 0.34 3H 0.02 92 Bobbin 6

OD 11 4

55 DOS 0.85 1H 0

92 Bobbin 3

OD 11 4

61 SAI 0.33 1H 0.06 102 PP 63 OD 11 4

61 SAI 0.63 1H

-0.05 99 PP 63 OD 11 4

61 DOS 1.73 1H 0.02 122 Bobbin 3

OD 11 4

63 DOS 0.41 1H 0

60 Bobbin 3

OD 11 4

65 DOS 0.22 1H 0.02 60 Bobbin 3

OD 11 4

69 DOS 1.37 1H

-0.12 83 Bobbin 3

OD 11 4

75 SAI 0.16 1H

-0.02 120 PP 51 OD 11 4

75 SAI 0.19 1H

-0.03 109 PP 51 OD 11 4

75 DOS 0.2 1H

-0.04 109 Bobbin 3

OD 11 4

76 DOS 0.46 2H

-0.08 98 Bobbin 4

OD 11 4

80 SAI 1.27 1H

-0.03 80 PP 63 OD 11 4

80 DOS 1.75 1H

-0.04 79 Bobbin 4

OD 11 4

83 SAI 0.16 1H

-0.06 107 PP 51 OD 11 4

83 DOS 0.28 1H

-0.06 115 Bobbin 12 OD 11 4

92 TWD 5

0.3 1C 0.08 121 Bobbin 9

OD 40%TW CLT @2C 11 4

92 TWD 40 3.12 2C

-0.04 117 Bobbin 9

OD 40%TWCLT@2C 11 4

93 TWD 7

0.43 1C

-0.06 139 Bobbin 10 OD 11 4

94 TWD 16 1.03 2C 0.1 125 Bobbin 10 OD 11 5

2 SAI 0.13 1H

-0.16 88 PP 27 OD 11 5

2 SAI 0.23 1H

-0.06 106 PP 27 OD 11 5

2 SAI 0.27 1H 0.03 97 PP 27 OD 11 5

2 DOS 0.63 1H

-0.04 110 Bobbin 5

OD 11 5

2 DIS 1.18 5H

-0.02 16 Bobbin 5

ID 11 5

4 DOS 0.41 1H 0

80 Bobbin 5

OD 11 5

9 DOS 0.24 2H

-0.02 64 Bobbin 5

OD 11 5

10 DIS 1.32 2H 0.06 12 Bobbin 5

ID 11 5

12 DOS 0.88 2H

-0.1 118 Bobbin 5

OD 11 5

20 DOS 0.42 1H 0

91 Bobbin 5

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 5

23 DOS 0.61 2H

-0.16 86 Bobbin 5

OD 11 5

34 SAI 0.1 1H

-0.1 113 PP 27 OD 11 5

34 SAI 0.23 1H 0.01 114 PP 27 0D 11 5

34 DOS 0.32 1H 0

31 Bobbin 5

0D 11 5

35 DOS 1.15 1H

-0.06 69 Bobbin 5

OD 11 5

38 DOS 0.53 3H

-0.14 106 Bobbin 12 OD 11 5

39 DOS 0.66 3H

-0.24 102 Bobbin 5

OD 11 5

43 SAI 0.78 1H

-0.04 99 PP 27 0D 11 5

43 DOS 1.42 1H

-0.06 90 Bobbin 5

OD 11 5

49 DOS 1.13 2H

-0.02 92 Bobbin 5

0D 11 5

51 DOS 0.28 3H

-0.02 93 Bobbin 3

0D 11 5

53 DOS 1.09 1H 0.04 100 Bobbin 3

O0 11 5

54 DOS 1.17 1H

-0.06 98 Bobbin 3

OD 11 5

59 DOS 1.2 1H 0.04 110 Bobbin 3

0D 11 5

59 DOS 0.78 2H

-0.2 96 Bobbin 3

OD 11 5

61 DOS 0.56 1H 0.08 96 Bobbin 3

OD 11 5

63 DOS 0.88 1H 0.06 88 Bobbin 4

OD 11 5

64 DOS 0.84 1H

-0.2 113 Bobbin 3

OD 11 5

66 SAI 1.62 1H

-0.04 78 Pp 63 OD sAI-OD,>2v DOS @1H 11 5

66 DOS 2.06 1H

-0.08 93 Bobbin 3

OD SAI-OD,>2v DOS @IH 11 5

66 DOS 0.17 2H

-0.08 90 Bobbin 3

OD SAI-OD,>2v DOS @1H 11 5

67 DOS 0.4 1H 0

105 Bobbin 3

OD 11 5

68 DOS 1.32 1H 0.06 108 Bobbin 3

OD 11 5

69 DOS 1.28 1H

-0.14 106 Bobbin 3

OD 11 5

71 DOS 0.33 1H

-0.06 69 Bobbin 3

OD 11 5

72 SAI 0.21 1H

-0.11 108 PP 63 OD sAI-OD,>2v DOS @1H 11 5

72 SAi 0.27 1H

-0.25 106 pp 63 OD, SAI-OD,>2v DOS @IH 11 5

72 SAI 0.72 1H 0.04 99 PP 63 OD SAI-OD,>2v DOS @1H 11 5

72 SAI 0.77 1H

-0.21 90 PP 63 OD SAI-OD,>2v DOS @1H 11 5

72 SAI 1.08 1H

-0.21 82 PP 63 OD SAI-OD,>2v DOS @1H 11 5

72 DOS 2.02 1H

-0.24 92 Bobbin 3

OD SAI-OD,>2v DOS @I H 11 5

72 DOS 0.57 2H 0

91 Bobbin 3

OD SAI-OD,>2v DOS @I H 11 5

76 DOS 0.97 1H 0.02 105 Bobbin 3

OD 11 5

80 DOS 0.99 2H 0

95 Bobbin 3

OD 11 5

82 DOS 1.66 1H

-0.12 97 Bobbin 3

OD 11 5

83 DOS 0.65 1H 0.04 111 Bobbin 5

OD 11 5

87 DOS 0.27 2H

-0.12 136 Bobbin 5

OD 11 5

91 SAI 0.16 2H 0.29 108 PP 53 OD 11 5

94 TWD 10 0.63 IC 0.04 137 Bobbin 9

OD 11 5

94 TWD 12 0.79 2C 0.06 149 Bobbin 9

OD 11 6

15 DOS 0.72 1H 0.2 91 Bobbin 22 OD 11 6

21 DIS 0.85 1H 0.06 28 Bobbin 21 ID 11 6

21 DOS 0.61 4H

-0.18 101 Bobbin 21 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc inch Deg Probe Cal IDOD Reason for Plugging 11 6

25 DOS 0.65 2H 0

55 Bobbin 21 OD.

11 6

27 DOS 0.85 1H

-0.1 70 Bobbin 24 OD 11 6

31 SAI 0.38 1H

-0.02 99 PP 22 OD 11 6

31 DOS 0.94 1H 0.03 35 Bobbin 24 OD 11 6

32 DOS 0.42 2H 0.01 77 Bobbin 24 OD 11 6

33 SAI 0.14 4H 0.14 104 PP 57 OD 11 6

33 DOS 0.43 4H 0.03 67 Bobbin 23 OD 11 6

40 SAI 0.2 1H

-0.03 118 PP 24 OD 11 6

40 DOS 0.48 1H

-0.06 93 Bobbin 24 OD 11 6

41 DOS 0.45 1H 0.06 64 Bobbin 23 OD 11 6

43 DOS 0.73 1H 0.04 83 Bobbin 25 OD 11 6

44 DOS 0.36 2H 0.08 67 Bobbin 25 OD 11 6

46 SCI 0.22 TSH

-0.02 106 PP 26 OD SCI-OD @TSH-0.02 11 6

47 SCI 0.38 TSH

-0.08 86 PP 26 OD SCI-OD @TSH-0.08 11 6

62 DOS 0.77 1H

-0.08 117 Bobbin 33 OD 11 6

67 SAI 0.14 1H 0.07 131 PP 38 OD 11 6

68 DOS 0.46 1H 0.02 73 Bobbin 33 OD 11 6

71 DOS 0.9 1H 0

98 Bobbin 33 OD 11 6

73 DOS 1.05 1H 0.1 89 Bobbin 33 OD 11 6

74 DOS 0.62 1H

-0.06 129 Bobbin 33 OD 11 6

76 DOS 1

1H 0.06 83 Bobbin 33 OD 11 6

81 DOS 0.5 2H 0.06 81 Bobbin 33 OD 11 6

86 DOS 0.96 2H 0

100 Bobbin 33 OD 11 6

88 DOS 0.28 2H 0.08 65 Bobbin 33 OD 11 6

92 DOS 0.29 2H 0.06 121 Bobbin 34 OD 11 6

93 TWD 13 0.83 lC 0.1 145 Bobbin 34 OD 11 7

10 SAI 0.12 1H

-0.03 120 PP 19 OD 11 7

10 DOS 0.34 1H 0.03 67 Bobbin 21 OD 11 7

12 DOS 0.2 1H 0.06 89 Bobbin 21 OD 11 7

16 DOS 0.49 4H

-0.17 126 Bobbin 21 OD 11 7

18 DOS 0.58 1H

-0.11 50 Bobbin 21 OD 11 7

18 DOS 0.41 2H 0.01 42 Bobbin 21 OD 11 7

27 DOS 0.4 1H

-0.08 112 Bobbin 23 OD 11 7

28 DOS 0.53 1H 0.1 62 Bobbin 23 OD 11 7

28 DOS 0.66 2H 0.06 88 Bobbin 23 OD 11 7

31 DOS 1.04 1H 0

74 Bobbin 23 OD 11 7

37 SAI 0.4 3H

-0.13 101 PP 57 OD 11 7

37 DOS 1.04 3H

-0.1 68 Bobbin 23 OD 11 7

39 DOS 1.19 1H 0

88 Bobbin 23 OD 11 7

49 DOS 0.49 6H

-0.29 125 Bobbin 36 OD 11 7

51 DOS 0.5 1H 0.04 77 Bobbin 35 OD 11 7

56 DOS 0.51 2C

-0.04 44 Bobbin 34 OD 11 7

57 DOS 0.49 3H 0.06 125 Bobbin 34 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 7

62 DOS 1.3 1H

-0.02 73 Bobbin 32 OD 11 7

63 DOS 0.6 1H 0.06 88 Bobbin 32 OD 11 7

68 SAI 0.31 1H

-0.08 108 PP 56 OD 11 7

68 SAI 0.36 1H

-0.18 98 PP 56 OD 11 7

68 DIS 0.33 1H 0.06 26 Bobbin 32 ID 11 7

73 DOS 0.51 1H

-0.02 95 Bobbin 32 OD 11 7

77 DOS 1.17 2H 0.14 94 Bobbin 32 OD 11 7

78 DOS 0.86 2H 0.08 75 Bobbin 33 OD 11 7

81 DOS 0.81 2H 0.08 110 Bobbin 32 OD 11 7

82 SAI 0.77 1H

-0.04 90 PP 41 0D 11 7

82 DOS 1.25 1H 0.02 115 Bobbin 32 OD 11 7

85 SAI 0.27 1H 0.03 102 PP 41 OD 11 7

85 DOS 0.41 1H 0.08 161 Bobbin 32 OD 11 8

2 TWD 7

0.41 2C

-0.1 139 Bobbin 22 0D 11 8

11 SAI 0.15 1H 0

113 PP 20 0D 11 8

11 DOS 0.46 1H 0.01 147 Bobbin 21 0D 11 8

24 SAI 0.1 2H 0.01 118 PP 68 0D 11 8

24 SAI 0.12 2H 0.02 116 PP 68 OD 11 8

24 DOS 0.27 2H 0.04 56 Bobbin 22 OD 11 8

31 DOS 0.33 3H 0

88 Bobbin 24 OD 11 8

32 SAI 0.13 3H 0.04 118 PP 22 OD 11 8

32 DOS 0.5 3H

-0.06 39 Bobbin 24 OD 11 8

42 SAI 0.12 1H

-0.01 102 PP 24 OD 11 8

42 SAI 0.25 1H 0.12 106 PP 24 OD 11 8

42 DOS 0.48 1H 0.06 73 Bobbin 24 OD 11 8

45 DOS 0.33 3H 0.04 61 Bobbin 26 OD 11 8

57 SAI 0.1 1H 0.06 108 PP 57 OD SAI-OD,>2v DOS @1H 11 8

57 SAI 0.27 1H

-0.02 95 PP 57 OD SAI-OD,>2v DOS @1H 11 8

57 SAI 1.67 1 H

-0.04 60 PP 57 OD SAI-OD,>2v DOS @1 H 11 8

57 DOS 2.43 1H 0.04 63 Bobbin 41 OD SAI-OD,>2v DOS @1 H 11 8

58 DOS 1.01 1H 0.12 95 Bobbin 35 OD 11 8

59 DOS 0.33 2H 0

114 Bobbin 35 OD 11 8

64 DOS 0.58 1H 0.12 111 Bobbin 33 OD 11 8

68 DOS 0.25 1H 0.04 83 Bobbin 33 OD 11 8

77 DOS 0.34 1H 0.02 112 Bobbin 33 OD 11 8

77 DOS 0.36 2H 0.06 52 Bobbin 33 OD 11 8

81 DOS 0.62 2H 0

101 Bobbin 33 OD 11 9

8 DOS 0.18 2H

-0.08 142 Bobbin 5

OD 11 9

14 DOS 0.26 2H

-0.1 90 Bobbin 5

OD 11 9

17 DOS 0.64 2H

-0.04 73 Bobbin 5

OD 11 9

20 DOS 0.54 1H 0.1 98 Bobbin 26 OD 11 9

20 DOS 0.9 2H

-0.01 85 Bobbin 26 OD 11 9

26 DOS 0.41 1H

-0.08 45 Bobbin 60 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 9

28 DOS 0.19 3H

-0.12 103 Bobbin 60 OD 11 9

43 SAI 0.18 1H 0.14 86 PP 26 OD 11 9

43 DOS 0.6 2H

-0.08 82 Bobbin 60 OD 11 9

47 DOS 0.42 2H

-0.07 112 Bobbin 60 OD 11 9

48 DOS 0.29 2H 0.04 80 Bobbin 36 OD 11 9

54 DOS 0.37 1H 0.02 135 Bobbin 34 OD 11 9

56 DOS 0.22 1 H 0.04 87 Bobbin 34 OD 11 9

57 DOS 0.57 1H 0.06 72 Bobbin 34 OD 11 9

67 DOS 1.45 1H

-0.08 97 Bobbin 33 OD 11 9

69 DOS 0.38 2H 0.02 67 Bobbin 32 OD 11 9

71 DOS 0.39 1H 0.1 101 Bobbin 32 OD 11 9

82 SAI 0.48 1H

-0.01 93 PP 41 OD 11 9

82 DOS 0.84 1H 0.02 95 Bobbin 32 OD 11 9

92 TWD 12 0.75 1C

-0.16 155 Bobbin 34 OD 11 9

93 TWD 7

0.45 1C

-0.27 143 Bobbin 35 OD 11 10 7

DOS 0.38 1H 0

88 Bobbin 22 OD 11 10 10 DOS 0.17 1H 0.06 66 Bobbin 22 OD 11 10 15 DOS 0.34 1H

-0.04 73 Bobbin 22 OD 11 10 15 DOS 0.45 2H

-0.03 75 Bobbin 22 OD 11 10 16 DOS 0.54 2H

-0.01 114 Bobbin 22 OD 11 10 23 DOS 0.62 2H 0.07 59 Bobbin 22 OD 11 10 23 DOS 0.59 3H

-0.01 86 Bobbin 22 OD 11 10 28 SAI 0.16 1H 0.02 112 PP 22 OD 11 10 28 DOS 0.31 1H 0.13 73 Bobbin 24 OD 11 10 28 DOS 0.68 2H 0.04 82 Bobbin 24 OD 11 10 39 SAI 1.18 1H 0.03 65 PP 23 OD 11 10 39 DOS 1.48 1H 0.09 70 Bobbin 41 OD 11 10 39 SAI 0.13 2H 0

105 PP 68 OD 11 10 39 SAI 0.27 2H

-0.03 94 PP 68 OD 11 10 39 DOS 0.45 2H 0.04 69 Bobbin 41 OD 11 10 39 DOS 0.49 2H 0

61 Bobbin 24 OD 11 10 45 DIS 0.89 2H 0.06 21 Bobbin 25 ID 11 10 48 DOS 0.26 2H 0.02 67 Bobbin 36 OD 11 10 62 DOS 0.37 1H 0

88 Bobbin 33 OD 11 10 68 DOS 1.46 1H

-0.1 88 Bobbin 33 0D 11 10 70 DOS 0.37 3H 0

77 Bobbin 33 0D 11 10 74 DOS 0.95 1H 0.02 95 Bobbin 33 OD 11 10 76 DOS 1.44 1H 0.13 97 Bobbin 33 OD 11 10 81 DOS 0.32 1H

-0.02 59 Bobbin 33 OD 11 10 85 SAI 0.32 1H 0.06 91 PP 42 OD 11 10 85 DOS 0.54 1H 0.1 141 Bobbin 33 OD 11 10 92 TWD 8

0.51 1C

-0.18 161 Bobbin 35 OD 11 10 93 TWD 19 1.25 1C

-0.26 133 Bobbin 34 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 11 4

DOS 0.73 1H 0.08 41 Bobbin 21 OD 11 11 8

DOS 0.3 1H 0.07 96 Bobbin 21 OD 11 11 15 SAI 0.29 3H

-0.35 106 PP 19 OD 11 11 22 SAI 0.12 2H

-0.16 108 PP 56 OD 11 11 22 SAI 0.18 2H 0.05 120 PP 56 OD 11 11 22 DOS 0.79 2H

-0.04 50 Bobbin 21 OD 11 11 29 DOS 0.84 2H 0

78 Bobbin 23 OD 11 11 38 DOS 0.39 1H 0.04 79 Bobbin 23 OD 11 11 40 SAI 0.26 2H

-0.09 108 PP 57 OD 11 11 40 SAI 0.28 2H

-0.01 102 PP 63 OD 11 11 40 DOS 1.17 2H 0.06 28 Bobbin 23 OD 11 11 43 DOS 0.39 1H 0.06 55 Bobbin 25 OD 11 11 53 DOS 0.73 1H

-0.02 92 Bobbin 34 OD 11 11 53 DOS 0.55 3H 0.02 57 Bobbin 34 OD 11 11 58 DOS 0.93 1H 0.12 107 Bobbin 34 OD 11 11 58 DOS 0.44 2H 0.08 114 Bobbin 34 OD 11 11 59 DOS 0.99 1H 0.06 76 Bobbin 34 OD 11 11 60 DOS 0.26 1H

-0.06 110 Bobbin 33 OD 11 11 60 DOS 0.38 3H 0.02 66 Bobbin 33 OD 11 11 62 DOS 0.47 1H 0.02 77 Bobbin 32 OD 11 11 62 DOS 1.01 2H 0.04 66 Bobbin 32 OD 11 11 64, DOS 0.45 1H 0.22 111 Bobbin 32 OD 11 11 65 DOS 1.47 1H 0.08 63 Bobbin 32 OD 11 11 67 DOS 0.6 1H

-0.08 67 Bobbin 33 OD 11 11 68 DOS 1.33 1H 0.1 78 Bobbin 32 OD 11 11 69 SCI 0.11 TSH 0.02 87 PP 38 OD SCI-OD @TSH+0.02 11 11 70 DOS 0.57 3H 0.06 114 Bobbin 32 OD 11 11 77 DOS 1.05 2H 0.04 70 Bobbin 32 OD 11 11 80 DOS 0.4 1H 0.04 114 Bobbin 32 OD 11 11 93 TWD 10 0.64 1C

-0.19 149 Bobbin 35 OD 11 12 2

SAI 0.23 1H

-0.21 110 PP 57 OD 11 12 2

SAI 0.9 1H 0.09 64 PP 57 OD 11 12 2

DOS 1.86 1H 0.08 53 Bobbin 36 OD 11 12 13 DOS 0.38 1H

-0.03 70 Bobbin 22 OD 11 12 27 DOS 0.52 2H 0.11 56 Bobbin 24 OD 11 12 31 DOS 0.36 2H 0.07 63 Bobbin 24 OD 11 12 48 DOS 0.27 2H 0.08 92 Bobbin 36 OD 11 12 63 SAI 0.1 2H 0.03 109 PP 56 OD 11 12 63 DOS 0.41 2H 0.02 64 Bobbin 33 OD 11 12 67 DOS 1.12 1H

-0.06 101 Bobbin 32 OD 11 12 67 DOS 0.93 3H 0

98 Bobbin 32 OD 11 12 70 SAI 0.41 1H 0.07 93 PP 56 OD SAI-OD,>2v DOS @1H 11 12 70 SAI 0.59 1H 0.06 101 PP 56 OD SAI-OD,>2v DOS @1H

-11

Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 12 70 SAI 1.51 1H 0.06 76 PP 56 OD SAI-OD,>2v DOS @1H 11 12 70 DOS 2.59 1H 0.08 80 Bobbin 33 OD SAI-OD,>2v DOS @1H 11 12 73 DOS 0.55 1H 0

102 Bobbin 33 OD 11 12 74 DOS 1.07 2H

-0.04 122 Bobbin 33 OD 11 12 76 DOS 0.51 1H 0.12 72 Bobbin 33 OD 11 12 78 DOS 0.41 2H 0.1 97 Bobbin 32 OD 11 12 91 TWD 19 1.26 1C

-0.18 136 Bobbin 35 OD 11 12 92 DIS 0.42 1H 0.08 23 Bobbin 35 ID 11 13 14 DOS 0.64 2H 0.14 80 Bobbin 21 OD 11 13 17 DOS 0.55 3H

-0.17 55 Bobbin 21 OD 11 13 17 DOS 0.61 4H

-0.18 81 Bobbin 21 OD 11 13 22 DOS 0.22 4H

-0.01 94 Bobbin 21 OD 11 13 23 DOS 0.68 1H

-0.06 83 Bobbin 21 OD 11 13 23 DOS 0.42 4H

-0.2 78 Bobbin 21 OD 11 13 24 DOS 0.56 1H

-0.13 114 Bobbin 21 OD 11 13 24 DOS 0.42 3H 0.1 124 Bobbin 21 OD 11 13 26 DOS 0.35 1H 0.19 128 Bobbin 23 OD 11 13 32 DOS 0.71 2H 0.04 57 Bobbin 23 OD 11 13 41 SAI 0.19 2H 0.21 98 PP 23 OD 11 13 41 DOS 0.21 2H 0.22 109 Bobbin 23 OD 11 13 41 DOS 0.96 4H 0.06 87 Bobbin 23 OD 11 13 44 SAI 0.13 2H 0.02 126 PP 68 OD 11 13 44 DOS 0.38 2H 0.1 76 Bobbin 25 OD 11 13 44 DOS 1.03 3H 0.03 45 Bobbin 25 OD 11 13 47 SCI 0.22 TSH 0

122 PP 25 OD SCI-OD @TSH-0.00 11 13 52 DOS 0.84 2H

-0.2 115 Bobbin 34 OD 11 13 53 DOS 0.35 1H 0.04 99 Bobbin 34 OD 11 13 53 DOS 0.5 2H 0.02 75 Bobbin 34 OD 11 13 56 DOS 1.08 1H 0.12 83 Bobbin 34 OD 11 13 58 DOS 0.81 1H 0.04 67 Bobbin 34 OD 11 13 59 DOS 0.6 1H 0.16 98 Bobbin 34 OD 11 13 61 DOS 0.83 1H 0.04 98 Bobbin 32 OD 11 13 77 DOS 1.06 1H 0.02 100 Bobbin 32 OD 11 13 77 DOS 0.65 2H 0

106 Bobbin 32 OD 11 13 81 DOS 1.49 1H 0.02 88 Bobbin 32 OD 11 13 81 DOS 0.42 2H

-0.06 72 Bobbin 32 OD 11 14 5

DOS 0.39 2H

-0.02 128 Bobbin 20 OD 11 14 6

SAI 0.23 2H 0.15 106 PP 57 OD SAI-ID/AONDB @2H 11 14 6

SAI 1.05 2H

-0.07 15 PP 57 ID SAI-ID/AONDB @2H 11 14 6

DIS 0.55 2H

-0.06 25 Bobbin 20 ID SAI-ID/AONDB @2H 11 14 13 DOS 0.69 1H 0

122 Bobbin 16 OD 11 14 15 DOS 0.24 4H 0.06 132 Bobbin 16 OD 11 14 20 DOS 0.5 1H

-0.06 71,1 Bobbin 1 16 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 14 20 DOS 0.32 3H 0.12 99 Bobbin 16 OD 11 14 24 SAI 0.28 2H 0.08 96 PP 56 OD 11 14 24 DOS 0.21 2H 0.2 96 Bobbin 18 OD 11 14 25 DOS 0.63 1H

-0.06 103 Bobbin 17 OD 11 14 26 SAI 0.26 2H 0.11 103 PP 57 OD 11 14 26 DOS 0.38 2H 0.12 64 Bobbin 18 OD 11 14 28 SAI 0.5 2H 0.21 9

PP 11 ID 11 14 42 DOS 0.25 1H 0.1 112 Bobbin 15 OD 11 14 52 DOS 0.38 1H

-0.04 116 Bobbin 35 OD 11 14 54 DOS 1.38 1H 0.06 86 Bobbin 35 OD 11 14 55 DOS 0.45 2H

-0.04 90 Bobbin 34 OD 11 14 59 DOS 0.37 1H 0

91 Bobbin 30 OD 11 14 62 DOS 0.45 1H 0

72 Bobbin 29 OD 11 14 62 SAI 0.13 2H

-0.08 106 PP 56 OD 11 14 62 DOS 0.41 2H 0.02 38 Bobbin 29 OD 11 14 63 SCI 0.2 TSH 0.02 135 PP 37 OD SCI-OD @TSH+0.02 11 14 66 DOS 0.31 1H 0

135 Bobbin 29 OD 11 14 66 DOS 0.34 3H 0.05 87 Bobbin 29 OD 11 14 69 DOS 0.39 2H 0.05 63 Bobbin 29 OD 11 14 70 DOS 0.32 1H 0.14 126 Bobbin 29 OD 11 14 77 DOS 0.48 1H 0.07 95 Bobbin 30 OD 11 14 78 DOS 0.97 1H 0.07 99 Bobbin 31 OD 11 14 80 SAI 0.2 1H

-0.23 106 PP 56 OD SAI-OD,>2v DOS @1H 11 14 80 SAI 0.23 1H

-0.11 114 PP 56 OD SAI-OD,>2v DOS @1H 11 14 80 SAI 0.94 1H 0.04 77 PP 56 OD SAI-OD,>2v DOS @1H 11 14 80 SAI 1.16 1H 0.04 85 PP 56 OD SAI-OD,>2v DOS @1H 11 14 80 DOS 2.3 1H 0.14 95 Bobbin 41 OD SAI-OD,>2v DOS @1H 11 14 83 SAI 0.44 1H

-0.14 104 PP 42 OD 11 14 83 DOS 0.9 1H

-0.07 69 Bobbin 31 OD 11 14 83 SAI 0.23 2H

-0.04 129 PP 42 OD 11 14 83 DOS 0.61 2H 0

152 Bobbin 31 OD 11 14 88 SAI 0.5 1H

-0.05 100 PP 41 OD 11 14 88 DOS 0.67 1H 0.05 88 Bobbin 31 OD 11 15 10 SAI 0.81 TSH

-9.11 16 PP 19 ID 11 15 10 SAI 1.32 TSH

-8.59 19 PP 19 ID 11 15 16 SAI 0.32 2H

-0.09 2

PP 11 ID 11 15 24 DOS 0.65 1H 0

85 Bobbin 17 OD SAI-ID/OD @2H 11 15 24 SAI 0.26 2H 0.07 118 PP 56 OD SAI-ID/OD @2H 11 15 24 SAI 0.87 2H

-0.11 12 PP 56 ID SAI-ID/OD @2H 11 15 24 DOS 0.65 2H

-0.06 41 Bobbin 17 OD SAI-ID/OD @2H 11 15 30 SAI 0.47 2H

-0.15 106 PP 57 OD 11 15 30 DOS 1.07 2H

-0.12 74 Bobbin 13 OD 11 15 31 DOS 0.83 2H

-0.04 81 Bobbin 13 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 15 40 DOS 0.26 1H 0.06 97 Bobbin 15 OD 11 15 42 DOS 0.58 1H 0.02 72 Bobbin 15 OD 11 15 61 SAI 0.23 1H

-0.01 119 PP 47 OD 11 15 61 DOS 0.5 1H 0.16 90 Bobbin 29 OD 11 15 63 DOS 0.39 1H 0.09 103 Bobbin 28 OD 11 15 65 DOS 1.49 1H 0.04 94 Bobbin 28 OD 11 15 66 DOS 0.34 1H 0

127 Bobbin 28 OD 11 15 68 DOS 0.7 1H 0.09 92 Bobbin 29 OD 11 15 71 DOS 0.5 1H

-0.06 112 Bobbin 30 OD 11 15 75 DOS 0.69 1H 0.02 105 Bobbin 30 OD 11 15 76 SAI 0.4 2H

-0.08 10 PP 11 ID 11 15 76 DIS 0.22 2H 0.02 41 Bobbin 30 ID 11 15 77 DOS 0.24 1H 0.09 121 Bobbin 31 OD 11 15 80 DOS 1.03 1H 0.07 95 Bobbin 30 OD 11 15 82 DOS 0.99 1H

-0.02 114 Bobbin 30 OD 11 15 88 DOS 0.69 2H 0.05 103 Bobbin 41 OD 11 15 92 TWD 11 0.7 1C

-0.15 145 Bobbin 30 OD 11 16 12 DOS 0.84 1H

-0.1 44 Bobbin 15 OD 11 16 22 DOS 0.39 2H 0.02 94 Bobbin 18 0D 11 16 27 DOS 0.48 1H 0.04 95 Bobbin 14 OD 11 16 27 DOS 1.27 2H 0

87 Bobbin 14 OD 11 16 31 DIS 0.55 2H 0

29 Bobbin 14 ID 11 16 57 DOS 0.37 2H 0.04 82 Bobbin 28 OD 11 16 58 SAI 0.17 1H

-0.23 116 PP 47 OD 11 16 60 DOS 0.48 1H 0.09 126 Bobbin 30 OD 11 16 62 DOS 0.37 1H

-0.02 100 Bobbin 28 OD 11 16 64 DOS 0.42 1H 0.14 98 Bobbin 29 OD 11 16 65 SCI 0.17 TSH

-0.05 87 PP.

37 OD SCI-OD @TSH-0.05 11 16 66 DOS 0.69 1H 0

106 Bobbin 29 OD SCI-OD @TSH+0.00 11 16 66 SCI 0.17 TSH 0

91 PP 39 OD SCI-OD @TSH+0.00 11 16 68 DOS 0.24 1H 0.09 89 Bobbin 28 OD 11 16 69 SAI 0.15 2H 0.17 134 PP 40 OD 11 16 70 DOS 0.59 1H 0.09 128 Bobbin 29 OD 11 16 79 SAI 0.13 2H

-0.11 78 PP 56 OD 11 16 79 DOS 0.5 2H m0.02 45 Bobbin 31 OD 11 16 80 DOS 0.66 2H 0.07 109 Bobbin 31 OD 11 16 82 DOS 0.32 1H 0.05 103 Bobbin 31 OD 11

.16 83 DOS 0.26 3H 0.05 97 Bobbin 31 OD 11 17 13 SAI 0.23 2H 0.17 104 PP 19 OD 11 17 16 SAI 0.94 2H

-0.13 13 PP 11 ID 11 17 16 DIS 0.52 2H

-0.04 38 Bobbin 15 ID 11 17 18 DOS 0.69 1H

-0.08 107 Bobbin 15 OD 11 17 19 DOS 0.22 1H 0.12 129 Bobbin 16 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 17 20 DIS 1.39 2H

-0.22 33 Bobbin 15 ID 11 17 21 DOS 0.25 1H 0.12 97 Bobbin 18 OD 11 17 24 SAI 0.22 2H

-0.27 116 PP 22 OD 11 17 24 DOS 0.67 2H

-0.22 39 Bobbin 17 OD 11 17 27 DIS 0.66 1H 0

21 Bobbin 13 ID 11 17 27 SAI 0.31 3H 0.12 99 PP 21 OD 11 17 27 DOS 0.8 3H 0.16 51 Bobbin 13 OD 11 17 28 SAI 0.27 2H

-0.16 95 PP 21 OD 11 17 30 DOS 0.36 1H 0.04 40 Bobbin 13 OD 11 17 35 TWD 14 0.26 7H 34.99 0

Bobbin 13 OD 11 17 41 DOS 0.68 1H 0.08 61 Bobbin 15 OD 11 17 42 DOS 0.61 2H 0.04 95 Bobbin 15 OD 11 17 44 DOS 0.4 2H 0

67 Bobbin 15 OD 11 17 45 DOS 1.25 1H 0.06 71 Bobbin 16 OD 11 17 45 DOS 0.29 2H 0.06 72 Bobbin 16 OD 11 17 49 DOS 0.68 1H 0

62 Bobbin 14 OD 11 17 50 DOS 0.24 3H 0.04 95 Bobbin 34 OD 11 17 51 DOS 0.5 1H 0.04 73 Bobbin 34 OD 11 17 53 DOS 0.46 1H 0.09 121 Bobbin 28 OD 11 17 55 SCI 0.2 TSH 0

85 PP 47 OD SCI-OD @TSH+0.00 11 17 56 SAI 1.82 1H 0.07 64 PP 57 OD SAI-OD,>2v DOS @IH 11 17 56 DOS 2.02 1H 0.07 72 Bobbin 41 OD SAI-OD,>2v DOS @1H 11 17 56 DOS 0.63 2H 0

95 Bobbin 41 OD SAI-OD,>2v DOS @1H 11 17 56 DOS 0.64 2H 0

91 Bobbin 28 OD SAI-OD,>2v DOS @1H 11 17 61 DOS 0.52 1H 0.09 80 Bobbin 28 OD 11 17 66 DOS 1.17 1H 0.11 114 Bobbin 28 OD 11 17 67 DOS 0.82 1H 0.2 137 Bobbin 28 OD 11 17 72 DOS 0.52 1H 0.15 127 Bobbin 30 OD 11 17 74 SAI 0.38 1H

-0.09 104 PP 56 OD SAI-OD,>2v DOS @1H 11 17 74 SAI 1.2 1H

-0.11 84 PP 56 OD SAI-OD,>2v DOS @1H 11 17 74 DOS 2.05 1H

-0.02 82 Bobbin 41 OD SAI-OD,>2v DOS @IH 11 17 74 TWD 17 0.33 7H 33.74 0

Bobbin 30 OD SAI-OD,>2v DOS @1H 11 17 75 DOS 0.91 2H 0.09 106 Bobbin 30 OD 11 17 76 SAI 0.34 1H

-0.25 111 PP 40 OD 11 17 76 DOS 0.43 1H

-0.13 76 Bobbin 30 OD 11 17 78 DOS 0.34 1H 0.04 114 Bobbin 30 OD 11 17 80 DOS 0.7 1H 0

95 Bobbin 30 OD 11 17 80 SAI 0.16 2H

-0.26 130 PP 41 OD 11 17 81 DOS 0.56 1H 0.09 88 Bobbin 30 OD 11 17 87 DOS 0.78 1H 0.09 98 Bobbin 30 OD 11 17 89 DOS 0.42 1H 0.15 142 Bobbin 30 OD 11 18 8

DOS 0.33 1H 0.04 47 Bobbin 16 OD 11 18 11 DOS 0.71 1H 0.02 106 Bobbin 16 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 18 11 DOS 0.31 2H 0.04 85 Bobbin 16 OD 11 18 30 DOS 0.75 1H 0.08 79 Bobbin 14 OD 11 18 30 DOS 0.66 2H 0.1 77 Bobbin 14 OD 11 18 31 DOS 0.59 1H

