ii DOCKET NUMBER PROD. & UTIL FAC T -_t,

Parameter VY Brunswick Comment Power Density, 5.2 5.2 Equivalent MW/assembly Number of 368 560 VY has 34% less fuel and cor Fuel Assem-respondingly lower steam blies flow than Brunswick.

Steam Line 331 391 VYhas 15% smaller length, Length, ft.

though the stem flow is corre spondingly less than Bruns wick.

Safety and Re-60 56 Equivalent lief Capacity,

% of Steam Bypass capac-86 69 VY has 25% greater capacity ity, % of Steam resulting in milder pressure rise following a tur bine/generator trip.

Turbine Valve

</= 0.1

<1= 0.1 Equivalent Closure Time, sec.

Main Steam

</= 5.0

</= 5.0

( Equivalent Valve Closure Time, sec.

SCRAM Inser-

</= 3.5

</= 3.5 Equivalent tion Time, sec.

7 qýelnplate_ =.5ECY-0;a8-DOCKETED USNRC

September 19, 2006 (3:37 pm)