-0.12 106 Bobbin 14 OD 11 18 31 SAI 0.29 2H

-0.03 112 PP 22 OD 11 18 31 DIS 0.8 2H

-0.12 27 Bobbin 14 ID 11 18 36 DOS 0.81 1H 0

96 Bobbin 13 OD 11 18 41 DOS 0.38 1H 0.06 74 Bobbin 16 OD 11 18 43 DOS 0.2 1H 0.06 105 Bobbin 15 OD 11 18 54 DOS 0.48 1H 0

96 Bobbin 29 OD 11 18 55 DOS 0.48 1H 0.13 139 Bobbin 28 OD 11 18 59 SCI 0.27 TSH 0.03 102 PP 48 OD SCI-OD @TSH+0.03 11 18 60 DOS 0.45 1H 0.09 76 Bobbin 28 OD 11 18 62 DOS 1.4 1H 0.07 104 Bobbin 29 OD 11 18 67 DOS 0.56 3H 0.07 112 Bobbin 29 OD 11 18 71 DOS 0.53 1H 0.16 93 Bobbin 31 OD 11 18 71 DOS 0.34 2H 0

92 Bobbin 31 OD 11 18 72 DOS 1.49 1H 0

97 Bobbin 31 OD 11 18 74 DOS 1.01 1H 0.14 114 Bobbin 31 OD 11 18 76 SAI 0.12 1H 0.07 89 PP 38 OD 11 18 76 SAI 0.17 1H

-0.18 109 PP 38 OD 11 18 77 DOS 0.57 1H

-0.05 119 Bobbin 31 OD 11 18 80 DOS 0.32 1H 0.05 119 Bobbin 31 OD 11 18 81 DOS 0.83 1H 0.04 92 Bobbin 30 OD 11 18 82 DOS 0.59 1H 0.09 108 Bobbin 31 OD 11 18 83 DOS 0.49 1H 0.04 107 Bobbin 30 OD 11 18 89 TWD 5

0.28 2C

-0.27 144 Bobbin 31 OD 11 19 15 SAI 1.27 3H

-0.01 15 PP 11 ID 11 19 15 DIS 1.39 3H 0.04 29 Bobbin 27 ID 11 19 23 SAI 0.33 2H

-0.01 106 PP 56 OD 11 19 23 DOS 0.47 2H 0.06 61 Bobbin 17 OD 11 19 31 DOS 0.35 1H 0

96 Bobbin 13 OD 11 19 31 SAI 0.15 2H 0.1 123 PP 57 OD 11 19 31 SAI 0.18 2H 0.04 112 PP 57 OD 11 19 31 DOS 0.63 2H 0.12 41 Bobbin 13 OD 11 19 34 DOS 0.62 2H 0

139 Bobbin 13 OD 11 19 40 DOS 0.54 2H 0.08 60 Bobbin 15 OD 11 19 41 DOS 0.29 1H 0.04 139 Bobbin 15 OD 11 19 42 DOS 0.71 1H 0.1 115 Bobbin 15 OD 11 19 44 DOS 1.29 1H 0.06 94 Bobbin 16 OD 11 19 46 SAl 0.28 1H 0.02 95 PP 26 OD 11 19 46 SAI 0.38 1H 0.02 94 PP 26 OD 11 19 46 DOS 0.92 1H 0.02 80 Bobbin 14 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 19 46 DOS 0.34 3H 0.04 84 Bobbin 14 OD 11 19 48 DOS 0.68 1H 0.16 94 Bobbin 13 OD SAI-OD @TSH+1.72 11 19 48 SAI 0.18 TSH 1.72 120 Pp 25 OD SAI-OD @TSH+1.72 11 19 49 DOS 0.51 1H 0

100 Bobbin 14 OD 11 19 52 SAI 0.08 1H 0.06 108 Pp 50 OD 11 19 52 DOS 0.66 1H 0.24 89 Bobbin 28 OD 11 19 52 SAI 0.16 2H 0.15 87 PP 68 OD 11 19 52 DOS 1.09 2H 0.26 50 Bobbin 28 OD 11 19 55 DOS 0.77 1H 0.2 117 Bobbin 29 OD 11 19 56 DOS 0.81 1H 0

103 Bobbin 28 OD SCI-OD @TSH+0.05 11 19 56 DOS 0.63 2H 0.18 89 Bobbin 28 OD SCI-OD @TSH+0.05 11 19 56 DOS 0.72 3H

-0.02 69 Bobbin 28 OD SCI-OD @TSH+0.05 11 19 56 SCI 0.34 TSH 0.05 102 PP 47 OD SCI-OD @TSH+0.05 11 19 58 DOS 0.42 2H 0.05 66 Bobbin 29 OD 11 19 59 DOS 1.14 1H 0.09 105 Bobbin 29 OD SCI-OD @TSH+0.00 11 19 59 DOS 0.53 4H

-0.05 119 Bobbin 29 OD SCI-OD @TSH+0.00 11 19 59 SCI 0.26 TSH 0

114 PP 47 OD SCI-OD @TSH+0.00 11 19 60 DOS 1.33 1H 0.14 104 Bobbin 29 OD 11 19 61 SAI 0.17 1H

-0.11 108 PP 47 OD 11 19 61 SAI 0.74 1H

-0.12 93 pp 47 OD 11 19 61 DOS 1.04 1H 0

67 Bobbin 29 OD 11 19 62 DOS 0.58 1H 0.18 128 Bobbin 28 OD 11 19 64 DOS 0.81 1H 0.07 110 Bobbin 29 OD 11 19 67 DOS 0.51 1H

-0.04 142 Bobbin 28 OD 11 19 68 DOS 0.85 2H 0.14 101 Bobbin 29 OD 11 19 68 DOS 0.73 3H 0.07 103 Bobbin 29 OD 11 19 73 DOS 0.16 1H 0.09 93 Bobbin 30 OD 11 19 75 DOS 1.2 1H 0.09 95 Bobbin 30 OD 11 19 83 DOS 0.48 1H 0.05 117 Bobbin 31 OD 11 19 84 DOS 0.34 2H 0.07 98 Bobbin 30 OD 11 19 87 DOS 1.08 1H 0.07 100 Bobbin 30 OD 11 20 18 DOS 0.6 2H

-0.02 45 Bobbin 16 OD 11 20 21 DOS 0.28 4H 0.1 100 Bobbin 16 OD 11 20 26 SAI 0.24 2H 0.01 108 PP 22 OD 11 20 26 DOS 0.34 2H 0.06 113 Bobbin 18 OD 11 20 27 DOS 0.36 4H 0.04 129 Bobbin 18 OD 11 20 28 SAI 0.93 2H

-0.19 9

PP 11 ID 11 20 28 DIS 1.59 2H

-0.12 17 Bobbin 14 ID 11 20 29 SAI 0.81 2H 0.15 13 PP 11 ID 11 20 29 DIS 0.65 2H 0.27 40 Bobbin 14 ID 11 20 33 SAI 0.31 1H

-0.13 9

Pp 11 ID 11 20 35 DOS 0.33 1H

-0.06 113 Bobbin 14 OD 11 20 40 SAI 0.07 1H 0.09 131 PP 24 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 20 40 SAI 0.13 1H 0.09 93 PP 24 OD 11 20 40 DOS 0.53 1H

-0.08 80 Bobbin 16 OD 11 20 40 SAI 0.15 3H

-0.03 101 PP 57 OD 11 20 40 SAI 0.15 3H

-0.03 91 PP 63 OD 11 20 40 DIS 0.57 3H 0

28 Bobbin 16 ID 11 20 41 DOS 0.26 1H 0.1 137 Bobbin 16 OD 11 20 42 DOS 0.36 1H

-0.04 101 Bobbin 16 OD 11 20 44 DOS 0.27 1H 0.12 62 Bobbin 15 OD 11 20 44 SAI 0.52 TSH

-8.27 13 PP 11 ID 11 20 46 DOS 0.71 2H

-0.08 146 Bobbin 13 OD 11 20 47 DOS 1.69 1H

-0.08 99 Bobbin 36 OD 11 20 49 DOS 1.01 1H 0.04 94 Bobbin 13 OD 11 20 51 DOS 0.76 1H 0

42 Bobbin 28 OD 11 20 62 SAI 0.24 2H 0.01 135 PP 56 OD 11 20 65 DOS 1.09 1H 0.11 108 Bobbin 29 OD 11 20 65 DOS 0.59 3H 0.11 104 Bobbin 29 OD 11 20 67 DOS 0.96 1H 0.11 121 Bobbin 29 OD 11 20 72 SAI 0.19 2H

-0.1 103 PP 56 OD 11 20 72 DOS 0.28 2H

-0.02 65 Bobbin 31 OD 11 20 76 SAI 0.41 3H 0.01 103 PP 56 OD 11 20 76 DOS 1.07 3H 0.14 147 Bobbin 41 OD 11 20 77 DOS 0.7 2H

-0.05 90 Bobbin 31 OD 11 20 88 TWD 6

0.35 1C

-0.25 162 Bobbin 31 OD 11 21 12 DOS 0.46 1H

-0.06 71 Bobbin 16 OD 11 21 13 SAI 1.06 3H

-0.06 11 PP 11 ID 11 21 13 DIS 0.95 3H 0.02 21 Bobbin 15 ID 11 21 29 DOS 0.71 2H

-0.12 62 Bobbin 13 OD 11 21 31 SAI 0.13 2H

-0.15 87 PP 57 OD 11 21 31 DIS 0.72 2H 0.04 42 Bobbin 13 ID 11 21 32 DOS 0.29 1H 0

92 Bobbin 13 OD 11 21 35 DOS 0.46 1H 0.04 82 Bobbin 13 OD 11 21 35 DOS 0.2 4H

-0.02 78 Bobbin 13 OD 11 21 36 DOS 0.56 1H 0.08 100 Bobbin 13 OD 11 21 36 DOS 1.02 3H 0.08 101 Bobbin 13 OD 11 21 40 DOS 0.38 3H 0.06 79 Bobbin 15 OD 11 21 42 DOS 0.53 1H 0.06 97 Bobbin 15 OD 11 21 42 DOS 0.64 3H 0.18 74 Bobbin 15 OD 11 21 49 SAI 0.21 1H 0.02 118 PP 25 OD 11 21 49 DOS 0.61 1H

-0.23 75 Bobbin 14 OD 11 21 51 SAI 0.38 2H

-0.1 3

PP 11 ID 11 21 51 DIS 0.72 2H 0.2 24 Bobbin 29 ID 11 21 54 SAI 0.82 1H

-0.08 14 PP 11 ID 11 21 54 DIS 0.62 1H 0.07 26 Bobbin 28 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 21 55 DOS 0.72 1H 0.11 93 Bobbin 29 OD 11 21 57 DOS 0.74 1H 0

82 Bobbin 41 OD SCI-OD @TSH+0.01 11 21 57 SCI 0.15 TSH 0.01 89 Pp 48 OD SCI-OD @TSH+0.01 11 21 60 DOS 0.28 1H 0.05 118 Bobbin 29 OD 11 21 65 SAI 0.14 2H

-0.11 139 PP 56 OD 11 21 65 SAI 0.27 2H

-0.1 126 PP 56 OD 11 21 65 DOS 0.68 2H

-0.09 64 Bobbin 41 OD 11 21 77 SAI 0.19 2H 0.23 124 PP 38 OD 11 21 81 DIS 0.43 2H

-0.02 26 Bobbin 31 ID 11 21 87 TWD 5

0.3 1C

-0.31 106 Bobbin 30 OD 11 22 23 SAI 0.76 2H 0.13 10 PP 11 ID SAI-ID @2H, >40%TW outside TSP 11 22 23 SAI 0.91 2H

-0.24 11 PP 11 ID SAI-ID @2H, >40%TW outside TSP 11 22 23 SAI 1.06 2H 0.4 13 PP 11 ID SAI-ID @2H, >40%TW outside TSP 11 22 23 DIS 1.27 2H

-0.16 22 Bobbin 18 ID SAI-ID @2H, >40%TW outside TSP 11 22 38 DOS 1.07 1H

-0.02 89 Bobbin 13 OD 11 22 40 DOS 0.62 1H 0.08 123 Bobbin 16 OD 11 22 44 DOS 0.76 2H 0.18 88 Bobbin 16 OD 11 22 46 DOS 0.99 1H

-0.1 76 Bobbin 13 OD 11 22 52 DOS 0.94 1H 0.07 103 Bobbin 28 OD 11 22 54 DOS 1.43 1H 0.05 93 Bobbin 29 OD 11 22 56 DOS 0.24 1H

-0.02 89 Bobbin 29 OD 11 22 59 DOS 0.31 4H

-0.04 83 Bobbin 28 OD 11 22 61 DIS 0.4 3H 0.04 15 Bobbin 28 ID 11 22 64 DOS 0.92 1H 0.09 99 Bobbin 28 OD 11 22 66 DOS 0.44 1H 0.11 105 Bobbin 29 OD 11 22 68 DOS 0.67 1 H 0.04 85 Bobbin 28 OD 11 22 69 SAI 0.25 1 H 0.03 105 PP 56 OD SAI-OD,<2v DOS @1 H Preventive 11 22 69 SAI 1.65 1 H 0

76 PP 56 OD SAI-OD,<2v DOS @1 H Preventive 11 22 69 DOS 1.96 1H 0.09 78 Bobbin 41 OD SAI-OD,<2v DOS @1 H Preventive 11 22 69 DOS 0.68 2H

-0.02 113 Bobbin 29 OD SAI-OD,<2v DOS @1 H Preventive 11 22 69 DOS 0.69 2H

-0.05 114 Bobbin 41 OD SAI-OD,<2v DOS @1H Preventive 11 22 70 SAI 0.44 1H

-0.08 104 PP 38 OD 11 22 70 SAI 0.47 1H

-0.06 98 PP 38 OD 11 22 70 DOS 1.45 1H 0

114 Bobbin 41 OD 11 23 14 SAI 0.68 3H

-0.1 14 PP 11 ID 11 23 14 DIS 0.82 3H

-0.04 10 Bobbin 15 ID 11 23 20 DOS 0.88 1H 0.04 72 Bobbin 15 OD 11 23 20 DOS 0.31 4H 0.06 81 Bobbin 15 OD 11 23 21 DOS 0.27 3H 0.02 118 Bobbin 17 OD 11 23 28 DOS 1.21 1H 0.08 103 Bobbin 13 OD 11 23 30 005 0.53 3H 0

62 Bobbin 13 OD 11 23 38 SAI 0.24 2H

-0.17 117 PP 24 OD 11 23 40 DOS 0.56 2H 0.02 45 Bobbin 15 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 23 41 DOS 1.43 1H 0

86 Bobbin 27 OD 11 23 43 DOS 1.48 1H 0.22 107 Bobbin 15 OD 11 23 48 DOS 0.38 1H 0

113 Bobbin 13 OD 11 23 51 DOS 1.45 1H 0.13 94 Bobbin 41 OD 11 23 52 DOS 0.21 1H 0

93 Bobbin 29 OD 11 23 54 SAI 0.18 1H

-0.03 117 PP 47 OD 11 23 55 DOS 0.71 1H 0.05 116 Bobbin 29 OD 11 23 58 SAI 0.15 3H

-0.01 117 PP 56 OD 11 23 58 DOS 0.48 3H 0.05 41 Bobbin 29 OD 11 23 59 SAI 0.16 1H

-0.16 95 PP 47 OD 11 23 59 SAI 0.22 1H 0.15 99 PP 47 OD 11 23 59 SAI 0.45 1H 0

98 PP 47 OD 11 23 59 DOS 0.63 1H 0.02 81 Bobbin 29 OD 11 23 60 DOS 0.34 1H 0.04 144 Bobbin 28 OD 11 23 66 DOS 0.49 1H 0

96 Bobbin 28 OD 11 23 74 DOS 0.79 1H 0.07 105 Bobbin 30 OD 11 23 87 TWD 4

0.26 2C

-0.02 148 Bobbin 30 OD 11 23 88 TWD 9

0.56 2C

-0.24 139 Bobbin 30 OD 11 24 12 SAI 0.15 2H

-0.01 114 PP 19 OD 11 24 17 DOS 1.33 1H 0.2 92 Bobbin 16 OD 11 24 19 DOS 0.25 1H

-0.02 97 Bobbin 16 OD 11 24 19 DOS 0.37 2H

-0.08 104 Bobbin 16 OD 11 24 25 DOS 0.49 1H 0

135 Bobbin 18 OD 11 24 40 DOS 1.18 1H

-0.08 96 Bobbin 16 OD 11 24 42 DOS 0.45 1H 0.04 125 Bobbin 16 OD 11 24 43 DOS 0.41 1H 0.16 137 Bobbin 16 OD 11 24 48 DOS 0.35 1H 0.12 135 Bobbin 14 OD 11 24 49 DOS 0.47 1H 0.04 109 Bobbin 13 OD 11 24 51 SAI 0.27 1H

-0.03 110 PP 50 OD 11 24 51 DOS 0.26 1H 0.13 94 Bobbin 28 OD 11 24 54 DOS 0.8 1H 0.29 101 Bobbin 29 OD 11 24 59 SCI 0.31 1H

-0.04 83 PP 48 OD SCI-OD @1H-0.04 11 24 59 DOS 0.45 1H 0

125 Bobbin 28 OD SCI-OD @1H-0.04 11 24 67 SAI 0.94 2H.

-0.05 13 PP 11 ID 11 24 67 DIS 0.91 2H 0.02 26 Bobbin 29 ID 11 24 71 DOS 0.32 1H 0

91 Bobbin 31 OD 11 24 77 DOS 0.45 1H 0.02 119 Bobbin 31 OD 11 24 80 DOS 0.77 1H 0

99 Bobbin 30 OD 11 24 87 TWD 23 1.59 2C

-0.23 123 Bobbin 31 OD 11 25 30 DOS 0.4 2H 0.06 88 Bobbin 13 OD 11 25 37 DOS 1.41 1H 0.1 105 Bobbin 13 OD 11 25 39 DOS 1.41 1H 0.08 104 Bobbin 13 OD 11 25 40 DOS 0.36 1H 0.08 111 Bobbin 15 00 Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 25 43 SAI 0.17 2H 0.06 89 PP 57 OD 11 25 43 DOS 1.03 2H 0.16 35 Bobbin 15 OD 11 25 44 SAI 1.17 1H 0.03 81 PP 57 OD 11 25 44 DOS 1.77 1H 0.12 84 Bobbin 36 OD 11 25 46 DOS 0.95 1H 0.06 94 Bobbin 13 OD 11 25 52 SAI 2.54 1H 0

50 PP 57 OD SAI-OD,>2v DOS @I1H 11 25 52 DOS 2.22 1 H 0.04 62 Bobbin 41 OD SAI-OD,>2v DOS @1 H 11 25 53 DOS 1.26 1H 0

102 Bobbin 29 OD 11 25 54 DOS 0.69 1H 0.18 109 Bobbin 28 OD 11 25 56 DOS 0.44 1H 0.04 93 Bobbin 28 OD 11 25 56 DOS 0.27 3H 0.07 79 Bobbin 28 OD 11 25 57 SAI 0.78 3H 0.1 13 PP 11 ID 11 25 57 DIS 0.41 3H 0.09 56 Bobbin 29 ID 11 25 60 SAI 0.14 1H 0.19 110 PP 47 OD 11 25 60 SAI 0.19 1H

-0.16 116 PP 47 OD 11 25 62 TWD 11 0.17 7H 28.35 0

Bobbin 28 OD 11 25 62 TWD 25 0.55 7H 44.12 0

Bobbin 28 OD 11 25 62 TWO 29 0.83 7H 63.06 0

Bobbin 28 OD 11 25 65 DOS 0.9 1H 0.04 108 Bobbin 28 OD 11 25 66 DOS 1.07 1H 0.15 77 Bobbin 28 OD 11 25 69 DOS 1.44 1H 0.09 99 Bobbin 28 OD 11 25 70 SAI 0.19 1H

-0.05 94 PP 38 OD 11 25 70 DOS 0.18 1H 0.04 111 Bobbin 30 OD 11 25 73 DOS 0.24 1H 0.09 95 Bobbin 30 OD 11 25 85 TWD 13 0.83 1C 0.04 135 Bobbin 30 OD 11 25 86 TWD 16 1.03 2C

-0.27 151 Bobbin 30 OD 11 25 87 TWD 10 0.6 1C

-0.04 144 Bobbin 30 OD 11 26 15 DOS 0.43 1H 0.04 84 Bobbin 18 OD 11 26 17 DOS 0.46 1H 0.08 126 Bobbin 17 OD 11 26 19 SAI 0.17 2H

-0.05 113 PP 56 OD 11 26 19 DOS 0.22 2H 0.04 93 Bobbin 20 OD 11 26 28 SAI 0.31 1H

-0.06 89 PP 57 OD 11 26 32 SAI 0.62 1H

-0.02 97 PP 57 OD 11 26 32 SAI 0.63 1H

-0.09 101 PP 57 OD 11 26 32 DOS 1.75 1H 0

87 Bobbin 36 OD 11 26 33 SAI 0.16 1H

-0.18 114 PP 57 OD 11 26 33 DOS 0.35 1H 0.28 106 Bobbin 13 OD 11 26 34 SAI 0.54 1H

-0.15 91 PP 16 OD 11 26 34 DOS 0.64 1H

-0.02 91 Bobbin 13 OD 11 26 36 DOS 0.33 1H 0.02 44 Bobbin 11 OD 11

.26 37 DOS 0.38 1H 0.08 87 Bobbin 11 OD 11 26 38 DOS 0.66 1H 0.04 114 Bobbin 11 OD 11 26 39 DOS 0.5 2H

-0.12 104 Bobbin 11 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 26 41 SAI 0.12 2H

-0.12 92 PP 57 OD 11 26 41 SAI 0.18 2H

-0.13 120 PP 57 OD 11 26 41 DIS 0.53 2H

-0.08 52 Bobbin 11 ID 11 26 42 DOS 1.3 1H 0.02 114 Bobbin 11 OD 11 26 42 DIS 0.48 2H 0

41 Bobbin 11 ID 11 26 43 DOS 1.17 1H 0.06 100 Bobbin 11 OD 11 26 44 DOS 0.27 1H 0.1 89 Bobbin 11 OD 11 26 44 DOS 0.42 2H

-0.04 61 Bobbin 11 OD 11 26 46 SAI 0.66 1H 0.09 100 PP 57 OD 11 26 46 DOS 1.78 1H 0.15 145 Bobbin 36 OD 11 26 47 DOS 0.24 1H 0.02 111 Bobbin 11 OD 11 26 52 DOS 0.78 1H

-0.02 125 Bobbin 7

OD 11 26 56 DOS 0.56 1H

-0.19 96 Bobbin 7

OD 11 26 56 DOS 0.32 2H

-0.04 82 Bobbin 7

OD 11 26 60 DOS 1.65 1H

-0.06 91 Bobbin 7

OD 11 26 60 DOS 0.45 2H 0

129 Bobbin 7

OD 11 26 63 SAI 0.29 1H 0.03 109 PP 56 OD SAI-OD,>2v DOS @IH 11 26 63 SAI 0.97 1 H

-0.09 93 PP 56 OD SAI-OD,>2v DOS @1H 11 26 63 DOS 2.37 1H

-0.08 93 Bobbin 7

OD SAI-OD,>2v DOS @IH 11 26 66 DOS 0.59 1H

-0.04 85 Bobbin 9

OD 11 26 67 DOS 0.35 1H 0

108 Bobbin 9

OD 11 26 86 TWD 18 1.17 2C

-0.16 128 Bobbin 10 OD 11 27 23 DOS 0.34 1H 0.04 131 Bobbin 20 OD 11 27 28 SAI 0.28 1H 0.2 116 PP 13 OD 11 27 28 DOS 0.61 1H 0.28 145 Bobbin 13 OD 11 27 32 DOS 0.67 1H 0.16 96 Bobbin 14 OD 11 27 34 DOS 0.24 1H 0.1 111 Bobbin 14 OD 11 27 35 SAI 0.24 1H 0.09 100 PP 57 OD 11 27 35 DIS 0.73 1H 0.1 48 Bobbin 12 ID 11 27 36 DOS 1

1H 0.08 119 Bobbin 11 OD 11 27 39 DOS 0.7 1H 0.14 117 Bobbin 12 OD 11 27 39 DOS 0.37 2H 0.08 88 Bobbin 12 OD 11 27 40 DOS 1.05 1H 0.16 96 Bobbin 11 OD 11 27 41 DOS 0.88 1H 0

98 Bobbin

.12 OD 11 27 42 SAI 0.14 1H 0.02 86 PP 57 OD SAI-OD,>2v DOS @1H 11 27 42 SAI 1.41 1H 0.01 79 PP 57 OD SAI-OD,>2v DOS @1H 11 27 42 DOS 2.16 1H 0.08 80 Bobbin 36 OD SAI-OD,>2v DOS @IH 11 27 44 DOS 0.8 1H

-0.02 135 Bobbin 11 OD 11 27 44 SAI 0.15 2H 0.04 64 PP 57 OD 11 27 44 SAI 0.15 2H

-0.01 80 PP 57 OD 11 27 46 DOS 0.42 1H 0.04 97 Bobbin 27 OD 11 27 48 DOS 0.36 1H 0.1 106 Bobbin 12 OD 11 27 51 DOS 0.22 2H

-0.04 94 Bobbin 8

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Dog Probe Cal IDOD Reason for Plugging 11 27 52 SAI 0.14 1H

-0.02 134 PP 57 OD SAI-OD,>2v DOS @1H 11 27 52 SAI 0.34 1H

-0.01 115 PP 57 OD SAI-OD,>2v DOS @1H 11 27 52 SAI 1.81 1 H 0.02 72 PP 57 OD SAI-OD,>2v DOS @1 H 11 27 52 DOS 2.21 1 H 0.02 84 Bobbin 7

OD SAI-OD,>2v DOS @1 H 11 27 54 DOS 0.8 1H 0.08 119 Bobbin 7

OD 11 27 59 SCI 0.13 TSH

-0.05 101 PP 32 OD SCI-OD @TSH-0.05 11 27 60 DOS 0.17 3H

-0.02 82 Bobbin 8

OD 11 27 64 DOS 0.32 5H

-0.08 145 Bobbin 9

OD 11 27 65 DOS 0.56 1H 0.04 109 Bobbin 10 OD 11 27 66 DOS 0.29 1H 0

82 Bobbin 9

OD 11 27 67 DOS 0.51 1H

-0.1 95 Bobbin 10 OD 11 27 69 DOS 0.5 1H 0.02 95 Bobbin 10 OD 11 27 70 DOS 0.16 1H

-0.06 65 Bobbin 9

OD 11 27 75 SAI 0.84 2H

-0.01 10 PP 11 ID 11 27 75 DIS 0.96 2H

-0.04 23 Bobbin 10 ID 11 27 80 DOS 0.84 1H

-0.19 95 Bobbin 10 OD 11 28 22 DOS 0.21 3H 0.08 52 Bobbin 20 OD 11 28 25 SAI 0.12 2H

-0.19 108 PP 57 OD 11 28 25 SAI 0.13 2H 0.03 89 PP 57 OD 11 28 25 DOS 0.12 2H 0.06 90 Bobbin 19 OD 11 28 26 DOS 0.87 1H 0.12 92 Bobbin 20 OD 11 28 29 SAI 0.27 1H 0.12 94 PP 13 OD 11 28 29 SAI 0.55 1H

-0.11 93 PP 13 OD 11 28 29 DOS 0.4 1H 0.02 103 Bobbin 13 OD 11 28 31 DOS 0.38 1H 0.12 138 Bobbin 13 OD 11 28 31 DOS 0.84 2H 0

86 Bobbin 13 OD 11 28 32 SAI 0.53 1H 0.02 101 PP 57 OD 11 28 32 SAI 0.79 1H 0.02 89 PP 57 OD 11 28 32 DOS 1.79 1H 0.04 90 Bobbin 36 OD 11 28 34 DOS 1.21 1H 0.16 98 Bobbin 13 OD 11 28 36 SAI 0.13 1H

-0.05 101 PP 57 OD 11 28 36 SAI 0.13 1H 0.17 102 PP 57 OD 11 28 36 DIS 0.41 1H 0.02 12 Bobbin 12 ID 11 28 38 DOS 0.31 1H 0.04 107 Bobbin 11 OD 11 28 39 DOS 0.54 1H 0.08 121 Bobbin 11 OD 11 28 40 SAI 0.26 1H 0.04 106 PP 15 OD 11 28 40 SAI 0.41 1H

-0.13 96 PP 15 OD 11 28 40 DOS 0.52 1H

-0.04 126 Bobbin 12 OD 11 28 41 DOS 1.43 1H 0.14 94 Bobbin 11 OD 11 28 41 DOS 0.33 4H 0

97 Bobbin 11 OD 11 28 43 DOS 0.25 1H 0.08 76 Bobbin 11 OD 11 28 45 DOS 0.45 1H 0.04 65 Bobbin 11 OD 11 28 47 DOS 0.56 1H 0.14 142 Bobbin 11 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 28 48 DOS 1.06 1H 0.16 89 Bobbin 13 OD 11 28 48 TWD 18 0.39 7H 50.29 0

Bobbin 13 OD 11 28 48 TWD 22 0.52 7H 72.86 0

Bobbin 13 OD 11 28 48 TWD 25 0.67 7H 84.63 0

Bobbin 13 OD 11 28 49 DOS 0.64 1H 0.08 83 Bobbin 12 OD 11 28 52 DOS 1.02 1H 0

73 Bobbin 8

OD 11 28 53 SAI 0.4 1H 0.09 98 PP 57 OD 11 28 53 SAI 1.01 1H 0.03 89 PP 57 OD 11 28 53 SAI 1.04 1H

-0.09 87 PP 57 OD 11 28 53 DOS 1.81 1H

-0.06 95 Bobbin 7

OD 11 28 54 DOS 0.62 1H 0.04 112 Bobbin 8

OD 11 28 55 DOS 1

1H

-0.02 104 Bobbin 7

OD 11 28 57 DOS 0.36 2H

-0.1 68 Bobbin 7

OD 11 28 59 DOS 1.05 1H 0.04 121 Bobbin 7

OD 11 28 63 DOS 0.44 2H

-0.04 71 Bobbin 7

OD 11 28 64 DOS 0.39 1H 0.12 113 Bobbin 10 OD 11 28 65 SAI 0.64 1H 0.03 93 PP 34 OD 11 28 65 DOS 0.75 1H 0.04 106 Bobbin 9

OD 11 28 85 TWD 18 1.22 lC 0

137 Bobbin 10 OD 11 29 17 DOS 0.28 1H 0

84 Bobbin 18 OD 11 29 24 DOS 0.62 2H 0.08 53 Bobbin 20 OD 11 29 25 DOS 0.3 1H 0.12 97 Bobbin 19 OD 11 29 25 DOS 0.87 3H

-0.16 96 Bobbin 19 OD 11 29 27 DOS 0.16 1H 0.08 80 Bobbin 13 OD 11 29 29 SAI 0.81 2H

-0.09 89 PP 57 OD 11 29 29 DOS 1.62 2H

-0.08 78 Bobbin 36 OD 11 29 31 DOS 0.55 1H 0.04 69 Bobbin 14 OD 11 29 34 DOS 0.81 1H 0.16 100 Bobbin 14 OD 11 29 35 DOS 0.84 1H 0.06 107 Bobbin 11 OD 11 29 37 SAI 0.78 2H 0.07 11 PP 11 ID 11 29 37 DIS 0.59 2H 0.18 35 Bobbin 12 ID 11 29 38 DOS 1.27 1H 0.14 105 Bobbin 11 OD 11 29 39 SAI 0.24 1H

-0.11 128 PP 15 OD 11 29 39 DOS 0.39 1H 0.06 109 Bobbin 12 OD 11 29 41 SAI 0.22 1H

-0.12 113 PP 57 OD 11 29 41 SAI 0.34 1H

-0.03 100 PP 57 OD 11 29 41 SAI 0.75 1H

-0.03 95 PP 57 OD 11 29 41 DOS 1.75 1H 0

94 Bobbin 12 OD 11 29 41 DIS 1.06 2H

-0.24 31 Bobbin 12 ID 11 29 42 DOS 0.32 1H 0.1 96 Bobbin 11 OD 11 29 43 SAI 0.66 1H

-0.02 99 PP 17 OD 11 29 43 DOS 1.92 1H 0.06 105 Bobbin 12 OD 11 29 45 DOS 0.46 1H 0.02 121 Bobbin 12 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 29 47 DOS 0.56 1H 0.1 125 Bobbin 12 OD 11 29 49 DIS 0.27 1H 0.04 34 Bobbin 11 ID 11 29 55 DOS 0.67 1H

-0.16 117 Bobbin 8

OD 11 29 60 DOS 0.41 2H

-0.04 114 Bobbin 8

OD 11 29 62 DOS 1.01 1H

-0.08 82 Bobbin 7

OD 11 29 63 DOS 0.51 1H 0.02 115 Bobbin 8

OD 11 29 64 DOS 0.94 1H 0.06 98 Bobbin 9

OD 11 29 68 SCI 0.31 2H 0.24 114 pp 56 OD SCI-OD @2H+0.24 11 29 72 DOS 0.31 1H

-0.06 118 Bobbin 10 OD 11 29 84 TWD 22 1.49 2C

-0.12 128 Bobbin 10 OD 11 30 21 SAI 0.56 2H

-0.05 12 Pp 11 ID 11 30 21 DIS 0.85 2H

-0.32 8

Bobbin 19 ID 11 30 22 DOS 0.52 4H

-0.12 62 Bobbin 20 OD 11 30 29 DOS 0.3 1H 0.08 105 Bobbin 13 OD 11 30 30 DOS 0.66 1H

-0.02 108 Bobbin 13 OD 11 30 30 SAI 0.25 2H

-0.03 115 PP 57 OD 11 30 30 DOS 0.4 2H 0.04 85 Bobbin 13 OD 11 30 31 DOS 1.27 1H 0.1 95 Bobbin 13 OD 11 30 31 SAI 0.14 2H

-0.12 98 PP 57 OD 11 30 31 DOS 0.68 2H

-0.02 83 Bobbin 13 OD 11 30 35 SAI 0.3 1H

-0.03 111 Pp 57 OD SAI-OD,>2v DOS @I1H 11 30 35 SAI 1.13 1H

-0.01 76 Pp 57 OD SAI-OD,>2v DOS @1H 11 30 35 DOS 2.01 1H 0.08 88 Bobbin 12 OD SAI-OD,>2v DOS @1H 11 30 38 DOS 0.88 1H 0.2 133 Bobbin 12 OD 11 30 39 DOS 1.19 1H 0.12 82 Bobbin 13 OD 11 30 40 DOS 1.26 1H 0

76 Bobbin 12 OD 11 30 44 SAI 0.45 1H 0

105 pp 57 OD SAI-OD,>2v DOS @1H 11 30 44 SAI 1.31 1H 0.04 80 pp 57 OD SAI-OD,>2v DOS @IH 11 30 44 DOS 2.08 1H 0.06 96 Bobbin 36 OD SAI-OD,>2v DOS @11H 11 30 45 DOS 0.13 1H 0.08 137 Bobbin 11 OD 11 30 48 DOS 1.35 1H 0.12 91 Bobbin 13 OD 11 30 50 DIS 0.24 4H

-0.08 46 Bobbin 7

ID 11 30 53 DOS 0.79 1H 0.04 97 Bobbin 7

OD 11 30 54 DOS 1.07 1H 0.02 114 Bobbin 8

OD 11 30 58 DOS 0.84 2H

-0.19 97 Bobbin 7

OD 11 30 58 SAI 0.21 4H

-0.19 109 pp 56 OD 11 30 58 DOS 0.93 4H

-0.19 57 Bobbin 7

OD 11 30 59 DOS 0.25 1H

-0.08 120 Bobbin 7

OD 11 30 59 SAI 0.66 2H

-0.06 12 pp 11 ID 11 30 59 DIS 0.5 2H

-0.1 41 Bobbin 7

ID 11 30 61 DOS 0.93 1H

-0.14 101 Bobbin 8

OD 11 30 63 DOS 0.43 1 H

-0.08 98 Bobbin 7

OD 11 30 66 DOS 0.99 1H

-0.12 94 Bobbin 10 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 30 67 SAI 0.99 2H 0.1 11 PP 11 ID 11 30 67 DIS 1.03 2H 0.08 26 Bobbin 9

ID 11 30 70 DOS 1.32 1H

-0.04 91 Bobbin 10 OD 11 30 74 SAI 0.11 2H 0.03 99 PP 56 OD SAI-OD @2H Wedge 11 30 74 DOS 0.28 2H 0.04 100 Bobbin 10 OD SAI-OD @2H Wedge 11 30 79 DOS 0.85 1H

-0.1 87 Bobbin 9

OD 11 30 83 TWD 16 1.05 1C

-0.16 125 Bobbin 10 OD 11 31 18 DOS 0.37 1H 0.08 66 Bobbin 17 OD 11 31 32 DOS 0.62 1H 0.08 113 Bobbin 13 OD 11 31 37 DOS 1.17 1H 0

89 Bobbin 11 OD 11 31 39 DOS 0.29 1H 0.28 98 Bobbin 11 OD 11 31 40 SAI 0.68 1H 0

97 PP 16 OD 11 31 40 DOS 0.3 1H 0.04 118 Bobbin 11 OD 11 31 41 DOS 1.15 1H

-0.02 95 Bobbin 12 OD 11 31 50 DOS 1.03 1H 0.06 91 Bobbin 8

OD 11 31 53 SAI 0.19 2H 0.1 108 PP 57 OD 11 31 53 SAI 0.23 2H 0.09 103 PP 57 OD 11 31 53 DOS 0.34 2H 0.04 150 Bobbin 8

OD 11 31 56 DOS 0.43 1H

-0.02 100 Bobbin 8

OD 11 31 63 DOS 0.73 1H 0.02 120 Bobbin 8

OD 11 31 65 DOS 0.31 1H

-0.02 118 Bobbin 10 OD 11 31 66 DOS 0.43 2H

-0.06 95 Bobbin 9

OD 11 31 69 DOS 0.48 1H

-0.04 73 Bobbin 10 OD 11 31 79 TWVD 12 0.74 lC

-0.31 36 Bobbin 10 OD 11 31 81 TWD 19 1.29 IC 0.27 134 Bobbin 10 OD 11 31 81 TWD 37 2.83 2C

-0.1 110 Bobbin 10 OD 11 32 24 SAI 0.25 2H

-0.19 88 PP 57 OD 11 32 24 DOS 0.18 2H 0.26 49 Bobbin 19 OD 11 32 28 DOS 1.09 1H 0

100 Bobbin 14 OD 11 32 32 DOS 0.87 1H 0

97 Bobbin 14 OD 11 32 44 DOS 0.17 2H 0.08 56 Bobbin 11 OD 11 32 48 DOS 1.06 2H 0.16 68 Bobbin 13 OD 11 32 69 DOS 0.31 2H 0

53 Bobbin 9

OD 11 32 78 TWD 6

0.36 lC

-0.29 89 Bobbin 10 OD 11 32 79 TWD 17 1.12 1C 0.08 129 Bobbin 9

OD 11 33 24 DOS 0.49 4H

-0.04 84 Bobbin 20 OD 11 33 34 SAI 0.31 1H

-0.06 107 PP 57 OD 11 33 37 DOS 0.45 1H 0.04 102 Bobbin 11 OD 11 33 39 DOS 0.36 1H 0.1 73 Bobbin 11 OD 11 33 42 DOS 0.31 3H 0

41 Bobbin 11 OD 11 33 43 DOS 1.49 1H 0.08 97 Bobbin 12 OD 11 33 44 DOS 0.22 7H 0.29 62 Bobbin 12 OD 11 33 50 DOS 0.25 2H

-0.02 50 Bobbin 8

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 33 53 DOS 0.27 1H 0.02 145 Bobbin 8

OD 11 33 54 DOS 0.24 1H

-0.06 54 Bobbin 7

OD 11 33 55 SAI 1.18 1H 0.07 93 PP 30 OD 11 33 55 DOS 1.45 1H 0.11 108 Bobbin 27 OD 11 33 57 DOS 1.08 1H 0

105 Bobbin 8

OD 11 33 71 DOS 1.05 1H

-0.08 99 Bobbin 9

OD 11 33 77 TWD 8

0.5 2C

-0.24 121 Bobbin 9

OD 11 33 79 TWD 11 0.71 1C 0.39 121 Bobbin 10 OD 11 34 24 SAI 0.44 3H 0.18 12 PP 11 ID 11 34 24 SAI 0.58 3H 0.01 14 Pp 11 ID 11 34 24 DIS 0.59 3H 0.04 7

Bobbin 19 ID 11 34 30 DOS 0.34 1H 0

101 Bobbin 13 OD 11 34 40 DOS 0.22 2H 0.06 78 Bobbin 11 OD 11 34 41 DOS 0.3 2H 0.08 53 Bobbin 11 OD 11 34 77 DOS 0.71 IC

-0.25 95 Bobbin 10 OD 11 34 79 TWD 11 0.71 1C

-0.25 134 Bobbin 10 OD 11 35 17 TWD 15 0.96 1C

-0.22 144 Bobbin 17 OD 11 35 21 DIS 0.63 4H 0.08 34 Bobbin 20 ID 11 35 29 DOS 0.66 1H 0.02 118 Bobbin 14 OD 11 35 34 SAI 0.13 1H 0.11 114 Pp 57 OD 11 35 34 SAI 0.14 1H 0.13 113 Pp 57 OD 11 35 34 SAI 0.26 1H 0.02 117 PP 57 OD 11 35 34 DOS 0.66 1H 0.04 35 Bobbin 14 OD 11 35 34 DOS 0.47 2H 0

70 Bobbin 14 OD 11 35 35 DOS 0.34 1H 0.04 47 Bobbin 11 OD 11 35 35 SAI 0.15 2H 0

117 PP 16 OD 11 35 35 DOS 0.14 2H 0.02 114 Bobbin 11 OD 11 35 39 DOS 0.31 1H 0.1 77 Bobbin 11 OD 11 35 59 SAI 1.37 3H

-0.07 15 PP 11 ID 11 35 59 DIS 1.03 3H

-0.12 38 Bobbin 8

ID 11 35 61 DOS

.1.32 2H

-0.16 85 Bobbin 7

OD 11 35 76 TWD 13 0.82 2C

-0.14 140 Bobbin 10 OD 11 35 77 TWD 5

0.32 1C 0.4 93 Bobbin 9

OD 11 35 78 TWD 17 1.15 1C

-0.27 128 Bobbin 10 OD 11 35 78 TWD 10 0.65 2C 0

148 Bobbin 10 OD 11 36 31 DOS 0.22 1H 0.08 117 Bobbin 13 OD 11 36 31 DOS 0.9 2H

-0.08 98 Bobbin 13 OD 11 36 32 DOS 0.63 1H 0.18 122 Bobbin 14 OD 11 36 40 DOS 0.17 1H 0.06 103 Bobbin 11 OD 11 36 42 SAI 0.18 2H 0.03 135 PP 57 OD 11 36 48 SAI 0.16 2H 0.08 104 PP 57 OD 11 36 48 SAI 0.17 2H 0.29 119 PP 57 OD 11 36 48 SAI 0.21 2H

-0.26 112 PP 57 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 36 48 DOS 0.82 2H

-0.2 50 Bobbin 13 OD 11 36 62 DOS 0.6 4H

-0.08 49 Bobbin 8

OD 11 36 64 DOS 1.01 2H

-0.23 109 Bobbin 10 OD 11 36 73 TWD 5

0.3 2C

-0.12 116 Bobbin 9

OD 11 36 76 TWD 7

0.45 1C

-0.26 92 Bobbin 9

OD 11 36 77 TWD 10 0.59 1C 0.27 142 Bobbin 10 OD 11 36 77 TWD 22 1.49 2C

-0.12 144 Bobbin 10 OD 11 37 32 DOS 0.96 1H 0.22 100 Bobbin 13 OD 11 37 36 DOS 0.68 1H 0.08 72 Bobbin 12 OD 11 37 36 DOS 0.53 2H

-0.06 120 Bobbin 12 OD 11 37 36 DOS 0.37 3H 0.02 92 Bobbin 12 OD 11 37 41 DOS 1.55 1H 0

87 Bobbin 12 OD 11 37 41 SAI 0.25 2H

-0.01 108 PP 57 OD 11 37 41 DOS 0.35 2H 0

88 Bobbin 12 OD 11 37 41 DOS 0.36 6H 0.04 99 Bobbin 12 OD 11 37 45 SAI 0.23 2H 0.08 114 PP 57 OD 11 37 45 DOS 0.48 2H 0.1 62 Bobbin 11 OD 11 37 46 TWD 29 1.35 7H 62.8 0

Bobbin 36 OD 11 37 54 DOS 0.35 1H

-0.02 77 Bobbin 7

OD 11 37 56 SAI 0.24 2H 0.2 141 PP 30 OD 11 37 56 DIS 1.08 2H 0.22 34 Bobbin 8

ID 11 37 59 DOS 0.38 2H 0.04 90 Bobbin 8

OD 11 37 75 TWD 11 0.66 2C

-0.04 127 Bobbin 10 OD 11 37 76 DOS 0.71 1C

-0.23 126 Bobbin 10 OD 11 38 32 DOS 1.02 1H 0

90 Bobbin 14 OD 11 38 36 DOS 1.49 1H 0.15 99 Bobbin 36 OD 11 38 36 DOS 0.46 2H

-0.08 65 Bobbin 11 OD 11 38 38 DOS 0.68 1H

-0.04 120 Bobbin 11 OD 11 38 40 DOS 0.88 1H

-0.06 102 Bobbin 11 OD 11 38 40 DOS 0.45 4H 0.04 98 Bobbin 11 OD 11 38 41 SAI 1.15 4H

-0.2 14 PP 11 ID 11 38 41 DIS 1.23 4H

-0.12 30 Bobbin 11 ID 11 38 44 DOS 0.19 1H

-0.04 75 Bobbin 11 OD 11 38 44 DOS 0.76 2H

-0.06 97 Bobbin 11 OD 11 38 46 DOS 0.68 1H 0

114 Bobbin 11 OD 11 38 49 SAI 0.2 2H 0.27 115 PP 18 OD 11 38 54 SAI 0.25 2H

-0.05 115 PP 30 OD SAI-ID/AONDB @2H 11 38 54 SAI 0.52 2H

-0.17 2

PP 30 ID SAI-ID/AONDB @2H 11 38 55 DOS 0.39 6H

-0.08 144 Bobbin 8

OD 11 38 64 DOS 0.26 1H

-0.02 96 Bobbin 10 OD 11 38 66 DOS 1.06 1H

-0.02 105 Bobbin 10 OD 11 38 68 DOS 0.44 6H

-0.08 77 Bobbin 9

OD 11 38 72 TWD 12 0.78 1C

-0.26 120 Bobbin 9

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 39 54 TWD 20 0.46 7H 129.4 0

Bobbin 7

OD 11 39 54 TWD 22 0.55 7H 66.39 0

Bobbin 7

OD 11 39 54 TWD 26 0.74 7H 101.7 0

Bobbin 7

OD 11 39 56 TWD 17 0.35 7H 131 0

Bobbin 8

OD 11 39 57 SAI 0.6 2H

-0.16 9

PP 11 ID 11 39 57 DIS 0.6 2H

-0.24 29 Bobbin 8

ID 11 39 58 DOS 0.33 2H

-0.22 112 Bobbin 8

OD 11 39 59 SAI 0.18 2H 0.01 125 PP 56 OD 11 39 59 DOS 0.34 2H

-0.04 143 Bobbin 8

OD 11 39 73 TWD 11 0.7 1C

-0.27 133 Bobbin 10 OD 11 40 27 DOS 0.94 1H 0

97 Bobbin 14 OD 11 40 29 DOS 0.76 1H 0.04 99 Bobbin 13 OD 11 40 31 DOS 0.68 1H 0.02 93 Bobbin 13 OD 11 40 35 TWD 15 0.28 7H 103.7 0

Bobbin 12 OD 11 40 39 DOS 0.36 1H 0.04 129 Bobbin 11 OD 11 40 40 DOS 0.35 3H 0.08 62 Bobbin 11 OD 11 40 45 TWD 14 0.24 7H 105.6 0

Bobbin 12 OD 1.1 40 50 SAI 0.3 1H 0.12 108 PP 29 OD 11 40 50 DOS 0.59 1H 0.06 148 Bobbin 7

OD 11 40 50 DIS 0.36 2H

-0.06 44 Bobbin 7

ID 11 40 51 DOS 0.38 6C

-0.04 142 Bobbin 8

OD 11 40 57 DIS 0.79 4H

-0.06 21 Bobbin 7

ID 11 40 63 DOS 0.51 1H 0

133 Bobbin 9

OD 11 40 66 DOS 0.89 1H 0.06 102 Bobbin 10 OD 11 40 68 DOS 0.83 1H

-0.02 51 Bobbin 9

OD 11 40 68 TWD 19 0.54 7H 68.34 0

Bobbin 9

OD 11 40 68 TWD 27 0.92 7H 103.2 0

Bobbin 9

OD 11 40 69 VOL 0.09 IC

-0.37 98 PP 74 OD 11 40 69 TWD 6

0.35 IC

-0.28 38 Bobbin 9

OD 11 40 70 DOS 0.31 2H

-0.04 94 Bobbin 10 OD 11 41 36 DOS 1.58 1H 0.1 95 Bobbin 12 OD 11 41 38 DOS 1.22 1H 0.14 104 Bobbin 12 OD 11 41 39 DOS 0.91 1H 0.12 122 Bobbin 12 OD 11 41 41 DOS 1.65 3H

-0.04 124 Bobbin 12 OD 11 41 44 TWD 8

0.15 7H 137.9 0

Bobbin 11 OD 11 41 44 TWD 13 0.25 7H 107.3 0

Bobbin 11 OD 11 41 53 DOS 0.53 2H

-0.16 79 Bobbin 8

OD 11 41 58 DOS 0.22 1H 0

125 Bobbin 8

OD 11 41 64 TWD 15 0.99 2C

-0.14 139 Bobbin 9

OD 11 41 68 SAI 0.11 2H 0.05 73 PP 68 OD 11 41 68 SAI 0.2 2H 0.01 135 PP 68 OD 11 41 68 DOS 0.58 2H

-0.06 58 Bobbin 10 OD 11 41 68 DOS 0.49 3H

-0.18 122 Bobbin 10 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13

  • SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 42 29 TWD 25 1.71 2C

-0.28 118 Bobbin 14 OD 11 42 36 SAI 0.55 1H

-0.09 92 PP 57 OD 11 42 36 SAI 0.8 1H 0.14 79 PP 57 OD 11 42 36 DOS 1.83 1H 0.19 87 Bobbin 36 OD 11 42 40 DOS 0.41' 1H 0.08 78 Bobbin 11 OD 11 42 45 SAI 1.41 3H 0.02 73 PP 57 OD SAI-OD,>2v DOS @3H 11 42 45 DOS 2.03 3H 0.08 74 Bobbin 12 OD SAI-OD,>2v DOS @3H 11 42 46 SAI 0.14 1H 0.15 108 PP 57 OD 11 42 49 DOS 0.27 2H 0.06 118 Bobbin 11 OD 11 42 50 SAI 0.14 4H 0.09 108 PP 57 OD 11 42 50 DOS 0.29 4H 0.02 73 Bobbin 7

OD 11 42 51 SAI 0.18 1H 0.18 94 PP 30 OD 11 42 51 SAI 0.25 1H 0.1 116 PP 30 OD 11 42 51 DOS 0.43 1H 0.12 133 Bobbin 7

OD 11 42 54 DOS 0.26 2H

-0.06 38 Bobbin 8

OD 11 42 57 DOS 0.45 4H

-0.08 145 Bobbin 7

OD 11 42 58 TWD 10 0.59 2C

-0.15 147 Bobbin 7

OD 11 42 62 TWD 18 1.2 1C

-0.25 122 Bobbin 8

OD 11 42 62 DOS 0.99 2H

-0.2 87 Bobbin 8

OD 11 42 64 DOS 0.57 2H

-0.18 118 Bobbin 10 OD 11 42 65 TWD 22 1.48 1C

-0.28 123 Bobbin 9

OD 11 43 30 TWD 20 0.49 7H 37.28 0

Bobbin 38 OD 11 43 40 DOS 0.78 2H 0.06 105 Bobbin 12 OD 11 43 41 DOS 0.93 3H 0.02 92 Bobbin 12 OD 11 43 44 DOS 0.52 2H 0

104 Bobbin 11 OD 11 43 47 DOS 0.63 2H

-0.06 96 Bobbin 12 OD 11 43 48 DOS 0.51 3H

-0.08 80 Bobbin 14 OD 11 44 41 DOS 0.34 2H

-0.04

92.

Bobbin 11 OD 11 44 44 DOS 0.42 1H 0.08 117 Bobbin 12 OD 11 44 47 SAI 0.69 1H 0

98 PP 18 OD 11 44 47 DOS 0.62 1H

-0.08 99 Bobbin 5

OD 11 44 52 DOS

.0.62 2H

-0.14 134 Bobbin 8

OD 11 44 54 DOS 0.83 1H 0.2 144 Bobbin 8

OD 11 44 55 TWD 5

0.3 2C 0.3 113 Bobbin 8

OD 11 44 59 TWD 4

0.25 1C 0.04 51 Bobbin 8

OD 11 44 60 TWD 21

.1.45 2C

-0.21 124 Bobbin 8

OD 11 44 61 TWD 25 1.71 IC

-0.26 163 Bobbin 8

OD 11 45 48 DOS 0.34 1H

-0.04 130 Bobbin 13 OD 11 45 54 DOS 0.39 2H 0.02 95 Bobbin 7

OD 11 45 59 TWD 12 0.76 2C

-0.22 140 Bobbin 8

OD 11 46 48 DOS 0.23 1H 0.02 149 Bobbin 14 OD 11 46 49 DOS 0.51 2H

-0.08 109 Bobbin 12 OD 11 46 51 TWD 36 2.69 1C

-0.12 126 Bobbin 8

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 11 46 54 TWD 11 0.66 IC

-0.22 130 Bobbin 8

OD 12 1

2 VOL 0.09 1C 0.05 61 PP 62 OD 12 1

2 TWD 3

0.15 1C

-0.02 71 Bobbin 4

OD 12 1

2 DOS 0.58 2H

-0.08 102 Bobbin 4

OD 12 1

10 DIS 0.51 2H

-0.16 26 Bobbin 4

ID 12 1

13 DIS 1.3 2H

-0.04 16 Bobbin 4

ID 12 1

21 DOS 0.61 3H

-0.06 72 Bobbin 4

OD 12 1

44 DOS 0.54 5H 0.13 117 Bobbin 7

OD 12 1

56 SAI 0.21 2H

-0.03 82 PP 66 OD 12 1

56 DIS 0.47 2H

-0.04 25 Bobbin 20 ID 12 1

60 DOS 0.22 1H

-0.1 58 Bobbin 8

OD 12 1

66 DOS 0.25 2H 0

117 Bobbin 6

OD 12 1

73 DIS 0.41 3H

-0.02 40 Bobbin 6

ID 12 1

87 SAI 2.6 TSH

-9.92 20 PP 22 ID 12 2

1 TWD 16 1.03 1C

-0.18 141 Bobbin 3

OD 12 2

1 VOL 0.24 2C

-0.1 135 PP 62 OD 12 2

1 TWD 10 0.64 2C

-0.09 155 Bobbin 3

OD 12 2

10 SAI 1.45 3H

-0.01 16 PP 25 ID 12 2

10 DIS 1.1 3H

-0.08 23 Bobbin 4

ID 12 2

12 DOS 0.31 1H 0.06 116 Bobbin 4

OD 12 2

12 DOS 0.19 2H 0.12 126 Bobbin 4

OD 12 2

12 DIS 0.38 3H

-0.12 15 Bobbin 4

ID 12 2

21 SCI 0.25 TSH

-0.01 127 PP 62 OD SCI-OD @TSH-0.01 12 2

22 DOS 0.47 6C 0.1 89 Bobbin 6

OD 12 2

28 SAI 0.92 3H

-0.19 16 PP 25 ID 12 2

28 DIS 0.48 3H

-0.21 23 Bobbin 6

ID 12 2

57 DOS 0.59 3H

-0.14 80 Bobbin 20 OD 12 2

64 DOS 0.67 2H

-0.12 86 Bobbin 20 OD 12 2

64 DOS 0.95 3H 0.06 65 Bobbin 20 OD 12 2

76 SAI 0.44 2H

-0.12 7

PP 22 ID 12 2

76 DIS 1.35 2H

-0.29 33 Bobbin 6

ID 12 2

78 SAI 0.53 1H 0.13 5

PP 22 ID 12 2

78 DIS 0.33 1H

-0.32 55 Bobbin 6

ID 12 2

79 SAI 0.45 3H

-0.09 7

PP 22 ID 12 2

79 DIS 0.19 3H 0.1 105 Bobbin 5

ID 12 2

85 DIS 0.16 4H

-0.12 42 Bobbin 20 ID 12 2

90 SAI 0.61 3H

-0.1 8

PP 69 ID 12 2

90 SAI 0.94 4H

-0.34 14 PP 22 ID 12 2

90 SAI 1.1 4H

-0.14 15 PP 22 ID 12 2

90 DIS 1.31 4H

-0.44 17 Bobbin 20 ID 12 2

92 SAI 0.31 5H

-0.07 11 PP 22 ID 12 2

92 SAI 0.35 5H

-0.41 8

PP 22 ID 12 2

92 SAI 0.62 5H 0.15 7

PP 22 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 2

92 DIS 0.38 5H 0.25 55 Bobbin 7

ID 12 2

93 SAI 0.49 4H 0.15 12 PP 22 ID 12 2

93 DIS 0.18 4H 0.18 54 Bobbin 20 ID 12 3

1 TWD 10 0.65 1C

-0.12 131 Bobbin 4

OD 12 3

8 DOS 0.75 5H

-0.19 119 Bobbin 3

OD 12 3

14 DOS 0.62 6H

-0.19 106 Bobbin 3

OD 12 3

18 SAI 0.19 6H

-0.26 115 PP 72 OD 12 3

18 DOS 0.38 6H

-0.27 94 Bobbin 3

OD 12 3

21 DOS 0.69 4H

-0.1 51 Bobbin 4

OD 12 3

45 DOS 0.3 2H 0

82 Bobbin 8

OD 12 3

46 SAI 0.6 7C 0.06 13 PP 61 ID 12 3

46 SAI 0.76 7C 0.03 12 PP 50 ID 12 3

50 DOS 0.54 1H

-0.02 120 Bobbin 5

OD 12 3

56 DOS 0.24 4H 0

71 Bobbin 7

OD 12 3

58 DOS 0.34 4H

-0.08 130 Bobbin 7

OD 12 3

59 DOS 0.79 1H 0.08 93 Bobbin 7

OD 12 3

61 DOS 0.69 1H 0

78 Bobbin 8

OD 12 3

62 DOS 0.21 2H 0.02 130 Bobbin 5

OD 12 3

80 DOS 0.92 1H 0.17 57 Bobbin 5

OD 12 3

89 DIS 1.08 5H 0.17 42 Bobbin 8

ID 12 3

91 DOS 0.53 2H

-0.08 72 Bobbin 7

OD 12 4

1 TWD 23 1.57 2C 0.02 119 Bobbin 3

OD 12 4

47 DOS 0.83 1H 0.02 90 Bobbin 6

OD 12 4

49 SAI 0.33 1H 0.05 104 PP 72 OD 12 4

49 DOS 1.05 1H 0.16 52 Bobbin 6

OD 12 4

50 SAI 0.34 2H

-0.12 101 PP 72 OD 12 4

50 DOS 0.88 2H

-0.14 108 Bobbin 6

OD 12 4

54 SAI 1.06 2H 0

15 PP 25 ID 12 4

54 DIS 0.55 2H

-0.04 33 Bobbin 8

ID 12 4

55 DIS 0.41 1H 0.19 22 Bobbin 7

ID 12 4

57 SAI 0.5 1H 0.08 6

PP 25 ID 12 4

57 DIS 0.56 1H 0.19 77 Bobbin 8

ID 12 4

58 SAI 0.34 1H

-0.32 17 PP 23 ID Multi SAl-ID @1H, Preventive 12 4

58 SAI 1.28 1H

-0.23 18 PP 23 ID Multi SAI-ID @IH, Preventive 12 4

58 SAI 3

1H 0.17 22 PP 23 ID Multi SAI-ID @1H, Preventive 12 4

58 DIS 2.82 1H 0.1 38 Bobbin 8

ID Multi SAl-ID @1H, Preventive 12 4

70 DOS 0.68 2H

-0.16 110 Bobbin 6

OD 12 4

72 SAI 0.16 1H

-0.05 124 PP 71 OD 12 4

72 DIS 0.35 1H

-0.1 23 Bobbin 6

ID 12 4

82 DOS 0.34 4H

-0.02 45 Bobbin 6

OD 12 4

84 SAI 0.6 1H 0

10 PP 22 ID 12 4

84 DIS 1.1 1H

-0.36 18 Bobbin 1

ID 12 4

85 SAI 0.18 3H

-0.16 113 PP 43 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 4

85 DOS 0.31 3H

-0.17 90 Bobbin 8

OD 12 4

90 DOS 0.45 4H

-0.27 133 Bobbin 8

OD 12 4

94 TWD 29 2.12 1C 0.11 121 Bobbin 9

OD 12 4

94 DOS 0.7 1H

-0.21 103 Bobbin 8

OD 12 4

94 DIS 1.2 6H

-0.02 11 Bobbin 8

ID 12 5

1 TWD 15 0.96 2C 0.07 139 Bobbin 3

OD 12 5

4 TWD 10 0.64 1C

-0.24 126 Bobbin 3

OD 12 5

19 DOS 1.19 3H

-0.1 54 Bobbin 3

OD 12 5

20 DOS 1.41 2H

-0.2 103 Bobbin 20 OD 12 5

20 DOS 0.43 4H

-0.1 78 Bobbin 20 OD 12 5

20 DOS 0.56 4H

-0.16 86 Bobbin 3

OD 12 5

20 SAI 0.14 6H

-0.09 112 PP 61 OD 12 5

27 SAI 0.15 TSH 0

67 PP 63 OD SAI-OD @TSH+0.00 12 5

42 DOS 0.89 4H

-0.1 108 Bobbin 7

OD 12 5

49 DOS 0:62 2H

-0.27 98 Bobbin 5

OD 12 5

50 DOS 0.59 1H

-0.06 102 Bobbin 5

OD 12 5

50 DOS 0.65 3H 0.1 83 Bobbin 5

OD 12 5

51 DOS 1.05 1H

-0.02 98 Bobbin 7

OD 12 5

51 DOS 0.35 3H 0.15 103 Bobbin 7

OD 12 5

52 SAI 0.4 2H 0.08 85 PP 72 OD 12 5

52 DOS 0.53 2H 0.02 72 Bobbin 7

OD 12 5

53 DOS 0.25 1H 0

124 Bobbin 7

OD 12 5

55 SAI 0.22 1H

-0.2 108 PP 66 OD 12 5

55 DOS 0.23 1H

-0.13 82 Bobbin 7

OD 12 5

57 DOS 0.79 1H 0.04 83 Bobbin 7

OD 12 5

58 DOS 0.26 6C

-0.07 115 Bobbin 5

OD 12 5

65 SAI 0.14 1H 0.01 117 PP 23 OD SAI-ID/AONDB @1H 12 5

65 SAI 0.67 1H

-0.14 10 PP 23 ID SAI-ID/AONDB @1H 12 5

65 DIS 0.18 1H

-0.08 27 Bobbin 5

ID SAI-ID/AONDB @IH 12 5

66 DOS 1.2 1H

-0.13 84 Bobbin 5

OD 12 5

66 SAI 0.77 2H

-0.05 12 PP 23 ID 12 5

66 DIS 0.97 2H

-0.42 9

Bobbin 5

ID 12 5

66 DOS 0.46 6H

-0.04 140 Bobbin 5

OD 12 5

70 DOS 0.44 2H

-0.1 106 Bobbin 5

0D 12 5

70 SAI 0.12 4H

-0:04 87 PP 71 0D 12 5

70 SAI 0.17 4H 0.07 120 PP 71 OD 12 5

70 DOS 0.64 4H

-0.02 95 Bobbin 5

OD 12 5

72 DIS 0.72 2H 0.08 27 Bobbin 5

ID 12 5

75 DOS 0.83 3H 0.1 139 Bobbin 5

0D 12 5

77 SAI 0.93 5H

-0.18 16 PP 22 ID 12 5

77 DIS 1.45 5H

-0.23 35 Bobbin 5

ID 12 5

78 SAI 1.15 1H 0.12 11 PP 22 ID 12 5

78 DIS 0.22 1H 0.13 48 Bobbin 5

ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IOD Reason for Plugging 12 5

91 DOS 0.65 1H

-0.15 105 Bobbin 7

OD 12 5

91 SAI 0.2 5H

-0.2 89 PP 42 OD 12 5

93 SAI 1.31 1H

-0.12 16 PP 22 ID 12 5

93 DIS 1.21 1H

-0.19 29 Bobbin 7

ID 12 6

7 DOS 0.29 4H 0.03 69 Bobbin 25 OD 12 6

14 SAI 0.34 1H

-0.33 126 Pp 60 OD 12 6

16 DOS 0.66 1H 0.14 120 Bobbin 23 OD 12 6

39 DOS 0.86 1H 0.02 108 Bobbin 22 OD 12 6

49 SAI 0.24 1H

-0.2 114 PP 73 OD 12 6

49 DOS 0.7 2H 0.05 85 Bobbin 22 OD 12 6

51 DOS 0.35 2H 0.16 122 Bobbin 32 OD 12 6

54 SAI 0.39 3H

-0.05 120 PP 72 OD 12 6

54 DOS 1.07 3H 0.03 96 Bobbin 32 OD 12 6

55 SAI 0.68 7C

-0.06 13 PP 62 ID 12 6

55 SAI 0.79 7C 0

13 PP 63 ID 12 6

56 SAI 0.3 2H

-0.07 116 PP 72 OD 12 6

56 DOS 1

2H 0

71 Bobbin 32 OD 12 6

58 DOS 0.49 3H 0.07 69 Bobbin 32 OD 12 6

59 SAI 0.21 1H 0.08 112 PP 72 OD 12 6

59 SAI 0.23 1H

-0.01 109 PP 72 OD 12 6

59 DOS 0.77 1H 0.1 72 Bobbin 32 OD 12 6

62 DOS 0.67 1H

-0.05 106 Bobbin 30 OD 12 6

62 DOS 0.51 6H

-0.03 123 Bobbin 30 OD 12 6

63 DIS 0.94 2H

-0.07 39 Bobbin 30 ID 12 6

65 SAI 0.28 2H 0.07 111 PP 71 OD 12 6

65 DOS 0.57 2H 0.09 44 Bobbin 30 OD 12 6

65 DOS 0.58 4H

-0.02 113 Bobbin 30 OD 12 6

65 SAI 0.15 5H

-0.16 133 PP 71 OD 12 6

65 SAI 0.23 5H

-0.05 126 PP 71 OD 12 6

65 DOS 0.55 5H

-0.05 89 Bobbin 30 OD 12 6

66 DOS 0.54 4H 0.19 89 Bobbin 30 OD 12 6

67 DIS 2

1H

-0.17 29 Bobbin 30 ID 12 6

74 SAI 0.39 3H

-0.41 10 PP 22 ID 12 6

74 SAI 0.77 3H

-0.05 8

PP 22 ID 12 6

74 DIS 1.74 3H 0

20 Bobbin 30 ID 12 6

78 SCI 0.21 1H 0.31 119 PP 37 OD SCI-OD @1H+0.31 12 6

81 SAI 0.23 1H

-0.14 88 PP 37 OD 12 6

81 DOS 0.84 4H

-0.12 122 Bobbin 30 OD 12 6

87 DOS 0.57 2H

-0.05 53 Bobbin 30 OD 12 6

92 SAI 0.16 1H 0.25 110 PP 35 OD 12 6

93 VOL 0.27 1C

-0.21 116 PP 61 OD 12 6

93 TWD 19 1.24 1C

-0.24 133 Bobbin 30 OD 12 7

2 TWD 42 3.42 2C

-0.07 116 Bobbin 24 OD 42%TW CLT@2C Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 7

4 TWD 11 0.71 1C 0

149 Bobbin 25 OD 12 7

13 DOS 0.84 1H 0.05 102 Bobbin 23 OD 12 7

17 DOS 0.65 1H

-0.02 120 Bobbin 24 OD 12 7

17 SAI 0.53 4H 0.01 15 PP 72 ID 12 7

17 DIS 0.82 4H

-0.16 39 Bobbin 24 ID 12 7

31 SAI 0.94 1H 0.06 14 PP 25 ID 12 7

31 DIS 0.96 1H 0.21 36 Bobbin 24 ID 12 7

31 SAI 1.63 7C

-0.27 21 PP 61 ID 12 7

31 SAI 2.37 7C

-0.22 20 PP 52 ID 12 7

31 DIS 2.79 7C

-0.21 26 Bobbin 24 ID 12 7

33 SAI 1.55 TSH

-1.78 31 PP 25 ID 12 7

49 SAI 0.38 1H 0.06 118 PP 72 OD 12 7

49 SAI 0.48 1H 0

82 PP 72 OD 12 7

49 DOS 1.72 1H 0.02 111 Bobbin 33 OD 12 7

52 DOS 0.61 1H

-0.03 119 Bobbin 32 OD 12 7

53 SAI 0.77 3H 0.02 14 PP 25 ID 12 7

53 DIS 0.5 3H 0.09 30 Bobbin 32 ID 12 7

54 SAI 0.19 1H

-0.2 122 PP 65 OD 12 7

54 DOS 0.74 2H 0.14 120 Bobbin 32 OD 12 7

63 DOS 0.48 3H 0.18 113 Bobbin 30 OD 12 7

65 SAI 0.3 2H

-0.05 109 PP 40 OD 12 7

65 DIS 0.97 2H

-0.16 37 Bobbin 30 ID 12 7

68 SAI 0.99 3H 0.21 14 PP 22 ID 12 7

68 DIS 1.27 3H 0.3 33 Bobbin 30 ID 12 7

72 DIS 0.92 2H

-0.03 32 Bobbin 30 ID 12 7

76 DIS 0.53 5H

-0.05 33 Bobbin 30 ID 12 7

77 SCI 0.25 5H 0.29 131 PP 36 OD SCI-OD @5H+0.29 12 7

79 DIS 0.43 5H

-0.05 28 Bobbin 30 ID 12 7

81 SCI 0.25 4H 0.29 115 PP 36 OD SCI-OD @4H+0.29 12 7

82 DOS 0.42 3H 0.02 118 Bobbin 30 OD 12 7

82 DOS 0.32 4H 0.16 80 Bobbin 30 OD 12 7

85 SAI 0.46 1H 0

106 PP 69 OD 12 7

85 DOS 0.96 1 H 0.02 144 Bobbin 30 OD 12 7

94 VOL 0.15 1C

-0.17 78 PP 61 OD 12 7

94 TWD 12 0.78 1C

-0.23 149 Bobbin 30 OD 12 8

4 SAI 1.28 5H

-0.11 16 PP 25 ID

.12 8

4 DIS 1.07 5H

-0.07 37 Bobbin 24 ID 12 8

15 SAI 1.35 2H

-0.04 16 PP 25 ID 12 8

15 DIS 1.13 2H 0.05 33 Bobbin 23 ID 12 8

17 SAI 0.21 1H 0.33 90 PP 58 OD 12 8

17 DIS 0.62 1H 0.35 29 Bobbin 25 ID 12 8

20 SAI 0.36 2H

-0.27 99 PP 58 OD 12 8

20 DOS 0.74 2H

-0.21 49 Bobbin 25 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1 R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 8

38 DOS 0.29 2H 0.03 82 Bobbin 23 OD 12 8

48 SAI 0.54 1H

-0.16 11 pp 25 ID 12 8

48 DIS 0.65 1H

-0.16 35 Bobbin 42 ID 12 8

55 SAI 1.58 1H

-0.03 17 PP 25 ID 12 8

55 DIS 1.31 1H 0.03 32 Bobbin 32 ID 12 8

56 SCI 0.49 1H 0.35 122 PP 65 OD SCI-OD @1H+0.35 12 8

57 SAI 2.42 1H

-0.22 21 PP 25 ID 12 8

57 DIS 3.03 1H

-0.21 30 Bobbin 32 ID 12 8

61 SAI 0.76 2H 0.13 15 PP 23 ID 12 8

61 SAt 1.53 2H

-0.19 16 PP 23 ID 12 8

61 DIS 1.78 2H

-0.17 24 Bobbin 32 ID 12 8

66 SAI 0.56 2H

-0.26 17 PP 23 ID 12 8

66 DIS 1.18 2H

-0.24 39 Bobbin 30 ID 12 8

68 DOS 0.46 1H

-0.03 138 Bobbin 30 OD 12 8

68 DOS 0.86 4H

-0.14 97 Bobbin 30 OD 12 8

82 SAI 0.42 4H

-0.08 11 pp 37 ID 12 8

88 SCI 0.27 2H 0.23 101 pp 34 OD SCI-OD @2H+0.23 12 8

92 TWD 12 0.77 2C

-0.17 130 Bobbin 30 OD 12 8

93 SAI 1.06 1H

-0.13 16 pp 22 ID 12 8

93 DIS 1.14 1H

-0.07 38 Bobbin 30 ID 12 9

3 TWD 11 0.67 1C

-0.02 150 Bobbin 24 OD 12 9

3 SAI 0.16 3H

-0.05 98 pp 82 OD 12 9

3 DOS 0.62 3H

-0.08 77 Bobbin 75 OD 12 9

27 SAI 0.31 3H

-0.15 9

pp 25 ID 12 9

27 DIS 0.29 3H

-0.27 70 Bobbin 75 ID 12 9

30 SAI 2.43 1H 0

19 pp 25 ID 12 9

30 DIS 1.57 1H

-0.04 44 Bobbin 75 ID 12 9

33 SAI 0.18 1H 0

102 pp 56 OD 12 9

38 SAI 2.8 2H

-0.18 16 pp 24 ID 12 9

38 DIS 2.03 2H

-0.12 37 Bobbin 31 ID 12 9

45 SAI 1.19 1H 0.18 15 pp 24 ID 12 9

45 DIS 0.87 1H 0.22 43 Bobbin 31 ID 12 9

53 SAI 1.32 1H 0.05 15 pp 25 ID 12 9

53 DIS 0.7 1H 0.1 20 Bobbin 32 ID 12 9

54 DIS 0.71 1H

-0.09 50 Bobbin 32 ID 12 9

55 SAI 0.13 1H

-0.19 115 pp 66 OD 12 9

56 SAI 1.3 1H

-0.26 15 pp 25 ID 12 9

56 DIS 1.87 1H

-0.32 26 Bobbin 7

ID 12 9

58 DOS 1.18 2H

-0.07 74 Bobbin 32 OD 12 9

79 DIS 0.94 4H

-0.26 35 Bobbin 75 ID 12 9

82 SAI 1.26 3H 0.15 16 pp 22 ID 12 9

82 DIS 1.61 3H 0.25 36 Bobbin 5

ID 12 9

92 TWD 15 0.96 2C

-0.07 128 Bobbin 9

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 10 3

TWD 8

0.51 2C

-0.08 137 Bobbin 25 OD 12 10 4

DIS 0.51 3H

-0.3 14 Bobbin 24 ID 12 10 4

DOS 0.48 3H

-0.02 75 Bobbin 24 OD 12 10 10 SAI 0.18 2H

-0.09 101 PP 72 OD 12 10 10 DOS 0.56 2H 0.04 74 Bobbin 22 OD 12 10 32 DOS 0.43 1H 0

72 Bobbin 25 OD 12 10 41 SAI 0.41 2H

-0.03 115 PP 54 OD 12 10 41 DOS 0.92 2H 0.02 102 Bobbin 23 OD 12 10 43 SAI 0.33 1H

-0.01 113 PP 53 OD 12 10 43 DIS 0.64 1H

-0.21 44 Bobbin 23 ID 12 10 43 DOS 0.45 2H

-0.21 85 Bobbin 23 OD 12 10 45 SAI 0.17 2H

-0.02 104 PP 51 OD 12 10 45 DIS 0.78 2H

-0.11 46 Bobbin 23 ID 12 10 49 SAI 0.73 3H 0.2 9

PP 25 ID 12 10 49 DIS 0.53 3H

-0.17 27 Bobbin 26 ID 12 10 49 DIS 0.65 3H 0.26 50 Bobbin 26 ID 12

10.

52 DOS 0.61 2H 0.23 82 Bobbin 32 OD 12 10 58 DOS 0.95 4H 0.12 81 Bobbin 32 OD 12 10 62 SAI 1.1 1H 0.02 18 PP 23 ID 12 10 62 DIS 0.64 1H 0.07 25 Bobbin 32 ID 12 10 64 DOS 0.79 1H

-0.05 134 Bobbin 30 OD 12 10 66 DOS 0.29 2H 0.1 118 Bobbin 30 OD 12 10 67 SAI 0.88 1H

-0.21 7

PP 23 ID 12 10 67 DIS 0.26 1H

-0.16 87 Bobbin 30 ID 12 10 68 SAI 1.67 1H

-0.15 15 PP 22 ID 12 10 68 DIS 1.64 1H

-0.07 29 Bobbin 30 ID 12 10 69 SAI 0.51 2H

-0.21 10 PP 22 ID 12 10 72 DOS 0.88

. 2H

-0.1 122 Bobbin 30 OD 12 10 73 DIS 0.8 6H 0.33 26 Bobbin 30 ID 12 10 74 DIS 1.17 1H

-0.21 29 Bobbin 30 ID 12 10 80 SAI 0.84 1H

-0.22 16 PP 22 ID SCI-OD @5H+0.28 12 10 80 SCI 0.18 5H 0.28 123 PP 36 OD SCI-OD @5H+0.28 12 10 81 SAI 0.36 1H

-0.2 110 PP 69 OD 12 10 81 DOS 0.53 1H

-0.14 120 Bobbin 30 OD 12 10 82 DOS 0.36 2H 0.26 84 Bobbin 30 OD 12 10 85 SAI 0.53 4H 0.16 14 PP 22 ID 12 10 85 DIS 0.47 4H 0.26 34 Bobbin 30 ID 12 11 18 SAI 0.26 2H

-0.26 116 PP 57 OD 12 11 20 SAI 1.79 2H 0.02 18 PP 25 ID 12 11 20 DIS 1.67 2H 0.09 29 Bobbin 24 ID 12 11 34 DOS 0.51 1H 0.05 63 Bobbin 24 OD 12 11 40 SAI 0.35 1H

-0.08 116 PP 53 OD 12 11 45 SAI 1.04 1H 0.19 6

PP 24 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 11 58 DOS 0.65 1H 0.02 99 Bobbin 32 OD 12 11 60 DOS 0.78 6H 0.05 87 Bobbin 32 OD 12 11 64 DOS 0.79 1H 0.17 156 Bobbin 30 OD 12 11 66 SAI 1.03 3H

-0.05 10 Pp 23 ID 12 11 66 DIS 1.19 3H

-0.03 26 Bobbin 30 ID 12 11 68 DIS 0.9 7H

-0.05 22 Bobbin 30 ID 12 11 71 SAI 0.43 1H 0.14 9

PP 22 ID 12 11 71 SAI 0.51 1H 0.05 10 PP 22 ID 12 11 71 SAI 1.32 1H

-0.16 17 PP 22 ID 12 11 71 SAI 1.34 1H

-0.21 16 PP 22 ID 12 11 71 DIS 2.79 1H

-0.17 38 Bobbin 30 ID 12 11 75 SAI 0.25 2H

-0.2 110 PP 38 OD 12 11 75 DIS 1.43 2H

-0.17 33 Bobbin 30 ID 12 11 75 DIS 0.88 4H

-0.14 49 Bobbin 30 ID 12 11 76 DOS 0.59 1H

-0.05 49 Bobbin 30 OD 12 11 82 DOS 0.68 2H

-0.03 68 Bobbin 30 OD 12 11 84 SAI 0.5 2H 0.1 11 PP 22 ID 12 11 87 SAI 2.15 1H

-0.1 20 PP 22 ID 12 11 87 DIS 2.38 1H

-0.02 40 Bobbin 30 ID 12 11 91 SAI 0.2 1H

-0.12 103 PP 34 OD 12 11 92 DOS 0.7 1H 0.17 74 Bobbin 30 OD 12 11 93 TWD 16 1.05 2C

-0.1 122 Bobbin 30 OD 12 12 3

TWD 11 0.72 lC

-0.02 132 Bobbin 25 OD 12 12 4

TWD 11 0.67 1C

-0.07 154 Bobbin 24 OD 12 12 8

DIS 1.12 1H

-0.09 30 Bobbin 24 ID 12 12 14 DOS 0.35 1H 0.06 138 Bobbin 23 OD 12 12 21 DIS 0.54 4H

-0.16 39 Bobbin 25 ID 12 12 35 DOS 0.58 1H 0.05 102 Bobbin 23 OD 12 12 46 SAI 0.3 2H 0.06 105 PP 72 OD 12 12 46 DOS 1.27 2H 0

56 Bobbin 23 OD 12 12 55 DOS 0.46 2H

-0.02 111 Bobbin 32 OD 12 12 63 DOS 0.68 1H

-0.14 116 Bobbin 32 OD 12 12 64 DOS 0.28 1H 0.03 79 Bobbin 30 OD 12 12 65 SAI 0.19 2H 0.25 71 PP 41 OD 12 12 65 DOS 0.77 2H 0.3 53 Bobbin 30 OD 12 12 65 DOS 0.57 5H

-0.12 107 Bobbin 30 OD 12 12 68 DOS 0.46 1H

-0.02 129 Bobbin 30 OD 12 12 69 DOS 0.54 1H

-0.07 116 Bobbin 30 OD 12 12 76 SAI 0.12 1H

-0.17 92 PP 39 OD 12 12 79 SCI 0.23 1H 0.3 113 PP 37 OD SCI-OD @1H+0.30 12 12 83 SAI 0.58 2H 0

95 PP 69 OD 12 12 83 DOS 1.02 2H 0.1 129 Bobbin 30 OD 12 12 86 SCI 0.24 1H 0.14 151 PP 35 OD Multi SCI-OD @IH Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 12 86 SCI 0.34 1H 0.37 127 PP 35 OD Multi SCI-OD @1H 12 12 86 SCI 0.44 1H

-0.28 133 PP 35 OD Multi SCI-OD @1H 12 12 86 DOS 0.72 4H

-0.17 85 Bobbin 30 OD Multi SCI-OD @IH 12 12 92 SCI 0.15 1H 0.38 129 PP 35 OD SCI-OD @1H+0.38 12 12 93 DOS 0.93 2H 0.05 110 Bobbin 30 OD 12 13 3

TWD 10 0.61 1C

-0.05 143 Bobbin 24 OD 12 13 5

VOL 0.07 1C 0

116 PP 62 OD 12 13 5

TWD 7

0.45 1C

-0.26 124 Bobbin 24 OD 12 13 6

TWD 19 1.27 2C

-0.1 126 Bobbin 24 0D 12 13 20 DOS 0.57 3H 0.09 41 Bobbin 24 0D 12 13 34 SAI 1.23 1H 0.16 18 PP 24 ID 12 13 34 DIS 1.27 1H 0.21 26 Bobbin 24 1D 12 13 34 DOS 0.49 2H 0.14 147 Bobbin 24 0D 12 13 34 DOS 0.94 3H

-0.21 120 Bobbin 24 0D 12 13 41 DOS 0.78 5H 0.09 114 Bobbin 22 0D 12 13 44 SAI 1.97 1H 0.03 21 PP 24 ID 12 13 44 DIS 2.62 1H 0.05 36 Bobbin 22 ID 12 13 51 DOS 1.36 1H 0.1 92 Bobbin 32 0D 12 13 52 DOS 0.42 1H 0.05 57 Bobbin 32 OD 12 13 52 DOS 0.35 2H 0.07 144 Bobbin 32 OD 12 13 53 DOS 0.33 5C 0.02 62 Bobbin 32 OD 12 13 60 SAI 1.44 2H

-0.02 16 PP 23 ID 12 13 60 DIS 1.19 2H 0.07 35 Bobbin 32 ID 12 13 66 SAI 0.2 2H 0.29 88 PP 40 OD 12 13 70 SCI 0.35 1H 0.34 108 PP 38 OD SCI-OD @1H+0.34 12 13 71 SVI 0.37 1H 0.32 96 PP 38 OD OD-SVI @1H+0.32 12 13 73 DOS 0.47 3H 0.05 146 Bobbin 30 OD 12 13 76 DOS 0.33 1H 0.02 105 Bobbin 30 OD 12 13 76 DOS 1.04 2H

-0.02 124 Bobbin 30 OD 12 13 79 SCI 0.19 1H 0.03 103 PP 36 OD SCI-OD @1H+0.03 12 13 80 DOS 0.99 2H

-0.14 115 Bobbin 30 OD 12 13 82 SAI 0.27 5H

-0.24 73 PP 71 OD 12 13 82 DOS 0.9 5H

-0.12 69 Bobbin 30 OD 12 13 83 DOS 0.22 1H 0

115 Bobbin 30 OD 12 13 83 SAI 0.15 3H 0.23 46 PP 37 OD 12 13 83 SAI 0.18 3H

-0.23 110 PP 37 OD 12 13 83 DOS 1.12 3H

-0.19 43 Bobbin 30 OD 12 13 83 SAI 0.14 5H 0.36 97 PP 37 OD 12 13 83 SAI 0.19 5H

-0.24 125 PP 37 OD 12 13 83 DOS 0.94 5H

-0.21 38 Bobbin 30 OD 12 13 84 SAI 0.27 1H

-0.07 99 PP 22 OD Multi SAI-ID/AONDB @1H 12 13 84 SAI 0.4 1H

-0.03 13 PP 22 ID Multi SAI-ID/AONDB @1H 12 13 84 SAI 0.4 1H 0.01 10 PP 22 ID Multi SAI-ID/AONDB @1H Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 13 84 DIS 0.5 1H 0.05 41 Bobbin 30 ID Multi SAI-ID/AONDB @1H 12 13 84 SAI 0.3 2H 0.23 101 pp 71 OD Multi SAI-ID/AONDB @1H 12 13 84 DOS 0.57 2H 0.3 71 Bobbin 30 OD Multi SAI-ID/AONDB @IH 12 13 84 DOS 0.48 3H 0.09 111 Bobbin 30 OD Multi SAI-ID/AONDB @1H 12 13 84 DOS 0.43 6C 0.03 66 Bobbin 30 OD Multi SAI-ID/AONDB @IH 12 13 87 DOS 0.62 2H 0

87 Bobbin 30 OD 12 13 90 DOS 0.89 3H 0

106 Bobbin 30 OD 12 13 92 TWD 10 0.61 2C

-0.05 136 Bobbin 30 OD 12 14 5

TWD 10 0.63 2C

-0.23 140 Bobbin 27 OD 12 14 5

SAI 0.28 2H 0.07 112 PP 78 OD 12 14 5

DOS 0.77 2H

-0.04 81 Bobbin 27 OD 12 14 7

SAI 0.19 2H 0.06 78 PP 62 OD 12 14 14 DOS 0.33 1H 0

142 Bobbin 16 OD 12 14 16 SAI 0.95 4H 0

14 PP 25 ID 12 14 16 DIS 0.57 4H 0.02 24 Bobbin 19 ID 12 14 19 DOS 0.56 1H 0.17 115 Bobbin 19 OD 12 14 22 DOS 0.29 1H 0.02 74 Bobbin 19 OD 12 14 23 DOS 0.31 2H

-0.04 54 Bobbin 19 OD 12 14 24 DOS 0.26 1H 0.08 107 Bobbin 19 OD 12 14 25 DIS 0.9 4H

-0.15 31 Bobbin 19 ID 12 14 27 DOS 1.26 1H 0.15 68 Bobbin 19 OD 12 14 30 SAI 0.38 2H

-0.01 103 PP 56 OD 12 14 30 DOS 1.31 2H 0.04 121 Bobbin 19 OD 12 14 31 DOS 0.53 3H 0.04 133 Bobbin 19 OD 12 14 36 DOS 0.49 2H 0.29 69 Bobbin 19 00 12 14 37 DOS 0.95 2H 0.1 90 Bobbin 19 OD 12 14 43 DOS 1.48 1H 0.21 137 Bobbin 19 OD 12 14 45 SAI 0.48 1H

-0.01 8

pp 24 ID 12 14 45 DIS 0.98 1H

-0.19 41 Bobbin 19 ID 12 14 48 DOS 0.64 1H

-0.04 113 Bobbin 21 OD 12 14 52 DOS 0.68 2H 0.06 145 Bobbin 28 OD 12 14 57 DIS 0.34 5H

-0.06 20 Bobbin 28 ID 12 14 58 SAI 0.47 4H 0.24 7

PP 25 ID 12 14 68 SAI 0.63 1H 0.07 8

PP 23 ID 12 14 70 SAI 0.36 1H

-0.06 8

Pp 22 ID 12 14 70 DIS 3.54 1H

-0.19 10 Bobbin 28 ID 12 14 74 SAI 1.02 1H

-0.2 11 PP 22 ID 12 14 74 DIS 5.59 1H

-0.04 15 Bobbin 28 ID 12 14 76 SAI 0.17 1H 0.24 82 pp 39 OD 12 14 76 SAI 0.45 1H 0.01 96 pp 39 OD 12 14 76 DOS 0.89 1H 0.06 142 Bobbin 28 OD 12 14 77 SCI 0.18 1H 0.31 103 PP 36 OD Multi SCI-0D @IH 12 14 77 SCI 0.22 1H 0.32 132 PP 36 OD Multi SCI-OD @1H Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 14 79 SAI 0.18 4H 0.32 80 Pp 37 OD 12 14 83 SCI 0.4 1H 0.3 125 PP 36 OD SCI-OD @1H+0.30 12 14 84 SAI 0.23 2H 0.3 124 PP 35 OD 12 14 84 DOS 0.62 2H 0.32 81 Bobbin 29 OD 12 14 91 TWD 15 0.95 10C

-0.15 130 Bobbin 29 OD 12 15 5

TWD 15 0.96 2C

-0.17 128 Bobbin 27 OD 12 15 18 DOS 0.35 2H 0.04 69 Bobbin 18 OD 12 15 26 DOS 0.62 1H 0.11 118 Bobbin 18 OD 12 15 32 SAI 0.32 2H 0

91 Pp 72 OD 12 15 32 DOS 0.85 2H 0.16 158 Bobbin 19 OD 12 15 33 SAI 0.26 3H

-0.05 101 PP 72 OD 12 15 33 DOS 0.58 3H 0

58 Bobbin 18 OD 12 15 35 DOS 0.68 1H 0.13 137 Bobbin 18 OD 12 15 35 DOS 0.45 5H 0.17 75 Bobbin 18 OD 12 15 42 SAI 0.26 2H 0.01 97 PP 53 OD 12 15 42 DOS 0.43 2H 0.06 162 Bobbin 19 OD 12 15 48 DOS 0.49 2H

-0.06 99 Bobbin 20 OD 12 15 61 DOS 0.99 1H

-0.11 99 Bobbin 28 OD 12 15 74 SAI 0.35 1H

-0.04 99 PP 38 OD SAI-OD,>2v DOS @1H 12 15 74 DOS 2.06 1H 0.03 168 Bobbin 33 OD SAI-OD,>2v DOS @IH 12 15 76 DOS 1.26 1H

-0.09 96 Bobbin 28 OD 12 15 79 SCI 0.31 1H 0.34 101 PP 36 OD SCI-OD @1H+0.34 12 15 80 DOS 0.47 1H 0.13 79 Bobbin 28 OD 12 15 81 SCI 0.19 1H 0.23 129 PP 36 OD SCI-OD @1H+0.23 12 15 81 SAI 0.17 4H

-0.24 109 Pp 36 OD SCI-OD @1H+0.23 12 15 85 SAI 0.14 2H 0.02 92 Pp 35 OD 12 15 92 DOS 0.99 1H

-0.04 86 Bobbin 29 OD 12 15 92 TWD 9

0.58 2C

-0.08 120 Bobbin 29 OD 12 16 9

DIS 0.68 4H 0.04 25 Bobbin 27 ID 12 16 12 SAI 0.54 5H 0

8 PP 25 ID 12 16 12 DIS 0.88 5H

-0.19 28 Bobbin 16 ID 12 16 30 SAI 0.16 2H 0.2 96 PP 72 OD 12 16 30 SAI 0.3 2H

-0.16 92 PP 72 OD 12 16 30 DOS 0.96 2H

-0.12 54 Bobbin 19 OD 12 16 33 DOS 0.64 1H 0.02 88 Bobbin 19 OD 12 16 33 SAI 0.38 2H 0.02 99 PP 72 OD 12 16 33 DOS 0.8 2H 0.02 150 Bobbin 19 OD 12 16 38 SCI 0.25 1H 0.27 116 PP 54 OD SCI-OD @1HH+0.27 12 16 40 SAI 0.82 2H

-0.04 82 PP 54 OD 12 16 40 DOS 1.49 2H 0.1 109 Bobbin 19 OD 12 16 44 DIS 0.84 4H 0

4 Bobbin 19 ID 12 16 52 DOS 0.58 2H

-0.04 107 Bobbin 28 OD 12 16 55 DOS 0.54 1H

-0.06 130 Bobbin 28 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 16 59 SAI 2.08 2H 0.01 16 PP 23 ID 12 16 59 DIS 2.45 2H 0.11 27 Bobbin 28 ID 12 16 60 SAI 0.45 2H

-0.2 10 PP 23 ID 12 16 82 SAI 0.66 1H 0.04 7

PP 22 ID 12 16 82 DIS 0.83 1H 0.17 31 Bobbin 29 ID 12 16 82 SAI 0.84 4H 0.07 16 PP 22 ID 12 16 82 DIS 0.82 4H

-0.19 50 Bobbin 29 ID 12 16 84 SCI 0.2 5H 0.32 137 PP 35 OD SCI-OD @5H+0.32 12 16 85 SAI 0.46 2H

-0.23 19 PP 22 ID 12 16 85 DIS 0.36 2H

-0.19 43 Bobbin 29 ID 12 16 87 SAI 1.3 2H 0.05 16 PP.

22 ID 12 16 87 DIS 1.27 2H 0.15 26 Bobbin 29 ID 12 16 88 SAI 0.28 2H

-0.26 9

PP 22 ID 12 16 88 SAI 1.2 2H

-0.03 15 PP 22 ID 12 16 88 DIS 1.26 2H 0.04 30 Bobbin 29 ID 12 16 90 DOS 1.02 1H 0.02 74 Bobbin 29 OD 12 17 9

SAI 0.72 6H

-0.05 12 PP 25 ID 12 17 9

DIS 1.02 6H

-0.15 15 Bobbin 27 ID 12 17 11 FSI 0.37 1H 24.72 76 Bobbin 27 12 17 11 FSI 0.38 1H 24.11 96 Bobbin 27 12 17 16 SAI 0.18 3H

-0.18 110 PP 72 OD 12 17 16 DOS 0.53 3H

-0.19 60 Bobbin 18 OD 12 17 22 SAI 0.33 1H

-0.25 138 PP 58 OD AONDB @1H >5v dent 12 17 24 SAI 0.17 1H

-0.31 111 PP 72 OD 12 17 24 DOS 0.97 1H

-0.13 55 Bobbin 18 OD 12 17 37 SAI 0.13 2H 0.15 112 PP 53 OD 12 17 38 SAI 0.23 1H

-0.34 123 PP 53 OD AONDB @1H >5v dent 12 17 38 DOS 0.54 2H 0.06 123 Bobbin 18 OD AONDB @1H >5v dent 12 17 44 SAI 0.26 1H

-0.1 104 PP 72 OD 12 17 44 DOS 0.5 1H

-0.11 114 Bobbin 18 OD 12 17 50 DOS 0.56 2H

-0.02 102 Bobbin 28 OD 12 17 54 SAI 1.84 1H 0.05 19 PP 24 ID 12 17 54 DIS 1.95 1H 0.13 42 Bobbin 28 ID 12 17 57 DIS 0.56 1H 0

34 Bobbin 28 ID 12 17 57 DOS 0.29 2H 0.06 104 Bobbin 28 OD 12 17

.57 DOS 0.33 3H 0

91 Bobbin 28 OD 12 17 59 SAI 1.66 1H 0.02 14 PP 23 ID 12 17 59 DIS 2.06 1H 0.15 29 Bobbin 28 ID 12 17 66 SAI 2.2 1H

-0.04 15 PP 23 ID 12 17 66 DIS 1.25 1H 0.11 28 Bobbin 28 ID 12 17 67 SAI 1

1H

-0.23 12 PP 23 ID 12 17 67 DIS 1.69 1H

-0.23 26 Bobbin 28 ID 12 17 67 SAI 0.14 3H

-0.08 155 PP 71 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 17 67 DOS 0.22 3H 0

91 Bobbin 28 OD 12 17 67 DOS 0.45 4H 0

149 Bobbin 28 OD 12 17 68 SAI 0.31 1H

-0.12 106 PP 71 OD 12 17 68 DOS 0.33 1H 0

112 Bobbin 28 OD 12 17 69 DOS 0.28 2H 0.02 120 Bobbin 28 OD 12 17 70 SAI 0.19 1H

-0.14 101 Pp 38 OD 12 17 75 DOS 0.71 2H

-0.02 101 Bobbin 28 OD 12

.17 76 DIS 1.73 4H

-0.23 25 Bobbin 28 ID 12 17 78 DIS 1.11 5H

-0.13 34 Bobbin 28 ID 12 17 79 SAI 0.21 1H 0.31 77 Pp 71 OD 12 17 79 DOS 0.45 1H 0.36 96 Bobbin 28 OD 12 17 83 DIS 0.99 5H

-0.26 56 Bobbin 19 ID 12 17 88 SAI 0.68 1H

-0.07 12 PP 71 ID 12 17 88 DIS 0.4 1H

-0.1 30 Bobbin 18 ID 12 17 88 SAI 0.7 2H 0.13 12 PP 22 ID 12 17 88 DIS 0.96 2H

-0.32 21 Bobbin 18 ID 12 17 88 SAI 0.24 5H 0.09 94 PP 80 OD 12 17 88 DOS 0.38 5H 0.1 89 Bobbin 18 OD 12 18 14 SAI 0.18 1H

-0.27 103 PP 72 OD 12 18 14 DIS 1.23 1H

-0.19 43 Bobbin 16 ID 12 18 22 SAI 0.12 1H 0.17 119 PP 57 OD 12 18 38 SCI 0.29 1H 0.31 105 PP 54 OD SCI-OD @1H+0.31 12 18 38 DOS 0.33 2H 0.35 130 Bobbin 19 OD SCI-OD @1H+0.31 12 18 40 DOS 0.88 1H 0.04 90 Bobbin 19 OD 12 18 40 DOS 0.21 2H 0.02 117 Bobbin 19 OD 12 18 40 DOS 0.99 5H

-0.17 99 Bobbin 19 OD 12 18 51 DOS 0.26 2H 0.06 87 Bobbin 28 OD 12 18 63 TWD 18 0.34 7H 36.84 0

Bobbin 18 OD 12 18 63 TWD 20 0.38 7H 49.33 0

Bobbin 18 OD 12 18 64 SAI 0.64 3H

-0.12 10 PP 23 ID 12 18 64 DIS 0.93 3H

-0.25 30 Bobbin 19 ID 12 18 67 SAI 0.81 1H

-0.19 16 Pp 71 ID 12 18 67 DIS 1.23 1H

-0.23 37 Bobbin 18 ID 12 18 84 DOS 0.24 1H

-0.02 131 Bobbin 18 OD 12 18 86 DOS 0.45 1H

-0.04 96 Bobbin 18 OD 12 18 89 DOS 0.58 2H

-0.13 81 Bobbin 19 OD 12 19 13 DOS 0.18 1H 0.23 51 Bobbin 16 OD 12 19 31 SAI 1.34 1H 0.07 77 PP 72 OD SAI-OD,>2v DOS @1H 12 19 31 DOS 2.23 1H 0.09 85 Bobbin 33 OD SAI-0D,>2v DOS @1H 12 19 31 SAI 0.55 4H

-0.05 12 PP 24 ID SAI-OD,>2v DOS @1H 12 19 31 DIS 1.02 4H

-0.08 38 Bobbin 18 ID SAI-OD,>2v DOS @1H 12 19 32 DOS 0.74 1H

-0.04 105 Bobbin 18 OD 12 19 33 DOS 0.32 2H 0.08 106 Bobbin 18 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 19 34 SAI 2.26 2H 0.04 14 PP 24 ID 12 19 34 DIS 1.44 2H 0.19 36 Bobbin 18 ID 12 19 36 DOS 0.35 1H 0.02 112 Bobbin 18 OD 12 19 36 SAI 0.26 2H 0.03 96 PP 72 OD 12 19 36 DOS 0.38 2H 0.11 147 Bobbin 18 OD 12 19 37 DOS 0.35 1H 0.02 119 Bobbin 18 OD 12 19 39 SAI 0.49 2H 0.05 103 PP 72 OD 12 19 39 DOS 0.58 2H 0.08 91 Bobbin 18 OD 12 19 39 TWD 17 0.31 7H 49.51 0

Bobbin 18 OD 12 19 39 TWD 17 0.31 7H 36.49 0

Bobbin 18 OD 12 19 40 SCI 0.19 1H 0

141 PP 53 OD SCI-OD @IH+0.00 12 19 41 SAI 0.23 1H

-0.02 105 PP 72 OD 12 19 41 SAI 0.76 1H

-0.12 87 PP 72 OD 12 19 41 DOS 1.41 1H

-0.04 91 Bobbin 18 OD 12 19 41 DOS 1.16 2H

-0.13 80 Bobbin 18 OD 12 19 48 SAI 0.23 1H 0.35 101 PP 72 OD 12 19 48 DOS 0.58 1H 0.34 103 Bobbin 20 OD 12 19 57 SAI 0.26 2H 0.28 72 PP 41 OD 12 19 57 SAI 0.37 2H

-0.07 95 PP 41 OD 12 19 65 DOS 0.5 2H 0

91 Bobbin 18 OD 12 19 67 TWD 18 0.34 7H 37.22 0

Bobbin 18 OD 12 19 67 TWD 22 0.44 7H 51.03 0

Bobbin 18 OD 12 19 67 TWD 24 0.52 7H 61.71 0

Bobbin 18 OD 12 19 67 TWD 29 0.75 7H 49.97 0

Bobbin 18 OD 12 19 67 TWD 29 0.79 7H 35.62 0

Bobbin 18 OD 12 19 70 DOS 0.34 1H

-0.02 149 Bobbin 19 OD 12 19 74 SAI 0.6 2H

-0.09 13 PP 22 ID 12 19 74 DIS 0.31 2H

-0.13 28 Bobbin 19 ID 12 19 79 SAI 0.19 1H

-0.14 87 PP 71 OD 12 19 79 SAI 0.25 1H 0.26 122 PP 71 OD 12 19 79 DOS 0.57 1H 0.22 119 Bobbin 18 OD 12 19 84 SAI 0.77 3H

-0.07 13 PP 71 ID 12 19 84 DIS 0.62 3H

-0.06 22 Bobbin 19 ID 12 19 89 TWD 11 0.68 2C

-0.1 151 Bobbin 18 OD 12 20 11 DIS 0.96 4H

-0.21 30 Bobbin 27 ID 12 20 25 DIS 0.28 2H

-0.02 32 Bobbin 19 ID 12 20 37 DTS 2.27 TEH 19.56 119 Bobbin 18 12 20 37 SAI 1.91 TSH

-1.74 17 PP 24 ID 12 20 40 DOS 0.29 1H 0.15 129 Bobbin 19 OD 12 20 43 DOS 0.99 1H 0.02 105 Bobbin 18 OD 12 20 43 SAI 0.19 3H

-0.08 122 PP 72 OD 12 20 43 DOS 0.5 3H

-0.06 98 Bobbin 18 OD 12 20 48 SAI 0.69 3H

-0.11 15 PP 24 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 20 48 DIS 0.18 3H 0.02 66 Bobbin 21 ID 12 20 51 SAI 0.29 1 H

-0.12 94 PP 72 OD 12 20 51 SAI 0.3 1H

-0.02 87 PP 72 OD 12 20 51 DOS 0.76 1H

-0.04 155 Bobbin 19 OD 12 20 54 SAI 0.34 1H

-0.07 84 PP 43 OD 12 20 54 DOS 0.36 1H 0.04 118 Bobbin 19 OD 12 20 55 DOS 0.84 2H

-0.24 72 Bobbin 18 OD 12 20 63 DOS 1.31 2H

-0.24 53 Bobbin 18 OD 12 20 72 SAI 0.15 1H

-0.07 100 PP 39 OD 12 20 72 DOS 0.21 1H

-0.09 89 Bobbin 19 OD 12 20 77 SAI 1.12 1H

-0.02 15 PP 22 ID 12 20 77 DIS 0.55 1H

-0.06 47 Bobbin 18 ID 12 20 78 SAI 0.22 TSH

-0.1 106 PP 37 OD SAI-OD @TSH-0.10 12 20 83 SAI

.0.21 1H

-0.12 122 PP 36 OD 12 20 83 SAI 0.25 1H

-0.11 120 PP 36 OD 12 20 83 DIS 1.77 1H

-0.22 48 Bobbin 18 ID 12 20 83 DOS 0.55 3H 0.04 102 Bobbin 18 OD 12 20 88 TWD 7

0.45 2C 0.41 15 Bobbin 18 OD 12 20 89 DOS 1.54 3H 0.04 101 Bobbin 19 OD 12 20 89 SAI 0.24 4H

-0.22 129 PP 35 OD 12 21 13 DIS 1.31 4H

-0.09 30 Bobbin 16 ID 12 21 17 DOS 0.26 2H 0.02 78 Bobbin 18 OD 12 21 19 DOS 0.68 2H

-0.08 75 Bobbin 18 OD 12 21 21 SAI 0.24 1H

-0.13 111 PP 57 OD 12 21 21 DOS 0.61 1H

-0.13 117 Bobbin 18 OD 12 21 23 DOS 0.6 6H

-0.19 122 Bobbin 18 OD 12 21 28 DOS 0.34 1H

-0.06 114 Bobbin 18 OD 12 21 28 DOS 0.12 2H 0

107 Bobbin 18 OD 12 21 30 DOS 0.93 2H 0

78 Bobbin 18 OD 12 21 32 SAI 0.28 1H 0.11 112 PP 55 OD 12 21 32 DOS 0.6 1H 0.34 91 Bobbin 18 OD 12 21 38 SAI 2.24 1H

-0.03 18 PP 24 ID 12 21 38 DIS 1.84 1H 0.04 34 Bobbin 18 ID 12 21 40 DOS 0.41 2H

-0.08 116 Bobbin 18 OD 12 21 44 DOS 0.53 1H

-0.02 103 Bobbin 18 OD 12 21 45 DOS 0.67 1H 0.11 108 Bobbin 20 OD 12 21 46 SAI 0.4 1H 0.11 115 Pp 72 OD 12 21 46 DOS 0.74 1H 0.27 111 Bobbin 20 OD 12 21 49 FSI 0.83 1H 41.36 72 Bobbin 21 12 21 52 DOS 0.66 1H 0.11 98 Bobbin 19 OD 12 21 55 DOS 0.89 3H 0.06 87 Bobbin 16 OD 12 21 55 DOS 0.23 4H

-0.1 112 Bobbin 16 OD 12 21 55 TWD 20 0.41 7H 57.11 0

Bobbin 16 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 21 55 TWD 24 0.56 7H 40.47 0

Bobbin 16 OD 12 21 56 DOS 1.04 1H

-0.13 106 Bobbin 17 OD 12 21 57 SAI 1.83 1H

-0.08 18 PP 23 ID 12 21 57 DIS 1.43 1H

-0.12 28 Bobbin 16 ID 12 21 58 DOS 0.54 2H

-0.13 102 Bobbin 17 OD 12 21 59 DOS 0.42 1H

-0.08 84 Bobbin 16 OD 12 21 60 DOS 0.44 1H

-0.02 59 Bobbin 17 OD 12 21 60 SAI 0.74 2H

-0.21 7

PP 23 ID 12 21 60 DIS 0.33 2H

-0.26 54 Bobbin 17 ID 12 21 60 DOS 0.72 4H

-0.26 107 Bobbin 17 OD 12 21 62 DOS 1.04 1H

-0.04 89 Bobbin 17 OD 12 21 65 SAI 1.92 2H 0

15 PP 23 ID 12 21 65 DIS 1.55 2H

-0.02 25 Bobbin 16 ID 12 21 65 TWD 15 0.27 7H 40.6 0

Bobbin 16 OD 12 21 65 TWD 15 0.29 7H 25.99 0

Bobbin 16 OD 12 21 65 TWD 16 0.3 7H 57.2 0

Bobbin 16 OD 12 21 71 DOS 0.79 3H 0.08 70 Bobbin 16 OD 12 21 72 SAI 0.25 4H 0.07 113 PP 71 OD 12 21 72 DIS 1.65 4H 0

13 Bobbin 17 ID 12 21 74 DOS 0.33 2H

-0.08 95 Bobbin 16 OD 12 21 82 DOS 1.37 1H

-0.16 83 Bobbin 16 OD 12 21 84 SCI 0.21 4H

-0.17 129 PP 34 OD SCI-OD @4H-0.17 12 21 87 SAI 0.25 1H 0.28 130 PP 35 OD 12 21 87 DIS 1.01 1H 0.3 27 Bobbin 17 ID 12 22 22 DOS 1.04 1H 0.12 102 Bobbin 19 OD 12 22 35 DOS 0.42 1H 0.31 102 Bobbin 19 OD 12 22 35 TWD 15 0.32 7H 25.27 0

Bobbin 19 OD 12 22 37 DOS 0.45 1H 0.08 116 Bobbin 19 OD 12 22 40 DOS 0.44 2H 0.04 82 Bobbin 19 OD 12 22 41 DOS 0.68 1H 0.06 114 Bobbin 19 OD 12 22 42 SAI 1.53 1H 0.09 17 PP 24 ID 12 22 42 DIS 1.46 1H 0.19 28 Bobbin 19 ID 12 22 46 DOS 0.7 1H 0.06 96 Bobbin 21 OD 12 22 55 SAI 1.28 3H 0.03 17 PP 24 ID 12 22 55 DIS 1.35 3H 0.06 27 Bobbin 16 ID 12 22 56 DOS 0.5 1H

-0.23 95 Bobbin 17 OD 12 22 57 SAI 0.12 1H

-0.2 96 PP 70 OD 12 22 57 SAI 0.21 1H 0.08 98 PP 70 OD 12 22 57 DOS 0.6 1H

-0.16 164 Bobbin 16 OD 12 22 57 DOS 0.36 2H

-0.14 99 Bobbin 16 OD 12 22 62 SAI 0.34 1H 0.07 82 PP 71 OD 12 22 62 DIS 0.84 1H

-0.02 31 Bobbin 17 ID 12 22 62 SAI 0.47 2H

-0.07 76 PP 40 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 22 62 DOS 0.75 2H

-0.26 42 Bobbin 17 OD 12 22 79 DOS 0.47 1H

-0.12 76 Bobbin 16 OD 12 22 79 SAI 0.14 2H 0.01 87 PP 37 OD 12 22 79 DIS 0.6 2H

-0.12 31 Bobbin 16 ID 12 22 80 SAI 0.21 1H

-0.18 88 PP 71 OD 12 22 80 DOS 0.8 1H

-0.26 131 Bobbin 17 OD 12 22 83 SAI 0.18 1H

-0.09 107 PP 36 OD 12 22 83 DIS 1.05 1H

-0.24 32 Bobbin 16 ID 12 22 84 DOS 0.72 1H

-0.13 104 Bobbin 17 OD 12 23 7

TWD 21 1.4 2C

-0.25 124 Bobbin 27 OD 12 23 17 DOS 0.92 1H 0.19 116 Bobbin 18 OD 12 23 18 DOS 0.5 1H 0.02 87 Bobbin 18 OD 12 23 22 DOS 0.44 1H 0.02 108 Bobbin 18 OD 12 23 25 SAI 1.11 3H

-0.22 15 PP 25 ID 12 23 25 DIS 1.15 3H

-0.17 37 Bobbin 18 ID 12 23 34 DOS 0.78 2H

-0.15 75 Bobbin 18 OD 12 23 40 DOS 0.68 1H 0

103 Bobbin 18 OD 12 23 52 SAI 0.14 1H 0.03 73 PP 42 OD 12 23 54 SAI 0.48 1H 0.1 16 PP 24 ID 12 23 54 DIS 0.44 1H 0.12 41 Bobbin 16 ID 12 23 58 DOS 0.63 1H

-0.06 76 Bobbin 16 OD 12 23 60 DOS 0.37 2H

-0.12 134 Bobbin 16 OD 12 23 71 SAI 0.15 2H

-0.1 105 PP 38 OD 12 23 71 SAI 0.17 2H

-0.12 99 PP 38 0D 12 23 71 DIS 1.61 2H

-0.19 32 Bobbin 17 ID 12 23 79 SAI 0.37 1H

-0.15 14 PP 22 ID 12 24 16 DOS 0.31 1H 0.12 103 Bobbin 19 OD 12 24 18 DOS 0.57 3H 0.02 118 Bobbin 19 OD 12 24 23 DOS 0.32 1H 0.31 84 Bobbin 19 OD 12 24 25 DOS 0.36 3H 0

77 Bobbin 19 OD 12 24 28 DOS 1.06 1H 0.06 89 Bobbin 19 OD 12 24 31 SAI 0.39 1H 0.06 90 PP 72 OD 12 24 31 DOS 0.43 1H 0.12 111 Bobbin 19 OD 12 24 32 SAI 0.36 1H 0.05 101 PP 55 OD 12 24 32 DOS 0.39 1H 0.08 76 Bobbin 19 OD 12 24 38 DIS 0.4 1H 0.04 27 Bobbin 18 ID 12 24 41 DOS 0.39 1H 0.08 111 Bobbin 19 OD 12 24 41 DOS 0.91 2H

-0.02 66 Bobbin 19 OD 12 24 44 DOS 0.65 1H 0.15 100 Bobbin 19 OD 12 24 49 SAI 0.27 2H

-0.19 110 PP 71 0D 12 24 49 DOS 0.29 2H 0.04 66 Bobbin 20 OD 12 24 51 DOS 0.36 1H

-0.04 110 Bobbin 17 OD 12 24 55 SAI 0.57 1H 0.03 100 PP 70 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 24 55 DOS 0.78 1H 0.02 117 Bobbin 17 OD 12 24 65 SAI 0.31 2H 0.03 112 PP 71 OD 12 24 65 DOS 0.39 2H

-0.09 107 Bobbin 17 OD 12 24 77 SAI 0.75 1H

-0.15 12 PP 22 ID 12 24 77 DIS 2.68 1H

-0.29 12 Bobbin 16 ID 12 25 12 DOS 0.46 1 H

-0.02 68 Bobbin 16 OD 12 25 17 SAI 1.1 2H

-0.3 14 PP 25 ID 12 25 17 DIS 0.65 2H 0.17 56 Bobbin 18 ID 12 25 17 DOS 0.37 3H

-0.11 60 Bobbin 18 OD 12 25 21 DOS 0.45 1H 0.08 81 Bobbin 18 OD 12 25 25 DOS 0.74 1H

-0.08 100 Bobbin 18 OD 12 25 25 DOS 0.77 3H 0.23 95 Bobbin 18 OD 12 25 25 DOS 0.66 5H 0.13 125 Bobbin 18 OD 12 25 32 SAI 0.78 1H

-0.02 94 PP 72 OD 12 25 32 DOS 1.08 1H 0.04 102 Bobbin 18 OD 12 25 33 DOS 0.29 1H 0.11 93 Bobbin 18 OD 12 25 37 SAI 0.2 1H 0.06 126 PP 72 OD 12 25 37 DOS 0.22 1H

-0.19 128 Bobbin 18 OD 12 25 41 DIS 0.64 4H

-0.19 20 Bobbin 18 ID 12 25 50 SAI 2.53 2H

-0.07 20 PP 24 ID 12 25 50 DIS 2.01 2H

-0.12 36 Bobbin 16 ID 12 25 55 SAI 0.37 2H 0.24 14 PP 23 ID 12 25 55 DIS 0.7 2H 0.19 22 Bobbin 17 ID 12 25 57 DOS 1.41 1H 0.02 82 Bobbin 17 OD 12 25 61 DOS 1.03 1H 0.06 77 Bobbin 17 OD 12 25 63 DOS 0.71 2H

-0.04 45 Bobbin 17 OD 12 25 64 DOS 0.4 2H

-0.16 90 Bobbin 16 OD 12 25 65 SAI 0.2 TSH

-0.08 90 PP 40 OD SAI-OD @TSH-0.08 12 25 67 DIS 0.93 2H

-0.3 23 Bobbin 17 ID 12 25 68 DOS 0.46 2H

-0.14 113 Bobbin 16 OD 12 25 69 DOS 0.91 3H 0.02 43 Bobbin 17 OD 12 25 74 SAI 1.71 1H

-0.26 20 PP 22 ID SAI-ID @1H, >40%TW outside TSP 12 25 74 DIS 3.17 1H

-0.35 30 Bobbin 16 ID SAI-ID @1H, >40%TW outside TSP 12 25 77 DOS 1.14 1H

-0.02 67 Bobbin 17 OD 12 25 78 SAI 0.3 1H

-0.04 108 PP 70 OD 12 25 78 DOS 0.28 1H

-0.06 143 Bobbin 16 OD 12 25 78 DOS 0.46 2H

-0.14 100 Bobbin 16 OD 12 25 78 DOS 0.58 3H

-0.14 82 Bobbin 16 OD 12 25 79 SAI 0.64 2H

-0.01 15 pp 22 ID 12 25 81 DOS 0.77 2H

-0.11 134 Bobbin 17 OD 12 25 83 DOS 0.14 2H

-0.04 125 Bobbin 17 OD 12 25 85 SAI 0.36 2H 0.03 74 PP 71 OD 12 25 85 DIS 1.63 2H

-0.25 22 Bobbin 17 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 25 85 SAI 0.16 3H

-0.04 130 PP 71 OD 12 25 85 DOS 0.88 3H

-0.19 44 Bobbin 17 OD 12 25 85 SAI 0.67 4H

-0.08 11 PP 22 ID 12 25 85 DIS 1.75 4H

-0.25 20 Bobbin 17 ID 12 25 87 DOS 0.4 1H 0

148 Bobbin 17 OD 12 25 87 DOS 0.89 2H

-0.23 112 Bobbin 17 OD 12 25 87 SAI 1.27 4H

-0.07 17 PP 22 ID 12 25 87 DIS 0.93 4H

-0.08 39 Bobbin 17 ID 12 26 9

DOS 0.34 1H 0.17 103 Bobbin 33 OD 12 26 10 TWD 31 2.23 2C

-0.12 124 Bobbin 33 OD 12 26 15 DIS 0.97 4H

-0.15 22 Bobbin 16 ID 12 26 16 DOS 0.63 4H 0.04 96 Bobbin 16 OD 12 26 17 DOS 0.22 1H 0.28 86 Bobbin 16 OD 12 26 17 DOS 0.79 2H

-0.04 142 Bobbin 16 OD 12 26 17 SAI 0.24 3H

-0.15 92 PP 72 OD 12 26 17 DOS 0.51 3H

-0.11 84 Bobbin 16 OD 12 26 18 DOS 0.35 5H 0.04 82 Bobbin 16 OD 12 26 22 SAI 1.71 4H

-0.02 13 PP 25 ID 12 26 22 DIS 1.72 4H 0.09 32 Bobbin 16 ID 12 26 24 DOS 0.25 1H 0.02 142 Bobbin 16 OD 12 26 26 DOS 0.45 1H 0.04 102 Bobbin 16 OD 12 26 27 SAI 0.4 1H

-0.03 104 PP 72 OD 12 26 27 SAI 0.49 1H

-0.06 104 PP 72 OD 12 26 27 SAI 1.1 1H 0.1 72 PP 72 OD 12 26 27 DOS 1.89 1H 0.13 81 Bobbin 16 OD 12 26 30 DIS 0.44 1H

-0.06 12 Bobbin 16 ID 12 26 32 SAI 0.32 1H 0.07 96 PP 72 OD 12 26 32 SAI 0.33 1H 0.07 103 PP 72 OD 12 26 32 DOS 0.85 1H 0.11 87 Bobbin 16 OD 12 26 33 DOS 0.19 1H

-0.02 84 Bobbin 16 OD 12 26 33 DOS 0.37 2H 0.06 78 Bobbin 16 OD 12 26 35 DOS 0.33 3H 0

91 Bobbin 14 OD 12 26 39 SAI 0.85 2H

-0.02 14 PP 24 ID 12 26 39 DIS 0.47 2H 0.06 22 Bobbin 14 ID 12 26 50 SAI 0.14 1H

-0.21 91 PP 70 OD 12 26 50 DOS 0.41 1H

-0.21 80 Bobbin 9

OD 12 26 51 DOS 0.25 3H 0.02 63 Bobbin 10 OD 12 26 52 SAI 0.4 2H 0

112 PP 70 OD 12 26 52 DOS 1.95 2H 0.03 112 Bobbin 33 OD 12 26 64 SAI 0.14 2H 0.08 82 PP 78 OD 12 26 64 DOS 0.68 2H 0.21 63 Bobbin 13 OD 12 26 68 TWD 22 0.41 7H 28 0

Bobbin 15 OD 12 26 68 TWD 24 0.46 7H 46.42 0

Bobbin 15 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 26 68 TWD 25 0.5 7H 68.02 0

Bobbin 15 OD 12 26 68 TWD 30 0.78 7H 86.5 0

Bobbin 15 OD 12 26 73 SAI 1.87 1H

-0.03 16 PP 22 ID 12 26 73 DIS 1.5 1H

-0.06 31 Bobbin 14 ID 12 26 79 SAI 1.2 1H 0.06 16 PP 22 ID 12 26 79 DIS 1.34 1H 0.04 31 Bobbin 9

ID 12 26 79 DOS 0.47 3H 0.06 137 Bobbin 9

OD 12 26 83 DOS 0.8 1H 0.1 110 Bobbin 16 OD 12 27 10 TWD 5

0.31 2C

-0.28 136 Bobbin 33 OD 12 27 11 TWD 12 0.76 1C 0.19 135 Bobbin 33 OD 12 27 16 DOS 0.69 3H 0.1 112 Bobbin 17 OD 12 27 19 SAI 0.26 1H

-0.13 115 PP 44 OD 12 27 20 DIS 0.21 1H 0.04 43 Bobbin 17 ID 12 27 27 DOS 0.38 1H 0.12 132 Bobbin 17 OD 12 27 27 DOS 0.57 3H 0

70 Bobbin 17 OD 12 27 29 DOS 0.48 1H 0.12 117 Bobbin 17 OD 12 27 32 DOS 0.22 1H 0.04 104 Bobbin 16 OD 12 27 32 DIS 0.81 3H

-0.23 19 Bobbin 16 ID 12 27 33 DOS 0.37 2H 0.02 134 Bobbin 17 OD 12 27 35 DIS 0.92 4H

-0.17 34 Bobbin 14 ID 12 27 44 SAI 0.14 1H 0.25 117 PP 52 OD 12 27 44 SAI 0.19 2H

-0.26 108 PP 70 OD 12 27 55 SAI 0.59 1H 0.31 12 PP 23 ID 12 27 55 DIS 2.79 1H 0.08 12 Bobbin 12 ID 12 27 56 SAI 0.72 1H

-0.16 8

PP 23 ID 12 27 56 DIS 1.73 1H

-0.4 16 Bobbin 12 ID 12 27 57 SAI 0.19 1H

-0.05 121 PP 70 OD 12 27 57 SAI 0.41 1H

-0.05 104 PP 70 OD 12 27 57 DOS 0.86 1H

-0.08 60 Bobbin 12 OD 12 27 58 DIS 1.1 2H 0.23 25 Bobbin 12 ID 12 27 63 SAI 1.18 2H

-0.2 19 PP 23 ID 12 27 63 SAI 1.2 2H 0.21 16 PP 23 ID 12 27 63 DIS 1.77 2H

-0.21 39 Bobbin 13 ID 12 27 64 SAI 0.63 3H

-0.06 10 PP 23 ID 12 27 64 DIS 1.78 3H

-0.27 14 Bobbin 13 ID 12 27 65 SAI 1.1 2H 0.12 15 PP 23 ID 12 27 65 DIS 0.52 2H

-0.17 13 Bobbin 14 ID 12 27 66 SAI 0.14 2H 0.15 72 PP 30 OD 12 27 66 SAI 0.17 2H

-0.14 102 PP 30 OD 12 27 67 SAI 0.77 1H 0.63 10 PP 23 ID 12 27 67 SAI 1.96 1H

-0.26 18 PP 23 ID 12 27 67 DIS 3.11 1H

-0.25 30 Bobbin 15 ID 12 27 67 SAI 0.72 4H

-0.14 12 PP 23 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 27 67 DIS 0.71 4H

-0.34 32 Bobbin 15 ID 12 27 68 DOS 0.56 1H 0.21 41 Bobbin 15 OD 12 27 69 SAI 0.84 1H 0.1 11 PP 22 ID 12 27 69 SAI 2.24 1H

-0.17 20 PP 22 ID 12 27 69 DIS 1.54 1H

-0.23 50 Bobbin 15 ID 12 27 72 SAI 0.5 2H 0.2 7

PP 32 ID 12 27 72 SAI 0.75 2H

-0.28 11 PP 32 ID 12 27 78 DOS 0.66 1H

-0.12 76 Bobbin 9

OD 12 27 83 SAI 0.22 2H

-0.17 121 PP 35 OD 12 27 83 DOS 0.84 2H

-0.28 112 Bobbin 16 OD 12 27 83 SAI 0.11 3H

-0.19 118 PP 71 OD 12 27 83 SAI 0.23 3H 0.09 124 PP 71 OD 12 27 83 DOS 0.67 3H 0.04 31 Bobbin 16 OD 12 27 83 DIS 1.25 4H

-0.1 29 Bobbin 16 ID 12 28 10 DOS 0.81 1H 0.09 87 Bobbin 33 OD 12 28 11 TWD 13 0.83 2C

-0.19 148 Bobbin 33 OD 12 28 19 DOS 0.15 1H 0

91 Bobbin 16 OD 12 28 23 DOS 0.5 1H 0.02 113 Bobbin 16 OD 12 28 24 DOS 0.74 1H 0.15 105 Bobbin 17 OD 12 28 27 SAI 0.46 2H

-0.06 111 PP 72 OD 12 28 27 DOS 0.72 2H 0.02 104 Bobbin 16 OD 12 28 29 DOS 1.18 1H 0.13 108 Bobbin 16 OD 12 28 29 DOS 0.71 2H

-0.04 100 Bobbin 16 OD 12 28 32 DOS 0.32 3H 0

93 Bobbin 17 OD 12 28 35 SAI 0.29 2H

-0.06 95 PP 72 OD 12 28 35 DOS 0.72 2H

-0.06 96 Bobbin 15 OD 12 28 36 SAI 0.15 2H

-0.02 85 PP 48 OD 12 28 36 DIS 1.24 2H

-0.23 37 Bobbin 14 ID 12 28 40 DIS 0.71 3H 0.04 45 Bobbin 14 ID 12 28 40 DOS 0.73 4H

-0.15 93 Bobbin 14 OD 12 28 40 SAI 0.28 5H 0.04 140 PP 69 OD 12 28 40 DOS 0.57 5H

-0.11 50 Bobbin 14 OD 12 28 41 DOS 0.75 1H 0.12 124 Bobbin 15 OD 12 28 47 SAI 0.83 3H 0.18 13 PP 24 ID 12 28 47 DIS 0.56 3H

-0.11 28 Bobbin 14 ID 12 28 49 DOS 0.8 2H

-0.15 54 Bobbin 14 OD 12 28 51 DOS 0.43 2H

-0.02 132 Bobbin 10 OD 12 28 53 DOS 1.12 1H

-0.06 124 Bobbin 9

OD 12 28 55 DOS 1.34 2H

-0.04 107 Bobbin 12 OD 12 28 60 DOS 0.19 2H 0

60 Bobbin 13 OD 12 28 62 DOS 0.56 1H

-0.09 60 Bobbin 13 OD 12 28 63 DOS 0.66 1H

-0.13 84 Bobbin 13 OD 12 28 66 SAI 0.44 2H 0.02 10 PP 23 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 28 66 DIS 0.35 2H

-0.29 48 Bobbin 15 ID 12 28 71 SAI 0.25 2H

-0.03 131 PP 32 OD 12 28 79 DIS 0.67 1H

-0.37 12 Bobbin 9

ID 12 28 82 DOS 0.78 1H

-0.18 149 Bobbin 16 OD 12 28 83 DIS 1.25 1H

-0.28 19 Bobbin 17 ID 12 28 84 SAI 0.23 1H

-0.1 109 PP 71 OD 12 28 84 SAI 0.42 1H

-0.1 105 PP 71 OD 12 28 84 DOS 0.82 1H

-0.04 124 Bobbin 16 OD 12 28 84 DOS 0.55 3H

-0.02 93 Bobbin 16 OD 12 29 11 DOS 0.67 1H

-0.05 79 Bobbin 33 OD 12 29 12 TWD 23 1.55 2C

-0.16 126 Bobbin 33 OD 12 29 17 DOS 0.83 1H 0.17 92 Bobbin 17 OD 12 29 19 DOS 0.56 1H

-0.04 120 Bobbin 17 OD 12 29 24 SAI 1.36 3H 0.25 14 PP 24 ID SAI-ID @3H, >40%TW outside TSP 12 29 24 DIS 1.12 3H 0.36 41 Bobbin 16 ID SAI-ID @3H, >40%TW outside TSP 12 29 25 DOS 0.59 1H 0.08 89 Bobbin 17 OD 12 29 25 DOS 0.54 2H 0.14 158 Bobbin 17 OD 12 29 26 SAI 0.33 1H

-0.01 103 PP 72 OD 12 29 26 DOS 0.26 1H 0.02 108 Bobbin 16 OD 12 29 27 DOS 0.22 2H

-0.15 57 Bobbin 17 OD 12 29 32 DOS 0.55 1H 0.28 124 Bobbin 16 OD 12 29 33 DOS 0.8 1H 0.06 97 Bobbin 17 OD 12 29 38 DOS 0.6 1H 0.1 122 Bobbin 15 OD 12 29 40 DOS 0.84 1H 0.14 91 Bobbin 15 OD 12 29 40 SAI 0.31 5H

-0.04 109 PP 78 OD 12 29 40 DOS 1.11 5H 0

116 Bobbin 15 OD 12 29 46 DOS 0.42 1H 0.08 122 Bobbin 15 OD 12 29 47 DOS 0.87 1H 0.15 102 Bobbin 15 OD 12 29 48 SAI 0.16 1H

-0.08 113 PP 70 OD 12 29 48 DIS 0.49 1H 0.06 33 Bobbin 14 ID 12 29 49 SAI 0.14 3H

-0.33 91 PP 52 OD 12 29 49 DIS 0.95 3H

-0.17 39 Bobbin 15 ID 12 29 50 DIS 0.67 3H

-0.25 26 Bobbin 9

ID 12 29 51 SAI 0.69 2H

-0.04 15 PP 24 ID 12 29 51 DIS 0.35 2H

-0.1 29 Bobbin 10 ID 12 29 52 DOS 1.22 1H 0

89 Bobbin 10 OD 12 29 54 DOS 0.39 1H

-0.04 102 Bobbin 10 OD 12 29 59 DOS 0.38 1H

-0.09 85 Bobbin 13 OD 12 29 61 SAI 0.13 3H

-0.08 117 PP 70 OD 12 29 61 SAI 0.17 3H

-0.03 115 PP 70 OD 12 29 61 DOS 0.63 3H 0.17 51 Bobbin 13 OD 12 29 62 DOS 0.24 2H

-0.06 60 Bobbin 13 OD 12 29 66 SAI 1.62 1H 0.08 17 PP 23 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 29 66 DIS 1.14 1H 0.02 26 Bobbin 15 ID 12 29 69 SAI 0.15 1H 0

127 PP 33 OD 12 29 69 DIS 1.39 1H

-0.3 22 Bobbin 15 ID 12 29 72 DOS 1.08 1H

-0.11 81 Bobbin 15 OD 12 29 72 DOS 0.42 3H

-0.02 52 Bobbin 15 OD 12 29 77 SAI 0.25 2H

-0.1 88 PP 71 OD 12 29 77 DOS 0.45 2H

-0.04 61 Bobbin 14 OD 12 29 79 DOS 0.31 1H

-0.02 96 Bobbin 10 OD 12 29 83 DIS 0.28 1H

-0.04 54 Bobbin 16 ID 12 30 12 DOS 0.49 1H

-0.03 77 Bobbin 33 OD 12 30 13 TWD 9

0.53 lC 0.19 61 Bobbin 33 OD 12 30 30 DOS 1.48 1H 0

95 Bobbin 17 OD 12 30 35 DOS 1.16 1H 0.04 102 Bobbin 15 OD 12 30 42 DOS 1.52 1H 0.03 92 Bobbin 33 OD SCI-OD @TSH+0.02 12 30 42 SCI 0.13 TSH 0.02 92 PP 48 OD SCI-OD @TSH+0.02 12 30 45 FSI 0.3 5H 45.85 53 Bobbin 15 12 30 47 DOS 0.5 1H

-0.06 64 Bobbin 14 OD 12 30 53 DOS 0.76 2H

-0.16 104 Bobbin 9

OD 12 30 56 SAI 3.14 1H

-0.11 22 PP 23 ID 12 30 56 DIS 2.07 1H 0.02 24 Bobbin 12 ID 12 30 57 DOS 1.14 2H 0

119 Bobbin 12 OD 12 30 59 DOS 0.6 1H

. 0 144 Bobbin 13 OD 12 30 59 SAI 0.49 4H

-0.07 87 PP 70 OD 12 30 59 DOS 0.72 4H

-0.11 74 Bobbin 13 OD 12 30 61 DOS 0.31 1H

-0.09 43 Bobbin 13 OD 12 30 62 SAI 0.32 1H 0.06 8

PP 23 ID 12 30 62 SAI 0.59 1H

-0.1 9

PP 23 I D 12 30 62 DIS 0.53 1H 0.17 67 Bobbin 13 ID 12 30 67 SAI 2.33 2H

-0.25 23 PP 23 ID 12 30 67 DIS 8.2 2H

-0.27 19 Bobbin 15 ID 12 30 69 DOS 0.68 1H

-0.04 120 Bobbin 15 OD 12 30 72 SAI 0.21 2H

-0.03 114 PP 33 0D 12 30 72 DOS 0.29 2H

-0.04 76 Bobbin 14 0D 12 31 15 DIS 0.48 7H 0.04 27 Bobbin 17 ID 12 31 16 DOS 0.99 2H 0.11 111 Bobbin 16 OD 12 31 22 SAI 0.18 3H

-0.06 108 PP 72 OD SAI-OD @3H Wedge 12 31 22 DOS 0.51 3H

-0.02 87 Bobbin 17 OD SAI-OD @3H Wedge 12 31 26 SAI 0.24 3H

-0.15 111 PP 72 OD 12 31 26 DOS 0.33 3H

-0.13 65 Bobbin 16 OD 12 31 31 DOS 0.79 1H 0.04 106 Bobbin 17 OD 12 31 34 DOS 0.86 2H

-0.17 125 Bobbin 16 OD 12 31 35 DOS 0.4 2H

-0.04 88 Bobbin 14 OD 12 31 37 SAI 0.66 3H

-0.08 10 PP 24 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 31 37 DIS 0.34 3H 0.11 17 Bobbin 14 ID 12 31 41 SAI 0.58 3H 0

93 PP 69 OD 12 31 41 DOS 0.85 3H 0.06 126 Bobbin 14 OD 12 31 44 SAI 0.09 4H 0.1 112 PP 52 OD 12 31 44 DIS 0.8 4H

-0.15 30 Bobbin 15 ID 12 31 47 SAI 3.13 2H

-0.01 22 PP 24 ID SAI-ID @2H, Preventive 12 31 47 DIS 3.81 2H

-0.06 29 Bobbin 15 ID SAI-ID @2H, Preventive 12 31 52 DOS 0.34 2H

-0.08 97 Bobbin 10 OD 12 31 53 SAI 2.61 2H

-0.19 21 PP 24 ID 12 31 53 DIS 2.46 2H

-0.25 36 Bobbin 10 ID 12 31 62 SAI 0.35 1H

-0.24 107 PP 28 OD 12 31 62 DOS 0.95 1H

-0.21 76 Bobbin 13 OD 12 31 63 SAI 0.15 1H

-0.16 117 PP 29 OD 12 31 63 SAI 0.37 1H

-0.17 99 PP 29 OD 12 31 63 DOS 0.35 2H

-0.11 91 Bobbin 13 OD 12 31 63 DOS 0.56 4H

-0.02 47 Bobbin 13 OD 12 31 64 SAI 0.28 1H

-0.09 122 PP 70 OD 12 31 64 SAI 0.49 1H 0.06 111 PP 70 OD 12 31 64 DOS 0.66 1H 0.04 131 Bobbin 13 OD 12 31 66 SAI 0.14 1H

-0.07 104 PP 70 OD SAI-ID/AONDB @1H 12 31 66 SAI 0.35 1H

-0.07 11 PP 70 ID SAI-ID/AONDB @1H 12 31 66 DIS 0.34 1H

-0.08 30 Bobbin 15 ID SAI-ID/AONDB @1H 12 31 66 SAI 1.03 4H 0.11 13 PP 23 ID SAI-ID/AONDB @IH 12 31 66 DIS 2.3 4H

-0.3 14 Bobbin 15 ID SAI-ID/AONDB @1H 12 31 68 SAI 0.84 1H 0.09 14 PP 23 ID 12 31 68 DIS 0.46 1H

-0.02 6

Bobbin 15 ID 12 31 80 SAI 0.17 4H

-0.05 97 PP 33 OD 12 32 24 DOS 0.34 2H 0.06 96 Bobbin 17 OD 12 32 29 DOS 1.31 1H 0.02 105 Bobbin 16 OD 12 32 30 SAI 0.89 2H

-0.22 20 PP 24 ID 12 32 30 DIS 1.74 2H

-0.17 26 Bobbin 17 ID 12 32 32 DOS 0.25 4H 0.02 128 Bobbin 16 OD 12 32 37 SAI 0.55 3H 0.07 8

PP 24 ID 12 32 37 DIS 0.24 3H 0.15 28 Bobbin 15 ID 12 32 42 DOS 0.91 1H

-0.04 111 Bobbin 14 OD 12 32 42 DOS 0.56 3H

-0.13 118 Bobbin 14 OD 12 32 43 DOS 1.54 4H 0

97 Bobbin 33 OD 12 32 44 DOS 1.01 2H 0.17 119 Bobbin 14 OD 12 32 44 DOS 0.56 3H 0.15 112 Bobbin 14 OD 12 32 44 SAI 0.98 4H

-0.17 16 PP 24 ID 12 32 44 DIS 1.95 4H

-0.13 25 Bobbin 14 ID 12 32 44 DOS 0.42 5H 0.11 115 Bobbin 14 OD 12 32 45 SAI 0.17 3H

-0.14 106 PP 70 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 32 45 SAI 0.26 3H 0

124 pp 70 OD 12 32 45 DOS 0.78 3H 0

91 Bobbin 15 OD 12 32 46 TWD 19 0.42 7H 32.32 0

Bobbin 14 OD 12 32 46 TWD 22 0.5 7H 56.9 0

Bobbin 14 OD 12 32 47 SAI 1.47 3H

-0.15 18 pp 24 ID 12 32 47 DIS 3.1 3H

-0.09 21 Bobbin 14 ID 12 32 47 DOS 0.49 4H 0.04 110 Bobbin 14 OD 12 32 50 DOS 0.54 1H 0.02 125 Bobbin 10 OD 12 32 50 TWD 24 0.51 7H 58.19 0

Bobbin 10 OD 12 32 50 TWD 28 0.67 7H 33.23 0

Bobbin 10 OD 12 32 50 TWD 31 0.91 7H 84.1 0

Bobbin 10 OD 12 32 51 DOS 0.27 5H

-0.09 57 Bobbin 10 OD 12 32 53 DOS 0.82 1H 0.16 101 Bobbin 9

OD 12 32 53 DOS 0.58 3H

-0.16 67 Bobbin 9

OD 12 32 54 SAI 0.28 1H

-0.05 108 PP 70 OD 12 32 54 SAI 0.37 1H

-0.09 118 Pp 70 OD 12 32 54 DOS 0.85 1H

-0.18 66 Bobbin 9

OD 12 32 59 DOS 1.12 1H

-0.17 95 Bobbin 12 OD 12 32 59 SAI 0.19 3H

-0.03 125 PP 70 OD 12 32 59 DIS 0.59 3H

-0.08 26 Bobbin 12 ID 12 32 59 SAI 0.33 4H

-0.14 7

PP 29 ID 12 32 62 SAI 0.58 1H

-0.02 10 Pp 23 ID 12 32 62 DIS 1.52 1H

-0.28 28 Bobbin 13 ID 12 33 16 DOS 0.64 1C 0.31 66 Bobbin 17 OD 12 33 31 DOS 1.01 3H 0.23 92 Bobbin 17 OD 12 33 40 SAI 0.26 1H

-0.02 118 PP 50 OD 12 33 44 DOS 0.48 2H 0.08 101 Bobbin 15 OD 12 33 45 DIS 0.6 4H 0.09 71 Bobbin 14 ID 12 33 47 TWD 12 0.25 7H 86.92 0

Bobbin 15 OD 12 33 49 DIS 0.35 2H

-0.02 29 Bobbin 15 ID 12 33 49 DIS 0.5 3H 0.02 26 Bobbin 15 ID 12 33 51 DOS 0.68 2H 0

128 Bobbin 10 OD 12 33 51 DIS 0.51 7H

-0.27 38 Bobbin 10 ID 12 33 54 TWD 16 0.28 7H 59.78 0

Bobbin 10 OD 12 33 56 DOS 0.46 2H

-0.04 57 Bobbin 12 OD 12 33 57 SAI 0.98 2H 0.17 16 PP 23 ID 12 33 57 DIS 0.54 2H 0.13 43 Bobbin 12 ID 12 33 68 SAI 0.09 2H 0.02 121 PP 23 OD Multi SAI-lD/AONDB @2H 12 33 68 SAI 0.17 2H

-0.01 81 PP 23 OD Multi SAI-lD/AONDB @2H 12 33 68 SAI 0.54 2H 0.04 17 PP 23 ID Multi SAI-ID/AONDB @2H 12 33 68 DIS 0.48 2H 0.02 46 Bobbin 15 ID Multi SAI-ID/AONDB @2H 12 33 69 SAI 0.33 2H

-0.03 17 PP 33 ID 12 33 71 SAI 0.35 1H

-0.02 101 PP 78 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 33 71 DOS 0.76 1H

-0.06 50 Bobbin 15 OD 12 33 71 SAI 0.34 2H 0.2 6

PP 33 ID 12 33 71 SAI 0.13 4H

-0.2 91 PP 33 OD 12 33 72 DIS 1.01 2H

-0.27 27 Bobbin 15 ID 12 33 72 SAI 0.89 4H 0

15 PP 22 ID 12 33 72 DIS 1.54 4H

-0.04 15 Bobbin 15 ID 12 34 17 TWD 13 0.83 1C

-0.15 114 Bobbin 16 OD 12 34 19 TWD 6

0.38 1C

-0.19 124 Bobbin 16 OD 12 34 19 VOL 0.13 2C

-0.06 129 PP 62 OD 12 34 19 TWD 2

0.13 2C

-0.04 82 Bobbin 16 OD 12 34 26 SAI 0.17 2H

-0.26 103 PP 72 OD SAI-ID/AONDB @2H 12 34 26 SAI 0.83 2H 0.02 12 PP 72 ID SAI-ID/AONDB @2H 12 34 26 DIS 0.63 2H 0.12 15 Bobbin 17 ID SAI-ID/AONDB @2H 12 34 27 DOS 0.54 1H 0.17 60 Bobbin 16 OD 12 34 36 SAI 0.89 3H

-0.05 12 PP 24 ID 12 34 36 DIS 0.45 3H

-0.02 40 Bobbin 14 ID 12 34 38 DOS 0.13 1H 0.26 100 Bobbin 14 OD 12 34 39 DOS 0.54 1H 0.19 117 Bobbin 14 OD 12 34 42 SAI 0.43 2H 0.1 5

PP 24 ID 12 34 42 DIS 0.59 2H

-0.06 49 Bobbin 14 ID 12 34 43 DIS 0.45 1H 0.06 28 Bobbin 15 ID 12 34 44 DOS 0.33 3H 0.09 115 Bobbin 14 OD 12 34 45 SAI 0.35 1H

-0.04 104 PP 52 OD 12 34 45 DOS 0.27 1H 0.1 22 Bobbin 15 OD 12 34 47 SAI 1.09 2H 0.07 15 PP 24 ID 12 34 47 DIS 0.99 2H 0.11 23 Bobbin 14 ID 12 34 51 SAI 0.64 6H 0.11 14 PP 24 ID 12 34 51 TWD 25 0.53 7H 114.5 0

Bobbin 10 OD 12 34 51 TWD 35 1.88 7H 88.86 0

Bobbin 42 OD 12 34 53 SAI 0.97 2H

-0.01 11 PP 24 ID 12 34 53 SAI 2.59 2H 0

18 PP 24 ID 12 34 53 DIS 1.95 2H

-0.06 28 Bobbin 9

ID 12 34 54 DOS 0.64 3H

-0.18 108 Bobbin 9

OD 12 34 55 SAI 2.35 1H

-0.21 18 PP 24 ID 12 34 55 DIS 2.51 1H

-0.23 33 Bobbin 12 ID 12 34 58 SAI 2.01 2H

-0.09 17 PP 23 ID 12 34 58 DIS 2.06 2H

-0.08 25 Bobbin 12 ID 12 34 59 SAI 0.77 2H 0

13 PP 23 ID 12 34 59 DIS 0.39 2H

-0.02 20 Bobbin 12 ID 12 34 61 SAI 0.3 1H

-0.08 104 PP 70 OD 12 34 61 DOS 0.63 1H

-0.09 37 Bobbin 13 OD 12 34 65 SAI 0.44 2H 0

7 PP 23 ID 12 34 66 SAl 0.19 1H 0.22 123 PP 31 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IOD Reason for Plugging 12 34 66 TWD 23 0.42 7H 88.94 0

Bobbin 15 OD 12 34 68 DOS 0.44 1H

-0.06 60 Bobbin 15 OD 12 34 71 DOS 1.15 1H 0.21 80 Bobbin 14 OD 12 34 71 DIS 1.09 2H

-0.35 21 Bobbin 14 ID 12 34 76 SAI 0.46 3H 0.04 110 PP 71 OD 12 34 76 DOS 1.11 3H 0.06 38 Bobbin 15 OD 12 34 77 SAI 0.09 1H

-0.13 117 PP 71 OD 12 34 77 SAI 0.19 1H 0.02 103 PP 71 OD 12 34 77 DOS 0.66 1H 0.06 97 Bobbin 15 OD 12 34 79 DIS 1.19 4H 0.02 10 Bobbin 15 ID 12 35 17 DOS 1.04 1C

-0.35 111 Bobbin 17 OD 12 35 18 DOS 0.65 IC 0.34 49 Bobbin 16 OD 12 35 19 TWD 31 2.3 1C

-0.27 125 Bobbin 17 OD 12 35 19 TWD 29 2.05 2C

-0.14 139 Bobbin 17 OD 12 35 27 DOS 0.36 1H

-0.02 95 Bobbin 17 OD 12 35 27 DOS 0.31 2H 0.08 123 Bobbin 17 OD 12 35 27 DOS 0.17 3H 0.04 99 Bobbin 17 OD 12 35 28 DOS 1.2 1H 0.06 81 Bobbin 17 OD 12 35 30 DOS 0.6 1H 0.02 132 Bobbin 16 OD 12 35 36 DOS 0.31 6H 0.06 49 Bobbin 15 OD 12 35 37 SAI 0.23 2H

-0.01 103 PP 78 OD 12 35 37 SAI 0.43 2H

-0.02 109 PP 78 OD

12.

35 37 DOS 0.67 2H 0.04 89 Bobbin 14 OD 12 35 40 DOS 0.36 1H 0.1 132 Bobbin 15 OD 12 35 41 DOS 0.66 2H

-0.04 134 Bobbin 14 OD 12 35 41 SAI 0.13 4H 0.09 99 PP 69 OD 12 35 41 DOS 0.3 4H 0.06 71 Bobbin 14 OD 12 35 42 DIS 1.29 2H

-0.19 19 Bobbin 15 ID 12 35 43 DOS 0.37 1H 0.04 107 Bobbin 14 OD 12 35 46 DOS 0.89 2H

-0.06 88 Bobbin 14 OD 12 35 49 SAI 1.86 2H

-0.02 18 PP 24 ID 12 35 49 DIS 1.91 2H 0.02 33 Bobbin 14 ID 12 35 50 SAI 0.19 1H 0.19 97 PP 70 OD 12 35 52 SAI 0.98 3H

-0.05 11 PP 24 ID 12 35 52 DIS 0.95 3H

-0.33 8

Bobbin 9

ID 12 35 55 DOS 1.48 1H 0

100 Bobbin 12 OD 12 35 56 SAI 0.76 2H 0.03 17 PP 24 ID 12 35 56 DIS 0.48 2H

-0.34 21 Bobbin 12 ID 12 35 60 SAI 0.14 1H 0.08 118 PP 70 OD SAI-OD,>2v DOS @1H 12 35 60 SAI 2.45 1H

-0.05 57 PP 70 OD SAI-OD,>2v DOS @1H 12 35 60 DOS 2.82 1H 0

77 Bobbin 33 OD SAI-OD,>2v DOS @1H 12 35 68 SAI 0.28 1H 0.07 98 PP 70 OD 12 35 68 DOS 0.95 1H 0.04 57 Bobbin 15 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 35 70 SAI 1.17 2H 0

13 Pp 22 ID 12 35 70 DIS 0.67 2H

-0.06 41 Bobbin 15 ID 12 36 24 DOS 0.63 3H 0.06 84 Bobbin 17 OD 12 36 24 DOS 0.35 4H

-0.08 94 Bobbin 17 OD 12 36 33 DOS 0.5 2H 0.04 52 Bobbin 16 OD 12 36 39 DOS 0.44 3H

-0.11 71 Bobbin 14 OD 12 36 39 DIS 0.2 5H

-0.09 36 Bobbin 14 ID 12 36 41 DOS 0.39 1H 0.15 139 Bobbin 15 OD 12 36 42 DOS 0.67 4H

-0.11 85 Bobbin 14 OD 12 36 49 DOS 0.73 2H 0.04 121 Bobbin 15 OD 12 36 54 DOS 0.33 1H 0.1 113 Bobbin 9

OD 12 36 58 TWD 16 0.27 7H 63.75 0

Bobbin 12 OD 12 36 59 DOS 0.72 1H 0

98 Bobbin 12 OD 12 36 59 SAI 0.21 2H 0.3 106 PP 70 OD 12 36 59 DOS 0.6 2H 0.21 75 Bobbin 12 OD 12 36 60 SAI 0.21 1H

-0.23 85 PP 28 OD 12 36 60 SAI 1.32 4H

-0.13 15 PP 23 ID 12 36 60 DIS 1.76 4H

-0.17 13 Bobbin 13 ID 12 36 63 TWD 22 0.46 7H 64.12 0

Bobbin 13 OD 12 36 63 TWD 33 1.15 7H 95.05 0

Bobbin 13 OD 12 36 68 TWD 18 0.31 7H 63.46 0

Bobbin 15 OD 12 36 68 TWD 24 0.47 7H 35.06 0

Bobbin 15 OD 12 37 19 TWD 21 1.39 lC 0.15 90 Bobbin 17 OD 12 37 20 TWD 14 0.92 IC 0.02 143 Bobbin 17 OD 12 37 20 DOS 0.43 1H

-0.04 97 Bobbin 17 OD 12 37 28 DOS 0.22 1H 0.17 74 Bobbin 17 OD 12 37 33 DOS 1.02 2H 0.1 104 Bobbin 17 OD 12 37 35 DOS 1.11 2H 0.13 86 Bobbin 14 OD 12 37 35 SAI 0.16 3H

-0.14 123 PP 69 OD 12 37 35 SAI 0.17 3H 0.17 113 PP 69 OD 12 37 35 DOS 0.37 3H 0.21 100 Bobbin 14 OD 12 37 45 SAI 0.12 5H 0

115 PP 70 OD 12 37 45 DIS 0.99 5H

-0.02 26 Bobbin 14 ID 12 37 51 DOS 0.28 2H

-0.08 98 Bobbin 10 OD 12 37 53 SAI 2.38 2H

-0.19 22 PP 24 ID 12 37 53 DIS 2.71 2H

-0.21 30 Bobbin 9

ID 12 37 63 DOS 0.66 1H

-0.26 98 Bobbin 13 OD 12 37 67 TWD 14 0.21 7H 125.9 0

Bobbin 15 OD 12 37 68 SAI 0.43 3H

-0.09 12 PP 33 ID 12 37 69 SAI 1.05 1H 0.04 11 PP 22 ID 12 37 69 SAI 1.65 1H 0.28 17 PP 22 ID 12 37 69 DIS 1.38 1H 0.25 47 Bobbin 15 ID 12 37 69 SAI 0.79 3H 0.14 13 PP 22 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 37 69 DIS 0.68 3H

-0.23 40 Bobbin 15 ID 12 37 70 SAI 2.47 1H 0

17 PP 22 ID 12 37 70 DIS 2.45 1H

-0.08 41 Bobbin 15 ID 12 37 71 SAI 0.19 2H 0.07 109 PP 70 OD 12 37 71 DOS 0.56 2H

-0.23 66 Bobbin 15 OD 12 37 73 SAI 0.85 3H 0

11 PP 22 ID 12 37 73 DIS 0.91 3H

-0.3 35 Bobbin 15 ID 12 37 74 SAI 1.6 3H

-0.01 14 PP 22 ID 12 37 74 DIS 1.42 3H 0.04 33 Bobbin 14 ID 12 38 22 TWD 32 2.33 2C

-0.17 151 Bobbin 16 OD 12 38 23 TWD 24 1.62 2C

-0.13 118 Bobbin 16 OD 12 38 23 DIS 0.32 7H 0.04 21 Bobbin 16 ID 12 38 24 VOL 0.15 1C

-0.17 133 PP 61 OD 12 38 24 TWD 9

0.55 IC

-0.33 78 Bobbin 17 OD 12 38 24 DOS 0.38 1H 0.02 101 Bobbin 17 OD 12 38 25 TWD 5

0.32 1C

-0.26 97 Bobbin 16 OD 12 38 25 TWD 15 0.96 2C

-0.11 148 Bobbin 16 OD 12 38 26 DOS 0.24 2H 0.25 114 Bobbin 17 OD 12 38 33 DOS 0.29 1H 0

131 Bobbin 16 OD 12 38 34 TWD 14 0.24 7H 65.31 0

Bobbin 16 OD 12 38 34 TWD 18 0.34 7H 34.17 0

Bobbin 16 OD 12 38 41 DOS 0.86 1H

-0.1 112 Bobbin 15 OD 12 38 42 DOS 0.69 6H 0.02 67 Bobbin 14 OD 12 38 49 TWD 29 0.91 7H 129.6 0

Bobbin 15 OD 12 38 51 TWD 19 0.34 7H 129 0

Bobbin 10 OD 12 38 51 TWD 25 0.53 7H 98.72 0

Bobbin 10 OD 12 38 52 TWD 28 0.68 7H 67.34 0

Bobbin 10 OD 12 38 53 TWD 31 0.88 7H 129.4 0

Bobbin 10 OD 12 38 60 TWD 20 0.38 7H 35.82 0

Bobbin 13 OD 12 38 60 TWD 21 0.43 7H 67.1 0

Bobbin 13 OD 12 38 64 SAI 0.15 2H

-0.08 97 pp 70 OD 12 38 64 DOS 0.44 2H

-0.02 49 Bobbin 13 OD 12 38 64 TWD 25 0.57 7H 99.58 0

Bobbin 13 OD 12 38 64 TWD 29 0.81 7H 129.5 0

Bobbin 13 OD 12 38 66 SAI 1.07 1H 0.12 16 Pp 23 ID 12 38 66 DIS 0.74 1H 0.06 35 Bobbin 14 ID 12 38 66 DOS 0.37 3H

-0.02 103 Bobbin 14 OD 12 38 66 TWD 24 0.52 7H 99.63 0

Bobbin 14 OD 12 38 66 TWD 25 0.53 7H 129.6 0

Bobbin 14 OD 12 38 67 TWD 16 0.27 7H 98.8 0

Bobbin 14 OD 12 38 72 TWD 11 0.17 7H 98.83 0

Bobbin 14 OD 12 38 72 TWD 18 0.3 7H 66.86 0

Bobbin 14 OD 12 38 74 SAI 0.33 4H

-0.07 117 pp 71 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 38 74 DOS 0.89 4H

-0.11 56 Bobbin 15 OD 12 39 23 DOS' 0.78 1H 0.15 136 Bobbin 17 OD 12 39 23 DOS 0.37 3H 0.12 82 Bobbin 17 OD 12 39 24 DOS 1.33 1H 0.09 90 Bobbin 16 OD 12 39 25 DOS 0.81 1H 0.04 85 Bobbin 17 OD 12 39 27 DOS 0.62 1H

-0.08 122 Bobbin 17 OD 12 39 46 DOS 0.24 2H 0.06 110 Bobbin 14 OD 12 39 49 SAI 0.25 2H

-0.22 125 PP 51 OD 12 39 57 TWD 28 0.7 7H 68.69 0

Bobbin 12 OD 12 39 57 TWD 28 0.71 7H 102.1 0

Bobbin 12 OD 12 39 59 DOS 0.89 2H 0.13 63 Bobbin 12 OD 12 39 66 DOS 0.85 3H

-0.04 100 Bobbin 15 OD 12 39 66 TWD 13 0.18 7H 132.3 0

Bobbin 15 OD 12 39 66 TWD 14 0.21 7H 101.2 0

Bobbin 15 OD 12 39 69 DIS 0.35 4H 0

33 Bobbin 15 ID 12 39 69 TWD 26 0.55 7H 132.4 0

Bobbin 15 OD 12 39 70 SAI 0.29 1H

-0.13 109 PP 32 OD 12 39 70 DIS 1.39 1H

-0.12 31 Bobbin 14 ID 12 39 71 TWD 19 0.35 7H 68.66 0

Bobbin 14 OD 12 39 71 TWD 25 0.54 7H 101.4 0

Bobbin 14 OD 12 39 73 DOS 0.53 1H 0.04 38 Bobbin 15 OD 12 39 73 SAI 0.81 2H

-0.1 14 PP 78 ID 12 39 73 SAI 1.55 2H 0.14 15 PP 78 ID 12 39 73 DIS 1.19 2H 0.11 42 Bobbin 15 ID 12 40 28 DOS 0.21 1H

-0.02 83 Bobbin 16 0D 12 40 34 DOS 0.35 1H 0.08 135 Bobbin 16 0D 12 40 42 TWD 8

0.12 7H 35.62 0

Bobbin 14 0D 12 40 56 SAI 0.31 2H 0.02 99 PP 70 0D 12 40 56 DOS 0.63 2H 0

160 Bobbin 12 OD 12 40 67 DOS 0.44 2H

-0.02 71 Bobbin 15 OD 12 40 68 SAI 0.15 1H 0.09 76 PP 70 OD 12 40 68 SAI 0.59 1H

-0.21 107 PP 70 OD 12 40 68 DOS 1.07 1H

-0.21 119 Bobbin 15 OD 12 40 68 SAI 0.37 2H

-0.19 113 PP 70 OD 12 40 68 DOS 0.69 2H

-0.19 87 Bobbin 15 OD 12 41 33 TWD 13 0.85 1C

-0.02 150 Bobbin 16 OD 12 41 34 DOS 0.87 2H 0

96 Bobbin 17 OD 12 41 35 DOS 0.44 4H 0.06 77 Bobbin 15 OD 12 41 46 TWD 19 0.42 7H 106.2 0

Bobbin 14 OD 12 41 50 TWD 14 0.23 7H 71.89 0

Bobbin 9

OD 12 41 52 TWD 12 0.19 7H 106.8 0

Bobbin 10 OD 12 41 54 DOS 0.55 1H 0.06 135 Bobbin 11 OD 12 41 58 DIS 0.47 4H

-0.04 20 Bobbin 12 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 12 41 65 DOS 0.49 1H

-0.04 111 Bobbin 13 OD 12 42 30 DOS 0.33 5H

-0.06 69 Bobbin 16 OD 12 42 34 DOS 0.36 1H 0.15 81 Bobbin 16 OD 12 42 38 SAI 0.31 4H

-0.13 95 PP 1 48 OD AONDB @4H >5v dent 12 42 52 PVN 10.32 2C 15.05 16 Bobbin 9

12 42 55 SAI 0.49 1H

-0.05 98 PP 28 OD 12 42 55 DOS 0.95 1H

-0.02 129 Bobbin 11 OD 12 42 58 DOS 0.3 4H

-0.06 130 Bobbin 12 OD 12 43 30 DOS 0.18 3H 0.04 72 Bobbin 17 OD 12 43 32 TWD 14 0.88 1C

-0.21 144 Bobbin 17 OD 12 43 33 TWD 24 1.66 1C

-0.23 118 Bobbin 16 OD 12 43 35 DOS 0.51 2H 0.06 73 Bobbin 15 OD 12 43 37 VOL 0.09 1C

-0.31 91 PP 61 OD 12 43 37 TWD 5

0.31 1C

-0.29 97 Bobbin 15 OD 12 43 45 PVN 13.1 1C 42.37 16 Bobbin 14 12 43 46 DIS 0.88 3H 0.11 31 Bobbin 14 ID 12 43 48 DOS 0.64 4H

-0.06 62 Bobbin 14 OD 12 43 49 SAI 1.45 3H

-0.08 17 PP 24 ID 12 43 49 DIS 1.23 3H 0.04 25 Bobbin 14 ID 12 43 64 TWD 20 1.36 2C

-0.08 123 Bobbin 13 OD 12 43 65 DOS 0.42 1H

-0.02 80 Bobbin 13 OD 12 44 37 VOL 0.29 1C

-0.27 108 PP 61 OD 12 44 37 TWD 11 0.69 1C

-0.26 130 Bobbin 14 OD 12 44 40 DIS 0.26 3H

-0.12 35 Bobbin 15 ID 12 44 55 DIS 1.22 3H

-0.08 14 Bobbin 11 ID 12 45 42 SAI 0.27 1H 0

107 PP 69 OD 12 45 42 DIS 1.54 1H 0

25 Bobbin 15 ID 12 45 44 DIS 0.72 3H 0.12 20 Bobbin 15 ID 12 45 52 SAI 0.2 2H

-0.3

88.

PP 70 OD 12 45 52 DIS 0.55 2H

-0.25 63 Bobbin 10 ID 12 45 56 DOS 0.54 1H

-0.02 101 Bobbin 12 OD 12 45 58 TWD 8

0.47 1C 0.08 143 Bobbin 12 OD 12 46 43 TWD 6

0.39 1C

-0.33 68 Bobbin 15 OD 12 46 49 DOS 1.3 1H

-0.02 88 Bobbin 15 OD 12 46 49 DOS 1.3 2H

-0.08 81 Bobbin 15 OD 12 46 52 DOS 0.46 1H

-0.04 100 Bobbin 10 OD 12 46 53 DIS 0.48 3H

-0.02 30 Bobbin 10 ID 13 1

3 DOS 0.26 1H

-0.02 57 Bobbin 4

OD 13 1

9 DIS 1.6 3C 0

17 Bobbin 2

ID 13 1

10 DIS 0.78 3C 0.02 20 Bobbin 2

ID 13 1

12 DIS 0.7 2C 0.02 27 Bobbin 2

ID 13 1

18 DIS 0.61 2H

-0.11 28 Bobbin 2

ID 13 1

30 DOS 0.37 5H

-0.04 51 Bobbin 1

OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 1

50 DOS 0.58 1H

-0.04 103 Bobbin 2

OD 13 1

55 DOS 0.44 1H

-0.04 122 Bobbin 2

OD 13 1

57 DOS 0.63 1H 0

96 Bobbin 3

OD 13 1

61 DOS 0.48 1H

-0.04 99 Bobbin 4

OD 13 1

79 DIS 0.69 4C

-0.04 14 Bobbin 2

ID 13 2

2 DOS 0.29 2H

-0.11 92 Bobbin 3

OD 13 2

45 DOS 0.36 1H 0

91 Bobbin 1

OD 13 2

49 DOS 0.42 2H 0

69 Bobbin 1

OD 13 2

54 DOS 0.42 2H

-0.07 70 Bobbin 2

OD 13 2

56 DOS 0.29 2H

-0.02 125 Bobbin 3

OD 13 2

63 DOS 0.42 3H

-0.09 102 Bobbin 4

OD 13 2

66 DOS 0.67 1H

-0.02 89 Bobbin 3

OD 13 2

66 DOS 0.41 5H

-0.04 77 Bobbin 3

OD 13 3

44 DOS 0.24 1H

-0.09 89 Bobbin 2

OD 13 3

60 DOS 0.41 1H 0.04 135 Bobbin 3

OD 13 3

64 DOS 0.22 1H

-0.02 87 Bobbin 3

OD 13 3

67 Stall in U-bend, Preventive 13 3

73 DOS 1.26 1H

-0.04 102 Bobbin 4

OD 13 3

77 DOS 0.4 1H

-0.09 138 Bobbin 4

OD 13 3

81 DOS 0.58 5H 0.07 93 Bobbin 4

OD 13 3

85 DOS 0.63 1H

-0.04 92 Bobbin 4

OD 13 4

4 DOS 0.2 1H

-0.02 99 Bobbin 3

OD 13 4

9 SAI 0.34 3H

-0.19 82 PP 69 OD 13 4

9 DOS 1.34 3H

-0.25 91 Bobbin 4

OD 13 4

48 DOS 0.57 4H

-0.02 125 Bobbin 2

OD 13 4

53 SAI 0.18 2H

-0.03 93 PP 69 OD 13 4

53 DOS 0.68 2H

-0.07 131 Bobbin 1

OD 13 4

62 DOS 0.43 7C

-0.09 129 Bobbin 1

OD 13 4

65 DIS 1.62 2H 0.24 16 Bobbin 4

ID 13 4

75 DOS 0.61 3H

-0.07 56 Bobbin 4

OD 13 4

77 SAI 0.38 1H 0.01 116 PP 70 OD 13 4

77 DOS 1.92 1H

-0.04 162 Bobbin 4

OD 13 4

83 DOS 0.32 1H 0.02 79 Bobbin 4

OD 13 5

11 SAI 0.18 3H

-0.06 61 PP 69 OD 13 5

11 DOS 1.15 3H

-0.2 24 Bobbin 4

OD 13 5

12 SAI 0.15 1H

-0.07 82 PP 69 OD 13 5

12 DOS 0.5 1H 0.07 44 Bobbin 3

OD 13 5

12 SAI 0.19 3H

-0.01 114 PP 69 OD 13 5

12 DOS 1.06 3H

-0.17 45 Bobbin 3

OD 13 5

20 SAI 0.25 1H

-0.06 99 PP 37 OD 13 5

42 DOS 0.33 1H

-0.07 101 Bobbin 1

00 13 5

74 DOS 0.99 1H

-0.04 114 Bobbin 3

00 13 5

94 DIS 0.81 1H

-0.04 24 Bobbin 1

ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IOD Reason for Plugging 13 6

30 DOS 0.22 1H 0.04 78

  • Bobbin 57 OD 13 6

36 SAI 0.19 1H 0

90 PP 28 OD 13 6

36 DIS 0.65 1H 0.07 30 Bobbin 57 ID 13 6

57 DOS 0.7 3H

-0.04 53 Bobbin 59 OD 13 6

59 DOS 0.94 1H 0.05 132 Bobbin 59 OD 13 6

68 DOS 0.37 4H

-0.02 84 Bobbin 59 OD 13 6

69 DOS 0.85 1H 0

119 Bobbin 59 OD 13 6

73 DOS 0.32 1H 0.07 91 Bobbin 59 OD 13 6

76 DOS 0.17 4H

-0.02 95 Bobbin 59 OD 13 6

79 SAI 0.32 1H 0.04 98 PP 81 OD 13 6

83 DOS 0.95 1H 0.13 138 Bobbin 62 OD 13 7

23 FSI 0.36 1H 10.64 60 Bobbin 54 13 7

24 DOS 0.42 2H 0.02 104 Bobbin 54 OD 13 7

30 DOS 0.91 5H

-0.07 61 Bobbin 56 OD 13 7

35 DOS 0.44 1H 0.07 83 Bobbin 57 OD 13 7

57 DOS 0.41 2H

-0.02 53 Bobbin 60 OD 13 7

59 DOS 0.21 1H 0.05 72 Bobbin 60 OD 13 7

60 DOS 0.46 1H

-0.07 126 Bobbin 59 OD 13 7

75 DOS 1.54 2H 0.16 99 Bobbin 60 OD 13 7

75 DOS 0.22 4H 0

111 Bobbin 60 OD 13 7

76 DOS 0.62 2H

-0.02 51 Bobbin 60 OD 13 7

83 DOS 0.81 1H 0.13 107 Bobbin 61 OD 13 7

85 DOS 0.57 1H 0.13 112 Bobbin 61 OD 13 7

93 SAI 0.16 2H

-0.08 92 PP 70 OD 13 7

93 DIS 1.05 2H 0.04 22 Bobbin 62 ID 13 7

94 SAI 0.47 5H

-0.08 110 PP 70 OD 13 7

94 DOS 0.57 5H 0

117 Bobbin 64 OD 13 8

7 SAI 0.19 1H 0.01 111 PP 80 OD 13 8

7 DOS 0.53 1H 0.09 140 Bobbin 57 OD 13 8

8 DOS 0.9 2H

-0.14 86 Bobbin 57 OD 13 8

8 DOS 0.41 4H

-0.04 109 Bobbin 57 OD 13 8

8 DOS 0.53 5C

-0.09 106 Bobbin 57 OD 13 8

9 DOS 0.37 4C

-0.09 94 Bobbin 55 OD 13 8

9 DOS 0.81 6C

-0.2 105 Bobbin 55 OD 13 8

11 DOS 1.04 1H 0.07 97 Bobbin 55 OD 13 8

11 DOS 1.13 3H 0.21 114 Bobbin 55 OD 13 8

12 DOS 0.74 3H 0.02 113 Bobbin 54 OD 13 8

12 DOS 0.87 6C

-0.18 100 Bobbin 54 OD 13 8

12 DOS 0.44 6H 0.09 107 Bobbin 54 OD 13 8

13 SAI 0.31 2H

-0.08 98 PP 69 OD 13 8

13 DOS 0.81 2H

-0.04 119 Bobbin 55 OD 13 8

54 DOS 0.22 1H 0.04 67 Bobbin 60 OD 13 8

61 DOS 0.27 1H 0.05 71 Bobbin 59 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 8

76 DOS 1.52 1H

-0.05 118 Bobbin 59 OD 13 8

79 SAI 0.18 1H

-0.04 78 PP 80 OD 13 8

79 DOS 0.8 1H 0

145 Bobbin 62 OD 13 8

90 DOS 0.23 1H 0.02 76 Bobbin 62 OD 13 9

37 DOS 0.81 1H 0

107 Bobbin 56 OD 13 9

57 SAI 0.85 1H 0

93 PP 69 OD 13 9

57 DOS 1.87 1H 0.06 99 Bobbin 60 OD 13 9

57 DOS 0.88 3H

-0.05 100 Bobbin 60 OD 13 9

57 DOS 0.23 4H 0.04 95 Bobbin 60 OD 13 9

57 DOS 0.41 5C

-0.05 85 Bobbin 60 OD 13 9

57 SAI 0.11 5H 0.13 76 PP 69 OD 13 9

57 SAI 0.15 5H

-0.02 89 PP 69 OD 13 9

57 SAI 0.25 5H

-0.01 99 PP 69 OD 13 9

57 DOS 1.78 5H 0.06 90 Bobbin 60 OD 13 9

58 DOS 1.4 1H 0.24 128 Bobbin 60 OD 13 9

58 SAI 0.33 3H 0.01 123 PP 69 OD 13 9

58 SAI 0.38 3H 0.01 101 PP 69 OD 13 9

58 SAI 0.54 3H 0.01 101 PP 69 OD 13 9

58 DOS 1.99 3H

-0.02 111 Bobbin 60 OD 13 9

61 SAI 0.24 1H

-0.04 101 PP 69 OD SAI-OD,>2v DOS @IH 13 9

61 SAI 0.45 1H

-0.04 101 PP 69 OD SAI-OD,>2v DOS @1H 13 9

61 DOS 2.15 1H 0.11 110 Bobbin 60 OD SAI-OD,>2v DOS @IH 13

'9 61 DOS 0.73 2H 0.11 118 Bobbin 60 OD SAI-OD,>2v DOS @1H 13 9

61 DOS 0.75 4H 0.13 127 Bobbin 60 OD SAI-OD,>2v DOS @1H 13 9

61 DOS 0.55 6H 0.11 92 Bobbin 60 OD SAI-OD,>2v DOS @1H 13 9

63 DOS 1.66 1H 0.2 116 Bobbin 60 OD SAI-OD,>2v DOS @4H 13 9

63 DOS 0.47 2H 0.09 102 Bobbin 60 OD SAI-OD,>2v DOS @4H 13 9

63 DOS 0.53 3H 0.06 106 Bobbin 60 OD SAI-OD,>2v DOS @4H 13 9

63 SAI 0.67 4H

-0.01 83 PP 69 OD SAI-OD,>2v DOS @4H 13 9

63 DOS 2.03 4H 0.06 109 Bobbin 60 OD SAI-OD,>2v DOS @4H 13 9

64 DOS 1.01 1H 0.15 128 Bobbin 60 OD 13 9

64 DOS 1.16 3H

-0.04 118 Bobbin 60 OD 13 9

64 SAI 0.28 4H

-0.04 147 PP 80 OD 13 9

64 DOS 1.03 4H 0

127 Bobbin 60 OD 13 9

64 DOS 0.34 6C

-0.09 95 Bobbin 60 OD 13 9

65 DOS 1.37 3H 0

121 Bobbin 60 OD 13 9

65 DOS 0.54 4H 0.09 127 Bobbin 60 OD 13 9

65 DOS 0.51 6H 0.05 147 Bobbin 60 OD 13 9

66 SAI 0.23 1H 0.06 104 PP 69 OD 13 9

66 SAI 0.56 1H 0.01 86 PP 69 OD 13 9

66 DOS 1.84 1H 0.13 104 Bobbin 60 OD 13 9

67 DOS 0.78 1H 0.07 95 Bobbin 60 OD 13 9

67 DOS 0.82 3H 0.15 118 Bobbin 60 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 9

67 DOS 1.47 4H

-0.02 109 Bobbin 60 OD 13 9

67 DOS 0.67 7H

-0.04 103 Bobbin 60 OD 13 9

68 DOS 1.08 2H 0.11 98 Bobbin 60 OD 13 9

68 DOS 0.72 6H 0.04 115 Bobbin 60 OD 13 9

69 DOS 0.61 1H 0.13 111 Bobbin 60 OD 13 9

69 DOS 1.43 3H

-0.05 101 Bobbin 60 OD 13 9

70 SAI 0.68 3H

-0.01 93 PP 69 OD 13 9

70 DOS 1.77 3H 0

100 Bobbin 60 OD 13 9

70 DOS 0.87 4H 0

124 Bobbin 60 OD 13 9

70 DOS 0.67 5C

-0.16 118 Bobbin 60 OD 13 9

70 DOS 1.52 5H

-0.04 83 Bobbin 60 OD 13 9

71 SAI 0.23 1H 0

111 PP 69 OD 13 9

71 DOS 1.11 1H 0

153 Bobbin 60 OD 13 9

72 SCI 0.23 TSH

-0.08 111 PP 49 OD SCI-OD @TSH-0.08 13 9

82 DOS 0.29 1H 0.07 93 Bobbin 62 OD 13 10 10 DOS 1.55 2H 0.09 169 Bobbin 68 OD 13 10 20 SAI 0.27 TSH

-2.3 6

PP 32 ID 13 10 21 DOS 0.52 4H 0.04 118 Bobbin 55 OD 13 10 35 DIS 0.23 4H

-0.02 31 Bobbin 57 ID 13 10 47 SAI 0.57 2H 0.11 89 PP 70 OD SAI-OD,>2v DOS @2H 13 10 47 DOS 2.3 2H 0.04 149 Bobbin 57 OD SAI-OD,>2v DOS @2H 13 10 68 SAI 0.21 2H 0.02 87 PP 69 OD 13 10 78 DOS 0.94 1H 0.04 101 Bobbin 62 OD SCI-OD @TSH-0.02 13 10 78 SCI 0.17 TSH

-0.02 108 PP 51 OD SCI-OD @TSH-0.02 13 10 79 SAI 0.17 3H

-0.03 85 PP 70 OD 13 10 79 DIS 1.12 3H

-0.04 23 Bobbin 62 ID 13 11 12 DOS 0.48 1H 0.04 101 Bobbin 55 OD 13 11 60 SAI 0.42 2H 0

94 PP 80 OD 13 11 60 DOS 0.64 2H 0

150 Bobbin 59 OD 13 11 74 SCI 0.12 TSH

-0.04 80 PP 48 OD SCI-OD @TSH-0.04 13 11 91 DOS 0.51 1H 0.02 40 Bobbin 62 OD 13 11 92 DIS 1.17 1H 0

34 Bobbin 61 ID 13 12 24 DOS 0.33 2H 0

84 Bobbin 55 OD 13 12 37 DOS 0.43 1H 0.04 92 Bobbin 57 OD 13 12 92 TWD 9

0.55 1C

-0.02 146 Bobbin 62 OD 13 13 10 SAI 0.22 1H 0

93 PP 37 OD 13 13 10 DOS 0.5 1H

-0.16 82 Bobbin 56 OD 13 13 41 DOS 0.29 5H 0.05 154 Bobbin 54 OD 13 13 90 DOS 0.32 1H 0.07 86 Bobbin 61 OD 13 13 91 TWD 5

0.28 1C

-0.04 134 Bobbin 61 OD 13 14 31 FSI 0.24 2H 14.43 111 Bobbin 33 13 14 61 SAI 0.22 1H 0.03 83 PP 80 OD 13 14 61 DOS 0.72 1H 0.09 147 Bobbin 43 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 14 73 DOS 0.81 2H 0.06 77 Bobbin 47 OD 13 14 74 DOS 0.17 2H 0.04 102 Bobbin 47 OD 13 14 86 DOS 0.61 3H 0

119 Bobbin 64 OD 13 15 4

TWD 10 0.62 1C

-0.22 135 Bobbin 17 OD 13 15 9

FSI 0.26 1H 1

87 Bobbin 18 13 15 32 FSI 0.29 TSH 6.22 69 Bobbin 33 13 15 64 TWD 11 0.15 7H 41.13 0

Bobbin 43 OD 13 15 68 DOS 0.25 2H 0.08 77 Bobbin 48 Ob 13 15 73 DOS 0.83 1H 0.24 123 Bobbin 47 OD 13 16 9

SAI 0.23 1H 0.05 81 PP 69 OD 13 16 9

DOS 0.97 1H 0.11 123 Bobbin 18 OD 13 16 44 DOS 0.25 2H 0.02 50 Bobbin 19 OD 13 16 49 SAI 0.46 1H 0

77 PP 69 OD 13 16 49 DOS 1.73 1H 0.02 132 Bobbin 33 OD 13 16 81 DOS 0.4 1H

-0.02 61 Bobbin 48 OD 13 16 89 DOS 0.7 1H 0.02 101 Bobbin 64 OD 13 17 20 DOS 0.59 1H 0.09 156 Bobbin 33 OD 13 17 22 DOS 0.57 1H 0.04 130 Bobbin 31 OD 13 17 23 DOS 0.49 2H 0

83 Bobbin 31 OD 13 17 70 DOS 0.56 1H 0.06 109 Bobbin 48 OD 13 18 8

DOS 0.34 1H 0.08 107 Bobbin 18 OD 13 18 21 SAI 0.17 2H

-0.02 81 PP 80 OD 13 18 21 DOS 0.44 2H 0.04 140 Bobbin 31 OD 13 18 34 DOS 0.39 2H 0.04 94 Bobbin 31 OD 13 18 35 DOS 0.35 1H 0.02 99 Bobbin 31 OD 13 18 36 DOS 0.3 2H 0.04 117 Bobbin 31 OD 13 18 40 DOS 0.78 4H 0.06 115 Bobbin 31 OD 13 18 51 DOS 0.72 1H 0.08 118 Bobbin 44 OD 13 18 51 DOS 1.06 2H 0.23 101 Bobbin 44 OD 13 18 55 DOS 1.23 2H 0.17 129 Bobbin 44 OD 13 18 68 DOS 0.56 1H 0

120 Bobbin 48 OD 13 18 71 DOS 0.91 2H 0.28 104 Bobbin 47 OD 13 18 73 DOS 0.9 1H 0.13 108 Bobbin 47 OD 13 19 19 DOS 0.39 1H 0.09 130 Bobbin 19 OD 13 19 20 SAI 0.25 1H 0.01 95 PP 69 OD 13 19 20 SAI 0.3 1H

-0.12 109 PP 69 OD 13 19 20 DOS 0.87 1H 0.04 80 Bobbin 19 OD 13 19 44 DOS 0.96 1H 0.26 71 Bobbin 19 OD 13 19 44 FSI 0.17 3H 27.65 72 Bobbin 19 13 19 55 FSI 0.3 TSH 15.7 71 Bobbin 43 13 19 57 FSI 0.36 TSH 34.14 51 Bobbin 43 13 19 61 FSI 0.24 TSH 35.07 59 Bobbin 43 13 19 61 FSI 0.36 TSH 34.11 54 Bobbin 43 Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 19 62 FSI 0.12 5H 11.93 56 Bobbin 43 13 19 64 FSI 0.14 2H 43.94 76 Bobbin 43 13 19 64 FSI 0.36 TSH 35.26 65 Bobbin 43 13 19 69 DOS 1.06 1H 0.15 101 Bobbin 47 OD 13 19 73 DOS 0.68 i1H 0.11 119 Bobbin 47 OD 13 19 78 DOS 0.48 1H 0.11 126 Bobbin 48 OD 13 19 80 SAI 0.38 1H 0.03 105 PP 81 OD 13 19 88 TWD 19 1.24 IC 0.06 131 Bobbin 64 OD 13 19 90 SAI 0.86 1H

-0.03 76 PP 70 OD 13 19 90 DOS 1.96 1H 0.09 115 Bobbin 68 OD 13 20 22 DOS 1.03 1H 0.15 117 Bobbin 53 OD 13 20 28 DOS 0.45 2H

-0.06 127 Bobbin 31 OD 13 20 33 SAI 0.27 1H

-0.01 107 PP 69 OD 13 20 33 DOS 0.94 1H 0

149 Bobbin 53 OD 13 20 35 DOS 1.38 1H 0.19 102 Bobbin 53 OD 13 20 38 SAI 0.58 2H 0

79 PP 69 OD 13 20 38 DOS 1.41 2H 0.11 145 Bobbin 31 OD 13 20 68 DOS 0.78 1H 0.21 97 Bobbin 47 OD 13 21 25 TWD 11 0.17 7H 39.58 0

Bobbin 32 OD 13 21 34 SAI 0.3 1H

-0.06 103 PP 29 OD 13 21 36 DOS 0.86 1H 0.17 113 Bobbin 53 OD 13 21 50 DOS 0.28 2H 0

123 Bobbin 43 OD 13 21 64 DOS 0.56 5H 0.09 100 Bobbin 43 OD 13 21 64 FSI 0.31 TSH 34.44 60 Bobbin 43 13 21 65 DOS 0.68 5H 0.02 44 Bobbin 43 OD 13 21 68 FSI 0.28 TSH 34.28 58 Bobbin 46 13 21 70 DOS 0.41 5H 0.04 101 Bobbin 48 OD 13 22 17 FSI 0.4 TSH 35.94 70 Bobbin 19 13 22 31 DOS 0.19 4H 0.08 100 Bobbin

.30 OD 13 22 31 DOS 0.18 5H 0.1 74 Bobbin 30 OD 13 22 33 SCI 0.18 TSH

-0.01 90 PP 56 OD SCI-OD @TSH-0.01 13 22 41 DOS 0.4 1H 0.06 128 Bobbin 32 OD 13 22 44 DOS 0.37 2H 0.04 78 Bobbin 19 OD 13 22 55 SAI 0.27 1H 0

104 PP 81 OD 13 22 67 DOS 0.46 6H 0.06 126 Bobbin 45 OD 13 22 73 DOS 0.24 2C 0

70 Bobbin 46 OD 13 22 76 TWD 10 0.13 7H 41.12 0

Bobbin 45 OD 13 22 81 DOS 0.83 1H 0.06 103 Bobbin 46 OD 13 22 87 DOS 0.81 1H

-0.05 105 Bobbin 64 OD 13 23 24 DOS 0.89 1H 0

117 Bobbin 53 OD 13 23 24 DOS 0.39 5H 0

88 Bobbin 53 OD 13 23 25 DOS 0.48 6H

-0.02 119 Bobbin 29 OD 13 23 26 SAI 0.12 1H

-0.07 81 PP 69 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 23 26 DOS 0.63 1H 0

143 Bobbin 53 OD 13 23 26 DOS 0.51 2H 0.04 103 Bobbin 53 OD 13 23 26 DOS 0.22 6H 0

101 Bobbin 53 OD 13 23 29 TWD 11 0.16 7H 60.7 0

Bobbin 29 OD 13 23 31 SAI 0.3 2H

-0.12 71 PP 69 OD 13 23 31 DIS 1.75 2H

-0.06 47 Bobbin 29 ID 13 23 33 TWD 10 0.15 7H 42.88 0

Bobbin 29 OD 13 23 39 DOS 0.36 2H 0.09 98 Bobbin 53 OD 13 23 42 DOS 0.4 2H 0.09 93 Bobbin 53 OD 13 23 43 DIS 1.44 2H

-0.13 30 Bobbin 19 ID 13 23 51 SAI 0.15 1H

-0.11 108 PP 80 OD 13 23 51 SAI 0.26 1H 0.03 95 PP 80 OD 13 23 51 DOS 0.64 1H 0.04 141 Bobbin 43 OD 13 23 53 DOS 0.65 2H 0

87 Bobbin 43 OD 13 23 56 TWD 10 0.14 7H 43.26 0

Bobbin 43 OD 13 23 57 TWD 11 0.14 7H 43.16 0

Bobbin 43 OD 13 23 57 TWD 12 0.16 7H 61.1 0

Bobbin 43 OD 13 23 64 TWD 10 0.14 7H 61.53 0

Bobbin 43 OD 13 23 64 TWD 11 0.15 7H 42.59 0

Bobbin 43 OD 13 23 66 FSI 0.6 TSH 34.44 60 Bobbin 43 13 23 67 DOS 0.46 1H 0.04 139 Bobbin 43 OD 13 23 68 DOS 1.22 2H 0.3 110 Bobbin 44 OD 13 24 8

DOS 0.42 1H 0.04 110 Bobbin 18 OD 13 24 17 DOS 0.39 1H 0.09 112 Bobbin 19 OD 13 24 27 DOS 0.3 2H 0.04 123 Bobbin 53 OD 13 24 28 DOS 0.89 1H 0.06 143 Bobbin 29 OD 13 24 30 DOS 0.24 2H 0.06 114 Bobbin 53 OD 13 24 41 SAI 0.54 1H

-0.02 99 PP 69 OD 13 24 41 DOS 1.51 1H 0

147 Bobbin 53 OD 13 24 41 DOS 0.16 4H 0

107 Bobbin 53 OD 13 24 45 DOS 0.25 5H 0

85 Bobbin 19 OD 13 24 86 DOS 0.5 1H 0.11 90 Bobbin 64 OD 13 25 36 SCI 0.44 TSH 0

93 PP 29 OD SCI-OD @TSH+0.0 13 25 40 TWD 9

0.11 7H 46.39 0

Bobbin 19 OD 13 25 56 TWD 10 0.12 7H 45.76 0

Bobbin 43 OD 13 25 67 TWD 10 0.14 7H 66.25 0

Bobbin 43 OD 13 25 76 DOS 1.28 1H 0.17 129 Bobbin 44 OD 13 25 81 SAI 0.26 1H 0.02 123 PP 70 OD 13 25 81 DOS 1.49 1H 0.09 159 Bobbin 64 OD 13 25 82 SAI 0.11 1H

-0.03 95 PP 81 OD 13 25 86 TWD 6

0.35 1C

-0.03 142 Bobbin 64 OD 13 26 21 DOS 0.24 1H 0.04 119 Bobbin 15 OD 13 26 41 SAI 0.17 1H 0.09 87 PP 24 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 26 41 DIS 1.43 1H

-0.21 25 Bobbin 5

ID 13 26 47 SAI 0.74 1 H 0

104 PP 69 OD 13 26 47 DOS 0.82 1H 0.06 111 Bobbin 7

OD 13 26 51 DOS 0.31 4H

-0.2 123 Bobbin 5

OD 13 26 54 DOS 0.36 5H

-0.04 123 Bobbin 7

OD 13 26 80 SAI 0.26 1H 0.03 84 PP 70 OD 13 26 80 DOS 1.61 1H 0.04 151 Bobbin 49 OD 13 27 25 TWD 11 0.14 7H 48.27 0

Bobbin 15 OD 13 27 31 TVVD 11 0.13 7H 47.9 0

Bobbin 6

OD 13 27 32 DOS 1.16 2H 0.29 103 Bobbin 12 OD 13 27 39 DOS 0.55 1H 0.04 99 Bobbin 9

OD 13 27 39 DOS 0.58 2H

-0.02 119 Bobbin 9

OD 13 27 44 SAI 0.17 TSH 0.07 120 PP 24 OD SAI-OD @TSH+0.07 13 27 45 SCI 0.41 TSH

-0.03 63 PP 23 OD SCI-OD @TSH-0.03 13 27 47 SAI 0.2 TSH 0.13 87 PP 23 OD SAI-OD @TSH+0.13 13 27 48 TWD 7

0.09 7H 71.24 0

Bobbin 7

OD 13 27 48 TWD 7

0.1 7H 29.48 0

Bobbin 7

OD 13 27 49 SAI 0.15 1H

-0.02 85 PP 21 OD 13 27 49 DIS 0.6 1H

-0.19 35 Bobbin 7

ID 13 28 20 TWD 10 0.12 7H 73.02 0

Bobbin 15 OD 13 28 25 TWD 10 0.12 7H 49.73 0

Bobbin 15 OD 13 28 32 TWD 10 0.14 7H 49.97 0

Bobbin 11 OD 13 28 38 SAI 0.07 TSH 0.56 101 PP 22 OD Multi SAI-OD @TSH 13 28 38 SAI 0.13 TSH 0.33 103 PP 22 OD Multi SAI-OD @TSH 13 28 45 TWD 9

0.12 7H 51.29 0

Bobbin 7

OD 13 28 45 TWD 10 0.13 7H 73.94 0

Bobbin 7

OD 13 28 48 DOS 1.01 1H 0.21 118 Bobbin 8

OD 13 28 52 TWV 8

0.14 7H 73.91 0

Bobbin 7

OD 13 28 52 TWD 10 0.18 7H 51.2 0

Bobbin 7

OD 13 28 56 TWD 9

0.14 7H 50.56 0

Bobbin 9

OD 13 28 56 TWD 9

0.14 7H 73.36 0

Bobbin 9

OD 13 28 63 TWD 9

0.12 7H 50.06 0

Bobbin 42 OD 13 28 81 DOS 0.42 1H 0.02 76 Bobbin 49 OD 13 29 18 DOS 0.44 1H 0.02 128 Bobbin 34 OD 13 29 21 DIS 0.89 3H

-0.11 48 Bobbin 15 ID 13 29 36 FSI 0.35 TSH 29.64 62 Bobbin 10 13 29 37 DOS 0.74 1H 0.08 119 Bobbin 10 OD 13 29 48 TWD 9

0.12 7H 30.31 0

Bobbin 7

OD 13 29 52 TWD 6

0.11 7H 53.35 0

Bobbin 5

OD 13 29 72 SAI 0.34 1H 0.05 99 PP 69 OD 13 29 72 DOS 0.74 1H 0.08 141 Bobbin 41 OD 13 29 84 DOS 0.58 1H 0.04 79 Bobbin 49 OD Ding in Ubend 7H+30.70, Preventive 13 30 32 DOS 0.79 2H 0.26 137 Bobbin 11 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 30 39 DOS 0.6 1H

-0.04 112 Bobbin 10 OD 13 30 42 DOS 0.35 1H 0.06 127 Bobbin 10 OD 13 30 45 SAI 0.31 TSH

-2.18 12 PP 20 ID 13 30 49 TWD 9

0.14 7H 53.12 0

Bobbin 7

OD 13 30 49 TWD 13 0.21 7H 99.22 0

Bobbin 7

OD 13 31 20 DOS 0.5 2H

-0.11 40 Bobbin 15 OD 13 31 34 TWD 11 0.16 7H 32.13 0

Bobbin 11 OD 13 31 36 SAI 0.44 TSH

-2.93 5

PP 20 ID 13 31 49 TWD 11 0.16 7H 54.15 0

Bobbin 7

OD 13 31 60 SAI 0.23 2H 0.03 104 PP 69 OD 13 31 60 DOS 0.91 2H 0.11 159 Bobbin 42 OD 13 31 63 DOS 0.38 2H 0

93 Bobbin 41 OD 13 31 70 SAI 0.24 2H 0.06 104 PP 80 OD 13 31 70 DOS 0.71 2H 0.06 99 Bobbin 41 OD 13 32 24 SAI 0.2 2H

-0.27 100 pp 69 OD 13 32 24 SAI 0.34 2H

-0.01 128 PP 69 OD 13 32 24 DOS 0.74 2H 0.06 124 Bobbin

35.

OD 13 32 25 DOS 0.5 2H

-0.04 82 Bobbin 15 OD 13 32 31 DOS 1.02 1H

-0.04 102 Bobbin 5

OD 13 32 38 TWD 14 0.21 7H 31.78 0

Bobbin 10 OD 13 32 38 TWD 26 0.64 7H 56.55 0

Bobbin 10 OD 13 32 39 DOS 0.4 1H

-0.02 100 Bobbin 10 OD 13 32 39 FSI 0.25 TSH 34.43 61 Bobbin 10 13 32 40 SAI 0.33 1H

-0.02 104 PP 69 OD 13 32 40 DOS 0.44 1H 0.06 127 Bobbin 7

OD 13 32 42 FSI 0.26 TSH 34.26 60 Bobbin 10 13 32 46 DOS 0.62 1H 0

112 Bobbin 8

OD 13 32 50 DOS 0.48 1H

-0.04 131 Bobbin 5

OD 13 32 51 SAI 0.2 TSH 0.13 85 pp 54 OD SAI-OD @TSH+0.13 13 32 65 SAI 0.45 4H

-0.01 97 PP 69 OD 13 32 65 DOS 1.52 4H 0.04 139 Bobbin 42 OD 13 32 79 SAI 0.15 2H

-0.05 113 PP 70 OD SAI-OD @2H Wedge 13 32 79 DOS 0.28 2H 0.15 49 Bobbin 51 OD SAI-OD @2H Wedge 13 33 23 TWD 12 0.16 7H 57.4 0

Bobbin 15 OD 13 33 27 TWD 13 0.16 7H 86.46 0

Bobbin 17 OD 13 33 37 SAI 0.45 TSH

-5.79 11 Pp 20 ID 13 33 43 FSI 0.31 TSH 34.25 40 Bobbin 10 13 33 43 FSI 0.33 TSH 35.17 45 Bobbin 10 13 33 44 DOS 0.4 1H 0.09 85 Bobbin 9

OD 13 33 57 TWD 18 0.33 7H 58.52 0

Bobbin 11 OD 13 33 64 TWD 14 0.21 7H 86.18 0

Bobbin 41 OD 13 33 64 TWD 16 0.25 7H 32.18 0

Bobbin 41 OD 13 33 64 TWD 22 0.45 7H 57.5 0

Bobbin 41 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 33 75 DIS 0.72 7H 0

19 Bobbin 42 ID 13 34 23 TWD 10 0.13 7H 59.44 0

Bobbin 15 OD 13 34 27 TWD 13 0.15 7H 89.53 0

Bobbin 17 OD 13 34 39 TWD 18 0.31 7H 32.89 0

Bobbin 10 OD 13 34 40 DOS 0.43 1H 0.06 126 Bobbin 7

OD 13 34 48 DOS 1.08 2H

-0.08 82 Bobbin 8

OD 13 34 68 TWD 15 0.22 7H 59.54 0

Bobbin 42 OD 13 34 70 TWD 10 0.16 7H 88.07 0

Bobbin 42 OD 13 34 77 DOS 0.31 3H 0.06 53 Bobbin 51 OD 13 34 77 FSI 0.14 TSH 13.17 61 Bobbin 51 13 34 78 TWD 12 0.76 1C

-0.24 135 Bobbin 51 OD 13 34 78 TWD 21 1.4 2C

-0.22 141 Bobbin 51 OD 13 35 18 1DIS 0.82 1H 0.08 14 Bobbin 15 ID 13 35 21 TWD 11 0.14 7H 91.41 0

Bobbin 15 OD 13 35 29 TWD 13 0.15 7H 60.3 0

Bobbin 17 OD 13 35 33 DOS 1.14 2H 0.21 128 Bobbin 11 OD 13 35 34 TWD 10 0.15 7H 91.79 0

Bobbin 11 OD 13 35 36 DOS 0.98 2H 0.29 122 Bobbin 10 OD 13 35 36 TWD 11 0.16 7H 60.95 0

Bobbin 10 OD 13 35 38 TWD 11 0.14.

7H 61 0

Bobbin 9

OD 13 35 40 TWD 10 0.14 7H 61.87 0

Bobbin 9

OD 13 35 40 FSI 0.19 TSH 34.03 66 Bobbin 9

13 35 41 TWD 10 0.14 7H 61.09 0

Bobbin 9

OD 13 35 44 FSI 0.21 TSH 33.84 81 Bobbin 9

13 35 44 FSI 0.23 TSH 34.79 106 Bobbin 9

13 35 48 TWD 11 0.15 7H 61.61 0

Bobbin 7

OD 13 35 48 TWD 11 0.16 7H 91.44 0

Bobbin 7

OD 13 35 52 TWD 8

0.15 7H 61.94 0

Bobbin 7

OD 13 35 57 TWD 14 0.18 7H 61.03 0

Bobbin 12 OD 13 35 68 TWD 11 0.16 7H 116.9 0

Bobbin 41 OD 13 36 34 TWD 10 0.14 7H 94.14 0

Bobbin 11 OD 13 36 36 TWD 11 0.14 7H 61.97 0

Bobbin 9

OD 13 36 38 SAI 0.19 1H

-0.04 115 PP 69 OD 13 36 38 DOS 0.31 1H 0.04 119 Bobbin 10 OD 13 36 38 TWD 12 0.18 7H 63.55 0

Bobbin 10 OD 13 36 40 SAI 0.31 1H

-0.01 102 PP 69 OD 13 36 40 DOS 0.5 1H 0.04 104 Bobbin 9

OD 13 36 40 FSI 0.22 TSH 34.99 75 Bobbin 9

13 36 40 FSI 0.23 TSH 34.04 70 Bobbin 9

13 36 42 SAI 0.34 1H 0

112 PP 69 OD 13 36 42 DOS 0.6 1H

-0.04 153 Bobbin 10 OD 13 36 48 TWD 12 0.19 7H 93.94 0

Bobbin 8

OD 13 36 53 TWD 8

0.14 7H 63.34 0

Bobbin 7

OD 71-

Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 36 53 TWD 8

0.15 7H 94.02 0

Bobbin 7

OD 13 36 56 TWD 12 0.21 7H 121.5 0

Bobbin 9

OD 13 36 56 TWD 20 0.41 7H 93.82 0

Bobbin 9

OD 13 36 56 TWD 27 0.71 7H 63.01 0

Bobbin 9

OD 13 36 57 TWD 16 0.27 7H 94.08 0

Bobbin 11 OD 13 36 59 TWD 14 0.21 7H 93.1 0

Bobbin 40 OD 13 36 61 TWD 22 0.39 7H 122.1 0

Bobbin 42 OD 13 36 61 TWD 31 0.87 7H 62.99 0

Bobbin 42 OD 13 36 61 TWD 35 1.47 7H 94.36 0

Bobbin 42 OD 13 36 64 DOS 0.5 2H

-0.02 94 Bobbin 42 OD 13 37 19 DIS 1.24 1H 0.04 15 Bobbin 15 ID 13 37 25 TWD 13 0.16 7H 96.47 0

Bobbin 17 OD 13 37 25 TWD 15 0.2 7H 63.44 0

Bobbin 17 OD 13 37 27 TWD 13 0.11 7H 95.51 0

Bobbin 17 OD 13 37 34 TWD 18 0.32 7H 96.93 0

Bobbin 11 OD 13 37 37 DOS 0.86 1H 0.15 137 Bobbin 10 OD 13 37 46 TWD 14 0.22 7H 63.76 0

Bobbin 7

OD 13 37 50 TWD 18 0.38 7H 96.44 0

Bobbin 5

OD 13 37 50 TWO 20 0.47 7H 123.3 0

Bobbin 5

OD 13 37 50 TWD 39 1.98 7H 64.72 0

Bobbin 5

OD 13 37 51 DOS 0.23 2H

-0.08 109 Bobbin 7

OD 13 37 53 DOS 0.21 3H

-0.07 50 Bobbin 8

OD 13 37 68 TWD 14 0.21 7H 95.49 0

Bobbin 41 OD 13 37 68 TWD 22 0.44 7H 64.53 0

Bobbin 41 OD 13 37 69 TWD 13 0.19 7H 64.19 0

Bobbin 41 OD 13 37 69 TWD 29 0.77 7H 95.26 0

Bobbin 41 OD 13 37 70 TWD 11 0.16 7H 64.38 0

Bobbin 41 OD 13 37 70 TWD 21 0.41 7H 95.18 0

Bobbin 41

, OD 13 37 75 TWD 14 0.91 2C

-0.3 134 Bobbin 41 OD 13 38 41 DIS 0.58 3H 0.02 13 Bobbin 10 ID 13 38 45 TWD 9

0.12 7H 65.89 0

Bobbin 7

OD 13 38 45 TWD 12 0.18 7H 127.6 0

Bobbin 7

OD 13 38 45 TWD 17 0.28 7H 99.12 0

Bobbin 7

OD 13 38 47 DOS 1.11 1H 0.06 80 Bobbin 8

OD

-13 39 24 SAI 0.17 2H

-0.2 100 PP 82 0D 13 39 24 SAI 0.25 2H 0.05 101 PP 82 OD 13 39 24 DOS 0.52 2H 0.06 142 Bobbin 36 OD 13 39 35 DOS 0.47 4H 0

67 Bobbin 10 OD 13 39 45 TWD 9

0.15 7H 102.2 0

Bobbin 8

OD 13 39 45 TWD 11 0.18 7H 68.21 0

Bobbin 8

OD 13 39 46 SAI 0.71 TSH

-2.78 10 PP 20 ID 13 39 52 TWD 8

0.14 7H 67.22 0

Bobbin 5

OD 13 39 66 TWD 25 0.57 7H 131.2 0

Bobbin 41 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 39 68 DIS 0.91 1H

-0.15 26 Bobbin 41 ID 13 39 69 TWD 10 0.15 7H 100.7 0

Bobbin 41 OD 13 39 69 TWD 11 0.16 7H 67.77 0

Bobbin 41 OD 13 40 34 TWD 11 0.17 7H 134.5 0

Bobbin 11 OD 13 40 34 TWD 18 0.34 7H 68.7 0

Bobbin 11 OD 13 40 34 TWD 27 0.72 7H 104.3 0

Bobbin 11 OD 13 40 41 TWD 23 0.5 7H 103.8 0

Bobbin 10 OD 13 40 41 TWD 26 0.66 7H 133.8 0

Bobbin 10 OD 13 40 47 DOS 0.37 2H

-0.06 108 Bobbin 7

OD 13 40 50 SAI 0.21 3H

-0.11 117 PP 69 OD 13 40 50 DOS 0.78 3H

-0.16 40 Bobbin 5

OD 13 40 55 SAI 0.43 1H 0.06 105

' PP 69 OD 13 40 55 DOS 0.47 1H

-0.04 107 Bobbin 8

OD 13 40 56 DOS 0.85 1H 0.09 117 Bobbin 10 OD 13 40 57 DOS 0.92 1H

-0.02 72 Bobbin 36 OD 13 40 59 DIS 0.81 2H

-0.06 35 Bobbin 11 ID 13 40 63 TWD 16 0.24 7H 134.7 0

Bobbin 42 OD 13 41 26 DOS 0.38 1H 0

65 Bobbin 17 OD 13 41 26 DOS 0.25 2H 0.06 91 Bobbin 17 OD 13 41 28 TWD 15 0.99 2C

-0.26 123 Bobbin 17 OD 13 41 32 DOS 1.13 1H 0.06 116 Bobbin 12 OD 13 41 36 DOS 0.32 1H 0.08 100 Bobbin 10 OD 13 41 50 TWD 19 0.28 7H 70.62 0

Bobbin 8

OD 13 41 50 TWD 20 0.28 7H 105.8 0

Bobbin 8

OD 13 41 50 TWD 25 0.42 7H 137 0

Bobbin 8

OD 13 41 52 TWD 9

0.13 7H 71.15 0

Bobbin 6

OD 13 41 52 TWD 9

0.13 7H 107.4 0

Bobbin 6

OD 13 41 60 TWD 10 0.14 7H 35.88 0

Bobbin 40 OD 13 41 61 TWD 11 0.16 7H 69.56 0

Bobbin 41

-0.04 85 PP 69 OD 13 41 63 DOS 0.36 2H

-0.08 71 Bobbin 41 OD 13 42 28 TWD 11 0.71 2C

-0.19 143 Bobbin 17 OD 13 42 28 DIS 0.56 2H 0.06 24 Bobbin 17 ID 13 42 32 TWD 19 1.3 2C

-0.19 140 Bobbin 11 OD 13 42 32 DOS 0.81 5H 0.24 108 Bobbin 11 OD 13 42 33 VOL 0.15 2C

-0.15 100 PP 67 OD 13 42 33 TWD 4

0.26 2C

-0.06 132 Bobbin 12 OD 13 42 45 TWD 8

0.1 7H 108.9 0

Bobbin 7

OD 13 42 45 TWD 9

0.12 7H 71.69 0

Bobbin 7

OD 13 42 55 DOS 0.51 1H

-0.04 114 Bobbin 7

OD 13 42 66 DOS 0.56 1C

-0.38 42 Bobbin 41 OD 13 43 36 DOS 0.67 1C

-0.32 115 Bobbin 10 OD 13 43 36 TWD 22 1.51 2C

-0.17 133 Bobbin 10 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 13 43 37 TWD 16 1.01 2C

-0.19 139 Bobbin 10 OD 13 43 53 TWD 7

0.12 7H 111.7 0

Bobbin 5

OD 13 43 57 TWD 11 0.17 7H 36.81 0

Bobbin 35 OD 13 43 64 TWD 24 1.65 1C

-0.25 121 Bobbin 41 OD 13 44 33 DIS 1.07 1C 0.3 14 Bobbin 12 ID 13 44 61 TWD 10 0.15 7H 148.8 0

Bobbin 40 OD 13 45 43 TWD 9

0.54 2C

-0.11 165 Bobbin 10 OD 14 1

2 DOS 0.4 6H 0.02 43 Bobbin 6

OD 14 1

7 DOS 0.22 4H 0.08 80 Bobbin 6

OD 14 1

39 DIS 0.23 3H 0.16 29 Bobbin 6

ID 14 1

89 Stall in U-bend, Preventive 14 2

2 DOS 0.72 5H

-0.02 102 Bobbin 5

OD 14 2

11 DOS 0.72 4H 0.08 105 Bobbin 4

OD 14 2

23 SAI 0.24 3H 0.04 106 PP 73 OD 14 2

23 DOS 0.58 3H 0.04 111 Bobbin 4

OD 14 2

34 SCI 0.13 1H 0.29 128 PP 61 OD SCI-OD @1H+0.29 14 2

44 DIS 0.4 3H 0.02 12 Bobbin 5

ID 14 2

49 DOS 0.63 1H 0.06 100 Bobbin 6

OD 14 2

58 DIS 0.23 4H 0.02 24 Bobbin 5

ID 14 2

66 FSI 0.37 1H 7.56 66 Bobbin 1

14 2

70 SCI 0.94 1H

-0.28 124 PP 46 OD SCI-OD @1H-0.28 14 2

74 DOS 0.35.

2H

-0.07 46 Bobbin 1

OD 14 2

92 TWD 11 0.68 1C

-0.22 116 Bobbin 9

OD 14 3

5 DOS 0.35 2H

-0.07 83 Bobbin 5

OD 14 3

9 SAI 0.14 3H

-0.09 68 PP 73 OD 14 3

9 DOS 0.56 3H

-0.04 154 Bobbin 4

OD 14 3

23 DOS 0.92 1H 0

109 Bobbin 3

OD 14 3

28 DOS 0.33 7C

-0.02 52 Bobbin 5

OD 14 3

35 DOS 0.51 2H

-0.09 121 Bobbin 3

OD 14 3

35 DOS 0.48 4H

-0.04 123 Bobbin 3

OD 14 3

42 DOS 0.76 1H 0.1 120 Bobbin 6

OD 14 3

43 DOS 0.48 2H 0

101 Bobbin 5

OD 14 3

44 SAI 0.24 1H 0.03 106 PP 73 OD 14 3

44 SAI 0.28 1H 0

93 PP 73 OD 14 3

44 SAI 0.48 1H

-0.1 105 PP 73 OD 14 3

44 DOS 1.06 1H

-0.06 100 Bobbin 6

OD 14 3

44 DOS 0.66 6C 0.09 64 Bobbin 5

OD 14 3

44 DIS 0.71 7C

-0.09 31 Bobbin 5

ID 14 3

47 SAI 0.14 1H 0.05 110 PP 71 OD SAI-OD,>2v DOS @1H 14 3

47 SAI 0.15 1H 0.07 120 PP 71 OD SAI-OD,>2v DOS @1H 14 3

47 SAI 0.17 1H 0.06 82 PP 71 OD SAI-OD,>2v DOS @1H 14 3

47 SAI 1.28 1H

-0.02 81 PP 71 OD SAI-OD,>2v DOS @1H 14 3

47 005 2.06 1H

-0.02 60 Bobbin 5

OD SAI-OD,>2v DOS @1H Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 3

49 DOS 0.34 1H

-0.07 109 Bobbin 5

OD 14 3

53 DOS 0.76 1H

-0.2 96 Bobbin 6

OD 14 3

73 DOS 0.39 5H

-0.04 129 Bobbin 2

OD 14 3

74 DOS 1.2 1H 0.2 128 Bobbin 2

OD 14 4

1 DOS 0.21 3H

-0.04 67 Bobbin 6

OD 14 4

1 DOS 0.27 6H 0

70 Bobbin 6

OD 14 4

2 VOL 0.2 2C 0.12 129 PP 71 OD 14 4

2 TWD 9

0.58 2C 0.08 154 Bobbin 11 OD 14 4

3 TWD 9

0.57 1C

-0.21 145 Bobbin 10 OD 14 4

3 TWD 7

0.46 2C

-0.15 153 Bobbin 10 OD 14 4

5 SAI 0.2 2H

-0.01 116 PP 70 OD 14 4

5 DOS 0.31 2H

-0.04 88 Bobbin 6

OD 14 4

6 SAI 0.21 3H

-0.04 108 PP 73 OD 14 4

6 DOS 1.13 3H

-0.08 155 Bobbin 6

OD 14 4

14 DIS 0.46 4H

-0.09 41 Bobbin 3

ID 14 4

37 DOS 0.71 2H 0.16 85 Bobbin 4

OD 14 4

37 DOS 0.49 3H

-0.08 133 Bobbin 4

OD 14 4

41 DOS 0.56 2H 0.08 103 Bobbin 6

OD 14 4

42 DOS 1.53 1H 0.02 125 Bobbin 5

OD 14 4

46 FSI 0.43 TSH 28.25 59 Bobbin 5

14 4

47 DOS 0.31 2H

-0.02 106 Bobbin 6

OD 14 5

2 DOS 0.48 5H

-0.02 125 Bobbin 5

OD 14 5

17 SCI 0.2 1H 0.33 119 PP 63 OD SCI-OD @1H+0.33 14 5

34 DOS 1.36 2H 0

93 Bobbin 3

OD 14 5

39 DOS 0.55 1H

-0.04 102 Bobbin 5

OD 14 5

45 DIS 0.62 1H 0.02 19 Bobbin 5

ID 14 5

47 DOS 0.97 1H

-0.07 101 Bobbin 5

OD 14 5

72 SAI 0.17 2H

-0.01 58 PP 46 OD 14 5

76 DOS 0.5 2H

-0.08 144 Bobbin 4

OD 14 5

77 DOS 0.59 2H 0.04 123 Bobbin 2

OD 14 5

78 SAI 0.31 3H

-0.2 113 PP 48 OD 14 5

78 DOS 1.43 3H

-0.2 51 Bobbin 1

OD 14 5

79 SAI 0.17 1H 0.16 109 PP 48 OD 14 5

79 DOS 0.79 1H 0.29 125 Bobbin 1

OD 14 5

80 DOS 0.92 3H

-0.11 103 Bobbin 1

OD 14 5

87 DOS 0.93 2H 0.07 109 Bobbin 1

OD 14 5

87 DOS 1.45 3H 0.04 103 Bobbin 1

OD 14 5

90 SCI 0.26 2H 0.28 145 PP 48 OD SCI-OD @2H+0.28 14 6

3 TWD 8

0.52 2C

-0.28 139 Bobbin 47 OD 14 6

10 DOS 0.67 3H 0.02 118 Bobbin 46 OD 14 7

30 SAI 0.16 1H 0.14 112 PP 61 OD 14 7

38 SAI 0.12 1H

-0.2 93 PP 60 OD 14 7

44 FSI 0.15 4H 21 56 Bobbin 44 Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 7

54 SAI 0.19 TSH

-0.13 103 PP 45 OD SAI-OD @TSH-0.13 14 7

78 DOS 0.28 1H 0.1 144 Bobbin 50 OD 14 8

31 DOS 0.73 1H 0.09 114 Bobbin 45 OD 14 8

32 DOS 0.35 3H 0.03 112 Bobbin 44 OD 14 8

34 DOS 0.92 1H

-0.02 109 Bobbin 44 OD 14 8

42 DOS 0.71 1H 0.07 138 Bobbin 45 OD 14

.9 2

TWD 29 2.07 2C

-0.2 121 Bobbin 11 OD 14 9

5 TWD 9

0.57 2C 0.08 139 Bobbin 46 OD 14 9

9 SAI 0.55 3H

-0.13 92 PP 73 OD 14 9

9 DOS 1.47 3H

-0.07 87 Bobbin 46 OD 14 9

14 DOS 0.93 2H 0

91 Bobbin 51 OD 14 9

15 DOS 0.74 2H 0.12 147 Bobbin 43 OD 14 9

16 DOS 0.41 2H 0.05 138 Bobbin 43 OD 14 9

21 DOS 1.07 2H 0.11 118 Bobbin 43 OD 14 9

37 SAI 0.12 1H

-0.04 98 pp 59 OD 14 9

37 SAI 0.16 1H

-0.06 103 PP 59 OD 14 9

37 SAI 0.42 1H

-0.03 100 pp 59 OD 14 9

37 DOS 1.46 1H 0

47 Bobbin 45 OD 14 9

39 DOS 1.07 1H 0

99 Bobbin 44 OD 14 9

40 DOS 0.45 1H 0.07 102 Bobbin 45 OD 14 9

53 DOS 0.46 3H 0.05 115 Bobbin 49 OD 14 9

55 SAI 0.19 1H

-0.1 121 PP 71 OD 14 9

55 SAI 0.37 1H

-0.17 91 PP 71 OD 14 9

55 DOS 1.25 1H

-0.11 130 Bobbin 75 OD 14 9

57 DOS 0.71 1H 0.21 125 Bobbin 49 OD 14 9

59 DOS 0.38 3H 0.09 76 Bobbin 49 OD 14 9

59 DOS 0.37 5H

-0.09 125 Bobbin 49 OD 14 9

61 DOS 0.51 1H 0.12 108 Bobbin 49 OD 14 9

65 SAI 0.3 1H 0.04 126 PP 71 OD 14 9

65 DOS 0.54 1H 0.03 66 Bobbin 49 OD 14 10 13 SAI 0.14 3H 0

111 PP 66 OD 14 10 23 DOS 0.74 1H 0.04 112 Bobbin 43 OD 14 10 35 SAI 0.14 1H 0

98 PP 60 OD 14 10 44 SAI 0.16 1H 0.03 106 PP 56 OD AONDB @1H >5v dent 14 10 79 DOS 1.09 2H 0.05 112 Bobbin 50 OD 14 10 93 SAI 0.19 1H

-0.32 113 PP 42 OD 14 11 3

TWD 6

0.38 2C

-0.1 146 Bobbin 46 OD 14 11 19 DOS 0.54 1H 0.08 110 Bobbin 43 OD 14 11 19 SAI 0.17 3H

-0.07 98 PP 73 OD 14 11 19 DOS 0.47 3H

-0.24 123 Bobbin 43 OD 14 11 20 DO 0.68 1H 0.15 111 Bobbin 62 OD 14 11 20 DIS 0.7 3H

-0.19 30 Bobbin 62 ID 14 11 25 SAI 0.17 1H 0.04 113 PP 72 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 11 25 SAI 0.93 1H 0.05 79 PP 72 OD 14 11 25 DOS 1.71 1H 0.12 105 Bobbin 45 OD 14 11 46 SAI 0.35 1H 0.09 109 PP 69 OD SAI-OD,>2v DOS @1H 14 11 46 SAI 0.39 1H 0.04 82 PP 69 OD SAI-OD,>2v DOS @IH 14 11 46 DOS 2.01 1H 0.12 162 Bobbin 44 OD SAI-OD,>2v DOS @1H 14 11 48 DOS 0.68 1H

-0.18 89 Bobbin 5

OD 14 11 53 SAI 0.19 1H

-0.18 113 PP 71 OD 14 11 53 DOS 1.04 1H

-0.22 50 Bobbin 5

OD 14 11 86 DOS 1.1 1H 0.03 104 Bobbin 50 OD 14 12 14 SAI 0.21 3H

-0.04 107 PP 80 OD 14 12 14 DOS 0.76 3H 0

139 Bobbin 42 OD 14 12 31 SAI 0.18 3H

-0.15 91 PP 62 OD 14 12 32 SAI 0.2 1H 0

117 PP 60 OD 14 12 32 SAI 0.29 1H

-0.04 113 PP 60 OD 14 12 43 SAI 0.14 1H

-0.03 104 PP 60 OD 14 12 58 DOS 0.99 1H 0.14 108 Bobbin 75 OD 14 12 61 DOS 0.35 1H 0.1 105 Bobbin 49 OD 14 12 66 DOS 0.26 4H 0

139 Bobbin 49 OD 14 12 72 SAI 0.25 1H 0.05 108 PP 80 OD 14 12 72 DOS 0.39 1H 0.03 96 Bobbin 49 OD 14 13 6

SAI 0.15 2H

-0.11 113 PP 68 OD 14 13 6

SAI 0.21 2H 0.09 105 PP 68 OD 14 13 6

SAI 0.38 2H 0.01 107 PP 68 OD 14 13 6

DOS 0.46 2H

-0.03 120 Bobbin 46 OD 14 13 10 SAI 0.14 2H

-0.08 67 PP 73 OD 14 13 10 DIS 1.05 2H

-0.2 56 Bobbin 46 ID 14 13 15 DOS 0.49 3H

-0.04 112 Bobbin 42 OD 14 13 31 SAI 0.24 1H

-0.07 102 PP 61 OD 14 13 32 DOS 0.98 1H 0.03 155 Bobbin 44 OD 14 13 33 FSI 0.22 TSH 9.75 55 Bobbin 44 14 13 48 DOS 1

2H 0.12 112 Bobbin 44 0D 14 13 51 SAI 0.2 1H

-0.05 101 PP 44 OD 14 13 51 DIS 0.94 1H

-0.22 48 Bobbin 49 ID 14 14 6

DOS 0.58 1H

.0.08 76 Bobbin 29 OD 14 14 7

SAI 0.15 2H

-0.06 122 PP 68 OD 14 14 7

SAI 0.44 2H 0.11 101 PP 68 OD 14 14 13 DOS 0.41 3H 0.02 139 Bobbin 32 OD 14 14 19 SAI 0.15 3H

-0.11 99 PP 64 OD 14 14 33 DOS 0.52 1H 0.04 135 Bobbin 35 OD 14 14 36 SAI 0.65 1H 0.07 100 PP 60 OD 14 14 36 DOS 0.91 1H

-0.17 58 Bobbin 51 OD 14 14 40 DOS 0.2 2H 0.04 68 Bobbin 40 OD 14 14 42 DOS 0.31 2H 0.06 141 Bobbin 40 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 14 47 DOS 0.78 1H 0.06 94 Bobbin 29 OD 14 14 47 DOS 0.34 4H

-0.04 89 Bobbin 29 OD 14 15 7

SAI 0.15 1H 0.19 111 PP 68 OD AONDB @1H >5v dent 14 15 22 TWD 11 0.16 7H 39.56 0

Bobbin 33 OD 14 15 23 TWD 13 0.18 7H 30.38 0

Bobbin 33 OD 14 15 29 SAI 0.47 1H 0

101 PP 62 OD 14 15 36 SAI 0.26 1H

-0.09 74 PP 59 OD 14 15 52 SAI 0.12 1H

-0.13 103 PP 44 OD 14 15 85 SAI 0.19 1H

-0.07 95 PP 73 OD 14 15 85 DOS 0.79 1H

-0.11 40 Bobbin 19 OD 14 16 38 DOS 0.47 2H 0.05 141 Bobbin 51 OD 14 16 39 DOS 0.25 2H 0

119 Bobbin 41 OD 14 16 51 SAI 0.19 1H 0.19 110 PP 45 OD 14 16 57 DOS 0.3 1H

-0.13 69 Bobbin 20 OD 14 16 58 DOS 0.29 1H

-0.1 72 Bobbin 20 OD 14 16 58 DOS 0.69 2H 0.06 94 Bobbin 20 OD 14 16 59 DOS 0.24 1H

-0.13 128 Bobbin 20 OD 14 16 60 DOS 0.8 1H

-0.06 105 Bobbin 20 0D 14 16 60 DOS 0.98 2H

-0.17 88 Bobbin 20 0D 14 16 62 DOS 0.17 2H

-0.12 74 Bobbin 20 OD 14 16 65 DOS 0.31 1H

-0.1 117 Bobbin 14 OD 14 16 65 SAI 0.11 2H 0.18 124 PP 35 OD 14 16 66 SAI 0.21 1H 0.03 106 PP 85 OD 14 16 66 SAI 0.23 1H

-0.11 95 PP 85 OD 14 16 66 DOS 0.56 1H

-0.21 92 Bobbin 14 OD 14 16 68 DOS 0.93 1H

-0.02 117 Bobbin 17 OD 14 16 69 SAI 0.11 2H

-0.29 126 PP 37 OD 14 17 4

TWD 9

0.59 2C

-0.26 135 Bobbin 29 OD 14 17 6

TWD 11 0.67 2C

-0.16 153 Bobbin 29 OD 14 17 24 SAI 0.33 1H 0.33 12 PP 24 ID 14 17 32 SAI 0.45 1H

-0.06 101 PP 59 OD 14 17 41 DOS 0.57 5H

-0.1 127 Bobbin 40 OD 14 17 42 DOS 0.65 2H 0.02 109 Bobbin 40 0D 14 17 46 DOS 0.31 4H 0.08 101 Bobbin 40 0D 14 17 71 SCI 0.14 TSH 0

110 PP 36 OD SCI-OD @TSH+0.00 14 17 76 SAI 0.2 1H 0.02 70 PP 71 OD 14 17 76 SAI 0.25 1H 0

103 PP 71 OD 14 17 76 DOS 0.66 1H

-0.02 128 Bobbin 18 OD 14 18 6

VOL 0.15 1C

-0.01 135 PP 71 OD 14 18 6

TWD 4

0.27 1C

-0.06 106 Bobbin 29 OD 14 18 6

TWD 8

0.48 2C

-0.08 152 Bobbin 29 OD 14 18 6

TWD 11 0.15 7H 47.78 0

Bobbin 29 OD 14 18 22 DOS 0.48 2H 0.14 97 Bobbin 33 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 18 50 SAI 0.26 1H 0.13 101 PP 71 OD SAI-OD,>2v DOS @1H 14 18 50 SAI 0.31 1H 0

109 PP 71 OD SAI-OD,>2v DOS @IH 14 18 50 SAI 0.47 1H

-0.13 99 PP 71 OD SAI-OD,>2v DOS @1H 14 18 50 DOS 2.21 1H

-0.06 109 Bobbin 20 OD SAI-OD,>2v DOS @1H 14 18 76 DOS 0.37 1H

-0.02 66 Bobbin 17 OD 14 18 79 DOS 0.24 1H

-0.04 81 Bobbin 17 OD 14 18 81 DOS 0.98 2H 0.08 88 Bobbin 20 OD 14 19 32 SAI 0.72 1H 0.01 108 PP 59 OD 14 19 32 DIS 0.92 1H

-0.2 11 Bobbin 35 ID 14 19 40 SAI 0.15 1H 0.03 114 PP 59 OD 14 19 45 DOS 1.51 1H 0.03 141 Bobbin 51 OD 14 19 45 SAI 0.22 2H

-0.22 113 PP 56 OD 14 19 47 SAI 0.13 1H 0.01 119 PP 71 OD 14 19 47 DIS 0.5 1H

-0.02 10 Bobbin 29 ID 14 19 50 DIS 1.05 1H

-0.32 15 Bobbin

.19 ID 14 19 57 DIS 1.55 3H

-0.21 28 Bobbin 19 ID 14 19 84 DOS 1.05 3H

-0.21 75 Bobbin 19 OD 14 20 25 SAI 0.23 1H

-0.65 8

PP 24 ID 14 20 25 DIS 2.73 1H

-0.24 16 Bobbin 35 ID 14 20 50 DOS 0.26 1H

-0.11 129 Bobbin 20 OD 14 21 51 SAI 0.24 1H

-0.06 112 PP 44 OD 14 21 67 SAI 0.76 5H

-0.17 19 PP 24 ID 14 21 67 DIS 0.49 5H

-0.17 53 Bobbin 16 ID 14 21 76 SAI 0.64 11H

-0.12 13 PP 24 ID 14 21 76 DIS 0.72 1H

-0.34 20 Bobbin 18 ID 14 21 84 SAI 0.68 1H 0.05 14 PP 24 ID 14 21 84 DIS 0.32 1H 0.06 34 Bobbin 19 ID 14 22 8

SAI 0.53 1H

-0.14 84 PP 73 OD 14 22 8

DOS 1.2 1H 0

109 Bobbin 29 OD 14 22 10 DOS 0.42 1H 0

114 Bobbin 30 OD 14 22 19 DOS 0.42 4H 0.08 135 Bobbin 32 OD 14 22 32 DOS 0.32 2H 0.04 79 Bobbin 35 OD 14 22 34 SAI 0.34 1H

-0.07 97 PP 72 OD 14 22 34 DOS 0.46 1H 0

62 Bobbin 35 OD 14 22 38 DOS 0.19 1H 0.06 70 Bobbin 40 OD 14 22 40 DOS 0.3 2H 0.1 152 Bobbin 40 OD 14 22 43 SAI 0.2 1H 0.01 110 PP 60 OD 14 22 44 DOS 0.57 1H

-0.11 115 Bobbin 40 OD 14 22 48 SAI 0.09 1H 0

125 PP 71 OD 14 22 48 DOS 0.3 1H 0.06 38 Bobbin 29 OD 14 22 81 DOS 0.59 1H 0.02 149 Bobbin 20 OD 14 22 82 FSI 0.29 TSH 33.39 72 Bobbin 20 14 22 84 FSI 0.27 TSH 31.36 63 Bobbin 20 Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 22 84 FSI 0.39 TSH 26.68 76 Bobbin 20 14 23 7

SAI 0.35 TSH

-4.73 0

PP 24 ID 14 23 7

SAI 0.37 TSH

-7.46 8

PP 24 ID 14 24 8

TWD 11 0.15 7H 46.76 0

Bobbin 29 OD 14 24 13 TWD 5

0.31 2C

-0.22 138 Bobbin 32 OD 14 24 16 DOS 0.36 1H 0.04 93 Bobbin 32 OD 14 24 54 DOS 0.46 2H

-0.13 64 Bobbin 22 OD 14 24 56 TWD 9

0.15 7H 44.35 0

Bobbin 20 OD 14 24 62 SAI 0.28 1H 0.05 110 PP 34 OD 14 24 68 SAI 0.1 1H 0.02 93 PP 37 OD 14 24 75 SAI 0.24 1H 0.13 105 PP 71 OD 14 24 75 DOS 0.25 1H 0

115 Bobbin 17 OD 14 25 8

SAI 0.16 1H

-0.05 87 PP 73 OD 14 25 8

SAI 0.16 1H 0.12 100 PP 73 OD 14 25 8

DOS 0.66 1H 0.04 99 Bobbin 29 OD 14 25 19 DOS 0.44 1H

-0.06 124 Bobbin 32 OD 14 25 23 DOS 0.96 1H 0.12 101 Bobbin 41 OD 14 25 36 SAI 0.23 1H 0.03 102 PP 59 OD 14 25 47 DOS 0.4 70

-0.06 96 Bobbin 40 OD 14 25 49 SCI 0.18 1H

-0.25 134 PP 56 OD SCI-OD @1H-0.25 14 25 50 DOS 0.12 2H 0

81 Bobbin 19 OD 14 25 60 SAI 0.81 1H

-0.04 88 PP 71 OD 14 25 60 DOS 1.32 1H

-0.06 134 Bobbin 19 OD

,14 25 84 DIS 2.61 1H 0.26 21 Bobbin 19 ID 14 26 9

TWD 10 0.13 7H 67.25 0

Bobbin 12 OD 14 26 12 DOS 0.7 1H 0.06 77 Bobbin 14 OD 14 26 13 DOS 1.11 2H 0

96 Bobbin 13 OD 14 26 20 DOS 1.5 4H 0.14 91 Bobbin 17 OD 14 26 24 DOS 0.18 4H 0.02 74 Bobbin 34 OD 14 26 24 DOS 0.21 6C

-0.08 113 Bobbin 34 OD 14 26 36 SAI 0.19 1H

-0.09 122 PP 72 OD 14 26 36 DOS 0.5 1H

-0.02 73 Bobbin 27 OD 14 26 37 SAI 0.78 6H 0.18 11 PP 25 ID 14 26 37 DIS 0.77 6H 0.2 21 Bobbin 27 ID 14 26 61 TWD 7

0.12 7H 31.35 0

Bobbin 12 OD 14 26 80 DOS 0.57 1H

-0.04 74 Bobbin 15 OD 14

.27 11 TWD 14 0.89 2C

-0.16 142 Bobbin 12 OD 14 27 12 TWD 11 0.66 2C

-0.18 144 Bobbin 13 OD 14 27 34 SAI 0.6 1H 0.04 105 PP 52 OD 14 27 34 DOS 1.03 1H 0.14 54 Bobbin 24 OD 14 27 34 DOS 0.91 4H 0.06 96 Bobbin 24 OD 14 27 34 SAI 0.19 5H

-0.06 116 PP 72 OD 14 27 34 DOS 0.48 5H 0

117 Bobbin 24 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 27 35 DOS 0.54 1H 0.02 133 Bobbin 24 OD 14 27 36 SAI 0.24 4H

-0.17 105 PP 72 OD 14 27 36 DOS 0.92 4H

-0.06 85 Bobbin 27 OD 14 27 40 DOS 0.39 1H 0.04 114 Bobbin 27 OD 14 27 42 DOS 0.34 1H 0.06 122 Bobbin 27 OD 14 27 55 DOS 1.46 1H 0.04 102 Bobbin 11 OD 14 27 76 TWD 7

0.1 7H 70.29 0

Bobbin 14 OD 14 27 76 TWD 10 0.16 7H 48.1 0

Bobbin 14 OD 14 28 12 TWD 19 1.26 2C

-0.08 135 Bobbin 12 OD 14 28 45 DOS 0.24 4H

-0.02 131 Bobbin 28 OD 14 28 57 SAI 0.24 TSH

-2.64 6

PP 24 ID 14 28 57 SAI 0.39 TSH

-6.5 5

PP 24 ID 14 28 58 SAI 0.28 2H 0.08 4

PP 29 ID 14 28 63 SAI 0.23 1H 0.11 103 PP 71 OD 14 28 63 SAI 0.33 1H 0.09 96 PP 71 OD 14 28 63 DOS 0.85 1H 0.02 60 Bobbin 13 OD 14 29 34 TWD 18 0.34 7H 75.51 0

Bobbin 24 OD 14 29 34 TWD 26 0.59 7H 95.66 0

Bobbin 24 OD 14 29 34 TWD 27 0.67 7H 32.57 0

Bobbin 24 OD 14 29 57 SAI 0.28 2H

-0.17 113 PP 80 OD 14 29 57 SAI 0.3 2H

-0.18 120 PP 71 OD 14 29 57 DOS 1.38 2H

-0.26 54 Bobbin 11 OD 14 30 56 SAI 0.16 TSH

-0.21 98 PP 28 OD SAI-OD @TSH-0.21 14 30 59 SAI 0.3 1 H

-0.16 110 PP 80 OD 14 30 59 DIS 1.17 1H

-0.26 29 Bobbin 9

ID 14 30 59 DIS 0.74 4H

-0.11 7

Bobbin 9

ID 14 30 76 TWD 8

0.12 7H 53.41 0

Bobbin 15 OD 14 31 34 TWD 20 0.38 7H 54 0

Bobbin 24 OD 14 31 34 TWD 29 0.76 7H 102.5 0

Bobbin 24 OD 14 31 34 TWD 36 1.4 7H 80.08 0

Bobbin 24 OD 14 31 42 TWD 10 0.16 7H 55.92 0

Bobbin 27 OD 14 31 42 TWD 15 0.25 7H 36.01 0

Bobbin 27 OD 14 31 45 TWD 12 0.15 7H 55.14 0

Bobbin 28 OD 14 31 47 TWD 10 0.12 7H 101.6 0

Bobbin 28 OD 14 31 47 TWD 15 0.21 7H 79.74 0

Bobbin 28 OD 14 31 55 TWD 16 0.33 7H 107.1 0

Bobbin 11 OD 14 31 55 TWD 19 0.43 7H 54.69 0

Bobbin 11 OD 14 31 55 TWD 19 0.45 7H 32.5 0

Bobbin 11 OD 14 31 55 TWD 29 0.97 7H 79.56 0

Bobbin 11 OD 14 31 57 DIS 0.52 3C 0.08 16 Bobbin 10 ID 14 31 64 TWD 10 0.18 7H 54.3 0

Bobbin 11 OD 14 31 67 TWD 11 0.21 7H 107.4 0

Bobbin 11 OD 14 31 67 TWD 12 0.23 7H 80.15 0

Bobbin 11 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During IR13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 31 67 TWD 16 0.34 7H 81.3 0

Bobbin 11 OD 14 31 72 TWD 10 0.16 7H 106.9 0

Bobbin 12 OD 14 32 24 DOS 0.41 1H 0.08 129 Bobbin 34 OD 14 32 25 DOS 0.24 4H 0

95 Bobbin 34 OD 14 32 26 DOS 0.47 2H 0.1 93 Bobbin 19 OD 14 32 28 SAI 0.36 1H 0.07 109 PP 72 OD 14 32 28 SAI 0.89 1H

-0.07 93 PP 72 OD 14 32 28 DOS 1.7 1H 0.04 100 Bobbin 34 OD 14 32 32 TWD 10 0.15 7H 106.2 0

Bobbin 22 OD 14 32 33 TWD 11 0.17 7H 55.58 0

Bobbin 24 OD 14 32 36 TWD 14 0.23 7H 35.29 0

Bobbin 27 OD 14 32 36 TWD 29 0.77 7H 56.14 0

Bobbin 27 OD 14 32 42 SAI 0.24 2H 0.01 83 PP 85 OD 14 32 42 DOS 0.28 2H 0.06 125 Bobbin 27 OD 14 32 43 TWD 25 0.5 7H 102.9 0

Bobbin 28 OD 14 32 49 DOS 0.45 1H 0.08 75 Bobbin 28 OD 14 32 62 TWD 6

0.11 7H 111.3 0

Bobbin 11 OD 14 32 70 SAI 0.25 1H 0.07 64 PP 71 OD 14 33 16 TWD 18 1.18 2C

-0.16 145 Bobbin 14 OD 14 33 17 VOL 0.2 2C 0

136 PP 71 OD 14 33 17 TWD 6

0.34 2C 0

123 Bobbin 34 OD 14 33 33 TWD 12 0.2 7H 109.8 0

Bobbin 24 OD 14 33 33 TWD 12 0.2 7H 85 0

Bobbin 24 OD 14 33 53 TWD 10 0.17 7H 34.91 0

Bobbin 8

OD 14 33 55 SAI 0.37 1H 0

117 PP 71 OD 14 33 55 DOS 0.32 1H

-0.04 109 Bobbin 10 OD 14 33 58 SAI 0.64 1H

-0.01 87 PP 80 OD 14 33 58 DIS 1.26 1H 0.4 12 Bobbin 10 ID 14 34 24 DOS 0.21 1H 0.04 79 Bobbin 34 OD 14 34 32 TWD 12 0.19 7H 59.29 0

Bobbin 22 OD 14 34 52 SAI 0.45 1H 0

90 PP 71 OD 14 34 52 DOS 0.46 1H

-0.02 70 Bobbin 8

OD 14 34 65 SCI 0.2 1H 0.09 140 PP 30 OD SCI-OD @1H+0.09 14 34 67 SAI 0.22 1H

-0.01 107 PP 71 OD 14 34 67 SAI 0.36 1H

-0.09 102 PP 71 OD 14 34 67 DOS 0.5 1H 0

101 Bobbin 12 OD 14 35 17 VOL 0.24 2C 0.03 118 PP 71 OD 14 35 17 TWD 6

0.34 2C 0.02 134 Bobbin 17 OD 14 35 20 TWD 20 1.38 2C

-0.16 140 Bobbin 17 OD 14 35 21 TWD 11 0.71 2C

-0.16 130 Bobbin 34 OD 14 35 22 TWD 14 0.91 20

-0.1 134 Bobbin 34 OD 14 35 22 TWD 13 0.17 7H 61.46 0

Bobbin 34 OD 14 35 36 SAI 0.39 2H 0.18 7

PP 24 ID Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 35 36 DIS 0.44 2H 0.31 29 Bobbin 27 ID 14 35 44 TWD 34 1.13 7H 37.75 0

Bobbin 28 OD 14 35 53 TWD 16 0.27 7H 121.2 0

Bobbin 7

OD 14 35 53 TWD 28 0.73 7H 60.57 0

Bobbin 7

OD 14 35 56 SAI 0.31 2H 0.09 5

PP 29 ID 14 35 56 SAI 0.23 3H

-0.1 5

PP 25 ID 14 35 56 SAI 0.42 3H 0.07 7

PP 25 ID 14 35 56 DIS 0.09 3H 0.02 17 Bobbin 10 ID 14 35 58 TWD 15 0.31 7H 91.09 0

Bobbin 11 OD 14 35 58 TWD 17 0.37 7H 33.43 0

Bobbin 11 OD 14 35 58 TWD 35 1.84 7H 60.09 0

Bobbin 51 OD 14 35 61 SAI 0.28 2H

-0.07 10 PP 24 ID 14 35 65 TWD 17 0.33 7H 36.67 0

Bobbin 12 OD 14 35 65 TWD 18 0.36 7H 90.18 0

Bobbin 12 OD 14 35 65 TWD 29 0.87 7H 60.36 0

Bobbin 12 OD 14 35 66 TWD 15 0.27 7H 36.94 0

Bobbin 12 OD 14 35 66 TWD 21 0.45 7H 89.98 0

Bobbin 12 OD 14 35 66 TWD 26 0.7 7H 60.83 0

Bobbin 12 OD 14 35 68 SAI 0.54 3H

-0.17 19 PP 24 ID SAI-ID @3H with ligament indication 14 35 68 DIS 0.38 3H

-0.13 47 Bobbin 12 ID SAl-ID @3H with ligament indication 14 36 19 TWD 15 0.93 2C

-0.2 141 Bobbin 17 OD 14 36 20 SAI 0.16 1H

-0.02 123 PP 55 OD 14 36 25 DOS 0.7 3H

-0.12 71 Bobbin 19 OD 14 36 46 TWD 29 0.71 7H 119.1 0

Bobbin 28 OD 14 36 47 SAI 0.34 1H 0.12 112 PP 51 OD 14 36 51 TWD 12 0.18 7H 93.03 0

Bobbin 7

OD 14 36 57 TWD 22 0.48 7H 62.11 0

Bobbin 9

OD 14 36 57 TWD 22 0.52 7H 34.44 0

Bobbin 9

OD 14 36 59 TWD 12 0.24 7H 94 0

Bobbin 11 OD 14 36 61 TWD 21 0.51 7H 124.1 0

Bobbin 11 OD 14 36 61 TWD 21 0.51 7H 123 0

Bobbin 11 OD 14 36 61 TWD 33 1.38 7H 93.56 0

Bobbin 11 OD 14 36 61 TWD 37 1.97 7H 62 0

Bobbin 11 OD 14 37 20 TWD 7

0.43 2C

-0.06 157 Bobbin 17 OD 14 37 24 VOL 0.17 2C

-0.04 115 PP 71 OD 14 37 24 TWD 9

0.54 2C

-0.12 163 Bobbin 19 OD 14 37 37 DOS 0.62 2H 0.12 121 Bobbin 23 OD 14 37 53 TWD 14 0.21 7H 127.2 0

Bobbin 7

OD 14 37 53 TWD 14 0.22 7H 64.01 0

Bobbin 7

OD 14 37 53 TWD 25 0.57 7H 37.17 0

Bobbin 7

OD 14 37 53 TWD 34 1.25 7H 94.65 0

Bobbin 7

OD 14 37 54 TWD 10 0.17 7H 95.38 0

Bobbin 9

OD 14 37 60 TWD 10 0.18 7H 37.03 0

Bobbin 11 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 37 66 TWD 10 0.16 7H 94.87 0

Bobbin 12 OD 14 37 66 TWD 20 0.42 7H 63.68 0

Bobbin 12 OD 14 37 66 TWD 20 0.43 7H 37.69 0

Bobbin 12 OD 14 38 21 SAI 0.21 1H 0.05 80 PP 73 OD 14 38 21 DIS 0.41 1H

-0.18 51 Bobbin 19 ID 14 38 21 TWD 19 1.27 2C

-0.2 142 Bobbin 19 OD 14 38 46 SAI 0.24 6H

-0.02 3

PP 50 ID 14 38 46 SAI 0.32 6H 0.25 6

PP 50 ID 14 38 62 TWD 12 0.21 7H 130.4 0

Bobbin 12 OD 14 38 69 SAI 0.56 2H 0.04 12 PP 30 ID 14 38 69 DIS 0.47 2H

-0.25 41 Bobbin 11 ID 14 38 72 SAI 0.51 1H 0.29 13 PP 24 ID 14 39 23 TWD 14 0.87 2C

-0.16 154 Bobbin 19 OD 14 39 30 DOS 0.46 3H

-0.17 46 Bobbin 21 OD 14 39 48 SAI 0.33 3H 0.13 11 PP 24 ID 14 39 48 DIS 0.71 3H

-0.12 29 Bobbin 28 ID 14 39 48 TWD 18 0.27 7H 100.8 0

Bobbin 28 OD 14 39 54 TWD 24 0.55 7H 100.3 0

Bobbin 10 OD 14 39 58 SAI 1.31 1H 0.29 16 PP 46 ID 14 39 58 DIS 1.34 1H 0.21 33 Bobbin 11 ID 14 39 58 TWD 10 0.18 7H 36.55 0

Bobbin 11 OD 14 39 58 TWD 12 0.23 7H 133.6 0

Bobbin 11 OD 14 39 58 TWD 25 0.69 7H 100.6 0

Bobbin 11 OD 14 39 58 SAI 0.25 TEH 15.38 9

PP 71 ID 14 39 58 SAI 3.65 TEH 1.37 24 PP 71 ID 14 39 58 SAI 3.87 TEH 0.71 31 PP 71 ID 14 39 58 DTS 19.65 TEH 1.05 39 Bobbin 11 14 39 58 DTS 19.97 TEH 0.29 50 Bobbin 11 14 39 58 SAI 0.36 TSH

-5.96 8

PP 58 ID 14 39 64 SCI 0.15 1H 0.3 85 PP 31 OD Multi SCI-OD @1H 14 39 64 SCI 0.19 1H

-0.11 139 PP 31 OD Multi SCI-OD @IH 14 39 64 SCI 0.2 1H 0.34 121 PP 31 OD Multi SCI-OD @1H 14 39 66 SAI 0.26 1H 0

112 PP 71 OD 14 39 66 DOS 0.75 1H

-0.11 117 Bobbin 11 OD 14 39 66 SAI 0.2 2H 0

113 PP 71 OD 14 39 66 DOS 0.37 2H

-0.08 144 Bobbin 11 OD 14 40 27 SAI 0.14 1H

-0.14 110 PP 54 OD 14 40 27 SAI 0.26 1H 0.1 93 PP 54 OD 14 40 60 TWD 9

0.16 7H 102.8 0

Bobbin 11 OD 14 40 63 TWD 10 0.18 7H 68.75 0

Bobbin 11 OD 14 40 63 TWD 11 0.21 7H 103.6 0

Bobbin 11 OD 14 40 63 TWD 16 0.34 7H 69.39 0

Bobbin 11 OD 14 40 64 SAI 0.22 1H 0.11 108 PP 71 OD Enclosure PG&E Letter DCL-06-131 Table 2 Location and Percent Through-Wall of Indications Identified During 1R13 SG Row Col Ind

%TW Volts Loc Inch Deg Probe Cal IDOD Reason for Plugging 14 40 64 DOS 0.42 1H 0.04 110 Bobbin 11 OD 14 40 64 TWD 22 0.56 7H 68.79 0

Bobbin 11 OD 14 40 64 TWD 33 1.38 7H 103.4 0

Bobbin 11 OD 14 40 66 TWD 8

0.14 7H 102.4 0

Bobbin 11 OD 14 41 63 TWD 13 0.26 7H 140.3 0

Bobbin 11 OD 14 41 63 TWD 16 0.32 7H 70.52 0

Bobbin 11 OD 14 41 63 TWD 18 0.4 7H 106.6 0

Bobbin 11 OD 14 42 28 DOS 0.32 1H 0

56 Bobbin 19 OD 14 42 29 DOS 0.74 1H 0.02 62 Bobbin 19 OD 14 42 54 SAI 0.2 1H 0.05 84 PP 80 OD 14 42 59 TWD 11 0.21 7H 143.2 0

Bobbin 11 OD 14 42 61 TWD 28 0.92 7H 70.72 0

Bobbin 11 OD 14 43 37 TWD 10 0.15 7H 72.59 0

Bobbin 23 OD 14 43 42 SAI 0.28 1H

-0.1 106 PP 72 0D 14 43 42 DOS 0.22 1H 0.04 122 Bobbin 27 0D 14 43 46 TWD 10 0.12 7H 143.5 0

Bobbin 28 0D 14 43 49 DOS 0.41 2H

-0.04 107 Bobbin 28 0D 14 43 53 DOS 1.28 1H

-0.13 106 Bobbin 7

0D 14 43 56 TWD 31 1.03 7H 146.2 0

Bobbin 9

OD 14 43 56 TWD 36 1.74 7H 111.8 0

Bobbin 9

OD 14 43 56 TWD 37 1.88 7H 145.7 0

Bobbin 9

OD 14 43 58 SCI 0.16 1H 0.28 125 PP 28 OD SCI-OD @1H+0.28 14 43 59 SCI 0.31 1H

-0.34 107 PP 29 OD SCI-OD @1H-0.34 14 43 59 TWD 10 0.17 7H 111.5 0

Bobbin 11 OD SCI-OD @1H-0.34 14 43 65 VOL 0.65 7H 109.4 39 PP 82 OD 14 43 65 TWD 27 0.84 7H 110.6 0

Bobbin 11 OD 14 44 34 TWD 25 1.71 2C

-0.14 133 Bobbin 23 OD 14 44 57 TWD 11 0.72 2C 0.02 149 Bobbin 9

OD 14 44 58 TWD 10 0.18 7H 75.11 0

Bobbin 11 OD 14 45 53 DOS 0.38 1H

-0.02 66 Bobbin 7

OD 14 45 54 DOS 0.24 2C

-0.15 133 Bobbin 9

OD 14 45 58 TWD 28 1.97 2C

-0.08 123 Bobbin 11 OD 14 45 58 TWD 20 0.49 7H 116.3 0

Bobbin 11 OD 14 46 42 SAI 0.4 1H

-0.14 10 PP.

24 ID 14 46 42 DIS 0.32 1H

-0.06 30 Bobbin 27 ID 14 46 44 SAI 0.43 1H

-0.02 103 PP 72 OD 14 46 44 DOS 0.52 1H 0.08 110 Bobbin 28 OD 14 46 48 DOS 0.8 1H 0.06 82 Bobbin 28

. OD